Indoor Units FBQ-C7VEB
air conditioning systems
technical data
Indoor Units FBQ-C7VEB
air conditioning systems
technical data
• Indoor Units • R-410A • FBQ-C7VEB
TABLE OF CONTENTS FBQ-C7VEB
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 For indoor units only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 3
3
Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 7 Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Wiring diagram
8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
9
Fan characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filter installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch box connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
• Split Sky Air • Indoor Units
13
21 22
1
• Indoor Units • R-410A • FBQ-C7VEB
1 t i y n k BU S E V r a7t o 0C i o 1- ld 4Q npB- RFS•I
Features Reduction in power consumption thanks to DC inverter fans
•
Home leave operation saves energy during absence
•
Improved comfort thanks to 3-step airflow control
•
Whisper quiet operation: down to 26 dBA sound pressure level
•
Maximum external static pressure (ESP) is 100Pa
•
1
•
Possibility to change ESP through wired remote control allows optimisation of the supply air volume
Standard air filter: removes airborne dust particles to ensure a steady supply of clean air
•
1
•
Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible
Easy installation thanks to automatic air flow adjustment towards nominal air flow rate
•
•
Energy efficient: up to class A energy labels
Built-in drain pump as standard increases reliability of the drain system
optional
via wired remote control
2
standard
3 steps
optional
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
2
Specifications
2-1 For indoor units only Nominal input (Indoor only)
Dimensions
FBQ71C7VEB
FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
0.14
0.14
0.35
0.35
0.35
0.35
0.35
Heating
kW
0.14
0.14
0.35
0.35
0.35
0.35
0.35
FBQ35C7VEB
FBQ50C7VEB
FBQ60C7VEB
FBQ71C7VEB
Colour
Non painted
Material
Galvanised steel
Packing
FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
Height
mm
355
355
355
355
355
355
355
mm
920
920
1,220
1,220
1,620
1,620
1,620
Depth
mm
900
900
900
900
900
900
900
Height
mm
300
300
300
300
300
300
300
Width
mm
700
700
1,000
1,000
1,400
1,400
1,400
Depth
mm
700
700
700
700
700
700
700
Unit
kg
25
25
34
34
45
45
45
Packed Unit
kg
28
28
41
41
53
53
53
440
440
740
740
1,140
1,140
1,140
3
3
3
3
3
3
3
mm
1.75
1.75
1.75
1.75
1.75
1.75
1.75
4
4
7
7
11
11
11
m²
0.148
0.148
0.249
0.249
0.383
0.383
0.383
16
16
16
16
16
16
16
mm Dimensions
Length
mm
Nr of Passes Face Area Nr of Stages Tube type Fin
Hi-XSS (7) Type
Symmetric waffle louvre
Treatment
Hydrophilic
Fan
Type
Air Flow Rate
Cooling
Sirocco fan High Low
m³/min
11
11
15
15
23
28
28
Heating
High
m³/min
16
16
18
18
32
39
41
Low
m³/min
11
11
15
15
23
28
29
Max
High
Pa
100
100
100
100
100
100
100
Standard
Pa
30
30
30
30
40
50
50
Motor
Quantity
1
1
1
1
1
1
1
Quantity
Fan
m³/min
1
1
2
2
3
3
3
16
16
18
18
32
39
39
Model
Brushless DC
Number of steps Motor
Fan
Speed (cooling)
High
rpm
10
10
8
8
9
9
9
1,186
1,186
942
942
1,060
1,218
1,218
Low
rpm
875
875
823
823
813
920
920
Speed (heating)
High
rpm
1,186
1,186
942
942
1,060
1,218
1,280
Low
rpm
875
875
823
823
813
920
967
Motor
Output (high)
W
140
140
350
350
350
350
350
Drive Cooling
Heating
Direct drive
Sound Power
High
dBA
63
63
57
57
61
66
66
Sound Pressure
High
dBA
37
37
37
37
38
40
40
Low
dBA
29
29
29
29
32
33
33
High
dBA
37
37
37
37
38
40
41
Low
dBA
29
29
29
29
32
33
34
9.52
9.52
9.52
15.9
15.9
15.9
625
625
625
Sound Pressure
Refrigerant
