Fan Coil Unit (FCU) Application Guide VTR8300 Series Room Controllers Table of contents VTR8300 and SCs | Fan coil terminal equipment controllers VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with wireless door switch VTR8350A5000 -VC3404E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan, dehumidification, 2-position valves VTR8300A5000 - VC3504E5000: Heating/cooling with changeover sensor: 2-pipe fan coil unit with 3-speed fan and wireless window switch VTR8350A5000 - VC3400E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan and dehumidification, 2-position valves VTR8300A5500 - VC3514E5000: Heating/cooling: 2-pipe fan coil unit with 3-speed fan and fresh air damper, 2-position valves VTR8300A5000 -VC3500E5000 -VC3300E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with slave relay pack VTR8300A5000 - VC3504E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan, 2-position valves with wired window switch VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with wired door switch Appendix A - Passive infra-red (PIR) motion detector cover specifications Appendix B - option network wiring if communicating models are used Appendix C - controllers’ occupancy sequence of operation schematic Appendix D - SED Series - wireless door & window switch Appendix E - VTR8300 controller & VC3000 relay pack 2 4 6 8 10 12 14 16 18 20 21 21 22 23 Application Guide 2 VTR8300 Fan Coil Controller Overview VTR8300 & Relay Pack This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components: the VTR8300 terminal equipment controller and the SC3000 relay pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, reducing overall costs and installation time. The SC3000 relay pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The VTR8300 Line Voltage Fan Coil Terminal Equipment Controller and SC3000 Relay Pack can be configured to handle a broad variety of applications covering all the standard implementations necessary for controlling line-voltage HVAC systems. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. In addition to controlling heating, cooling and fan activity, depending on the model the VTR8300 can handle wireless networking and switches, passive infrared (PIR) occupancy detection using either onboard or remote sensors, and dehumidification control. The applications described here cover all these features, and in combination with the VTR8300’s advanced scheduling and occupancy controls can provide the functionality for any required line-voltage HVAC implementation. Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 3 VTR8300 and SCs | Fan coil terminal equipment controllers Commercial interface (local override) Power Part Number Description Humidity PIR Cover VTR8300A0Axx Stand-alone fan coil terminal equipment controller No No Stand-alone VTR8300A0Bxx BACnet fan coil terminal equipment controller No No BACnet® VTR8300A0Pxx Wireless fan coil terminal equipment controller No No ZigBee® Pro Wireless VTR8300A5Axx Stand-alone fan coil terminal equipment controller No Yes Stand-alone VTR8300A5Bxx BACnet® fan coil terminal equipment controller No Yes BACnet® VTR8300A5Pxx Wireless fan coil terminal equipment controller Yes Yes ZigBee® Pro Wireless VTR8350A0Axx Stand-alone fan coil terminal equipment controller Yes No Stand-alone VTR8350A0Bxx BACnet fan coil terminal equipment controller Yes No BACnet® VTR8350A0Pxx Wireless fan coil terminal equipment controller Yes No ZigBee® Pro Wireless VTR8350A5Axx Stand-alone fan coil terminal equipment controller Yes Yes Stand-alone VTR8350A5Bxx BACnet fan coil terminal equipment controller Yes Yes BACnet® VTR8350A5Pxx Wireless fan coil terminal equipment controller Yes Yes ZigBee® Pro Wireless ® ® ® Communication Transformer relay packs for fan coil units Power Part Number Description SC3500E5045 1 heat/cool output, 1 cool output, and 3 fan outputs SC3504E5045 1 heat/cool output, 1 cool output, 3 fan outputs, and four inputs SC3514E5045 1 heat/cool output, 1 cool output, 3 fan outputs, Occupancy output (7Vdc), and four inputs SC3400E5045 1 heat/cool output, 1 Modulating pulsed Vdc output for SSR electric reheat control, and 3 fan outputs SC3404E5045 1 heat/cool output, 1 Modulating pulsed Vdc output for SSR electric reheat control, and 3 fan outputs SC3300E5045 3 slave fan outputs Power Part Number Description SED-DOR-P-5045 Wireless door switch SED-WIN-P-5045 Wireless window