Fan Coil Unit (FCU) Application Guide VTR8300 Series Room Controllers
Table of contents VTR8300 and SCs | Fan coil terminal equipment controllers VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with wireless door switch VTR8350A5000 -VC3404E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan, dehumidification, 2-position valves VTR8300A5000 - VC3504E5000: Heating/cooling with changeover sensor: 2-pipe fan coil unit with 3-speed fan and wireless window switch VTR8350A5000 - VC3400E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan and dehumidification, 2-position valves VTR8300A5500 - VC3514E5000: Heating/cooling: 2-pipe fan coil unit with 3-speed fan and fresh air damper, 2-position valves VTR8300A5000 -VC3500E5000 -VC3300E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with slave relay pack VTR8300A5000 - VC3504E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan, 2-position valves with wired window switch VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with wired door switch Appendix A - Passive infra-red (PIR) motion detector cover specifications Appendix B - option network wiring if communicating models are used Appendix C - controllers’ occupancy sequence of operation schematic Appendix D - SED Series - wireless door & window switch Appendix E - VTR8300 controller & VC3000 relay pack
2 4 6 8 10 12 14 16 18 20 21 21 22 23
Application Guide
2
VTR8300 Fan Coil Controller
Overview VTR8300 & Relay Pack This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components: the VTR8300 terminal equipment controller and the SC3000 relay pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, reducing overall costs and installation time. The SC3000 relay pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The VTR8300 Line Voltage Fan Coil Terminal Equipment Controller and SC3000 Relay Pack can be configured to handle a broad variety of applications covering all the standard implementations necessary for controlling line-voltage HVAC systems.
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
In addition to controlling heating, cooling and fan activity, depending on the model the VTR8300 can handle wireless networking and switches, passive infrared (PIR) occupancy detection using either onboard or remote sensors, and dehumidification control. The applications described here cover all these features, and in combination with the VTR8300’s advanced scheduling and occupancy controls can provide the functionality for any required line-voltage HVAC implementation.
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
3
VTR8300 and SCs | Fan coil terminal equipment controllers Commercial interface (local override) Power
Part Number
Description
Humidity
PIR Cover
VTR8300A0Axx
Stand-alone fan coil terminal equipment controller
No
No
Stand-alone
VTR8300A0Bxx
BACnet fan coil terminal equipment controller
No
No
BACnet®
VTR8300A0Pxx
Wireless fan coil terminal equipment controller
No
No
ZigBee® Pro Wireless
VTR8300A5Axx
Stand-alone fan coil terminal equipment controller
No
Yes
Stand-alone
VTR8300A5Bxx
BACnet® fan coil terminal equipment controller
No
Yes
BACnet®
VTR8300A5Pxx
Wireless fan coil terminal equipment controller
Yes
Yes
ZigBee® Pro Wireless
VTR8350A0Axx
Stand-alone fan coil terminal equipment controller
Yes
No
Stand-alone
VTR8350A0Bxx
BACnet fan coil terminal equipment controller
Yes
No
BACnet®
VTR8350A0Pxx
Wireless fan coil terminal equipment controller
Yes
No
ZigBee® Pro Wireless
VTR8350A5Axx
Stand-alone fan coil terminal equipment controller
Yes
Yes
Stand-alone
VTR8350A5Bxx
BACnet fan coil terminal equipment controller
Yes
Yes
BACnet®
VTR8350A5Pxx
Wireless fan coil terminal equipment controller
Yes
Yes
ZigBee® Pro Wireless
®
®
®
Communication
Transformer relay packs for fan coil units Power
Part Number
Description
SC3500E5045
1 heat/cool output, 1 cool output, and 3 fan outputs
SC3504E5045
1 heat/cool output, 1 cool output, 3 fan outputs, and four inputs
SC3514E5045
1 heat/cool output, 1 cool output, 3 fan outputs, Occupancy output (7Vdc), and four inputs
SC3400E5045
1 heat/cool output, 1 Modulating pulsed Vdc output for SSR electric reheat control, and 3 fan outputs
SC3404E5045
1 heat/cool output, 1 Modulating pulsed Vdc output for SSR electric reheat control, and 3 fan outputs
SC3300E5045
3 slave fan outputs
Power
Part Number
Description
SED-DOR-P-5045
Wireless door switch
SED-WIN-P-5045
Wireless window switch
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Wireless accessories for VTR8300 Series
Fax: (514) 321-4150 February 2015
Application Guide
4
VTR8300 Fan Coil Controller
VTR83X0AxPxx with SC3500E5000 Relay: Heating/cooling 4-pipe fan coil unit with 3-speed fan and 2-position valves with wireless door switch
Fan
Airflow Direction
Cooling Coil
Heating Coil
2 POSITION
2 POSITION
COOLING VALVE
HEATING VALVE
VTR8300 Onboard PIR Sensor
SC3500E5000
AND / OR
Door Switch
SED-DOR-P-5000 Refer to the Wireless Door and Window Switch Installation Guide for the door pairing procedure.
