Transcript
General Purpose US Fuses General Purpose US Fuses
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK TEL 0044 191 490 1547 FAX 0044 477 5371 TEL 0044 117 977 4647 FAX 0044 977 5582 WWW.THORNEANDDERRICK.CO.UK
General Purpose US Fuses
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000 AJT (Class J TD) ®
SMARTSPOT® with Maximum circuit protection Amp-trap 2000® SmartSpot® AJT fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product line the AJT fuse provides IEC Type “2” (No Damage) protection to main, feeder, and branch circuits, for all types of loads — yet, they require only half the mounting space needed for 600VAC Class RK fuses. AJT’s time delay characteristics for handling typical in-rush currents, its current limiting ability.
Highlights • • • • •
Features /Benefits • Solid State SmartSpot Indicator • Time delay for motor starting and transformer inrush • 300kA interrupting rating - self-certified, UL witnessed tests • Extremely current limiting for low peak let-thru current • Most current limiting UL class fuse • Small footprint requires less mounting space and allows smaller, more economical fuse blocks • Easy 2-to-1 selectivity for prevention of nuisance shutdowns • Unique Class J dimensions prevent replacement errors • High-visibility orange label gives instant recognition • Metal-embossed date and catalog number for traceability and lasting identification • Fiberglass body provides dimensional stability in harsh industrial settings • High-grade silica filler ensures fast arc quenching • Optional EI Indicator/Switch mount for AJT70 to 600 open fuse indication
Ratings
Smart Spot Indicator Time Delay Highly Current Limiting DC Ratings Optional Mechanical Indicator (70 to 600A fuses)
Applications • • • • • • • • • •
Motor Circuits Mains Feeders Branch Circuits Lighting, Heating and General Loads Transformers Control Panels Circuit Breaker Back-up Bus Duct Load Centers
Approvals AJT (1-600): • UL Listed to Standard 248-8 • DC Listed to UL Standard 198L • CSA Certified to Standard C22.2 No. 248.8 • IEC 269-2-1
AC: 1 to 600A 600VAC, 200kA I.R. (self certified for 600VAC, 300kA I.R.,UL witnessed) DC: 1 to 600A 500VDC, 100kA I.R.
GPUS1
AJT (70-600) EI: • UL Component Recognized • DC Tested to UL Standard 198L
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000 AJT (Class J TD) ®
Standard Fuse Ampere Ratings, Catalog Numbers and Ref Numbers Ampere Rating
1 1-1/4 1-1/2 1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10 3 3-2/10 3-1/2 4 4-1/2 5 5-6/10 6 6-1/4 7 8 9 10 12 15 17-1/2 20
Catalog Number
AJT1 AJT1-1/4 AJT1-1/2 AJT1-6/10 AJT1-8/10 AJT2 AJT2-1/4 AJT2-1/2 AJT2-8/10 AJT3 AJT3-2/10 AJT3-1/2 AJT4 AJT4-1/2 AJT5 AJT5-6/10 AJT6 AJT6-1/4 AJT7 AJT8 AJT9 AJT10 AJT12 AJT15 AJT17-1/2 AJT20
Reference Number
Ampere Rating
Catalog Number
25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600
AJT25 AJT30 AJT35 AJT40 AJT45 AJT50 AJT60 AJT70* AJT80* AJT90* AJT100* AJT110* AJT125* AJT150* AJT175* AJT200* AJT225* AJT250* AJT300* AJT350* AJT400* AJT450* AJT500* AJT600*
X214748 C215765 B215258 G216275 H216782 P219364 A200882 T223094 M201422 Q211683 L212714 W212194 W214241 Y214749 H216276 J216783 D217813 P218329 Q219365 M219891 D222574 Y217302 C217812 N218328 A218845 Z201939
Reference Number
X211160 W213229 M213727 C215259 D215766 Z217303 B218846 L201421* W211159* V212193* B215764* F216780* A217810* Y218843* K219889* Y200880* V211158* K212713* L213726* W214747* G216781* M218327* N219363* C222573*
*For optional indicator/switch mount add EI. For Example: AJT100EI .See table below Note: Indicator not available for rating 1A to 7A.
Recommended Fuse Blocks With Box Connectors for Amp-trap® Class J Fuses Fuse Ampere Rating
0-30 31-60 61-100 101-200 201-400 401-600
600V OR LESS 1 Pole Catalog Number
US3J1I US6J1I 61036J 62001J 64031J 6631J
3 pole Reference Number
Catalog Number
Reference Number
M212922 F222047 Z201640 D214455 X218543 P201125
US3J3I US6J3I 61038J 62003J 64033J 6633J
K214967 M211381 G212917 E214962 S219068 A201641
A variety of pole configurations and termination provisions is available.
12/04
GPUS2
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000 AJT (Class J TD) ®
Dimensions AMPERE RATING
In.
1-30 31-60 61-100 101-200 201-400 401-600
2-1/4 2-3/8 4-5/8 5-3/4 7-1/8 8
A mm
In.
57 13/16 60 1-1/16 117 1-1/8 146 1-5/8 181 2-1/8 203 2-1/2
B mm
In.
C mm
In.
D mm
In.
E mm
21 27 29 41 54 64
1/8 3/16 1/4 3/8
3.2 4.8 6.3 9.5
3/4 1-1/8 1-5/8 2
19 29 41 51
1 1-3/8 1-7/8 2-1/8
25 35 48 54
In.
F mm
G In.
3-5/8 92 3/8 4-3/8 111 3/8 5-1/4 133 17/32 6 152 11/16
H mm
In.
mm
10 10 14 18
9/32 9/32 13/32 17/32
7 7 10 13
1-60A 70-600A
Optional Indicator/Microswitch Mount (EI) dimensions:
Note: Fuses with the EI option will receive the AOS-S or AOS-Q Add-On-Switch whiech is ordered reparately.
Catalog Number
Reference Number
AJT70EI AJT80EI AJT90EI AJT100EI AJT110EI AJT125EI AJT150EI AJT175EI AJT200EI AJT225EI AJT250EI AJT300EI AJT350EI AJT400EI AJT450EI AJT500EI AJT600EI
Y201938 P211682 V214240 F216274 W217300 L218326 M219362 R223092 K201420 N211681 V213228 T214239 A215257 X217301 Z218844 L219890 S223093
GPUS3
A
2.80 (71.0)
3.22 (81.8)
3.24 (82.2)
3.61 (91.8)
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000 AJT (Class J TD) ®
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
AJT 1 to 600
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data AJT 30 to 600, 600 Volts AC
230 Volt Three Phase Class J AJT Fuses Motor HP
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
12/04
Three Phase Motor Fuse Selection
1/2 3/4 1 1-1/2 2 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 GPUS4
Full Load Amperes at 230V
2.2 3.2 4.2 6 6.8 9.6 15.2 22 28 42 54 68 80 104 130 154 192 248 312 360 480
Recommended Fuse Ampere Rating Motor Acceleration Times Minimum Typical Heavy Load 2 sec. 5 sec. Over 5 sec.
3 4 5 8 8 12 20 30 35 50 70 80 100 125 175 200 250 300 400 450 600
3-1/2 5 6-1/4 9 10 15 25 35 40 60 80 100 125 150 200 225 300 350 450 500 -
4 6 8 10 12 17-1/2 30 40 50 80 100 125 150 200 250 300 350 450 600 600 -
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000 AJT (Class J TD) ®
Three Phase Motor Fuse Selection 380 Volt Three Phase Class J AJT Fuses Full
575 Volt Three Phase Class J AJT Fuses
Recommended Fuse Ampere Rating
Motor
Load
HP
Amperes
Minimum
Typical
Heavy Load
at 380V
2 sec.
5 sec.
Over 5 sec.
1.3 1.9 2.5 3.6 4.1 5.8 9.2 13.3 17 25 33 41 48 68 79 93 116 150 189 218 291
1-6/10 2-1/2 3-2/10 4-1/2 5 8 12 17-1/2 20 30 40 50 60 80 90 110 150 175 250 300 350
2 2-8/10 4 5-6/10 6 8 15 20 25 40 50 60 80 100 125 150 175 225 300 350 450
2-1/4 3-1/2 4-1/2 6 7 10 17-1/2 25 30 45 60 70 90 125 150 175 200 250 350 400 500
1/2 3/4 1 1-1/2 2 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200
Three Phase Motor Fuse Selection Full
Motor Acceleration Times
Recommended Fuse Ampere Rating
Motor
Load
HP
Amperes
Minimum
Typical
Heavy Load
at 575V
2 sec.
5 sec.
Over 5 sec.
.9 1.3 1.7 2.4 2.7 3.9 6.1 9 11 17 22 27 32 41 52 62 77 99 125 144 192 240 289
1-1/4 1-6/10 2-1/4 3 3-2/10 5 8 12 15 20 30 35 40 50 70 80 100 125 150 175 250 300 350
1-1/2 2 2-1/2 3-1/2 4 6 9 15 17-1/2 25 35 40 50 60 80 90 125 150 200 225 300 350 450
1-6/10 1-1/2 3 4-1/2 5 7 12 17-1/2 20 30 35 50 60 70 90 110 150 175 225 250 350 400 500
1/2 3/4 1 1-1/2 2 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300
Motor Acceleration Times
460 Volt Three Phase Class J AJT Fuses Full
Recommended Fuse Ampere Rating
Motor
Load
HP
Amperes
Minimum
Typical
Heavy Load
at 460V
2 sec.
5 sec.
Over 5 sec.
1.1 1.6 2.1 3 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156 180 240 302 361
1-1/2 2 2-1/2 3-1/2 4 6 10 15 17-1/2 25 35 40 50 70 80 100 125 175 200 225 300 400 450
1-6/10 2-1/4 3-2/10 4-1/2 5 8 12 15 20 30 40 50 60 80 100 125 150 200 225 250 350 450 600
2 3 4 5-6/10 6 9 15 20 25 40 50 60 70 90 125 150 175 250 300 350 450 600 -
1/2 3/4 1 1-1/2 2 3 5 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300
Motor Acceleration Times
Minimum - Minimum sizing may not be heavy enough for motors with code letter G or higher. Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds. Heavy Load - In accordance with Table 430-152. If this fuse is not sufficient to start the load, it may be increased to a maximum of 225% of fullload amperes (430-52 Exc. 2b). Use this column for Design E Motors.
GPUS5
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000 A4BQ (Class L TD) ®
Put the highest current-limitation... at your service. Amp-trap 2000® A4BQ fuses are 20% more current limiting than any other Class L fuse on the market. When correctly coordinated, they bring a superior level of protection to service entrance equipment. Downstream circuit components have maximum protection against short circuit let-thru current. A4BQ’s built-in, 4-second time delay characteristic (at 500% of rated current) accommodates harmless inrush currents with no nuisance opening.
Features /Benefits
Highlights
• Fastest operation under short circuit conditions: Let-thru currents are typically 20% lower, with a corresponding let-thru energy (clearing I2t) up to 40% lower than the next fastest Class L fuse • Time delay for high inrush loads such as motors and transformers, without nuisance opening • 300kA interrupting rating - self-certified, UL witnessed tests • Most current limiting for lowest peak let-thru current; even at fault currents up to 300kA • Pure silver links ensure lowest let-thru current and longer fuse life • Easy 2-to-1 selectivity for prevention of nuisance shutdowns and “blackouts” • Rejection-style design prevents replacement errors • High-visibility orange label gives instant recognition • Reduced inventory because A4BQ can replace all older types of Class L fuses now in service • Metal-embossed date and catalog number for traceability and lasting identification • Fiberglass body provides dimensional stability in harsh industrial settings • High-grade silica filler ensures fast arc quenching
• Time Delay • Industry’s Most Current-Limiting Class L Fuse • Pure Silver Elements • AC & DC Rated
Applications • • • • •
Mains, Feeders Large Motors Lighting, Heating and General Loads Circuit Breaker Back-up DC Rated: UPS DC Links, Battery Disconnects, Other DC Applications
Approvals • UL Listed to Standard 248-10 (601-6000A) • DC Listed to UL Standard 198L (601-3000A) • CSA Certified to Standard C22.2 No. 248.10 (601-6000A)
Ratings AC: 100 to 6000A 600VAC, 200k A I.R.(self certified for 600VAC, 300k A I.R.,UL witnessed) 4-second delay at 500% rating Note: 100-600A ratings are non-listed
DC: 601 to 3000A 600VDC, 100kA I.R.