switch Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Wireless accessories for VTR8300 Series Fax: (514) 321-4150 February 2015 Application Guide 4 VTR8300 Fan Coil Controller VTR83X0AxPxx with SC3500E5000 Relay: Heating/cooling 4-pipe fan coil unit with 3-speed fan and 2-position valves with wireless door switch Fan Airflow Direction Cooling Coil Heating Coil 2 POSITION 2 POSITION COOLING VALVE HEATING VALVE VTR8300 Onboard PIR Sensor SC3500E5000 AND / OR Door Switch SED-DOR-P-5000 Refer to the Wireless Door and Window Switch Installation Guide for the door pairing procedure. Configuration Parameter Name Fan Menu Fan cont. heat. BI2 Pulsed heating Pipe no. Seq. operation Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. Configuration Settings L-M-H-A On Door Dry Off 4 Ht - Cl | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Remote PIR Sensor Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 5 SC3500E5000 1 Tx/Rx Com Sequence of Operation and Wiring Options Occupied Mode Setpoints revert to those defined by occupied cooling and heating. • BACnet® and Wireless communication models available (see Appendix B for network wiring). Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. • Can be configured for 2-pipe systems (without changeover). • Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closed. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closed. Wireless Door Switch Wireless door switch automatically toggles occupancy. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. 7 VDC 3 Com SCom Tx / Rx UI 17 - BI2 2 7 Vdc UI 16 - BI1 BACnet REF BACnet- BACnet+ VTR8300 Fax: (514) 321-4150 February 2015 Application Guide 6 VTR8300 Fan Coil Controller VTR8350AXxXX with SC3404E5000 Relay: Cooling and electric heat 2-pipe fan coil unit with 3-speed fan, dehumidification and 2-position valves Fan Airflow Direction Cooling Coil Electric Heating 2 POSITION COOLING VALVE VTR8300 SSR SOLID STATE RELAY (GENERIC) SC3404E5000 Configuration parameter name Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. L-M-H-A On On 2 Ht-Cl | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Fan menu Fan cont. heat Pulsed heating Pipe no. Seq. operation Configuration settings Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 7 SC3404E5000 1 Tx/Rx 2 7 Vdc 3 Com Com 7 VDC Tx / Rx VTR8300 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 Heat - SCom Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary. Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Options • BACnet® and Wireless communication models available (see Appendix B for network wiring). • Remote wall mount or return duct sensor ready. • Can be configured for 2-pipe systems with changeover. • Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring. • Universal input can be configured for changeover sensor. St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. UI 17 - BI2 SOLIDSTATE (-) RELAY (4-32Vdc) (+) UI 16 - BI1 BACnet REF BACnet- BACnet+ 10 Heat + Fax: (514) 321-4150 February 2015 Application Guide 8 VTR8300 Fan Coil Controller VTR8300AxPxx with SC3504E5000 relay: Heating/cooling with changeover sensor 2-pipe fan coil unit with 3-speed fan and wireless window switch Window Switch SED-WIN-P-5000 Fan Airflow Direction Cooling / Heating Coil Supply Sensor 2 POSITION SENSOR COOLING VALVE / HEATING VALVE VTR8300 C/O AND / OR SENSOR Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2 SC3504E5000 Onboard PIR Sensor Configuration Parameter Name Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. L-M-H-A On Window COS 2 Cool | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Fan Menu Fan cont BI1 RUI1 Pipe No Seq. operation Configuration Settings Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 9 SC3504E5000 1 Tx/Rx VTR8300 3 Com Com 7 VDC Tx / Rx 2 7 Vdc 4 RUI 1 5 SCom 6 RBI 2 SCom Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Wireless Window Switch Wireless window switch automatically locks out heating/cooling when window is opened. Options • BACnet® and Wireless communication models available (see Appendix B for network wiring). • Remote wall mount or duct sensor ready. • Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. On Call for Heat If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. UI 17 - BI2 UI 16 - BI1 BACnet REF BACnet- BACnet+ 7 SS 8 RS Fax: (514) 321-4150 February 2015 Application Guide 10 VTR8300 Fan Coil Controller VTR8350Axxxx with SC3400E5000 relay: Cooling and electric heat 2-pipe fan coil unit with 3-speed fan, dehumidification and 2-position valves Fan Airflow Direction Cooling Coil Electric Heating 2 POSITION COOLING VALVE VTR8300 SSR SOLID STATE RELAY (GENERIC) SC3400E5000 Configuration parameter name Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. L-M-H-A On On 2 Cool-Rht | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Fan menu Fan cont. heat. Pulsed Heating Pipe No Seq. operation Configuration settings Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 11 SC3400E5000 1 2 3 Com 7 VDC Tx / Rx VTR8300 9 SCom Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary. Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value. Options • BACnet® and Wireless communication models available (see Appendix B for network wiring). • Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closed and dehumidification is disabled. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. UI 17 - BI2 SOLIDSTATE (-) RELAY (4-32Vdc) (+) UI 16 - BI1 BACnet REF BACnet- BACnet+ 10 Fax: (514) 321-4150 February 2015 Application Guide 12 VTR8300 Fan Coil Controller VTR8300AxxxX with SC3514E5000 Relay: Heating/cooling 2-pipe fan coil unit with 3-speed fan, fresh air damper and 2-position valves Fresh Air Fan Airflow Direction DAMPER Cooling / Heating Coil Supply Sensor 2 POSITION SENSOR COOLING VALVE / HEATING VALVE Return Air VTR8300 C/O Supply Sensor: 10K Ohm type 2. SENSOR Changeover Sensor: 10K Ohm type 2. SC3514E5000 Configuration Parameter Name Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. L-M-H-A On Window COS Occ Out 2 Cool | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Fan menu Fan cont. heat BI1 RUI1 Pulsed Heating Pipe no. Seq. operation Configuration Settings Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 13 SC3514E5000 1 Tx/Rx VTR8300 3 Com Com Tx / Rx 7 VDC 2 7 Vdc 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 OCC - SCom Sequence of Operation and Wiring On Call for Heat Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Options • BACnet® and Wireless communication models available (see Appendix B for network wiring). • Remote wall mount or return duct sensor ready. • Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. UI 17 - BI2 UI 16 - BI1 BACnet REF BACnet- BACnet+ 7Vdc RELAY COIL Fax: (514) 321-4150 February 2015 Application Guide 14 VTR8300 Fan Coil Controller VTR8300Axxxx with SC3500E5000 and SC3300E5000 RELAYS: Heating/cooling 4-pipe fan coil unit with 3-speed fan and 2-position valves with slave relay pack Fan Airflow Direction Cooling Coil Heating Coil 2 POSITION 2 POSITION COOLING VALVE HEATING VALVE VTR8300 SC3300E5000 Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | Configuration Settings L-M-H-A On 4 Ht-Cl St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Configuration Parameter Name Fan menu Fan cont. heat Pipe No Seq. operation SC3500E5000 Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 15 SC3500E5000T 1 2 3 Com 7 VDC Tx / Rx VTR8300 SC3300E5000 1 2 Sequence of Operation and Wiring Options Occupied Mode Setpoints revert to those defined by occupied cooling and heating. • BACnet® and Wireless communication models available (see Appendix B for network wiring). • Can be configured for 2-pipe systems without changeover. • Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. SCom UI 17 - BI2 UI 16 - BI1 BACnet REF BACnet- BACnet+ 3 Fax: (514) 321-4150 February 2015 Application Guide 16 VTR8300 Fan Coil Controller VTR8300AXPxx with SC3504E5000 relay: Cooling and electric heat 2-pipe fan coil unit with 3-speed fan and 2-position valves with wired window switch Window Switch SED-WIN-P-5000 Fan Airflow Direction Cooling / Heating Coil Supply Sensor 2 POSITION SENSOR COOLING VALVE / HEATING VALVE VTR8300 C/O SENSOR AND / OR Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2 SC3504E5000 Onboard PIR Sensor Configuration Parameter Name Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. L-M-H-A On Window COS 2 Cool | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Fan menu Fan cont. heat BI1 RUI1 Pipe no. Seq. operation Configuration Settings Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 17 SC3504E5000 1 Tx/Rx 2 7 Vdc 3 Com Com 7 VDC Tx / Rx VTR8300 4 RUI 1 5 SCom 6 RBI 2 SCom SCom Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes. On Call for Heat If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Wired Window Switch The window switch automatically