Type
Piping connections
Liquid (OD)
Type
Gas
Type
R-410A Diameter (OD)
Drain
Flare connection mm
6.35
6.35
6.35
9.52 Flare connection
Diameter (OD)
mm
Diameter (OD)
mm
9.52
12.7
12.7
15.9 VP25 (O.D. 32 / I.D. 25)
Heat Insulation Drain-up Height
1
>350
Nr of Rows Fin Pitch
3 2
Width
Required Ceiling Void Heat Exchanger
FBQ60C7VEB
kW
Unit
Weight
FBQ50C7VEB
Cooling
2-2 Technical Specifications Casing
FBQ35C7VEB
Both liquid and gas pipes mm
625
• Split Sky Air • Indoor Units
625
625
625
3
• Indoor Units • R-410A • FBQ-C7VEB
2
Specifications
2-2 Technical Specifications
FBQ35C7VEB
FBQ50C7VEB
FBQ60C7VEB
FBQ71C7VEB
Decoration Panel
BYBS45DJW1
BYBS45DJW1
BYBS71DJW1
BYBS71DJW1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1
Model Colour Dimensions
1 2
Weight
FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
White (10Y9/0,5) H
mm
55
55
55
55
55
55
55
W
mm
800
800
1,100
1,100
1,500
1,500
1,500
D
mm
500
500
500
500
500
500
500
kg
3.5
3.5
4.5
4.5
6.5
6.5
6.5
Air Filter
Resin net with mold resistance
Safety Devices
PC board fuse PC board fuse (fan driver) Drain pump fuse
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m. Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. The sound pressure values are mentioned for a unit installed with rear suction
Remote Control
4
Wired
BRC1D528
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
3
Safety device settings Safety devices PC Board Fuse FBQ
PC Board Fuse (Fan Driver)
35
50
60
71
100
125
140
250V 3.15A
250V 3.15A
250V 3.15A
250V 3.15A
250V 3.15A
250V 3.15A
250V 3.15A 250V 6.3A
250V 5A
250V 5A
250V 6.3A
250V 6.3A
250V 6.3A
250V 6.3A
Fan Motor Thermal Protector
°C
—
—
—
—
—
—
—
Drain Pump Fuse
°C
145
145
145
145
145
145
145
3 1 3
4
Options
FBQ35-140C Options Item Panel related Air inlet and air discharge outlet related
Type
FBQ35
Decoration panel Air discharge adapter for round duct
FBQ50 BYBS45D KDAJ25K56A
FBQ60,71 BYBS71D KDAJ25KA71A
FBQ100,125,140 BYBS125D KDAJ25KA140A
FBQ60,71
FBQ100,125,140
Operation Control Item Remote Control Wired Type Option BCB for external el. heater, humidifier and/or hour meter (*1), (*3) Adapter for wiring (interlock for fresh air intake fan) (*3) Wiring adapter for electrical appendices (*3) Central remote control Unified ON/OFF control Schedule timer Interface adapter for sky air series Remote ON/OFF and FORCED OFF kit Mounting plate for adapter PCB
Type
FBQ35
FBQ50 BRC1D528 EKRP1B2A KRP1BA54 KRP4A51 DCS302CA51 DCS301BA51 DST301BA51 DTA112BA51 EKRORO3 KRP4A96
NOTES (*1): Electrical heater and humidifier are field supply. These parts should not be installed inside the equipment (refer to installation manual EKRP1B2A) (*2): If installing an electrical heater, an option PCB for external heater (EKRP1B2) for each indoor unit is required. (*3): Mounting plate KRP4A96 is required for these options. Maximum 2 option PCB’s can be mounted.
Contents of accessory bag Description Hexagon tapping screw (M5x16) Round plain washer for wood Installation and operation manual Hose band Insulation for joint (GAS) Insulation for joint (LIQUID) Drain hose Drain hose sealing material Sealing material
Quantity FBQ35,50,60,71,100,125,140 16 8 1 1 1 1 1 1 2
3TW31279-3A
• Split Sky Air • Indoor Units
5
• Indoor Units • R-410A • FBQ-C7VEB
4
Options
EKRORO3
4
On
Terminal X2M Screw to control box replacing the original terminal
INPUT
1
Operating method
Wire specifications
Connector (White)
T1,T2Switch Off Remote controller
On Off
unit
connect to indoor PCB (X30A)
Standard On setting: ’forced off’ Off Alternative setting: ’on/off’
On Off
Input ’ON’ = closed contact.