*Please contact factory for special trigger actuator
GPUS7
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000 A4BQ (Class L TD) ®
Standard Fuse Ampere Ratings Ampere Rating
Catalog Number
Reference Number
100 150 200 250 300 350 400 450 500 600 601 650 700 750 800 900 1000 1200 1350 1400 1500 1600 1800 2000 2500 3000 3500 4000 5000 6000
A4BQ100 A4BQ150 A4BQ200 A4BQ250 A4BQ300 A4BQ350 A4BQ400 A4BQ450 A4BQ500 A4BQ600 A4BQ601 A4BQ650 A4BQ700 A4BQ750 A4BQ800 A4BQ900 A4BQ1000 A4BQ1200 A4BQ1350 A4BQ1400 A4BQ1500 A4BQ1600 A4BQ1800 A4BQ2000 A4BQ2500 A4BQ3000 A4BQ3500 A4BQ4000 A4BQ5000 A4BQ6000
J215771 X218336 L222581 H200889 F201945 Y211690 E213237 D214248 F214756 K215772 H217311 M217821 Y218337 K218854 Z219373 W219899 P216282 R216790 G217310 L217820 J218853 Y219372 V219898 B223101 V201429 F211168 E212202 W213735 K215266 Q216283
100-800A
801-2000A
3001-4000A
2001-3000A
Safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
4001-6000A
Dimensions AMPERE RATING
In.
mm
In.
mm
In.
mm
In.
mm
In.
mm
100-600 601-800 801-1200 1201-1600 1601-2000 2001-2500 2501-3000 3001-4000 4001-5000 5001-6000
8-5/8 8-5/8 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4
219 219 273 273 273 273 273 273 273 273
2 2-1/2 2-1/2 3 3-1/2 4-1/2 5 5-3/4 6-1/4 7-1/8
51 63 63 76 89 114 127 146 159 181
5/16 3/8 3/8 7/16 1/2 3/4 3/4 3/4 1 1
8 9 9 11 12 19 19 19 25 25
1-5/8 2 2 2-3/8 2-3/4 3-1/2 4 4-3/4 5-1/4 5-3/4
41 51 51 60 70 89 102 121 133 146
2-13/32 2-13/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32
61 61 88 88 88 88 88 88 88 88
12/04
A
B
C
GPUS8
D
E
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000 A4BQ (Class L TD) ®
A4BQ (601 to 6000) Let-Thru Current in kilo-Amperes Available Fault 601 RMS AMPS 10,000 15,000 20,000 25,000 30,000 35,000 40,000 50,000 60,000 80,000 100,000 150,000 200,000
800
RMS IP RMS 7.4 8.3 9.1 9.8 10 11 12 13 13 14 16 18 20
17 19 21 23 24 25 27 29 30 33 36 41 45
8.7 10 11 12 13 13 14 15 16 17 19 21 24
1000 IP 20 23 25 27 29 30 32 34 36 40 43 49 54
RMS IP 10 12 13 13 14 15 16 17 18 20 22 25 27
23 27 29 31 33 35 37 40 42 46 50 57 63
1200
1600
RMS
IP
RMS
10 13 14 15 16 17 18 19 20 23 24 28 31
23 30 33 35 37 39 41 44 47 52 56 64 71
10 15 17 18 20 20 21 23 25 27 29 33 37
2000
IP RMS 23 35 39 42 45 47 49 53 57 62 67 77 84
2500
IP RMS
10 23 15 35 20 46 22 50 23 53 24 56 25 58 27 63 29 67 32 73 34 79 39 90 43 100
3000
IP RMS
10 23 15 35 20 46 25 58 29 66 30 69 31 72 34 78 36 83 40 91 43 98 49 112 53 123
10 15 20 25 30 35 36 39 41 45 49 56 61
4000 IP RMS
23 35 46 58 69 81 83 89 94 104 112 128 141
10 15 20 25 30 35 40 48 51 57 61 70 77
5000
IP RMS 23 35 46 58 69 81 92 111 118 130 140 160 176
10 15 20 25 30 35 40 50 60 67 72 82 90
6000
IP
RMS
IP
23 35 46 58 69 81 92 115 138 153 165 189 208
10 15 20 25 30 35 40 50 60 77 83 94 104
23 35 46 58 69 81 92 115 138 176 190 217 239
The current limiting effect of A4BQ Class L fuses is presented in the table above. This table correlates actual fuse peak let-thru currents with equal value peak currents reached in the first half cycle (worst case) of short circuits in unfused circuits. The let-thru current is expressed as “Apparent RMS Symmetrical Amperes” in order to be more useful for practical applications. The currents are based on an assumed 15% power factor. Example: An A4BQ1200, when applied in a circuit with 40,000 RMS symmetrical amperes available, will limit that current during a short circuit, to an apparent 18,000 RMS symmetrical amperes. Under this condition, any equipment being protected would be subjected to only 18,000 RMS amperes.
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
A4BQ 601 to 6000
TIME IN SECONDS
GPUS9
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000 A4BQ (Class L TD) ®
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – A4BQ 601 to 6000, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
12/04
GPUS10
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000® A2D and A6D (Class RK1 TD)
Upgrade yesterday’s circuits to today’s Type 2 protection Amp-trap 2000® SmartSpot® A2D, A6D fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product line the A2D, A6D fuses provide IEC Type “2” (No Damage) protection to main, feeder, and branch circuits, for all types of loads — A2D, A6D’s time delay characteristics for handling harmless in-rush currents, its current limiting ability and wide range of ratings (from 1 to 600 Amperes) — give excellent protection for all your applications.
Features /Benefits
Ratings
• Solid State SmartSpot Indicator • Time delay for motor starting and transformer inrush currents without nuisance opening • 300kA interrupting rating - self-certified, UL witnessed tests • Extremely Current Limiting for low peak let-thru current • Easy 2-to-1 selectivity for prevention of nuisance shut downs and “black outs” • Rejection-style design prevents replacement errors (when used with recommended fuse blocks) • High-visibility orange label gives instant recognition • Reduced inventory by taking the place of RK5, K, and H fuses • Metal-embossed date and catalog number for easier traceability and lasting identification • Fiberglass body provides dimensional stability in harsh industrial settings • Brass end-caps (blade-style) for cooler operation and superior performance
A2D AC: 1/10 to 600A 250VAC, 200kA I.R. (self certified for250VAC, 300kA I.R., UL witnessed) A6D AC: 1/10 to 600A 600VAC, 200kA I.R. (self certified for 600VAC, 300kA I.R.)
GPUS11
Highlights • • • •
SmartSpot Indicator Time Delay Current Limiting Plated Terminals
Applications • • • • • • •
Motors Safety Switches Transformers Branch Circuit Protection Disconnects Control Panels All General-purpose Circuits
Approvals • UL Listed to Standard 248-12 • CSA Certified to Standard C22.2 No. 248.12
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000® A2D and A6D (Class RK1 TD)
Standard Fuse Ampere Ratings Ampere Rating
Cat. Number 250V 600V
Ref. Number 250V 600V
Amp. Rating
Cat. Number 250V 600V
Ref. Number 250V 600V
1/10
A2D1/10R
A6D1/10R
Q215248
R201932
10
A2D10R
A6D10R
Z216268
G211675
15/100
A2D15/100R
A6D15/100R
M217292
D212707
12
A2D12R
A6D12R
Z216774
M212186
2/10
A2D2/10R
A6D2/10R
J223085
C216271
15
A2D15R
A6D15R
R217802
N213222
3/10
A2D3/10R
A6D3/10R
K212184
G219357
17-1/2
A2D17-1/2R
A6D17-1/2R
C218318
E213720
4/10
A2D4/10R
A6D4/10R
N214740
E201415
20
A2D20R
A6D20R
P200872
C216777 Q217295
1/2
A2D1/2R
A6D1/2R
T215757
P211153
25
A2D25R
A6D25R
B201412
6/10
A2D6/10R
A6D6/10R
R218837
N214234
30
A2D30R
A6D30R
B212705
E219884
8/10
A2D8/10R
A6D8/10R
Q200873
D216778
35
A2D35R
A6D35R
L213220
W222567
1
A2D1R
A6D1R
Q218836
M214233
40
A2D40R
A6D40R
R215249
S201933
1-1/8
A2D1-1/8R
A6D1-1/8R
K213219
V222566
45
A2D45R
A6D45R
V215758
Q211154 E212708
1-1/4
A2D1-1/4R
A6D1-1/4R
A212704
D219883
50
A2D50R
A6D50R
N217293
1-4/10
A2D1-4/10R
A6D1-4/10R
B213717
L223087
60
A2D60R
A6D60R
E219355
R214743
1-6/10
A2D1-6/10R
A6D1-6/10R
J214230
R200874
70
A2D70R
A6D70R
N201929
E218320
1-8/10
A2D1-8/10R
A6D1-8/10R
M214739
D201414
75
A2D75R
-
L211150
-
2
A2D2R
A6D2R
P201930
V217805
80
A2D80R
A6D80R
D211672
S218838
2-1/4
A2D2-1/4R
A6D2-1/4R
C219882
T215251
90
A2D90R
A6D90R
J212183
F219356
2-1/2
A2D2-1/2R
A6D2-1/2R
D219354
Q214742
100
A2D100R
A6D100R
P215247
N211152
2-8/10
A2D2-8/10R
A6D2-8/10R
S222564
X215760
110
A2D110R
A6D110R
S215756
F211674
3
A2D3R
A6D3R
C213718
M223088
125
A2D125R
A6D125R
Y216267
L212185
3-2/10
A2D3-2/10R
A6D3-2/10R
E211673
T218839
150
A2D150R
A6D150R
Y216773
C212706
3-1/2
A2D3-1/2R
A6D3-1/2R
M211151
F218321
175
A2D175R
A6D175R
L217291
M213221
4
A2D4R
A6D4R
A216269
H211676
200
A2D200R
A6D200R
Q217801
D213719
4-1/2
A2D4-1/2R
A6D4-1/2R
K214231
S200875
225
A2D225R
A6D225R
B218317
L214232
5
A2D5R
A6D5R
S217803
P213223
250
A2D250R
A6D250R
P218835
P214741
5-6/10
A2D5-6/10R
A6D5-6/10R
A216775
N212187
300
A2D300R
A6D300R
C219353
S215250
6
A2D6R
A6D6R
T222565
V215252
350
A2D350R
A6D350R
B219881
W215759
6-1/4
A2D6-1/4R
A6D6-1/4R
D218319
F213721
400
A2D400R
A6D400R
R222563
B216270
7
A2D7R
A6D7R
K223086
Y215761
450
A2D450R
A6D450R
H223084
B216776
8
A2D8R
A6D8R
C201413
R217296
500
A2D500R
A6D500R
N200871
P217294
9
A2D9R
A6D9R
Q201931
W217806
600
A2D600R
A6D600R
A201411
T217804
Dimensions Ampere A Rating In. 250V-A2D 0-30 2 31-60 3 61-100 5-/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-A6D 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8
12/04
mm
In.
B mm
In.