locks out heating/cooling when window opens. Options • BACnet® and Wireless communication models available (see Appendix B for network wiring). • Models available with factory installed PIR sensor. • Remote wall mount or duct sensor ready. • Can be configured for 2-pipe systems with changeover. • Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring. • Universal input can be configured for changeover sensor. St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. BI1 (Window) UI 17 - BI2 UI 16 - BI1 BACnet REF BACnet- BACnet+ 7 SS 8 RS Fax: (514) 321-4150 February 2015 Application Guide 18 VTR8300 Fan Coil Controller VTR8300AXPxx with SC3500E5000 RELAY: Heating/cooling 4-pipe fan coil unit with 3-speed fan and 2-position valves with wired door switch Fan Airflow Direction Cooling Coil Heating Coil 2 POSITION 2 POSITION COOLING VALVE HEATING VALVE VTR8300 Onboard PIR Sensor SC3500E5000 AND / OR Door Switch SED-DOR-P-5000 Viconics Technologies Inc. 028-6047-03 | Configuration Parameter Name Configuration Settings Fan menu Fan cont. heat BI2 Pipe No Seq. Operat L-M-H-A On Door Dry 4 Ht-Cl 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Remote PIR Sensor Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 19 SC3500E5000 1 Tx/Rx VTR8300 Com SCom UI 17 - BI2 3 Com SCom Sequence of Operation and Wiring Options Occupied Mode Setpoints revert to those defined by occupied cooling and heating. • BACnet® and Wireless communication models available (see Appendix B for network wiring). • Models available with factory installed PIR sensor. • Can be configured for 2-pipe systems without changeover. • Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Door Switch Door switch automatically toggles occupancy. Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. BI2 (Door) UI 16 - BI1 BACnet REF BACnet- BACnet+ Tx / Rx 7 VDC 2 7 Vdc Fax: (514) 321-4150 February 2015 Application Guide 20 VTR8300 Fan Coil Controller Appendix A - Passive infra-red (PIR) motion detector cover specifications PIR cover sequence of operation Initially, the controller is in Stand-by mode. Stand-by setpoints are used at the controller. As soon as the PIR detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The Occupied setpoints are used. If no motion is detected in the room for the entire Stand-By Time duration (adjustable parameter), the room then switches to Stand-by mode and stand-by setpoints are used. While in Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied mode, any motion will switch the room back to Occupied mode. Typical Detection Pattern for PIR Lens Horizontal Angles (Typical) Vertical Angle (Typical) Transverse motion: 4-5 ft/s / 1.5 m/s Recommended installation height for PIR sensor: 4 - 5 ft. / 1.2-1.5 m Sensor Ranges A = 20 ft. / 6.1 m B = 14 ft. / 4.3 m C = 11 ft. / 3.4 m 40O A Center 30O 20O 20O B B 20O 20O C C Center Energy savings Typical Savings of 10-30% 85 80 50% 30% 50 45 40 35 20% 30 25 20 10% 15 10 5 0 0% 0 2 4 6 8 10 12 14 16 18 20 22 24 Time of Day (EST) Typical Consumption Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | PIR Thermostat Consumption St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 Savings | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. 40% 65 60 55 Saving Percentage The PIR can maximize your energy saving from 10-30% by relaxing temperature set points in unoccupied zones during scheduled periods. Energy Usage (KWh) 75 70 Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 21 Appendix B - option network wiring if communicating models are used Wireless Communication BACnet® communication wiring BACnet thermostat 1 BACnet thermostat 2 BACnet thermostat 3 + - ref + - ref + - ref Notes: - Wiring should be daisy chained - Respect polarity - If using 2 conductors shielded wires, connect the shield of each feed together on the back of the controller. ONLY ground the shield at one location. DO NOT connect the shield to the ref terminal. No communication wires required Appendix C - controllers’ occupancy sequence of operation schematic Setpoints 26.5°C 80°F Unoccupied cool 24.5°C 76°F Stand-by cool 22°C 72°F Occupied cool 22°C 72°F Deadband 70°F 21°C 70°F 21°C Stand-by heat Stand-by time 66°F 19°C Unoccupied time Unoccupied heat Movement detected Stand-by timer reset | 9245 Langelier Blvd. | Into Stand-by mode Unoccupied timer reset 62°F 16.5°C Into Unoccupied mode St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Time