Configuration Parameter Name Fan Menu Fan cont. heat. BI2 Pulsed heating Pipe no. Seq. operation
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
Configuration Settings L-M-H-A On Door Dry Off 4 Ht - Cl
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Remote PIR Sensor
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
5
SC3500E5000
1 Tx/Rx Com
Sequence of Operation and Wiring
Options
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
•
BACnet® and Wireless communication models available (see Appendix B for network wiring).
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating.
•
Can be configured for 2-pipe systems (without changeover).
•
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback.
Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closed. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closed. Wireless Door Switch Wireless door switch automatically toggles occupancy. Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
7 VDC
3 Com
SCom
Tx / Rx
UI 17 - BI2
2 7 Vdc
UI 16 - BI1
BACnet REF
BACnet-
BACnet+
VTR8300
Fax: (514) 321-4150 February 2015
Application Guide
6
VTR8300 Fan Coil Controller
VTR8350AXxXX with SC3404E5000 Relay: Cooling and electric heat 2-pipe fan coil unit with 3-speed fan, dehumidification and 2-position valves
Fan
Airflow Direction
Cooling Coil
Electric Heating
2 POSITION COOLING VALVE
VTR8300
SSR
SOLID STATE RELAY (GENERIC)
SC3404E5000
Configuration parameter name
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
L-M-H-A On On 2 Ht-Cl
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Fan menu Fan cont. heat Pulsed heating Pipe no. Seq. operation
Configuration settings
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
7
SC3404E5000
1 Tx/Rx 2 7 Vdc 3 Com
Com
7 VDC
Tx / Rx
VTR8300
4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 Heat -
SCom
Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary. Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Options •
BACnet® and Wireless communication models available (see Appendix B for network wiring).
•
Remote wall mount or return duct sensor ready.
•
Can be configured for 2-pipe systems with changeover.
•
Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring.
•
Universal input can be configured for changeover sensor.
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
UI 17 - BI2
SOLIDSTATE (-) RELAY (4-32Vdc) (+) UI 16 - BI1
BACnet REF
BACnet-
BACnet+
10 Heat +
Fax: (514) 321-4150 February 2015
Application Guide
8
VTR8300 Fan Coil Controller
VTR8300AxPxx with SC3504E5000 relay: Heating/cooling with changeover sensor 2-pipe fan coil unit with 3-speed fan and wireless window switch
Window Switch
SED-WIN-P-5000 Fan
Airflow Direction
Cooling / Heating Coil
Supply Sensor
2 POSITION
SENSOR
COOLING VALVE / HEATING VALVE
VTR8300 C/O
AND / OR
SENSOR
Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2
SC3504E5000
Onboard PIR Sensor
Configuration Parameter Name
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
L-M-H-A On Window COS 2 Cool
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Fan Menu Fan cont BI1 RUI1 Pipe No Seq. operation
Configuration Settings
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
9
SC3504E5000
1 Tx/Rx
VTR8300
3 Com
Com
7 VDC
Tx / Rx
2 7 Vdc 4 RUI 1 5 SCom 6 RBI 2
SCom
Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Wireless Window Switch Wireless window switch automatically locks out heating/cooling when window is opened.
Options •
BACnet® and Wireless communication models available (see Appendix B for network wiring).
•
Remote wall mount or duct sensor ready.
•
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
On Call for Heat If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature. Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
UI 17 - BI2
UI 16 - BI1
BACnet REF
BACnet-
BACnet+
7 SS 8 RS
Fax: (514) 321-4150 February 2015
Application Guide
10
VTR8300 Fan Coil Controller
VTR8350Axxxx with SC3400E5000 relay: Cooling and electric heat 2-pipe fan coil unit with 3-speed fan, dehumidification and 2-position valves
Fan
Airflow Direction
Cooling Coil
Electric Heating
2 POSITION COOLING VALVE
VTR8300
SSR
SOLID STATE RELAY (GENERIC)
SC3400E5000
Configuration parameter name
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
L-M-H-A On On 2 Cool-Rht
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Fan menu Fan cont. heat. Pulsed Heating Pipe No Seq. operation
Configuration settings
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
11
SC3400E5000
1 2 3
Com
7 VDC
Tx / Rx
VTR8300
9
SCom
Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature.