C mm
In.
D mm
In.
E mm
51 76 149 181 219 264
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 53 66
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
127 13/16 139 1-1/16 200 1-5/16 244 1-13/16 295 2-9/16 340 3-1/8
21 27 34 46 66 80
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
GPUS12
61-600A
0-60A
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000® A2D and A6D (Class RK1 TD)
Recommended Fuse Blocks with Box Connectors for Amp-trap® Class RK1 Fuses Fuse Ampere Rating
0-30 31-60 61-100 101-200 201-400 401-600
Fuse Ampere Rating
0-30 31-60 61-100 101-200 201-400 401-600
Catalog Number 250V 1 Pole 3 pole
20306R 20606R 21036R 22001R 24001R 2631R
20308R 20608R 21038R 22003R 24003R 2633R
Catalog Number 600V 1 Pole 3 pole
60306R 60606R 61036R 62001R 64001R 6631R
60308R 60608R 61038R 62003R 64003R 6633R
Reference Number 250V 1 pole 3 pole
T213411 B212383 D201621 R213915 J219566 H214942
K215956 E214939 M212899 G214941 D222022 P215960
Ref. Number 600V 1 pole 3 pole
H212389 K212391 W204788 V212906 D219055 J216990
K214438 M214440 Z211875 B213924 M222030 E218021
A variety of pole configurations and termination provisions is available.
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
A2D 15 to 600
TIME IN SECONDS
GPUS13
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000® A2D and A6D (Class RK1 TD)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
A2D 1/10 to 10
TIME IN SECONDS
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA,600V FUSES
A6D 15 to 600
TIME IN SECONDS
12/04
GPUS14
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000® A2D and A6D (Class RK1 TD)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
A6D 1/10 to 8
TIME IN SECONDS
Peak Let-Thru Current Data A6D 30 to 600, 600 Volts AC MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data A2D 30 to 600, 250 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
NOTE: SEE APPLICATION INFORMATION SECTION OF CATALOG (LOW VOLTAGE FUSES FOR MOTOR PROTECTION) FOR GUIDELINES ON THREE PHASE MOTOR FUSE SELECTION, CLASS RK1 A2D & RK1 A6D FUSES GPUS15
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000® ATDR (Class CC TD)
The best protection for today’s small motors Amp-trap 2000® ATDR small-dimension fuses can provide IEC Type 2 “no damage” protection to your facility’s increasingly sensitive branch circuit components and small motors – minimizing the risk of fault-related damage. ATDR Class CC fuses deliver the best time delay characteristics in their class with excellent cycling ability for small motor loads.
Features /Benefits
Applications
• Time delay for motor starting inrush currents without nuisance opening • Highly current limiting for low peak let-thru current • Improved cycling ability for frequent motor starts/stops without nuisance fuse opening • Rejection-style design prevents replacement errors (when used with recommended fuse blocks) • High-visibility orange label ensures instant recognition, simplifies replacement • Metal-embossed date and catalog number for traceability and lasting identification • Fiberglass body provides dimensional stability in harsh industrial settings • High-grade silica filler ensures fast arc quenching and optimum current limitation
• • • •
Small Motors Contactors Lighting, Heating and General Loads Branch Circuit Protector
Approvals • UL Listed to Standard 248-4 • CSA Certified to Standard C22.2 No. 248.4
• DC Listed to UL Standard 198L
Ratings AC: 1/4 to 30A 600VAC, 200kA I.R. DC: 1/4 to 30A 300VDC, 100kA I.R.
Highlights • • • •
Time Delay Best Choice for Small Motor Protection Highly Current-Limiting AC & DC Rated
GPUS17
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000® ATDR (Class CC TD) Standard Fuse Ampere Ratings Ampere Rating
1/4 1/2 8/10 1 1-1/8 1-1/4 1-4/10 1-1/2 1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10 3 3-2/10 3-1/2
Catalog Number
Reference Number
Ampere Rating
ATDR1/4 ATDR1/2 ATDR8/10 ATDR1 ATDR1-1/8 ATDR1-1/4 ATDR1-4/10 ATDR1-1/2 ATDR1-6/10 ATDR1-8/10 ATDR2 ATDR2-1/4 ATDR2-1/2 ATDR2-8/10 ATDR3 ATDR3-2/10 ATDR3-1/2
W200855 Q223068 K201397 T217275 Y218820 J218301 K219337 Y217785 K219866 Z222547 S212168 T213204 J212689 L213703 Y215232 J216254 C215742
4 4-1/2 5 5-6/10 6 6-1/4 7 7-1/2 8 9 10 12 15 7-1/2 20 25 30
Small Motor Fuse Protection, 600 Volts AC or Less Motor Full load Amperes
ATDR Minimum Duty
Rating* Normal Duty
.71 - .89 .90 - 1.19 1.20 - 1.34 1.35 - 1.79 1.80 - 2.25 2.26 - 2.69 2.70 - 2.90 2.91 - 3.20 3.21 - 3.75 3.76 - 4.50 4.51 - 5.34 5.35 - 5.69 5.70 - 6.70 6.71 - 7.79 7.80 - 8.88 8.89 - 11.1 11.2 - 13.3 13.4 - 15.2
1-1/4 1-6/10 2 2-1/2 3 4 4 5 5 6 8 10 12 12 15 17-1/2 20 25
1-6/10 2 2-1/2 3 4 5 6 6 7 8 10 12 12 15 17-1/2 20 25 30
Catalog Number
ATDR4 ATDR4-1/2 ATDR5 ATDR5-6/10 ATDR6 ATDR6-1/4 ATDR7 ATDR7-1/2 ATDR8 ATDR9 ATDR10 ATDR12 ATDR15 ATDR17-1/2 ATDR20 ATDR25 ATDR30
Dimensions
* The 1996 National Electrical Code allows time-delay Class CC fuses to be sized at up to 400% (maximum) of motor FLA, if needed.
Recommended Fuse Blocks for Class CC Fuses Catalog Number
Reference number
Pessure Number Ultrasafe Copper Pressure Screw Screw Ultrasafe Copper Plate of Box Plate Indicating Connector Connector Indicating Connector Box Poles w/ Double Connector Connector w/ Double w/ Double Connector Fuse Fuse w/ Double Quick Quick Holder Holder Quick Connects
Quick
Connects
Connects
Connects ADDER
30310R
30320R
30350R
1
USCC1I
30311R
30321R
30351R
X213943
2
USCC2I
30312R
30322R
30352R
D217008
3
USCC3I
30313R
30323R
30353R
Y218038
12/04
W204857
Z217510
N213429
R212397
M218534
G213929
Z212910
Y219579
V214447
M213428
B222779
X214955
GPUS18
Reference Number
V217276 Z217786 K218302 Z218821 L219338 L219867 A222548 R223069 X200856 Y201915 J201396 X201914 V211135 L211656 R214214 V214723 G216758
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000® ATDR (Class CC TD)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
ATDR 1/4 to 30
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – ATDR 1/4 to 30, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
GPUS19
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000® ATQR (Class CC TD)
Take control of fault currents headed for your control transformer ATQR small-dimension fuses feature time delay characteristics ideally suited for the high inrush currents of control transformers, solenoids, and similar inductive loads. The newest member of our Amp-trap 2000® family of fuses - ATQR fuses provide superior protection for the branch circuits of electrical distribution systems.
Features /Benefits
Applications
• Time delay for control transformer inrush loads without nuisance opening • Highly current limiting for low peak let-thru current • Rejection-style design prevents replacement errors (when used with recommended fuse blocks) • High-visibility orange label ensures instant recognition, and simplifies replacement • Metal-embossed date and catalog number for traceability and lasting identification • Fiberglass body provides dimensional stability in harsh industrial settings • High-grade silica filler ensures fast arc quenching and high current limitation
• • • •
Control Transformers Solenoids Inductive Loads Lighting, Heating and General-purpose Loads
Approvals • UL Listed to Standard 248-4 • CSA Certified to Standard C22.2 No. 248.4
Ratings AC: 1/10 to 30A 600VAC, 200kA I.R.
Highlights • Time Delay • Best Choice for Small Transformer Protection • Most Current-Limiting
GPUS21
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000® ATQR (Class CC TD)
Standard Fuse Ampere Ratings, Reference Numbers Ampere Rating
Catalog Number
Reference Number
Ampere Rating
Catalog Number
1/10 1/8 15/100 3/16 2/10 1/4 3/10 4/10 1/2 6/10 3/4 8/10 1 1-1/8 1-1/4 1-4/10 1-1/2 1-6/10 1-8/10 2 2-1/4 2-1/2
ATQR1/10 ATQR1/8 ATQR15/100 ATQR3/16 ATQR2/10 ATQR1/4 ATQR3/10 ATQR4/10 ATQR1/2 ATQR6/10 ATQR3/4 ATQR8/10 ATQR1 ATQR1-1/8 ATQR1-1/4 ATQR1-4/10 ATQR1-1/2 ATQR1-6/10 ATQR1-8/10 ATQR2 ATQR2-1/4 ATQR2-1/2
E201921 A212175 S223507 J222556 Q216766 V211664 V219875 D211143 C211142 V213711 A223077 L215750 F218827 H222555 T219874 Z223076 T219345 E200863 R201403 D214731 K215749 G215240
2-8/10 3 3-2/10 3-1/2 4 4-1/2 5 5-6/10 6 6-1/4 7 7-1/2 8 9 10 12 15 17-1/2 20 25 30
ATQR2-8/10 ATQR3 ATQR3-2/10 ATQR3-1/2 ATQR4 ATQR4-1/2 ATQR5 ATQR5-6/10 ATQR6 ATQR6-1/4 ATQR7 ATQR7-1/2 ATQR8 ATQR9 ATQR10 ATQR12 ATQR15 ATQR17-1/2 ATQR20 ATQR25 ATQR30
Reference Number
Q216260 T218310 V219346 G218828 S201404 F201922 W211665 B212176 T212698 D213213 B214223 E214732 H215241 R216261 S212697 C213212 T213710 A214222 D217284 H217794 F200864
Recommended ATQR Class CC Primary Fuses For Single Phase Control Transformers Trans Primary VA Volts Fla 600 0.04 480 0.05 240 0.10 25 208 0.12 120 0.21 600 0.08 480 0.10 240 0.21 50 208 0.24 120 0.42 600 0.13 480 0.16 240 0.31 75 208 0.36 120 0.63 600 0.17 480 0.21 240 0.42 100 208 0.48 120 0.83 600 0.25 480 0.31 240 0.63 150 208 0.72 120 1.25 600 0.33 480 0.42 240 0.83 200 208 0.96 120 1.67 600 0.42 480 0.52 250 240 1.04 208 1.2 120 2.08 12/04
ATQR AMPS 1/10 1/10 2/10 1/4 4/10 1/4 1/4 4/10 1/2 6/10 1/4 3/10 1/2 3/4 1 3/10 4/10 6/10 1 1-1/2 1/2 1/2 1 1-1/2 2-1/2 1/2 6/10 1-1/2 2 3 6/10 1-1/8 2 3 4*
* Secondary protection is required for these ratings. + Fuse will withstand 30 x FLA for .01 second ++ Fuse will withstand 25 x FLA for .01 second
GPUS22
Trans Primary VA Volts Fla 0.50 600 480 0.63 300 240 1.25 208 1.44 120 2.5 600 0.83 480 1.04 500 240 2.08 208 2.40 120 4.17 600 1.25 480 1.56 750 240 3.13 208 3.61 120 6.25 600 1.67 480 2.08 1000 240 4.16 208 4.81 120 8.33 600 2.50 480 3.13 1500 240 6.25 208 7.21 120 12.5 600 3.33 2000 480 4.17 240 8.33 208 9.62 600 5.00 3000 480 6.25 240 12.5 5000 600 8.33 480 10.4
ATQR AMPS 1-1/8 1-1/2 2-1/2 3 5* 1-1/2 2 4* 6* 10* 2-1/2 3 7* 8* 15* 3 4* 10* 12* 20* 5* 7* 10 20* 25* 8* 10* 20++* 20++* 12+* 15+* 30++* 20++* 25+*
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP 2000® ATQR (Class CC TD)
Recommended Fuse Blocks for Class CC Fuses Catalog Number Number of Poles
Ultrasafe Indicating Fuse Holder
Screw with Double Quick Connects
Pressure Plate with Double Quick Connects
Copper Box Connector
ADDER 1 2 3
USCC1I USCC2I USCC3I
30310R 30311R 30312R 30313R
30320R 30321R 30322R 30323R
30350R 30351R 30352R 30353R
Number of Poles
Ultrasafe Indicating Fuse Holder
Screw with Double Quick Connects
Pressure Plate with Double Quick Connects
Copper Box Connector
ADDER 1
X213943
W204857 R212397
Z217510 M218534
N213429 G213929
2 3
D217008 Y218038
Z212910 M213428
Y219579 B222779
V214447 X214955
Reference Number
Primary fuses - If primary FLA is less than 2 amps, fuse may be 300% max. (500% for motor control). If primary FLA exceeds 2 amps but is less than 9 amps, fuse may not exceed 167% of primary FLA unless secondary protection is used, when it may be increased to 250%. Fuse sizes shown are based on approx. 40 x FLA for .01 sec.