Forced off
On/off operation
Input ’on’ stops operation + disables control Input ’off’ enables control
Input off→on: starts operation, remote control is still enabled. Input on→off: stops operation, remote control is still enabled.
Selection of ’FORCED OFF’ and ’ON/OFF’ operation
Setting
Mode No.
First code NO
Forced off On/off operation
12 (22)
1
Second code NO 01 02
3TW31601-1
6
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
3
FBQ35C NOTES
1 2 View A-A
3
Detail B
Refer to ‘outlook drawing for installing optional accessories’ when installing optional accessories. The required ceiling depth varies according to the configuration of the specific system. For maintenance of the air filter, it is necessary to provide a service access panel. Refer to the ‘filter installation method’ drawing
1 5
or more (service space)
suspension bolt
or more (service space)
Detail B
(suspension position)
(suspension position)
Item 1 2 3 4 5 6 7 8 9 10
Name Liquid pipe connection Gas pipe connection Drain pipe connection Remote control wiring connection Power supply connection Drain hole Air filter Air suction side Air discharge side Nameplate
Description Ø6.35 flare connection Ø9.52 flare connection VP25 (OD Ø32, ID Ø25) VP25 (OD Ø32, ID Ø25) -
3TW31274-1 FBQ50C
Detail B
View A-A
350 or more (Service space)
Suspension bolt
or more (Service space)
Detail B
(Suspension position)
(Suspension position)
Nr
Name
Description
1 2 3 4 5 6 7 8 9 10
Liquid pipe connection Gas pipe connection Drain pipe connection Remote control wiring connection Power supply connection Drain hole Air filter Air suction side Air discharge side Nameplate
ø 6.35 flare (connection) ø 12.70 (flare connection) VP25 (O.D. ø 32 /I.D. ø 25)
NOTE
1 2
VP25 (OD ø 32 /I.D. ø 25)
3
Refer to ‘outlook drawing for installing optional accessories’ when installing optional accessories. The required ceiling depth varies according to the configuration of the specific system. For maintenance of the air filter, it is necessary to provide a service access panel. Refer to the ‘filter installation method’ drawing.
3TW31214-1
• Split Sky Air • Indoor Units
7
• Indoor Units • R-410A • FBQ-C7VEB
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
FBQ60C
1 5
View A-A Detail B
350 or more (Service space)
Suspension bolt
Detail B
or more (Service space)
(Suspension position)
(Suspension position)
Nr 1 2 3 4 5 6 7 8 9 10
Name Liquid pipe connection Gas pipe connection Drain pipe connection Remote control wiring connection Power supply connection Drain hole Air filter Air suction side Air discharge side Nameplate
NOTE
Description ø 6.35 flare (connection) ø 12.70 (flare connection) VP25 (O.D. ø 32 /I.D. ø 25)
1
VP25 (OD ø 32 /I.D. ø 25)
3
2
Refer to ‘outlook drawing for installing optional accessories’ when installing optional accessories. The required ceiling depth varies according to the configuration of the specific system. For maintenance of the air filter, it is necessary to provide a service access panel. Refer to the ‘filter installation method’ drawing.
3TW31294-1 FBQ71C
View A-A Detail B
350 or more (Service space)
Suspension bolt
Detail B
or more (Service space)
(Suspension position)
(Suspension position)
Nr 1 2 3 4 5 6 7 8 9 10
Name Liquid pipe connection Gas pipe connection Drain pipe connection Remote control wiring connection Power supply connection Drain hole Air filter Air suction side Air discharge side Nameplate
NOTE
Description ø 9.52 flare (connection) ø 15.90 (flare connection) VP25 (O.D. ø 32 /I.D. ø 25)
1
VP25 (OD ø 32 /I.D. ø 25)
3
2
Refer to ‘outlook drawing for installing optional accessories’ when installing optional accessories. The required ceiling depth varies according to the configuration of the specific system. For maintenance of the air filter, it is necessary to provide a service access panel. Refer to the ‘filter installation method’ drawing.
