Transcript
FA 6-200
6V200Ah
Front Access SLA Battery Range Summary By combining the newly developed paste formula with up-to-date AGM structures, BSB created the innovation FA range of batteries. The range features 12 years design life and front access connections for fast, easy installation and maintenance. This series is highly suited to telecom applications, UPS systems and other back up applications.
Application · Communication Equipment · Medical Equipment · Emergency Power System
· Telecom · Control Equipment · UPS
General Features · Easy maintenance and installation · No need for extra (wrench space) above battery · Sealed and maintenance free operation · Non-Spillable construction design · ABS containers and covers(UL94 V0,optional) · Safety valve installation for explosion proof · Maximized energy density for installation in relay rack trays · High quality and high reliability · Exceptional deep discharge recovery performance · Flexible design for multiple installation positions
3mm ( 0.12 inch)
18 mm ( 0.71 inch)
M 8 mm ( 0.31 inch)
Construction Safety valve Terminal Separator Electrolyte
Lead dioxide Lead ABS ABS Epoxy Resin
...... ...... ...... ......
EPDR Copper AGM Sulfuric acid
Terminal Dimensions
250mm (9.84inch)
Positive ...... Negative ...... Container ...... ...... Cover Sealant ......
363mm (14.3inch)
125mm (4.92inch)
Battery Model
FA 6-200
Designed Floating Life Capacity(20oC)
Dimensions
12 Years 20HR(10.6A,1.80V)
10HR(20A,1.80V)
212Ah
200Ah
5HR(35.4A,1.75V) 177Ah
135Ah
Length
Width
Height
Total Height
363mm(14.3inch)
125mm(4.92inch)
250mm(9.84nch)
250mm(9.84inch)
Approx. Weight
34Kg (75.0 lbs)
Internal Resistance
Full charged at 20oC: 0.0017 Ohm
Self Discharge
3% of capacity declined per month at (20oC)
Capacity Affected by Temp.(10HR) Charge Voltage(20oC)
1HR(135A,1.60V)
40oC 109%
20oC
0oC
100%
85%
Cycle use 7.1-7.2V(-15mV/ oC), max. Current: 50A
Page 1 of 2
-15oC 65% Float use 6.8-6.9V(-9mV/ oC)
FA 6-200
6V200Ah
Charge Voltage
Constant Charge at 0.25CA-2.35V (20oC)
(CA) (V/Cell)
(%) 120 100
0.25
Charge Capacity
Charge Voltage
2.35 80
2.17 100%Discharge
0.20
60
2.00
50%Discharge
0.15
40
0.10 20
1.83
0.05
0
0
Discharge Characteristic (20oC)
Charge Characteristic
Charge Current
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge Capacity
Front Access SLA Battery
2.17 2.00 1.83 0.25CA 0.1CA 0.05CA
1.67 1.60
3CA
2CA
1CA
6
12
30
1.33 0
12
2
2.25
110 105
2.17
100 95 90
Capacity (%)
Battery Voltage (V/Cell)
3
10 Hour
20
Self Discharge Characteristics
Relationship of OCV and state of charge
2.00
60
Min
Time(hour)
2.08
0.6CA
85 80 75 70 65 60 55 50
1.92
1.83
45
0
10
20
30
40
50
60
70
80
90
100
40 0
o
1
2
20oC
o
40 C
30 C 3 4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC F.V/Time
5min
10min
15min
30min
1h
3h
5h
10h
20h
1.60V 1.67V
707 636
485 442
396 384
212 206
135 133
54.9 54.7
36.2 36.0
21.3 21.0
11.2 11.1
1.70V 1.75V
604 537
426 394
371 350
202 198
132 131
54.5 54.3
35.8 35.4
20.8 20.5
11.0 10.8
1.80V 1.85V
485 368
366 301
334 289
192 177
129 128
54.1 53.9
35.0 34.5
20.0 19.8
10.6 10.1
Constant power discharge ratings-watts at 20oC F.V/Time
5min
10min
15min
30min
1h
3h
5h
10h
20h
1.60V 1.67V
1160 1099
800 790
623 617
398 390
239 231
108 106
68.1 67.9
40.7 40.1
21.3 21.1
1.70V 1.75V
1027 957
770 720
607 571
380 370
225 223
105 104
67.5 67.1
39.8 39.1
21.0 20.7
1.80V 1.85V
858 687
669 555
537 468
360 330
219 217
102 102
66.0 65.1
38.4 37.8
20.3 19.1
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED Page 2 of 2
(Updated: 1-Nov-2010)