Dimensions
GPUS23
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP 2000® ATQR (Class CC TD)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
ATQR 1/8 to 30
TIME IN SECONDS
MAX. INSTANTANEOUS PEAK LET-THRU CURRENT
Peak Let-Thru Current Data – ATQR 1/8 to 30, 600 Volts AC
AVAILABLE CURRENT IN RMS SYM. AMPERES
12/04
GPUS24
General Purpose US US Fuses General Purpose Fuses American Power Fuses TRI-ONIC® TR and TRS (Class RK5 TD)
The industry’s Most popular fuse for Motor circuit protection. Tri-onic® SmartSpot® fuses now provide a visual open fuse indicator. With advanced material technology added to the existing product the TR and TRS current limiting time delay fuses are engineered for overcurrent protection of motors and transformers, service entrance equipment, feeder and branch circuits. Tri-onic proven time delay characteristic safely handles harmless starting currents and inrush currents associated with today’s motors and transformers.
Features /Benefits
Highlights
• Solid State SmartSpot Indicator • Time delay for motor start-ups and transformer inrush currents without nuisance opening • Current limiting for low peak let-thru current • Rejection-style design prevents replacement errors (when used with recommended fuse blocks) • Easy-to-read label for quick recognition and replacement • Metal-embossed date and catalog number for traceability and lasting identification • Fiberglass body provides dimensional stability in harsh industrial settings • Brass end-caps (blade-style) for cooler operation and superior performance • High-grade silica filler ensures fast arc quenching and high current limitation
• Time Delay • Current Limiting • AC & DC Rated
Ratings
Applications • • • • • • •
Motor Circuits Mains Feeders Branch Circuits Transformers Service Entrance Equipment General-purpose Protection
Approvals • UL Listed to Standard 248-12 • CSA Certified to Standard C22.2 No. 248.12 • DC Listed to UL Standard 198L
TR AC: 1/10 to 600A 250VAC, 200kA I.R. DC: 1/10 to 2 8/10A and 35 to 400A, 250VD, 20 A.I.R 3 to 30A & 450 to 600A, 160VDC, 20kA I.R. TRS AC: 1/10 to 600A, 600VAC, 200kA I.R. DC: 1/10 to 12A, 600VDC, 20kA I.R. 70 to 600A, 600VDC, 100kA I.R. 15 to 60A, 300VDC, 20kA I.R.
GPUS25
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses TRI-ONIC® TR and TRS (Class RK5 TD)
Standard Fuse Ampere Ratings Catalog Number
Ampere Rating 1/10 15/100 2/10 3/10 4/10 1/2 6/10 8/10 1 1-1/8 1-1/4 1-4/10 1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10 3 3-2/10 3-1/2 4 4-1/2 5 5-6/10 6 6-1/4 7 8 9
600V
250V TR1/10R TR15/100R TR2/10R TR3/10R TR4/10R TR1/2R TR6/10R TR8/10R TR1R TR1-1/8R TR1-1/4R TR1-4/10R TR1-6/10R TR1-8/10R TR2R TR2-1/4R TR2-1/2R TR2-8/10R TR3R TR3-2/10R TR3-1/2R TR4R TR4-1/2R TR5R TR5-6/10R TR6R TR6-1/4R TR7R TR8R TR9R
Reference Number 250V 600V
TRS1/10R TRS15/100R TRS2/10R TRS3/10R TRS4/10R TRS1/2R TRS6/10R TRS8/10R TRS1R TRS1-1/8R TRS1-1/4R TRS1-4/10R TRS1-6/10R TRS1-8/10R TRS2R TRS2-1/4R TRS2-1/2R TRS2-8/10R TRS3R TRS3-2/10R TRS3-1/2R TRS4R TRS4-1/2R TRS5R TRS5-6/10R TRS6R TRS6-1/4R TRS7R TRS8R TRS9R
F222530 E201898 Z214198 C217260 Z223053 Y223052 R216238 T219322 Z212151 Q218284 E217768 E218803 R219320 S219850 J215725 A213187 Q212672 S213686 T219851 N216741 Q216237 A212152 G222531 E214709 R212673 S218286 S218286 G218805 V219852 H222532
Ampere Rating
Catalog Number 600V
250V
W216748 F223059 X216749 J212160 Y216750 N217776 L213197 R217779 H212159 G212158 J211125 H213194 G214205 R215732 Q222539 H214206 J213195 S215733 P215224 N201906 M200847 D219860 A216246 M211128 H223061 V215735 K212161 Z216751 R218814 S222541
10 12 15 17-1/2 20 25 30 35 40 45 50 60 70 75 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600
Reference Number
TR10R TR12R TR15R TR17-1/2R TR20R TR25R TR30R TR35R TR40R TR45R TR50R TR60R TR70R TR75R TR80R TR90R TR100R TR110R TR125R TR150R TR175R TR200R TR225R TR250R TR300R TR350R TR400R TR450R TR500R TR600R
TRS10R TRS12R TRS15R TRS17-1/2R TRS20R TRS25R TRS30R TRS35R TRS40R TRS45R TRS50R TRS60R TRS70R TRS75R TRS80R TRS90R TRS100R TRS110R TRS125R TRS150R TRS175R TRS200R TRS225R TRS250R TRS300R TRS350R TRS400R TRS450R TRS500R TRS600R
250V D200839 S201381 D211120 S211639 D214708 G215217 F217769 F218804 E200840 F201899 B213188 P216742 Q219848 E222529 W223050 B200837 K216738 B218800 N219317 P219847 D222528 V223049 A200836 P201378 B201895 A211117 P211636 N218282 C218801 P219318
600V N218811 B219858 B201389 K211126 P217777 B219329 K213196 J214207 Q217778 Q218813 D201391 M214716 Y213691 P215730 W216242 L217774 D214202 K215220 N215729 S216745 K217773 K218808 Y219855 L222535 J200844 J201902 G211123 E212156 W212677 F213192
Note: Indicator not available (1/10-7) Amps
Recommended Fuse Blocks With Box Connectors For Tri-onic® Class RK5 Fuses 0-60A
61-600A
Dimensions Ampere A Rating In. 250V-TR Fuses 0-30 2 31-60 3 61-100 5-7/8 101-200 7-1/8 201-400 8-5/8 401-600 10-3/8 600V-TRS Fuses 0-30 5 31-60 5-1/2 61-100 7-7/8 101-200 9-5/8 201-400 11-5/8 401-600 13-3/8 12/04
mm
In.
B mm
In.
C mm
In.
D mm
In.
E mm
51 76 149 181 219 264
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 53 66
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
127 13/16 139 1-1/16 200 1-5/16 244 1-13/16 295 2-9/16 340 3-1/8
21 27 34 46 66 80
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
GPUS26
Fuse Ampere Rating 0-30 31-60 61-100 101-200 201-400 401-600
Catalog Number Ref. Number 250V 250V 1 Pole 3 pole 1 pole 3 pole 20306R 20308R T213411 K215956 20606R 20608R B212383 E214939 21036R 21038R D201621 M212899 22001R 22003R R213915 G214941 24001R 24003R J219566 D222022 2631R 2633R H214942 P215960
Fuse Ampere Rating
Catalog Number 600V 1 Pole 3 pole
0-30 31-60 61-100 101-200 201-400 401-600
60306R 60606R 61036R 62001R 64001R 6631R
60308R 60608R 61038R 62003R 64003R 6633R
Ref. Number 600V 1 pole 3 pole H212389 K212391 W204788 V212906 D219055 J216990
K214438 M214440 Z211875 B213924 M222030 E218021
A variety of pole configurations and termination provisions is available.
General Purpose US US Fuses General Purpose Fuses American Power Fuses TRI-ONIC® TR and TRS (Class RK5 TD)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
TR 15 to 600
TIME IN SECONDS
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
TR 1/10 to 12
TIME IN SECONDS GPUS27
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses TRI-ONIC® TR and TRS (Class RK5 TD)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA , 600V FUSES
TRS 15 to 600
TIME IN SECONDS
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA. 600V FUSES
TRS 1/10 to 12
TIME IN SECONDS 12/04
GPUS28
General Purpose US US Fuses General Purpose Fuses American Power Fuses TRI-ONIC® TR and TRS (Class RK5 TD)
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – TR 30 to 600, 250 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – TRS 15 to 600, 600 Volts AC
Note: See Application Information page L9 for All Motor and Transformer Tables.
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
GPUS29
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses TRI-ONIC® TRS - RDC (DC Rated TD)
DC RATED FOR TOUGH DC APPLICATIONS The Tri-onic DC fuse series is designed for DC circuit protection in surface and underground mines. The TRS-RDC is MSHA approved and meets the industry’s most severe third party requirements for 600VDC rated fuses. The TRS-RDC is a time-delay fuse with essentially the same time-current characteristic as the standard Tri-onic.
Features /Benefits
Highlights
• DC rated for mine duty and other long time-constant applications
• Time Delay • DC Rated
• Time delay for motor start-ups and high inrush loads without nuisance opening
Applications
• Rugged glass melamine body for superior reliability in harsh environments
Ratings DC: 1 to 30A 300VDC, 20kA.I.R. (Consult Factory forAvailability)
• • • •
Mine Circuits Trailing Cables Pump Motors Rail Heaters
Approvals • MSHA Approval No. 28-26-0
DC: 35 to 400A 600VDC, 20kA I.R.
GPUS31
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses TRI-ONIC® TRS - RDC (DC Rated TD)
Standard Fuse Ampere Ratings, Catalog Numbers Ampere Rating
Catalog Number
Ampere Rating
Catalog Number
Ampere Rating
Catalog Number
Ampere Rating
Catalog Number
Ampere Rating
Catalog Number
1 2 3 5 6 8
TRS1RDC TRS2RDC TRS3RDC TRS5RDC TRS6RDC TRS8RDC
10 12 15 20 30 35
TRS10RDC TRS12RDC TRS15RDC TRS20RDC TRS30RDC TRS35RDC
40 45 50 60 70 80
TRS40RDC TRS45RDC TRS50RDC TRS60RDC TRS70RDC TRS80RDC
90 100 125 150 175
TRS90RDC TRS100RDC TRS125RDC TRS150RDC TRS175RDC
200 250 300 400
TRS200RDC TRS250RDC TRS300RDC TRS400RDC
Standard Fuse Ampere Ratings, Reference Numbers Ampere Rating
Reference Number
Ampere Rating
Reference Number
Ampere Rating
Reference Number
Ampere Rating
Reference Number
Ampere Rating
Reference Number
1 2 3 5 6 8
Z212680 G223060 T215734 D211649 B216247 E219861
10 12 15 20 30 35
A219328 P222538 M201905 P218812 C213695 L214715
40 45 50 60 70 80
B218294 C219330 P201907 Q215225 E214203 H217265
90 100 125 150 175
X218290 G214711 V216241 G217264 W218289
200 250 300 400
X219325 D223057 Y201386 Y211644
31-60 AMPERES 61-400 AMPERES
Dimensions AMPERE RATING
In.
