12V85Ah
Front Access SLA Battery Range Summary By combining the newly developed paste formula with up-to-date AGM structures, BSB created the innovation FA range of batteries. The range features 12 years design life and front access connections for fast, easy installation and maintenance. This series is highly suited to telecom applications, UPS systems and other back up applications.
Application · Telecom · Control Equipment · UPS
· Communication Equipment · Medical Equipment · Emergency Power System
General Features · Easy maintenance and installation · No need for extra (wrench space) above battery · Sealed and maintenance free operation · Non-Spillable construction design · ABS containers and covers(UL94 V0,optional) · Safety valve installation for explosion proof · Maximized energy density for installation in relay rack trays · High quality and high reliability · Exceptional deep discharge recovery performance · Flexible design for multiple installation positions
3mm ( 0.12 inch)
18mm (0.71inch)
M6mm (0.24inch)
Construction Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
Lead dioxide Lead ABS ABS Epoxy Resin
Safety valve Terminal Separator Electrolyte
...... ...... ...... ......
EPDR Copper AGM Sulfuric acid
Terminal Dimensions
105mm(4.13inch)
270mm(10.6inch)
390mm(15.4inch)
Battery Model
FA 12-85
Designed Floating Life Capacity(20oC)
Dimensions
12 Years 20HR(4.5A,1.80V)
10HR(8.5A,1.80V)
5HR(14.7A,1.75V)
90AH
85AH
73.5AH
Length
Width
Height
Total Height
390mm(15.4inch)
105mm(4.13inch)
270mm(10.6inch)
270mm(10.6inch)
Approx. Weight
53.3AH
31Kg (68.4 lbs)
Internal Resistance
Full charged at 20oC: 0.0065 Ohm
Self Discharge
3% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
1HR(53.3A,1.60V)
40oC
20oC
0oC
-15oC
109%
100%
85%
65%
Cycle use 14.1-14.4V(-30mV/ oC), max. Current: 21.25A
Page 1 of 2
Float use 13.5-13.7V(-18mV/ oC)
FA 12-85
12V85Ah
Charge Voltage
(CA) (V/Cell)
(%) 120 100 80
0.25
Constant Charge at 0.25CA-2.35V (20oC) Charge Capacity
Charge Voltage
2.35
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
0
Discharge Characteristic (20oC)
Charge Characteristic
Charge Current
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
Front Access SLA Battery
2.17 2.00 1.83 0.25CA 0.1CA 0.05CA
1.67 1.60
3CA
2CA
1CA
6
12
30
1.33 0
12
2
60
3
Min
Time(hour)
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge 2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
0.6CA
2.08
2.00
85 80 75 70 65 60 55 50
1.92
1.83
o
0
10
20
30
40
50
60
70
80
90
100
40 0
1
2
20oC
o
40 C
45
30 C 3 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC
F.V/ Time 1.60V 1.67V 1.70V 1.75V 1.80V 1.85V
5min 298 268 254 226 204 155
10min 204 186 179 166 154 127
15min 149 145 139 132 126 109
30min 89.3 86.7 85.0 83.3 80.8 74.3
1h 53.3 53.2 53.1 52.5 51.8 51.3
3h 23.3 23.2 23.1 23.0 22.9 22.8
5h 15.0 14.9 14.8 14.7 14.6 14.4
10h 9.01 8.85 8.81 8.66 8.50 8.36
20h 4.70 4.64 4.60 4.55 4.50 4.23
30min 168 165 161 156 152 139
1h 105 102 98.8 97.9 96.3 95.4
3h 44.5 44.3 44.2 43.9 43.3 43.1
5h 28.5 28.3 28.2 28.0 27.8 27.4
10h 18.0 17.8 17.6 17.3 17.0 16.7
20h 9.41 9.37 9.35 9.33 9.00 8.46
Constant power discharge ratings-watts at 20oC
F.V/ Time 1.60V 1.67V 1.70V 1.75V 1.80V 1.85V
5min 490 465 434 405 363 291
10min 338 334 326 304 283 235
15min 264 261 257 241 227 198