3TW31234-1
8
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing
3
FBQ100-140C
1 5
View A-A Detail B
350 or more (Service space)
Suspension bolt
Detail B
or more (Service space)
(Suspension position)
(Suspension position)
Nr
Name
Description
1 2 3 4 5 6 7 8 9 10
Liquid pipe connection Gas pipe connection Drain pipe connection Remote control wiring connection Power supply connection Drain hole Air filter Air suction side Air discharge side Nameplate
ø 9.52 flare (connection) ø 15.90 (flare connection) VP25 (O.D. ø 32 /I.D. ø 25)
NOTE
1 2
VP25 (OD ø 32 /I.D. ø 25)
3
Refer to ‘outlook drawing for installing optional accessories’ when installing optional accessories. The required ceiling depth varies according to the configuration of the specific system. For maintenance of the air filter, it is necessary to provide a service access panel. Refer to the ‘filter installation method’ drawing.
3TW31254-1
• Split Sky Air • Indoor Units
9
• Indoor Units • R-410A • FBQ-C7VEB
5
Dimensional drawing & centre of gravity
5-2
Centre of gravity
FBQ35-140C
1 5
MODEL FBQ35,50 FBQ60,71 FBQ100~140
A 283 441 619
B 700 1000 1400
4TW31189-1A
10
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
6
Piping diagram
3
FBQ35-140C
Heat exchanger
1
Refrigerant flow Cooling Heating
6
Refrigerant pipe connection port diameters Model FBQ35C FBQ50C FBQ60C FBQ71C FBQ100C FBQ125C FBQ140C
Gas 9.52 12.70 12.70 15.90 15.90 15.90 15.90
Liquid 6.35 6.35 6.35 9.52 9.52 9.52 9.52
Liquid pipe connection port
Gas pipe connection port
3TW31275-1
• Split Sky Air • Indoor Units
11
• Indoor Units • R-410A • FBQ-C7VEB
7
Wiring diagram
7-1
Wiring diagram
FBQ35-50C7VEB L N
indoor
1
,
: Connector : Wire clamp : Protective earth (screw)
norm.emg
7
Transmission wiring central remote control note 2
1N~220-240V 50Hz 1N~220V 60Hz
Colors BLK BLU BRN GRY ORG PNK RED WHT YLW GRN
wired remote control (optional accessory)
Common power supply note 4
Switch box (indoor) Indoor unit A1P A2P C1 F1U, F2U F4U HAP KPR, K1R L1R
Printed circuit board Printed circuit board (fan) Capacitor Fuse (T, 5A, 250V) Fuse (T, 6.3A, 250V) Light emitting diode (Service monitor green) Magnetic relay Reactor
M1F M1P PS Q1DI R1 R2 R1T R2T R3T
Motor (fan) Motor (drain pump) Switching power supply Earth leak detector Resistor (current limiting) Current sensing device Thermistor (suction air) Thermistor (liquid) Thermistor (gas)
SS1 S1L V1R V2R X1M X2M Z1C Z1F RC
Selector switch (emergency) Float switch Diode bridge Power module Terminal strip (power supply) Terminal strip (control) Noise filter (ferrite core) Noise filter Signal receiver circuit
TC
: Field wiring : Live : Neutral
: Black : Blue : Brown : Gray : Orange : Pink : Red : White : Yellow : Green
Signal transmission circuit
Connector optional accessory X28A X33A X35A X85A X33A
Connector (Power supply for wiring) Connector (for wiring) Connector (adapter) Connector (for multi zoning) Connector (for wiring)
SS1
Selector switch (emergency)
Wired remote control
2TW31276-1A NOTES
1 2 3 4
Use copper conductors only. When using the central remote controller, see manual for connection to the unit. The remote control model varies according to the combination system. See technical materials and catalogues, etc. before connecting. Refer to installation manual.