A mm
In.
B mm
In.
C mm
In.
D mm
In.
E mm
1-30 31-60 61-100 101-200 201-400
5 5-1/2 7-7/8 9-5/8 11-5/8
127 139 200 244 295
13/16 1-1/16 1-5/16 1-13/16 2-9/16
21 27 34 46 66
1/8 3/16 1/4
3 5 6
3/4 1-1/8 1-5/8
19 28 41
1 1-3/8 1-7/8
25 35 48
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
TRS-RDC 60 to 400
TIME IN SECONDS
12/04
GPUS32
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A4J (Class J FA)
FOR EXCELLENT CURRENT LIMITING PROTECTION A4J Class J fuses deliver excellent current-limiting protection to a wide variety of applications. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings, interrupting ratings, or current-limiting capability.
Highlights • Fast Acting • Very Current-Limiting • DC Ratings
Applications Features /Benefits • High current limitation for low peak let-thru current • Unique dimensions prevent replacement by other fuseclasses • Fiberglass body provides dimensional stability in harsh industrial environments * Easy-to-read imprint label for quick recognition and replacement
• • • • • • • •
Capacitors Loadcenters Panelboards Switchboards Bus Duct Feeder Circuits Circuit Breakers Lighting, Heating, and General Loads
Approvals • UL Listed to Standard 248-8. • CSA Certified to Standard C22.2 No. 248.8 • DC Tested to UL198L limits • EC 269-2-1
Ratings AC: 1 to 600A 600VAC, 200kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.
GPUS33
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® A4J (Class J FA)
Standard Fuse Ampere Ratings, Reference Numbers Ampere Rating
Catalog Number
Reference Number
Ampere Rating
Catalog Number
Reference Number
Ampere Rating
Catalog Number
Reference Number
1 3 6 10 15 20 25 30 35 40
A4J1 A4J3 A4J6 A4J10 A4J15 A4J20 A4J25 A4J30 A4J35 A4J40
V217299 J219888 T211157 Z217809 K218325 X218842 L219361 A222571 Q223091 X200879
45 50 60 70 80 90 100 110 125 150
A4J45 A4J50 A4J60 A4J70 A4J80 A4J90 A4J100 A4J110 A4J125 A4J150
J201419 X201937 M211680 H212711 J213724 R214237 N223089 V200877 V201935 R211155
175 200 225 250 300 350 400 450 500 600
A4J175 A4J200 A4J225 A4J250 A4J300 A4J350 A4J400 A4J450 A4J500 A4J600
Q212189 G212710 X215254 T217298 K219360 H219887 Z222570 W200878 W201936 S211156
Recommended Fuse Blocks With Box Connectors for Amp-trap Class J Fuses Fuse 600V OR LESS Ampere 1 Pole 3 pole Rating Cat N° Ref N° Cat N° Ref N° 1-60A
0-30 31-60 61-100 101-200 201-400 401-600
US3J1I US6J1I 61036J 62001J 64031J 6631J
M212922 F222047 Z201640 D214455 X218543 P201125
US3J3I US6J3I 61038J 62003J 64033J 6633J
K214967 M211381 G212917 E214962 S219068 A201641
A variety of pole configurations and termination provisions is available. Refer to the fuse block section of this catalog for details. 70-600A
Dimensions Ampere Rating
In.
1-30 31-60 61-100 101-200 201-400 401-600
2-1/4 2-3/8 4-5/8 5-3/4 7-1/8 8
12/04
A
B mm
In.
57 13/16 60 1-1/16 117 1-1/8 146 1-5/8 181 2-1/8 203 2-1/2
C
D
E
F
mm
In.
mm
In.
mm
In.
mm
21 27 29 41 54 64
1/8 3/16 1/4 3/8
3.2 4.8 6.3 9.5
3/4 1-1/8 1-5/8 2
19 29 41 51
1 1-3/8 1-7/8 2-1/8
25 35 48 54
GPUS34
In.
G mm
In.
3-5/8 92 3/8 4-3/8 111 3/8 5-1/4 133 17/32 6 152 11/16
H mm
In.
mm
10 10 13 18
9/32 9/32 13/32 17/32
7 7 10 13
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A4J (Class J FA)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
A4J 30 to 600
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – 30 to 600, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
GPUS35
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A4BY (Class L)
Count on the high interrupting rating of our most widely-used class L fuse When it comes to protecting service entrance equipment, feeder circuits, and circuit breakers, A4BY fuses have been the industry’s favorite. The A4BY is a 100% rated device and may be applied at continuous currents up to its ampere rating. A 4-second minimum time delay at 500% rating allows the A4BY to pass normal current surges and to coordinate with ground fault relays.
Applications • • • • • •
Features /Benefits
Mains, Feeders Circuit Breakers Loadcenters Panelboards Switchboards Metering Centers
Approvals
• Unique dimensions prevent replacement by other fuse classes • Blade stamped catalog numbers for permanent identification • Glass melamine body and plated terminals provide superior reliability in harsh environments
• UL Listed to Standard 248-10 (601-6000A) • CSA Certified to Standard C22.2 No. 248.10 (601-6000A) • DC Tested to UL 198L limits (601-6000A)
Ratings AC: 200 to 6,000A 600VAC,200kA I.R. Indicators: Optional built-in fuse indicators (-TI) are available. Consult factory.
DC: 200 to 2500A 300VDC, 100kA I.R.
Highlights • • • •
Current-Limiting 4-Second Time Delay DC Ratings Uniform Characteristics in all Ampere Ratings
GPUS37
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® A4BY (Class L)
Standard Fuse Ampere Ratings Ampere Rating
Catalog Number
Ref. Number
Ampere Rating
Catalog Number
Ref. Number
Ampere Rating
Catalog Number
Ref. Number
200 250 300 350 400 500 600 601 650 700 750 800
A4BY200 A4BY250 A4BY300 A4BY350 A4BY400 A4BY500 A4BY600 A4BY601 A4BY650 A4BY700 A4BY750 A4BY800
P217823 P222584 J201948 Y212725 Z213738 T216286 Q217824 C219376 Z219902 Q222585 M200893 Z201433
801 900 1000 1100 1200 1201 1350 1400 1500 1600 1601 1800
A4BY801 A4BY900 A4BY1000 A4BY1100 A4BY1200 A4BY1201 A4BY1350 A4BY1400 A4BY1500 A4BY1600 A4BY1601 A4BY1800
K211172 C211694 X201431 H211170 A211692 X212724 G213239 Y213737 H214758 L215267 T216792 K217313
2000 2001 2500 3000 3001 3500 4000 4001 5000 6000
A4BY2000 A4BY2001 A4BY2500 A4BY3000 A4BY3001 A4BY3500 A4BY4000 A4BY4001 A4BY5000 A4BY6000
A218339 M218856 L200892 J211171 H212205 H213240 G214251 J214759 V216793 N218857
3001-4000A
2001-3000A
4001-6000A
200-800A
801-2000A
Dimensions Ampere Rating
In.
A mm
In.
B mm
In.
C mm
In.
D mm
In.
mm
200-600* 601-800 801-1200 1201-1600 1601-2000 2001-2500 2501-3000 3001-4000 4001-5000 5001-6000
8-5/8 8-5/8 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4 10-3/4
219 219 273 273 273 273 273 273 273 273
2 2-1/2 2-1/2 3 3-1/2 4-1/2 5 5-3/4 6-1/4 7-1/8
51 63 63 76 89 114 127 146 159 181
5/16 3/8 3/8 7/16 1/2 3/4 3/4 3/4 1 1
8 9 9 11 13 19 19 19 25 25
1-5/8 2 2 2-3/8 2-3/4 3-1/2 4 4-3/4 5-1/4 5-3/4
41 51 51 60 70 89 102 121 133 146
2-13/32 2-13/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32 3-15/32
61 61 88 88 88 88 88 88 88 88
Safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
12/04
GPUS38
E
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A4BY (Class L)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
A4BY 200 to 6000
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – A4BY 300 to 6000, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
GPUS39
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A4BT (Class L TD)
when your heavier loads need protection A4BT fuses won’t let you down The high interrupting rating of A4BT current limiting fuses is ideally suited for protecting mains, feeders, and general circuits. The 10-second time delay at 500% of fuse rating is ideal for large motors and other loads with a high inrush. A4BT fuses are suitable for DC applications up to 500VDC. An A4BT fuse can be applied to normal loads up to its full ampere rating to allow 100% rating of equipment.
Highlights • • • •
Features /Benefits • Unique dimensions prevent replacement by other fuse classes. • Blade-stamped catalog numbers for permanent identification • Glass melamine body and plated terminal provide superior reliability in harsh environments
Ratings AC: 200 to 2,000A 600VAC, 200kA I.R.
Current-Limiting Full 10-Second Delay DC Ratings Uniform Characteristics in all Ampere Ratings
Applications • • • • • •
Motors Motor Controllers Transformers Panelboards Mains Feeders
Approvals
DC: 200 to 2,000A 500VDC, 100kA I.R.
• UL Listed to Standard 248-10 (601-2000A) • CSA Certified to Standard C22.2 No. 248.10 (601-2000A) • DC Tested to UL 198L limits (601-2000A)
GPUS41
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® A4BT (Class L TD)
Standard Fuse Ampere Ratings, Catalog Numbers
Three Phase Motor Fuse Selection 460 Volt Three Phase Motors
Ampere Catalog Ampere Catalog Ampere Catalog Rating Number Rating Number Rating Number 200 250 300 350 400 500 600
A4BT200 A4BT250 A4BT300 A4BT350 A4BT400 A4BT500 A4BT600
601 650 700 750 800 900 1000
A4BT601 A4BT650 A4BT700 A4BT750 A4BT800 A4BT900 A4BT1000
1100 1200 1400 1500 1600 1800 2000
A4BT1100 A4BT1200 A4BT1400 A4BT1500 A4BT1600 A4BT1800 A4BT2000
Motor
Full Load
Recommended A4BT Ampere Rating Motor Acceleration Times HPAmperes Typical
Heavy Load
300
at 460V
5 seconds
Over 5 seconds
360
601
700
Standard Fuse Ampere Ratings, Reference Numbers 575 Volt Three Phase Motors
Ampere Ref. Ampere Ref. Ampere Ref. Rating Number Rating Number Rating Number 200 250 300 350 400 500 600
W212723 E214249 G214757 L215773 R216284 J217312 N217822
601 650 700 750 800 900 1000
Z218338 L218855 A219374 X219900 N222583 K200891 M222582
1100 1200 1400 1500 1600 1800 2000
J200890 W201430 G201946 G211169 Z211691 F212203 F213238
400 500
200-800A
382 472
601 700
700 1000
801-2000A
Dimensions Ampere Rating
In.
A mm
In.
B mm
In.
C mm
In.