On a Demand for Dehumidification Dehumidification achieved via cooling coil using reheat if necessary. Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode. Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Options •
BACnet® and Wireless communication models available (see Appendix B for network wiring).
•
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closed and dehumidification is disabled.
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
UI 17 - BI2
SOLIDSTATE (-) RELAY (4-32Vdc) (+) UI 16 - BI1
BACnet REF
BACnet-
BACnet+
10
Fax: (514) 321-4150 February 2015
Application Guide
12
VTR8300 Fan Coil Controller
VTR8300AxxxX with SC3514E5000 Relay: Heating/cooling 2-pipe fan coil unit with 3-speed fan, fresh air damper and 2-position valves
Fresh Air
Fan
Airflow Direction
DAMPER
Cooling / Heating Coil
Supply Sensor
2 POSITION
SENSOR
COOLING VALVE / HEATING VALVE
Return Air
VTR8300 C/O
Supply Sensor: 10K Ohm type 2.
SENSOR
Changeover Sensor: 10K Ohm type 2.
SC3514E5000
Configuration Parameter Name
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
L-M-H-A On Window COS Occ Out 2 Cool
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Fan menu Fan cont. heat BI1 RUI1 Pulsed Heating Pipe no. Seq. operation
Configuration Settings
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
13
SC3514E5000
1 Tx/Rx
VTR8300
3 Com
Com
Tx / Rx
7 VDC
2 7 Vdc 4 RUI 1 5 SCom 6 RBI 2 7 SS 8 RS 9 OCC -
SCom
Sequence of Operation and Wiring
On Call for Heat
Occupied Mode Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter.
If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected.
Options •
BACnet® and Wireless communication models available (see Appendix B for network wiring).
•
Remote wall mount or return duct sensor ready.
•
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes.
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
UI 17 - BI2
UI 16 - BI1
BACnet REF
BACnet-
BACnet+
7Vdc RELAY COIL
Fax: (514) 321-4150 February 2015
Application Guide
14
VTR8300 Fan Coil Controller
VTR8300Axxxx with SC3500E5000 and SC3300E5000 RELAYS: Heating/cooling 4-pipe fan coil unit with 3-speed fan and 2-position valves with slave relay pack
Fan
Airflow Direction
Cooling Coil
Heating Coil
2 POSITION
2 POSITION
COOLING VALVE
HEATING VALVE
VTR8300
SC3300E5000
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
Configuration Settings L-M-H-A On 4 Ht-Cl
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Configuration Parameter Name Fan menu Fan cont. heat Pipe No Seq. operation
SC3500E5000
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
15
SC3500E5000T
1 2 3
Com
7 VDC
Tx / Rx
VTR8300
SC3300E5000 1 2
Sequence of Operation and Wiring
Options
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
•
BACnet® and Wireless communication models available (see Appendix B for network wiring).
•
Can be configured for 2-pipe systems without changeover.
•
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
SCom
UI 17 - BI2
UI 16 - BI1
BACnet REF
BACnet-
BACnet+
3
Fax: (514) 321-4150 February 2015
Application Guide
16
VTR8300 Fan Coil Controller
VTR8300AXPxx with SC3504E5000 relay: Cooling and electric heat 2-pipe fan coil unit with 3-speed fan and 2-position valves with wired window switch
Window Switch
SED-WIN-P-5000
Fan
Airflow Direction
Cooling / Heating Coil
Supply Sensor
2 POSITION
SENSOR
COOLING VALVE / HEATING VALVE
VTR8300 C/O
SENSOR
AND / OR
Changeover Sensor: 10K Ohm type 2 Supply Sensor: 10K Ohm type 2
SC3504E5000 Onboard PIR Sensor
Configuration Parameter Name
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
L-M-H-A On Window COS 2 Cool
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Fan menu Fan cont. heat BI1 RUI1 Pipe no. Seq. operation
Configuration Settings
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
17
SC3504E5000
1 Tx/Rx 2 7 Vdc 3 Com
Com
7 VDC
Tx / Rx
VTR8300
4 RUI 1 5 SCom 6 RBI 2
SCom
SCom
Sequence of Operation and Wiring Occupied Mode Setpoints revert to those defined by occupied cooling and heating. Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes. On Call for Heat If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes.