FBQ60-140C7VEB
only for 60 class
only for 60 class
L N ,
: Connector : Wire clamp : Protective earth (screw)
NORM. EMG
Transmission wiring central remote control note 2
1N~220-240V 50Hz 1N~220V 60Hz
Wired remote control (optional accessory) Common power supply note 4
: Field wiring : Live : Neutral
Colors BLK BLU BRN GRY ORG PNK RED WHT YLW GRN
: Black : Blue : Brown : Gray : Orange : Pink : Red : White : Yellow : Green
Switch box (indoor) A1P A2P A3P C1, C2, C3 F1U F3U HAP KPR, K1R
Indoor unit Printed circuit board Printed circuit board (fan) Printed circuit board (capacitor) Capacitor Fuse (T, 5A, 250V) Fuse (T, 6.3A, 250V) Light emitting diode (service monitor green) Magnetic relay
L1R M1F M1P PS Q1DI R2 R3, R4 R1T R2T
Reactor Motor (fan) Motor (drain pump) Switching power supply Earth leak detector Current sensing device Resistor (electric discharge) Thermistor (suction air) Thermistor (liquid)
R3T R5T SS1 S1L V1R V2R Z1C Z1F RC
Thermistor (gas) Thermistor NTC (Current limiting) Selector switch (emergency) Float switch Diode bridge Power module Noise filter (ferrite core) Noise filter Terminal strip (power supply)
TC Y1E X33A X35A X38A R1T SS1
Terminal strip (control) Electronic expansion valve Connector optional accessory Connector (for wiring) Connector (adapter) Connector (for wiring) Wired remote control Thermistor (air) Selector switch (main/sub)
2TW31296-1A NOTES
1 2 3 4
12
Use copper conductors only. When using the central remote controller, see manual for connection to the unit. The remote control model varies according to the combination system. See technical materials and catalogues, etc. before connecting. Refer to installation manual.
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
8
Sound data
8-1
Sound pressure spectrum
FBQ35-50C
3
FBQ60C
8
Sound pressure level [dB]
Sound pressure level [dB]
1
Octave band center frequency (Hz)
Octave band center frequency (Hz)
High-tap
High-tap
Medium-tap
Medium-tap
Low-tap
Low-tap
3TW31217-2
3TW31297-2
NOTES
1 2 3 4 5
NOTES
Data is valid at free field condition Data is valid at nominal operation condition dBA= A-weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressures 0dB = 20μPa Location of microphone Unit
Suction
1 2 3 4 5
Discharge
Data is valid at free field condition Data is valid at nominal operation condition dBA= A-weighted sound pressure level. (A-scale according to IEC) Reference acoustic pressures 0dB = 20μPa Location of microphone Unit
Suction
Microphone
Discharge
Microphone
Sound pressure level [dB]
FBQ100C
Sound pressure level [dB]
FBQ71C
Octave band center frequency [dB]
Octave band center frequency [dB]
High-tap Medium-tap Low-tap
High-tap Medium-tap Low-tap 3TW31297-2
3TW31257-2
Notes
Data is valid at free field condition Data is valid at nominal operation condition dBA = A-weighted sound power level. (A-scale according to IEC) Reference acoustic pressures 0dB = 20μPa Location of microphine 1.5m
Suction
Unit
2m 1.5m
2m
Discharge
Microphone 1m
1 2 3 4 5
Data is valid at free field condition Data is valid at nominal operation condition dBA = A-weighted sound power level. (A-scale according to IEC) Reference acoustic pressures 0dB = 20μPa Location of microphine Suction 1.5m
Notes 1 2 3 4 5
Unit
2m 1.5m
2m
Discharge
Microphone 1m
• Split Sky Air • Indoor Units
13
• Indoor Units • R-410A • FBQ-C7VEB
8
Sound data
8-1
Sound pressure spectrum
FBQ125C
FBQ140C
Sound pressure level [dB]
8
Sound pressure level [dB]
1
Octave band center frequency [dB]
Octave band center frequency [dB]
High-tap Medium-tap Low-tap
High-tap Medium-tap Low-tap 3TW31267-2
3TW31337-2
Notes
Data is valid at free field condition Data is valid at nominal operation condition dBA = A-weighted sound power level. (A-scale according to IEC) Reference acoustic pressures 0dB = 20μPa Location of microphine 1.5m
Suction
Unit
2m 1.5m
2m
Discharge
Microphone 1m
14
1 2 3 4 5
Data is valid at free field condition Data is valid at nominal operation condition dBA = A-weighted sound power level. (A-scale according to IEC) Reference acoustic pressures 0dB = 20μPa Location of microphine Suction 1.5m