D mm
In.
mm
200-600 601-800 801-1200 1201-1600 1601-2000
8-5/8 8-5/8 10-3/4 10-3/4 10-3/4
219 219 273 273 273
2 2-1/2 2-1/2 3 3-1/2
51 63 63 76 89
5/16 3/8 3/8 7/16 1/2
8 9 9 11 13
1-5/8 2 2 2-3/8 2-3/4
41 51 51 60 70
2-13/32 2-13/32 3-15/32 3-15/32 3-15/32
61 61 88 88 88
Safety Note: Class L fuses are dimensioned for one-way interchangeability. A Class L fuse of any lower ampere rating can be substituted for a given Class L fuse.
12/04
GPUS42
E
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A4BT (Class L TD)
MELTING TIME – CURRENT DATA, 600V AC/500V DC FUSES
A4BT 200 to 2000
TIME IN SECONDS
Peak Let-Thru Current Data – A4BT 300 to 2000, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
GPUS43
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A3T and A6T (Class T FA)
These small dimension fuses are the right fit... for a tight fit Fast acting A3T and A6T Class T fuses combine two highly desirable features -- high current limitation and a small physical size. Their unique dimensions prevent the substitution of other fuses with lower voltage ratings or current limiting capability. These fuses have glass melamine bodies for superior dimensional stability and catalog numbers stamped into the blades for permanent identification.
Highlights
Features /Benefits • Extremely current limiting for low peak let-thru current • Unique dimensions prevent replacement by other fuse classes • Blade-stamped catalog numbers for permanent identification • Small physical size for greater design flexibility
Ratings
• • • •
Fast Acting Extremely Current Limiting Small Physical Size DC Ratings
Applications • • • • •
Loadcenters Panelboards Switchboards Circuit Breakers Metering Centers
Approvals
A3T AC: 1 to 1200A 300VAC, 200kA I.R. DC: 1 to 1200A 160VDC, 50kA I.R.
• UL Listed to Standard 248-15 • CSA Certified to Standard C22.2 No. 248.15 • DC Tested to UL Standard 198L
A6T AC: 1 to 800A 600VAC, 200kA I.R. DC: 1 to 800A 300VDC, 100kA I.R
GPUS45
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® A3T and A6T (Class T FA)
Standard Fuse Ampere Ratings Ampere
Catalog Number
Reference Number
Ampere
Catalog Number
Reference Number
Rating
300V
600V
300V
600v
Rating
300V
600V
1 3 6 10 15 20 25 30 35 40 45 50 60 70 80 90 100
A3T1 A3T3 A3T6 A3T10 A3T15 A3T20 A3T25 A3T30 A3T35 A3T40 A3T45 A3T50 A3T60 A3T70 A3T80 A3T90 A3T100
A6T1 A6T3 A6T6 A6T10 A6T15 A6T20 A6T25 A6T30 A6T35 A6T40 A6T45 A6T50 A6T60 A6T70 A6T80 A6T90 A6T100
Q212212 R214766 Y217831 E212731 Q213247 G213745 P214258 V215275 W215782 B216293 C216800 T217321 J218347 F213744 Q214765 V215781 R217319
L219384 H201441 S213249 G219909 Z222593 P223113 W200901 R201955 T211180 L211702 S212214 G212733 J213747 Q214259 W215276 V217322 W218864
110 125 150 175 200 225 250 300 350 400 450 500 600 700 800 1000 1200
A3T110 A3T125 A3T150 A3T175 A3T200 A3T225 A3T250 A3T300 A3T350 A3T400 A3T450 A3T500 A3T600 A3T700 A3T800 A3T1000 A3T1200
A6T110 A6T125 A6T150 A6T175 A6T200 A6T225 A6T250 A6T300 A6T350 A6T400 A6T450 A6T500 A6T600 A6T700 A6T800 -
300V
600V
G218345 H219381 D219906 W222590 L223110 S200898 E201438 N201952 Q211177 H211699 P212211 D212730 P213246 N214257 T215274 W217829 T218862
K219383 F219908 Y222592 N223112 V200900 G201440 Q201954 S211179 K211701 R212213 F212732 R213248 H213746 S214767 D216801 -
A6T
A3T
A3T 1-60 A6T 1-30
A6T 31-60
A3T 61-1200 A6T 61-800
Dimensions Ampere Rating A3T 1-30 31-60 61-100 101-200 201-400 401-600 601-800 801-1200 A6T 1-30 31-60 61-100 101-200 201-400 401-600 601-800
12/04
A
B
In.
mm
In.
.88 .88 2.16 2.44 2.75 3.06 3.38 4.00
22.4 22.4 54.9 62.0 69.8 77.7 85.8 102
.41 .56 .81 1.06 1.33 1.62 2.08 2.52
1.50 1.57 2.95 3.26 3.62 3.98 4.33
38.1 39.9 74.9 82.8 92.1 101.2 110.0
.57 .81 .82 1.07 1.62 2.06 2.50
C mm
D
F
G
J
In.
mm
In.
mm
In.
mm
In.
mm
In.
mm
10.3 14.1 20.6 26.9 33.8 41.1 52.8 64.0
.12 .19 .25 .31 .38 .44
3.2 4.8 6.4 7.8 9.7 11.2
.75 .88 1.00 1.25 1.75 2.00
19.0 22.4 25.4 31.8 44.4 50.8
1.56 1.70 1.84 2.03 2.22 2.53
39.6 43.2 46.7 51.6 56.4 64.3
.28 .34 .41 .48 .55 .61
7.1 8.6 10.4 12.2 14.0 15.5
.82 .83 .84 .84 .88 1.03
20.8 21.1 21.3 21.3 22.4 26.2
14.5 20.6 20.8 27.2 41.3 52.4 63.5
1.51 .12 .19 .25 .31 .37
38.4 3.2 4.8 6.4 7.9 9.5
1.00 .75 .88 1.00 1.25 1.75
25.4 19.1 22.4 25.4 31.8 44.4
2.35 2.51 2.72 2.95 3.17
59.7 63.7 69.1 75.0 80.5
.28 .34 .41 .48 .56
7.1 8.6 10.4 12.2 14.1
1.58 1.61 1.70 1.70 1.70
40.1 41.0 43.2 43.2 43.2
GPUS46
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A3T and A6T (Class T FA)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 300V FUSES
A3T 30 to 1200
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – A3T 30 to 1200, 300 Volts AC
GPUS47
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® A3T and A6T (Class T FA)
MELTING TIME – CURRENT DATA, 600V FUSES
A6T 1 to 800
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – A6T 30 to 800, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
12/04
GPUS48
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® A2K and A6K (Class RK1FA)
These fast-acting fuses deliver a high degree of current limitation where Current-limiting A2K and A6K fuses provide excellent protection where high available short circuit currents exist. These fast-acting fuses are particularly good for branch/feeder circuits and back-up protection.
Features /Benefits • Rejection style design prevents replacement by other fuse classes • Fiberglass body provides dimensional stability in harsh industrial environments • Easy-to-read imprint label for quick recognition and replacement • High degree of current limitation for low peak letthru current
Ratings
Applications
A2K AC: 1 to 600A 250VAC, 200kA I.R. DC: 1 to 600A 250VDC, 200kA I.R. A6K AC: 1 to 600A 600VAC, 200kA I.R. DC: 1 to 600A 300VDC, 200kA I.R.
• • • • • • •
Loadcenters Panelboards Switchboards Bus Duct Feeder Circuits Non-inductive Loads Lighting Circuits
Approvals • UL Listed to Standard 248-12 • CSA Certified to Standard C22.2 No. 248.12 • DC tested to UL Standard 198L
Highlights • Highly Current-Limiting • Fast Acting • Rejection Style
GPUS49
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® A2K and A6K (Class RK1FA)
Standard Fuse Ampere Ratings Ampere
Catalog Number
Reference Number
Rating
250V
600V
250V
600V
Rating
250V
600V
250V
600V
A2K1R A2K3R A2K5R A2K6R A2K10R A2K12R A2K15R A2K20R A2K25R A2K30R A2K35R A2K40R A2K45R A2K50R A2K60R
A6K1R A6K3R A6K4R A6K5R A6K6R A6K8R A6K10R A6K15R A6K20R A6K25R A6K30R A6K35R A6K40R A6K45R A6K50R A6K60R
M215245 N217799 P222561 L200869 G213216 F214227 J214736 Q215754 W216265 W216771 J217289 Z218315 M218833 Z219879 F223082
A219880 M201928 H212182 J213218 H214229 L214738 N218834 B219352 Q222562 G223083 M200870 Z201410 K211149 C211671 Z212703 A213716
70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600
A2K70R A2K80R A2K90R A2K100R A2K110R A2K125R A2K150R A2K175R A2K200R A2K225R A2K250R A2K300R A2K350R A2K400R A2K450R A2K500R A2K600R
A6K70R A6K80R A6K90R A6K100R A6K110R A6K125R A6K150R A6K175R A6K200R A6K225R A6K250R A6K300R A6K350R A6K400R A6K450R A6K500R A6K600R
H211147 A211669 F212180 L215244 V216264 V216770 H217288 M217798 Y218314 L218832 Z219350 Y219878 N222560 E223081 K200868 X201408 K201926
K217290 P217800 A218316 Y201409 L201927 J211148 B211670 G212181 Y212702 H213217 Z213715 G214228 K214737 N215246 R215755 X216266 X216772
1 3 4 5 6 8 10 12 15 20 25 30 35 40 45 50 60
Ampere
Catalog Number
Reference Number
Recommended Fuse Blocks With Box Connectors For Amp-trap Class RK1Fuses Fuse Catalog Number Ref.Number Ampere 250 V 250 V Rating 1 Pole 3 Pole 1 Pole 3 Pole 0-30 31-60 61-100 101-200 201-400 401-600
0-60A
20306R 20606R 21036R 22001R 24001R 2631R
20308R 20608R 21038R 22003R 24003R 2633R
T213411 B212383 D201621 R213915 J219566 H214942
K215956 E214939 M212899 G214941 D222022 P215960
Fuse Catalog Number Ref.Number Ampere 600 V 600 V Rating 1 Pole 3 Pole 1 Pole 3 Pole 0-30 31-60 61-100 101-200 201-400 401-600
61-600A
60306R 60606R 61036R 62001R 64001R 6631R
60308R 60608R 61038R 62003R 64003R 6633R
H212389 K212391 W204788 V212906 D219055 J216990
K214438 M214440 Z211875 B213924 M222030 E218021
Dimensions Ampere A Rating In. mm 250V-A2K Fuses
0-30 31-60 61-100 101-200 201-400 401-600
2 3 5-7/8 7-1/8 8-5/8 10-3/8
B
C
D
E
In.
mm
In.
mm
In.
mm
In.
mm
51 76 149 181 219 264
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 53 66
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
127 139 200 244 295 340
13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8
21 27 34 46 66 80
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
600V-A6K Fuses
0-30 31-60 61-100 101-200 201-400 401-600 12/04
5 5-1/2 7-7/8 9-5/8 11-5/8 13-3/8
50
A variety of pole configurations and termination provisions is available. Refer to the fuse block section of this catalog for details.
General Purpose USUSFuses General Purpose Fuses American Power Fuses AMP-TRAP® A2K and A6K (Class RK1FA)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
A2K30 to 600
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – A2K30 to 600, 250 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
GPUS51
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® A2K and A6K (Class RK1FA)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
A6K 30 to 600
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – A6K 30 to 600, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
12/04
GPUS52
General Purpose USUSFuses General Purpose Fuses American Power Fuses AMP-TRAP® AG (Class G)
AMP-TRAP AG Fuses fit right in to a wide variety of industrial applications The Ferraz Shawmut Amp-trap AG fuse series is a complete line of Class G fuses. AG fuses safely fit a wide variety of applications. Class G fuses are made in four physical sizes and provide good branch-circuit protection for lighting, heating, and appliance circuits.