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Wired Window Switch The window switch automatically locks out heating/cooling when window opens.
Options •
BACnet® and Wireless communication models available (see Appendix B for network wiring).
•
Models available with factory installed PIR sensor.
•
Remote wall mount or duct sensor ready.
•
Can be configured for 2-pipe systems with changeover.
•
Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring.
•
Universal input can be configured for changeover sensor.
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
BI1 (Window)
UI 17 - BI2
UI 16 - BI1
BACnet REF
BACnet-
BACnet+
7 SS 8 RS
Fax: (514) 321-4150 February 2015
Application Guide
18
VTR8300 Fan Coil Controller
VTR8300AXPxx with SC3500E5000 RELAY: Heating/cooling 4-pipe fan coil unit with 3-speed fan and 2-position valves with wired door switch
Fan
Airflow Direction
Cooling Coil
Heating Coil
2 POSITION
2 POSITION
COOLING VALVE
HEATING VALVE
VTR8300 Onboard PIR Sensor
SC3500E5000
AND / OR
Door Switch
SED-DOR-P-5000
Viconics Technologies Inc. 028-6047-03
|
Configuration Parameter Name
Configuration Settings
Fan menu Fan cont. heat BI2 Pipe No Seq. Operat
L-M-H-A On Door Dry 4 Ht-Cl
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Remote PIR Sensor
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
19
SC3500E5000
1 Tx/Rx
VTR8300 Com SCom
UI 17 - BI2
3 Com
SCom
Sequence of Operation and Wiring
Options
Occupied Mode Setpoints revert to those defined by occupied cooling and heating.
•
BACnet® and Wireless communication models available (see Appendix B for network wiring).
•
Models available with factory installed PIR sensor.
•
Can be configured for 2-pipe systems without changeover.
•
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Stand-by Mode (only available when PIR motion detector sensor is used) Setpoints revert to those defined by stand-by cooling and heating. Unoccupied Mode Setpoints revert to those defined by unoccupied heating and cooling. Occupied Override Mode System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Door Switch Door switch automatically toggles occupancy. Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
BI2 (Door)
UI 16 - BI1
BACnet REF
BACnet-
BACnet+
Tx / Rx
7 VDC
2 7 Vdc
Fax: (514) 321-4150 February 2015
Application Guide
20
VTR8300 Fan Coil Controller
Appendix A - Passive infra-red (PIR) motion detector cover specifications PIR cover sequence of operation
Initially, the controller is in Stand-by mode. Stand-by setpoints are used at the controller. As soon as the PIR detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The Occupied setpoints are used. If no motion is detected in the room for the entire Stand-By Time duration (adjustable parameter), the room then switches to Stand-by mode and stand-by setpoints are used. While in Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied mode, any motion will switch the room back to Occupied mode.
Typical Detection Pattern for PIR Lens Horizontal Angles (Typical)
Vertical Angle (Typical)
Transverse motion: 4-5 ft/s / 1.5 m/s
Recommended installation height for PIR sensor: 4 - 5 ft. / 1.2-1.5 m Sensor Ranges
A = 20 ft. / 6.1 m B = 14 ft. / 4.3 m C = 11 ft. / 3.4 m
40O
A
Center
30O
20O
20O
B
B 20O
20O
C
C Center
Energy savings Typical Savings of 10-30% 85 80
50%
30%
50 45 40 35
20%
30 25 20
10%
15 10 5 0
0% 0
2
4
6
8
10
12
14
16
18
20
22
24
Time of Day (EST) Typical Consumption
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
PIR Thermostat Consumption
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
Savings
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
40%
65 60 55
Saving Percentage
The PIR can maximize your energy saving from 10-30% by relaxing temperature set points in unoccupied zones during scheduled periods.
Energy Usage (KWh)
75 70
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
21
Appendix B - option network wiring if communicating models are used Wireless Communication
BACnet® communication wiring BACnet thermostat 1 BACnet thermostat 2 BACnet thermostat 3
+ -
ref
+ -
ref
+ -
ref
Notes: - Wiring should be daisy chained - Respect polarity - If using 2 conductors shielded wires, connect the shield of each feed together on the back of the controller. ONLY ground the shield at one location. DO NOT connect the shield to the ref terminal.