Notes 1 2 3 4 5
Unit
2m 1.5m
Discharge
Microphone 1m
• Split Sky Air • Indoor Units
2m
• Indoor Units • R-410A • FBQ-C7VEB
8
Sound data
8-2
Sound power spectrum
FBQ35-50C
3
FBQ60C
8
Sound power level [dB]
Sound power level [dB]
1
Octave band center frequency (Hz)
Octave band center frequency (Hz)
High-tap
High-tap
Medium-tap
Medium-tap
Low-tap
Low-tap
3TW31217-1
3TW31297-1
NOTES
1 2 3
NOTES
dBA= A-weighted sound power level. (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744
1 2 3
Sound pressure level [dB]
FBQ100C
Sound pressure level [dB]
FBQ71C
dBA= A-weighted sound power level. (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744
Octave band center frequency [dB]
Octave band center frequency [dB]
High-tap Medium-tap Low-tap
High-tap Medium-tap Low-tap 3TW31297-1
3TW31257-1
Notes 1 2 3
Notes
dBA = A-weighted sound power level. (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744
• Split Sky Air • Indoor Units
1 2 3
dBA = A-weighted sound power level. (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744
15
• Indoor Units • R-410A • FBQ-C7VEB
8
Sound data
8-2
Sound power spectrum
FBQ125-140C
8
Sound pressure level [dB]
1
Octave band center frequency [dB]
High-tap Medium-tap Low-tap 3TW31267-1
Notes 1 2 3
16
dBA = A-weighted sound power level. (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
9
Fan characteristics
3
FBQ35-50C Fan characteristics (3) (airflow auto adjustment)
1
H (max ESP)
Upper limint of ESP (max ESP )
External static pressure [Pa]
External static pressure [Pa]
Fan characteristics (1)
Lower limit of ESP (max ESP)
M (max ESP) L (max ESP) Upper limint of ESP (std ESP )
H (std ESP) M (std ESP)
9
Upper limint of ESP Upper limint of ESP by airflow auto adjustment H M Upper limint of ESP by airflow auto adjustment
L
Lower limit of ESP (std ESP)
L (std ESP)
Lower limit of ESP
Airflow [m3/min]
Airflow [m3/min]
Fan characteristics (2) (Field setting with remote control)
External static pressure [Pa]
Range of available air flow rate (H)
NOTES
1 2
Airflow [m3/min]
Fan characteristics as shown are in “fan only” mode. ESP: External static pressure 3TW31218-1
FBQ60C Fan characteristics (3) (airflow auto adjustment)
Upper limint of ESP (max ESP )
External static pressure [Pa]
External static pressure [Pa]
Fan characteristics (1)
H (max ESP) M (max ESP)
L (max ESP) Lower limit of ESP (max ESP) Upper limint of ESP (std ESP )
H (std ESP)
M (std ESP) L (std ESP)
Upper limint of ESP Upper limint of ESP by airflow auto adjustment
H M L
Upper limint of ESP by airflow auto adjustment
Lower limit of ESP (std ESP)
Lower limit of ESP
Airflow [m3/min]
Airflow [m3/min]
Fan characteristics (2) (Field setting with remote control)
External static pressure [Pa]
Range of available air flow rate (H)
NOTES 3/min]
Airflow [m
1 2
Fan characteristics as shown are in “fan only” mode. ESP: External static pressure 3TW31298-1
• Split Sky Air • Indoor Units
17
• Indoor Units • R-410A • FBQ-C7VEB
9
Fan characteristics
FBQ71C
9
Fan characteristics (3) (Airflow auto adjustment)
External static pressure [Pa]
1
External static pressure [Pa]
Fan characteristics (1)
H (max. ESP)
Upper limit of ESP (max. ESP) M (max. ESP)
Lower limit of ESP (max. ESP)
L (max. ESP)
Upper limit of ESP (std. ESP)
H (std ESP)
M (std ESP)
L (std ESP)
Upper limit of ESP
Upper limit of ESP by airflow auto adjustment H M L
Lower limit of ESP by airflow auto adjustment
Lower limit of ESP (std. ESP)
Lower limit of ESP
Airflow [m³/min]
Airflow [m³/min]
Fan characteristics (2) (Field setting with remote control)
External static pressure [Pa]
Range of available air flow rate (H)
NOTES
1 2
Airflow [m³/min]
Fan characteristics as shown ar in “fan only” mode. ESP: External static pressure 3TW31298-1
FBQ100C Fan characteristics (1)
Fan characteristics (3) (Airflow auto adjustment)
Lower limit of ESP (max. ESP)
M (max. ESP) L (max. ESP) Upper limit of ESP (std. ESP) L (std ESP)
H (std ESP) M (std ESP)
Upper limit of ESP by airflow auto adjustment