Features /Benefits • Four unique sizes from 1-60 amperes do not allow inter-changeability with other fuse classes • Fiberglass bodies provide dimensional stability in harsh industrial settings
Applications • • • •
Ratings AC: 1/2 to 20A 600VAC, 100K A I.R. 25 to 60A, 480VAC, 100k A I.R.
Lighting Heating* Appliances Branch Circuits
* Except in Canada where fuses must be “P” or “D” type.
Highlights
Approvals
• Current-Limiting • Time Delay (above 5A)
• UL Listed to Standard 248-5 • CSA Certified to Standard C22.2No. 248.5
Standard Fuse Ampere Ratings Ampere Rating
Catalog Number
Ref. Number
1/2 1 1-1/2 2 3 4 5 6 8 10 15 20 25 30 35 40 45 50 60
AG1/2 AG1 AG1-1/2 AG2 AG3 AG4 AG5 AG6 AG8 AG10 AG15 AG20 AG25 AG30 AG35 AG40 AG45 AG50 AG60
P201470 T223140 B200929 R211730 Y213277 B215304 L216831 H217863 F218896 Z201985 A211209 Z212243 L212760 P213775 Y214289 D215812 H216322 A217350 R218377
Dimensions AMPERE RATING
In.
A mm
In.
B mm
In.
C mm
1/2-15A 20A 25, 30A 35-60A
1.31 1.41 1.62 2.25
33.3 35.8 41.2 57.2
.406 .406 .406 .406
10.3 10.3 10.3 10.3
.28 .28 .28 .50
7.1 7.1 7.1 12.7
Cross Reference: AG will replace the following fuses: Bussmann SC, Littelfuse SLC
GPUS53
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® AG (Class G)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 480V FUSES
AG 15 to 60
TIME IN SECONDS
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 480V FUSES
AG 1 to 10
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LETTHRU AMPERES
Peak Let-Thru Current Data – AG 1 to 60, 480 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
12/04
GPUS54
General Purpose US US Fuses General Purpose Fuses American Power Fuses AMP-TRAP® ATMR (Class CC)
Small Fuse - Big protection for general circuits Amp-trap ATMR fuses, in the Class CC family, are the smallest dimension 600V fuses suitable for branch circuit protection. The ATMR is a popular choice for economical protection of control circuits and control circuit transformers where available short circuit currents exceed 10,000 amperes. ATMR’s rejection dimensions prevent substitution by lesser rated fuses. These fast acting fuses give current limiting protection to general circuits.
Features /Benefits • Rejection style design prevents replacement errors when used with recommended fuse blocks • Fiberglass body provides dimensional stability in harsh industrial environments • Versatile design for individual component and branch circuit protection
Ratings
Applications
AC: 1/10 to 30A 600VAC, 200kA I.R.
• • • •
Highlights • Fast Acting • Very Current-Limiting
Approvals
Primary Fuse Sizing for Control Transformer
• UL Listed to Standard 248-4 • CSA Certified to Standard C22.2No. 248.4
ATMR Rating Transformer Volt-Amperes
480V primary
50 75 100 150 200 250 300 350 500 750 1000
1/2* 3/4* 1 1-1/2 2 2 3 3-1/2 5 7 -
Control Circuits Lighting General Loads Branch Circuit Protection
600V primary
3/10* 1/2* 3/4* 1* 1-1/2* 2 2 2 4 6 8
Standard Fuse Ampere Ratings
All rating will wiyhstand inrush currents of 40 times transformer full load for 1/2 cycle unless otherwise noted. * These ratings will withstand inrush currents of 35 times transformer full load for 1/2 cycle.
GPUS55
Ampere Rating
Catalog Number
1/10 1/8 2/10 1/4 3/10 1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3
ATMR1/10 ATMR1/8 ATMR2/10 ATMR1/4 ATMR3/10 ATMR1/2 ATMR3/4 ATMR1 ATMR1-1/4 ATMR1-1/2 ATMR2 ATMR2-1/2 ATMR3
Reference Ampere Number Rating C217789 P219341 B201918 C218824 W214218 N218305 Z214727 L216256 Y217279 K216761 A200859 N201400 N212693
3-1/2 4 5 6 7 8 9 10 12 15 20 25 30
Catalog Reference Number Number ATMR3-1/2 ATMR4 ATMR5 ATMR6 ATMR7 ATMR8 ATMR9 ATMR10 ATMR12 ATMR15 ATMR20 ATMR25 ATMR30
Y213208 G215746 M216257 L216762 Z217280 D217790 P218306 P219870 D222551 V223072 Z211139 Q211660 C215236
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses AMP-TRAP® ATMR (Class CC)
Recommended Fuse Blocks For Amp-Trap® Class CC Fuses Catalog Number
Reference Number
Number ULTRAScrew Pressure Copper ULTRAScrew Pressure Copper of SAFE Connector Plate Box SAFE Connector Plate Box Poles Indicating w/ Double Connector Connector Indicating w/ Double Connector Connector Fuse Quick w/ Double Fuse Quick w/ Double Holder Connects Quick Holder Connects Quick Connects Connects
ADDER 1 2 3
USCC1I USCC2I USCC3I
30310R 30311R 30312R 30313R
30320R 30321R 30322R 30323R
30350R W204857 Z217510 N213429 30351R X213943 R212397 M218534 G213929 30352R D217008 Z212910 Y219579 V214447 30353R Y218038 M213428 B222779 X214955
Refer to the Class CC Fuse Block section of this catalog for other details.
Dimensions
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
ATMR 1/10 to 30
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LETTHRU AMPERES
Peak Let-Thru Current Data – ATMR 3/4 to 30, 600 Volts AC
CURRENT IN AMPERES 12/04
GPUS56
General Purpose US US Fuses General Purpose Fuses American Power Fuses One-Time OT, OTN, OTS (Class K-5)
For versatility and economy, these general purpose fuses are hard to beat OT, OTN and OTS general purpose fuses provide low cost protection for feeder and branch circuits serving lighting, heating, and other non-motor loads OT, OTN and OTS fuses will safely interrupt available short circuit currents up to 50,000 amperes in all ratings. OT, OTN and OTS fuses are not rejection fuses – care should be taken to ensure that replacement fuses do not have lower interrupting ratings than original fuses. OTN 15 through 60 satisfy the Canadian electrical code requirement for Type “P,” low melting-point, non-time delay fuses.
Features /Benefits
Highlights
• Easy to read imprint label for quick recognition and replacement • Low cost for high protection value
• Versatile • Lowest cost protection for circuits serving non-inductive loads
Ratings
Applications
OT AC: 1 to 600A 250VAC, 50kA I.R. DC: 1 to 600A 250VDC, 20kA I.R. OTN (Canada) AC: 15 to 60A 250VAC, 50kA I.R. OTS AC: 1 to 600A 600VAC, 50kA I.R. DC: 1 to 600A 300VDC, 20kA I.R.
• • • •
Feeders Branch Circuits Resistive Heating Residential and Small Commercial Installations
Approvals • UL Listed to Standard 248-9 • CSA Certified toStandard C22.2 No. 248.9* • DC Tested to UL Standard 198L * The Canadian Electrical Code requires these fuses in ratings 15 through 60A to be of the low melting point design use OTN 15-60.
GPUS57
12/04
General Purpose General Purpose US Fuses US Fuses American Power Fuses One-Time OT, OTN, OTS (Class K-5)
Standard Fuse Ampere Ratings Ampere Rating
Catalog Number 250V 600V
1 2 3 4 5 6 7 8 10 12 15 20 25 30 35 40 45 50 60
OT1 OT2 OT3 OT4 OT5 OT6 OT7 OT8 OT10 OT12 OT15 OT20 OT25 OT30 OT35 OT40 OT45 OT50 OT60
OTS1 OTS2 OTS3 OTS4 OTS5 OTS6 OTS7 OTS8 OTS10 OTS12 OTS15 OTS20 OTS25 OTS30 OTS35 OTS40 OTS45 OTS50 OTS60
Reference Number 250V 600V
H218277 Y222523 K201374 Q212143 W214701 H216230 Z217763 J218278 X218796 H219312 J219842 P223044 V200831 W201890 J211631 H212665 K213679 A215211 F216734
Ampere Rating
D215720 L218280 M219845 Y200834 Y211115 T212146 R223506 W213183 K216232 H216736 X217255 Z218798 L219315 B222526 S223047 N201377 Z201893 M211634 L212668
65 70 75 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600
Catalog Number 250V 600V
OT65 OT70 OT75 OT80 OT90 OT100 OT110 OT125 OT150 OT175 OT200 OT225 OT250 OT300 OT350 OT400 OT450 OT500 OT600
Reference Number 250V 600V
OTS65 OTS70 OTS75 OTS80 OTS90 OTS100 OTS110 OTS125 OTS150 OTS175 OTS200 OTS225 OTS250 OTS300 OTS350 OTS400 OTS450 OTS500 OTS600
V201889 T211111 H211630 P212142 G212664 Y215209 Z215716 F216228 D216732 S217251 X217761 G218276 W218795 G219311 H219841 X222522 N223043 T200830 J201373
A222525 R223046 X200833 M201376 T213181 L213680 S214192 X214702 B215212 C215719 J216231 G216735 W217254 A217764 K218279 Y218797 K219314 L219844
OTN 15 to 60A: consult us.
Recommended Fuse Blocks With Box Connectors For One-Time Class K-5 Fuses Fuse Catalog Number Ampere 250 V Rating 1 Pole 3 Pole 0-30 31-60 61-100 101-200 201-400 401-600
0-60A
20306 20606 21036 22001 24001 2631
20308 20608 21038 22003 24003 2633
Fuse Catalog Number Ampere 600 V Rating 1 Pole 3 Pole 0-30 31-60 61-100 101-200 201-400 401-600
61-600A
Dimensions Ampere Rating
A In.
B mm
250V-OT, OTN FUSES 0-30 2 51 31-60 3 76 61-100 5-7/8 149 101-200 7-1/8 181 201-400 8-5/8 219 401-600 10-3/8 264 600V-OTS FUSES 0-30 5 127 31-60 5-1/2 139 61-100 7-7/8 200 101-200 9-5/8 244 201-400 11-5/8 295 401-600 13-3/8 340
12/04
C
D
E
In.
mm
In.
mm
In.
mm
In.
mm
9/16 13/16 1-1/16 1-9/16 2-1/16 2-9/16
14 21 27 40 53 66
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
13/16 1-1/16 1-5/16 1-13/16 2-9/16 3-1/8
21 27 34 46 66 80
1/8 3/16 1/4 1/4
3 5 6 6
3/4 1-1/8 1-5/8 2
19 28 41 51
1 1-3/8 1-7/8 2-1/4
25 35 48 57
GPUS58
60306 60606 61036 62001 64001 6631
60308 60608 61038 62003 64003 6633
Ref.Number 250 V 1 Pole 3 Pole Z212381 N211865 S201105 Y213415 T219046 F214434
F215446 C214431 Q211867 E214433 K215450
Ref.Number 600 V 1 Pole 3 Pole V211871 X211873 K201627 M212393 H218530 Z216475
X213920 Z213922 S211363 H213424 T219575 W217507
A variety of pole configurations and termination provisions is available. Refer to the fuse block section of this catalog for details.
General Purpose US US Fuses General Purpose Fuses American Power Fuses One-Time OT, OTN, OTS (Class K-5)
CURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 250V FUSES
OT 30 to 600; OTN 30, 60
TIME IN SECONDS
ACURRENT IN AMPERES
MELTING TIME – CURRENT DATA, 600V FUSES
OTS 30 to 600
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – OT, OTN & OTS 30 to 600, 250 and 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES GPUS59
12/04
General Purpose US US Fuses General Purpose Fuses American Power Fuses Renewable RF/RFS and RL/RLS (Class H)
Traditional protection for circuits with less than 10,000A Short circuit current RF and RFS general purpose fuses are suitable for application where available short circuit currents do not exceed 10,000 amperes. RF and RFS renewable fuses use matched RL and RLS die-cut zinc links from 1 to 600 amperes in 32 ratings.