No communication wires required
Appendix C - controllers’ occupancy sequence of operation schematic Setpoints 26.5°C 80°F
Unoccupied cool 24.5°C 76°F
Stand-by cool 22°C 72°F
Occupied cool
22°C 72°F
Deadband 70°F 21°C
70°F 21°C
Stand-by heat
Stand-by time
66°F 19°C Unoccupied time
Unoccupied heat
Movement detected Stand-by timer reset
|
9245 Langelier Blvd.
|
Into Stand-by mode Unoccupied timer reset
62°F 16.5°C
Into Unoccupied mode
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Time
Next movement detected
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Occupied heat
Viconics Technologies Inc. 028-6047-03
Deadband
Deadband
Fax: (514) 321-4150 February 2015
Application Guide
22
VTR8300 Fan Coil Controller
Appendix D - sed series - wireless door & window switch Wireless ZigBee ® Pro door & window switch Wireless door switches used with an onbaord or remote PIR sensor provide advanced local occupancy routines allowing for increased energy savings during occupied hours without sacrificing occupant comfort. Wireless window switches are used to monitor exterior windows and or patio and balcony doors being opened or closed. This prevents unnecessary energy consumption by the tenants. Fan Coil Terminal Equipment Controllers with SED Series ZigBee® wireless switches can be used in network ready mode with or without integration to a central management system to allow for advanced functions such as central reservation and occupancy functions. A combination of up to twenty SED Series door and or window switches can be used simultaneously with a single Fan Coil Terminal Equipment Controller. The SED Series switches are factory delivered with 2 AAA batteries and are ready to be installed, configured and used right out of the box. Due to the extremely small current consumption of the switches, the expected battery life is approximately 10 years and is equivalent to the battery shelf life. No tools are required for commissioning or servicing the door switch. A very simple interface with an onboard LED & hidden switch provides all the required functions for local interaction. Local information for battery life and connectivity (heartbeat) are provided at the Fan Coil Terminal Equipment Controller local display through the ZigBee® wireless network. Each switch is factory supplied with a magnet, a locking security tamper proof screw and self tapping mounting screws.
Model selection Window Switch
Door Switch
SED-WIN-P-5045
SED-DOR-P-5045
Hidden Switch
Pull Tab
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
LED (switch side)
Fax: (514) 321-4150 February 2015
Application Guide
VTR8300 Fan Coil Controller
23
Appendix E - VTR8300 controller & SC3000 relay pack Product overview The VTR8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil unit thermostats. The VTR8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet® MSTP or wireless ZigBee® Pro networked models. No previous building automation training is required for the easy installation and commissioning process. Installation can be completed in approximately fifteen minutes, reducing costs and providing increased savings. The SC3000 Series Line Voltage Switching Transformer Relay Pack Controllers has been designed for silent control of typical high voltage fan coil device loads (90 to 277 VAC multi-voltages capable). It uses advanced microprocessor-based circuitry with a built-in transformer that eliminates all typical required peripheral components when automating a Fan Coil unit with traditional building automation systems. The SC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single master VTR8300 Terminal Equipment Controller. A single VTR8300 Terminal Equipment Controller can control up to 10x SC3000 Series Relay Pack. The SC3000 Series Relay Packs are line-powered units. The extremely compact unit locally contains all the relay outputs for fan switching and valve control. Models are also available for extra monitoring / control inputs of the Fan Coil Units.
Typical fan coil unit setup
Typical Fan Coil Unit
H
C
C
C
1 Tx/Rx 2 7 Vdc Power Supply
3 Com
SC3404E5000
4 RUI 1 5 SCom 6 RBI 2
Electrical Cabinet
WHITE
90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC
7 SS 8 RS
BLACK
9 Heat 10 Heat +
FAN LOW
1/2 HP or 13A FAN MED Max
5A Max
RED BLUE
FAN HIGH
BROWN
COOL
YELLOW
1 Tx/Rx 2 7 Vdc 3 Com
Power Supply
4 RUI 1 5 SCom
xxx-xxxx-xx
6 RBI 2
WHITE
90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC
7 SS 8 RS 9 Heat 10 Heat +
BLACK
FAN LOW
1/2 HP or 13A FAN MED Max
5A Max
RED BLUE
FAN HIGH
BROWN
COOL
YELLOW
Mixed daisy chained and Star topology
Daisy chained topology
Star topology
Viconics Technologies Inc. 028-6047-03
|
9245 Langelier Blvd.
|
St.-Leonard | Quebec | Canada | www.viconics.com |
[email protected]
H1P 3K9
|
Tel: (514) 321-5660
|
© 2015 Viconics Technologies Inc. All rights reserved.
Low Voltage Connections to VTR8300 Controller