Next movement detected Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Occupied heat Viconics Technologies Inc. 028-6047-03 Deadband Deadband Fax: (514) 321-4150 February 2015 Application Guide 22 VTR8300 Fan Coil Controller Appendix D - sed series - wireless door & window switch Wireless ZigBee ® Pro door & window switch Wireless door switches used with an onbaord or remote PIR sensor provide advanced local occupancy routines allowing for increased energy savings during occupied hours without sacrificing occupant comfort. Wireless window switches are used to monitor exterior windows and or patio and balcony doors being opened or closed. This prevents unnecessary energy consumption by the tenants. Fan Coil Terminal Equipment Controllers with SED Series ZigBee® wireless switches can be used in network ready mode with or without integration to a central management system to allow for advanced functions such as central reservation and occupancy functions. A combination of up to twenty SED Series door and or window switches can be used simultaneously with a single Fan Coil Terminal Equipment Controller. The SED Series switches are factory delivered with 2 AAA batteries and are ready to be installed, configured and used right out of the box. Due to the extremely small current consumption of the switches, the expected battery life is approximately 10 years and is equivalent to the battery shelf life. No tools are required for commissioning or servicing the door switch. A very simple interface with an onboard LED & hidden switch provides all the required functions for local interaction. Local information for battery life and connectivity (heartbeat) are provided at the Fan Coil Terminal Equipment Controller local display through the ZigBee® wireless network. Each switch is factory supplied with a magnet, a locking security tamper proof screw and self tapping mounting screws. Model selection Window Switch Door Switch SED-WIN-P-5045 SED-DOR-P-5045 Hidden Switch Pull Tab Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. LED (switch side) Fax: (514) 321-4150 February 2015 Application Guide VTR8300 Fan Coil Controller 23 Appendix E - VTR8300 controller & SC3000 relay pack Product overview The VTR8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil unit thermostats. The VTR8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet® MSTP or wireless ZigBee® Pro networked models. No previous building automation training is required for the easy installation and commissioning process. Installation can be completed in approximately fifteen minutes, reducing costs and providing increased savings. The SC3000 Series Line Voltage Switching Transformer Relay Pack Controllers has been designed for silent control of typical high voltage fan coil device loads (90 to 277 VAC multi-voltages capable). It uses advanced microprocessor-based circuitry with a built-in transformer that eliminates all typical required peripheral components when automating a Fan Coil unit with traditional building automation systems. The SC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single master VTR8300 Terminal Equipment Controller. A single VTR8300 Terminal Equipment Controller can control up to 10x SC3000 Series Relay Pack. The SC3000 Series Relay Packs are line-powered units. The extremely compact unit locally contains all the relay outputs for fan switching and valve control. Models are also available for extra monitoring / control inputs of the Fan Coil Units. Typical fan coil unit setup Typical Fan Coil Unit H C C C 1 Tx/Rx 2 7 Vdc Power Supply 3 Com SC3404E5000 4 RUI 1 5 SCom 6 RBI 2 Electrical Cabinet WHITE 90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC 7 SS 8 RS BLACK 9 Heat 10 Heat + FAN LOW 1/2 HP or 13A FAN MED Max 5A Max RED BLUE FAN HIGH BROWN COOL YELLOW 1 Tx/Rx 2 7 Vdc 3 Com Power Supply 4 RUI 1 5 SCom xxx-xxxx-xx 6 RBI 2 WHITE 90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC 7 SS 8 RS 9 Heat 10 Heat + BLACK FAN LOW 1/2 HP or 13A FAN MED Max 5A Max RED BLUE FAN HIGH BROWN COOL YELLOW Mixed daisy chained and Star topology Daisy chained topology Star topology Viconics Technologies Inc. 028-6047-03 | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | www.viconics.com | [email protected] H1P 3K9 | Tel: (514) 321-5660 | © 2015 Viconics Technologies Inc. All rights reserved. Low Voltage Connections to VTR8300 Controller Fax: (514) 321-4150 February 2015