Upper limit of ESP
External static pressure [Pa]
External static pressure [Pa]
H (max. ESP) Upper limit of ESP (max. ESP)
H M L
Lower limit of ESP by airflow auto adjustment
Lower limit of ESP
Lower limit of ESP (std. ESP)
Airflow [m³/min]
Airflow [m³/min]
Fan characteristics (2) (Field setting with remote control)
External static pressure [Pa]
Range of available air flow rate (H)
NOTES
1 2
Fan characteristics as shown ar in “fan only” mode. ESP: External static pressure
Airflow [m³/min]
3TW31258-1
18
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
9
Fan characteristics
3
FBQ125C Fan characteristics (1)
Fan characteristics (3) (Airflow auto adjustment)
1
Upper limit of ESP
External static pressure [Pa]
External static pressure [Pa]
H (max. ESP) Upper limit of ESP (max. ESP) M (max. ESP) Lower limit of ESP (max. ESP)
L (max. ESP) H (std ESP)
Upper limit of ESP (std. ESP)
M (std ESP)
Lower limit of ESP (std. ESP)
L (std ESP)
9
Upper limit of ESP by airflow auto adjustment H M L
Lower limit of ESP by airflow auto adjustment Lower limit of ESP
Airflow [m³/min]
Airflow [m³/min]
Fan characteristics (2) (Field setting with remote control)
External static pressure [Pa]
Range of available air flow rate (H)
NOTES
1 2
Airflow [m³/min]
Fan characteristics as shown ar in “fan only” mode. ESP: External static pressure 3TW31268-1
FBQ140C Fan characteristics (3) (airflow auto adjustment)
H (max ESP)
Upper limint of ESP (max ESP )
External static pressure [Pa]
External static pressure [Pa]
Fan characteristics (1)
Lower limit of ESP (max ESP)
M (max ESP) H (std ESP) Upper limint of ESP L (max ESP) (std ESP ) Lower limit of ESP (std ESP) M (std ESP)
Upper limint of ESP Upper limint of ESP by airflow auto adjustment H
M L
Upper limint of ESP by airflow auto adjustment
Lower limit of ESP
L (std ESP)
Airflow [m3/min]
Airflow [m3/min]
Fan characteristics (2) (Field setting with remote control)
External static pressure [Pa]
Range of available air flow rate (H)
NOTES Airflow [m3/min]
1 2
Fan characteristics as shown are in “fan only” mode. ESP: External static pressure 3TW31268-1
• Split Sky Air • Indoor Units
19
• Indoor Units • R-410A • FBQ-C7VEB
10
Installation
10 - 1 Installation method FBQ35-140C
1
Rear Suction
Bottom Suction
Ceiling return
Ceiling return
10 Drain pump up height
Direct installation of inlet panel Installation with duct
Wide variety of installation methods Number 1 2 3 4 5
Description Main body Air outlet duct Inlet panel Acces panel Air inlet duct
Field supply Optional accessory optional accessory Field supply
Easy modification from rear to bottom suction
3TW31183-1
20
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FBQ-C7VEB
10
Installation
10 - 2 Filter installation method
3
FBQ35-140C (or less)
1 10
Installation without air inlet duct
Installation with air inlet duct
NOTES Nr. 1 2 3 4 5 6
Description Suspended Ceiling Ceiling opening Service access panel (optimal) Air filter Air inlet duct Duct service opening
1
2
When installing the unit with rear suction, a service opening is necessary for the maintenance of the air filters. When installing the unit with a suction duct. A service opening must be provided in the duct.
3TW31184-4
• Split Sky Air • Indoor Units
21
• Indoor Units • R-410A • FBQ-C7VEB
10
Installation
10 - 3 Switch box connection FBQ35-140C
1 10
Emerg. Norm.
Common power supply
3TW31184-5
22
• Split Sky Air • Indoor Units
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin units comply with the European regulations that guarantee the safety of the product.
Naamloze Vennootschap Zandvoordestraat 300 B-8400 Oostende, Belgium www.daikin.eu BTW: BE 0412 120 336 RPR Oostende
Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products.
The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for the environmont is set in the EMAS and ISO 14001 systems. Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende
Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intension to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.