Transcript
K3590-OM 4/01
FA260KP-OM, FA560KP-OM REMOTE KEYPADS INSTALLATION INSTRUCTIONS The FA260KP-OM and FA560KP-OM are addressable remote keypads intended for use with the FA408C and FA848C control panels. They have the following features: • Option for continuous or timed backlit display • Dedicated Function Keys • Built-in Sounders • Keypad addresses set via the keypad keys (no DIP switches required). KEYPAD DISPLAYS AND LEDs
WIRING AND INSTALLATION
The keypads have the following display features: Model
Fixed-Word Display
2-Line Alpha Display
2-Digit Zone Identifier
Custom Zone Descriptors
The keypads can be surface-mounted directly to a drywall, or to a single- or double-gang electical box. 1.
Remove the case back by pushing against each of two tabs. Pry apart the case back as each tab is depressed. See diagram below.
* Use the FA560KP-OM with the red color insert (provided for fire installations) as required by the local authority having jurisdiction.
2.
Route wiring from the control panel through the opening in the case back.
The following table shows the LEDs and their functions:
3.
Mount the case back to a wall or electrical box.
LED
Function
4.
Red
Lights when the system is armed in any mode.
Green
Lights when the system is "ready" to be armed.
Wire directly from the keypad’s terminal block to the terminal block on the control panel (see control’s Summary of Connections label for correct terminal connections).
X
FA260KP-OM FA560KP-OM*
X X
X
TURNING BACKLIGHT TIMER ON and OFF
Wiring Table (all Keypads)
FA260KP-OM
Keypad
Press and hold down the INSTANT and CODE keys at the same time for about three seconds. Press the [1] key that toggles a zero or one in the display: 0 = Backlight always on 1 = Backlight on a 120-second timeout.
DO
GRN
+
RED
−
BLK
DI
YEL
Control Panel Terminals
Press [✱] key to exit this Backlight menu.
FA560KP-OM Press and hold down the INSTANT and CODE keys at the same time for about three seconds. Press the [1] key to toggle the display between: 0 = Backlight always on and 1 = Backlight on a 120-second timeout. Press [✱] key to exit this Backlight menu.
Remove case back by pushing in the 2 tabs along keypad's bottom edge and pulling case apart.
SETTING THE KEYPAD ADDRESS
USING THE SOUNDER MENU (FA560KP-OM only)
The keypad can be set for an address of 1-8. The keypad's default address is 8.
1. Press the BYPASS and CODE keys at the same time and hold down for two seconds. This accesses the Sounder Menu. 2. Press the [1] key to toggle through the four modes listed above (stop at desired mode). 3. Press the [2] key to toggle through the sounder volume choices (high or low appears on the display). 4. Press the [3] key to adjust the sound of the key acknowledge (Ack H or L appears on the display). 5. Press the [✱] key to exit the Sounder Menu.
To change the keypad's address, do the following: 1. Enter Address mode: Power up the keypad. Within 60 seconds of power-up, press and hold down the Stay and Code keys at the same time for 3 seconds. (If unable to enter Address mode, power up and try again.) The current keypad address will be displayed. If 10 seconds have passed with no key entry, the keypad automatically exits Address mode. If this happens, you must power down, power up and enter Address mode again. 2. If the panel does not send a valid command to the keypad, the display will remain blank. 3. Exit Address mode: Press [✱] to save the displayed address and exit Address mode.
VIEWING THE KEYPAD ADDRESS Press and hold down the STAY and CODE keys at the same time for about 3 seconds. The current address is displayed. No key entry is allowed. Press any key to exit or wait 10 seconds to exit viewing mode.
TURNING THE SOUNDER ON/OFF FA260KP-OM: Press the BYPASS and CODE keys at the same time and hold down for two seconds until you hear a beep. Press any key to toggle the sounder on or off. 0 = Sounder off 1 = Sounder on. FA560KP-OM: There are four modes available in the Sounder Menu. They are as follows: • Off – No Sounds at all • Key – Only Key Clicks • Fire – Only Fire Sounder (temporal sounder – not supported by all panels) • On – Normal Sounder Keys (all sounds on)
SPECIFICATIONS Physical: FA260KP-OM: 6-5/8'H x 4-7/8"W x 1-5/16"D FA560KP-OM: 7-5/16'H x 5-3/8"W x 1-3/8"D
Displays: FA260KP-OM: Fixed-Word LCD (backlit) FA560KP-OM: 2 x 16 alphnumeric LCD (backlit)
Sounder: FA260KP-OM: Speaker FA560KP-OM: Speaker
Current: FA260KP-OM: 150mA (backlight and sounder on). 75mA standby mode (backlight on) FA560KP-OM: 150mA (backlight and sounder on). 80mA standby mode (backlight on)
REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR WARRANTY INFORMATION AND LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
175 Eileen Way, Syosset, New York 11791 Copyright 2001
¬.20Al K3590-OM 4/01