Note: To be replace by TR (250V) and TRS (600V) compatible class RK5
Features /Benefits
Applications
• Knurled bushings for ease of disassembly • Rugged construction for maximum service life
• General purpose loads where short circuits are 10,000 amperes or less
• Precision die-cut renewal links renew quickly and give repeatable performance
Approvals • UL Listed to Standard 248-7 • CSA Certified to Standard C22.2 No. 248.7
Ratings RF AC: 1 to 600A 250VAC, 10kA I.R. RFS AC: 1 to 600A 600VAC, 10kA I.R.
Highlights • Renewable • 32 Renewal Link Ratings
GPUS61
12/04
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x38 US) Time Delay ATQ 500VAC (TD)
Amp-trap® ATQ midget time-delay fuses are rated a full 500 volts AC with 42 ampere ratings from 1/10 to 30A. They are an excellent choice for supplemental protection of circuits up to 30A where the available short circuit current does not exceed 10,000A. (Not for Branch Circuit Protection).
Features /Benefits
Applications
• Numerous ratings for a wide variety of applications up to 500VAC • Time delay (12 seconds at 200% rating) for circuits with high inrush current • UltraSafe TM fuse holder: refer to Fuse Blocks and Fuse Holders section for details, Catalog Number and Reference Number
• Supplemental protection of lighting, solenoid, motor, and transformer circuits • Transformers • Control Panels • Circuit Breaker Back-up • Bus Duct • Load Centers
Ratings
Approvals
• AC: 1/10 to 30A 500VAC, 10kA I.R.
• UL Listed to Standard 248-14 • CSA Certified to Standard C22.2 No. 248.14
Highlights • Time Delay
Standard Fuse Ampere Ratings, Catalog Numbers Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Rating
Number
Rating
Number
Rating
Number
Rating
Number
Rating
Number
Rating
Number
Rating
Number
3/10 4/10 1/2 6/10 8/10 1
ATQ3/10 ATQ4/10 ATQ1/2 ATQ6/10 ATQ8/10 ATQ1
1-1/8 ATQ1-1/8 2 1-1/4 ATQ1-1/4 2-1/8 1-4/10 ATQ1-4/10 2-1/4 1-1/2 ATQ1-1/2 2-1/2 1-6/10 ATQ1-6/10 2-8/10 1-8/10 ATQ1-8/10 3
ATQ2 ATQ2-1/8 ATQ2-1/4 ATQ2-1/2 ATQ2-8/10 ATQ3
3-2/10 3-1/2 4 4-1/2 5 5-6/10
ATQ3-2/10 ATQ3-1/2 ATQ4 ATQ4-1/2 ATQ5 ATQ5-6/10
6 6-1/4 7 8 9 10
ATQ6 ATQ6-1/4 ATQ7 ATQ8 ATQ9 ATQ10
12 14 15 20 25 30
ATQ12 ATQ14 ATQ15 ATQ20 ATQ25 ATQ30
ATQ1/10 1/10 1/8 ATQ1/8 15/100 ATQ15/100 ATQ3/16 3/16 2/10 ATQ2/10 1/4 ATQ1/4
Standard Fuse Ampere Ratings, Reference Numbers Ampere Reference
Ampere Reference
Ampere Reference Ampere Reference
Ampere
Rating
Number
Rating
Rating
Number
Rating
Number
Rating
Number
Rating
Number
1/10 1/8 15/100 3/16 2/10 1/4
S211662 A213210 J215748 D201920 E218826 Q212695
P216259 F217792 B217282 N216764 R218308 G222554
3-2/10 3-1/2 4 4-1/2 5 5-6/10
D200862 Y223075 T211663 Z212174 B213211 S213709
6 6-1/4 7 8 9 10
Z214221 C214730 P216765 C217283 S218309 R213708
12 14 15 20 25 30
Y214220 B214729 E215238 S219344 S219873 B211141
Number
3/10 Q201402 4/10 R212696 1/2 Y212173 6/10 F215239 8/10 G217793 1 E217791
Number
Rating
1-1/8 R219872 2 1-1/4 R219343 2-1/8 1-4/10 F222553 2-1/4 1-1/2 Q218307 2-1/2 1-6/10 X223074 2-8/10 1-8/10 C200861 3
GPUS63
Reference Ampere Reference Ampere Reference
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) Time Delay ATQ 500VAC (TD)
TIME IN SECONDS
Melting Time – Current Data 1/10 - 3-1/2 Amperes, 500 Volts AC
CURRENT IN AMPERES
TIME IN SECONDS
Melting Time – Current Data 4 - 30 Amperes, 500 Volts AC
CURRENT IN AMPERES
12/04
GPUS64
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x38 US) Time Delay TRM
Tri-onic® TRM time-delay midget fuses are rated 250 volts AC and are offered in 36 ampere ratings from 1/10A to 30A. They have 12 seconds time delay at 200% rating to provide supplemental protection of small motors, small transformers and other high inrush loads, plus many other 250 volt applications. (Not for Branch Circuit Protection).
Features /Benefits
Highlights
• Numerous ratings for a wide variety of applications • 250VAC rating in all sizes up to 30A • Time delay for circuits with high inrush currrent • UltraSafe TM fuse holder: refer to Fuse Blocks and Fuse Holders section for details,Catalog Number and Reference Number
• Time Delay • 250 VAC Rated
Ratings
Approvals
• AC: 1/10 to 30A 250VAC, 10kA I.R.
• UL Listed to Standard 248-14 • CSA Certified to Standard C22.2 No. 248.14
Applications • • • •
Small Motors Small Transformers Lighting Circuits Control Circuits
Standard Fuse Ampere Ratings, Catalog Numbers Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Ampere
Catalog
Rating
Number
Rating
Number
Rating
Number
Rating
Number
Rating
Number
Rating
Number
1/10 15/100 2/10 3/10 4/10 1/2
TRM1/10 TRM15/100 TRM2/10 TRM3/10 TRM4/10 TRM1/2
6/10 8/10 1 1-1/8 1-1/4 1-4/10
TRM6/10 TRM8/10 TRM1 TRM1-1/8 TRM1-1/4 TRM1-4/10
1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10
TRM1-6/10 TRM1-8/10 TRM2 TRM2-1/4 TRM2-1/2 TRM2-8/10
3 3-2/10 3-1/2 4 4-1/2 5
TRM3 TRM3-2/10 TRM3-1/2 TRM4 TRM4-1/2 TRM5
5-6/10 6 6-1/4 7 8 9
TRM5-6/10 TRM6 TRM6-1/4 TRM7 TRM8 TRM9
10 12 15 20 25 30
TRM10 TRM12 TRM15 TRM20 TRM25 TRM30
Reference
Standard Fuse Ampere Ratings, Reference Numbers Ampere
Reference
Ampere
Reference
Ampere
Reference
Ampere
Reference
Ampere
Reference
Ampere
Rating
Number
Rating
Number
Rating
Number
Rating
Number
Rating
Number
Rating
Number
1/10 15/100 2/10 3/10 4/10 1/2
R217273 M223065 P212165 V215229 W217783 V217782
6/10 8/10 1 1-1/8 1-1/4 1-4/10
X222545 G201394 M214210 T215228 Q214719 Y215738
1-6/10 1-8/10 2 2-1/4 2-1/2 2-8/10
E216250 C216754 S200852 R211132 T201911 H211653
3 3-2/10 3-1/2 4 4-1/2 5
H213700 R214720 N214211 F216251 D216755 G218299
5-6/10 6 6-1/4 7 8 9
W218818 H219335 H219864 N223066 T200853 V201912
10 12 15 20 25 30
V218817 G219334 W222544 F212686 Q213201 Z215739
GPUS65
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) Time Delay TRM
TIME IN SECONDS
Melting Time – Current Data 1/10 - 3-1/2 Amperes, 250 Volts AC
CURRENT IN AMPERES
TIME IN SECONDS
Melting Time – Current Data 4 - 30 Amperes, 250 Volts AC
CURRENT IN AMPERES
12/04
GPUS66
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x38 US) Time Delay GFN
GFN midget indicating fuses are available in 34 ratings from 1/10A through 30A. These timedelay fuses have built-in blown fuse indicators which pop out at the end of the fuse to visually indicate when the fuse has operated to open the circuit. Indicators may be used to trip a switch for remote as well as visual indication. (Not for Branch Circuit Protection).
Features /Benefits
Ratings
• Pin indicator provides visual indication of open fuse or actuates switch for remote signaling • Numerous ratings for a wide variety of applications • 12 second time delay at 200% rating • UltraSafeTM fuse holder: refer to Fuse Blocks and Fuse Holders section for details, Catalog Number and Reference Number
• AC: 1/10 to 10A 250VAC, 200A I.R., 125VAC, 10kA I.R.; 12 to 15A 125VAC, 10kA I.R.; 20 to 30A 32VAC, 10kA I.R.
Highlights • Pin Indicating • Time Delay
Applications • For supplemental protection of circuits where time delay and blown fuse indication are required, such as solenoid circuits or control circuits.
Melting Time – Current Data 1 - 30 Amperes, 250 Volts AC
Approvals • UL Listed to Standard 248-14 (1/10 to 15A) • CSA Certified to Standard C22.2 No.248.14 (1/10 to 15A)
TIME IN SECONDS
Standard Fuse Ampere Ratings Ampere Rating 1/10 1/8 15/100 2/10 1/4 3/10 4/10 1/2 6/10 8/10 1 1-1/8 1-1/4 1-4/10 1-1/2 1-6/10 1-8/10
Catalog Number GFN1/10 GFN1/8 GFN15/100 GFN2/10 GFN1/4 GFN3/10 GFN4/10 GFN1/2 GFN6/10 GFN8/10 GFN1 GFN1-1/8 GFN1-1/4 GFN1-4/10 GFN1-1/2 GFN1-6/10 GFN1-8/10
Reference Number K222557 T201405 C212177 C214224 G200865 F217286 X219348 B223078 H201924 Y211667 R216767 V218311 J217795 H218829 E217285 W219347 W219876
Ampere Rating 2 2-1/4 2-1/2 3 3-2/10 3-1/2 4 4-1/2 5 6-1/4 8 10 12 15 20 25 30
Catalog Number GFN2 GFN2-1/4 GFN2-1/2 GFN3 GFN3-2/10 GFN3-1/2 GFN4 GFN4-1/2 GFN5 GFN6-1/4 GFN8 GFN10 GFN12 GFN15 GFN20 GFN25 GFN30
Reference Number V212699 W213712 E213214 M215751 S216768 S216262 W218312 J218830 L222558 V201406 F211145 G201923 E211144 X211666 F214733 J215242 J215242
CURRENT IN AMPERES GPUS67
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) Fast Acting A6Y-2B
A6Y “Type 2B” Amp-trap® midget fuses are fast acting on short circuits, yet have sufficient time delay to offer supplemental protection for small motors, transformers, and control circuits. (Not for Branch Circuit Protection).
Highlights • Fast Acting
Features /Benefits
Applications
• Moderate amount of time delay for circuits with inrush characteristics • Fast acting on short circuits • UltraSafeTM fuse holder: refer to Fuse Blocks and Fuse Holders section for details,Catalog Number and Reference Number
• Supplemental protection of 600V (up to 3A) and 500V (3-2/10-15A) AC circuits • Small motors, transformers, and control circuits
Ratings
Approvals • Ferraz Shawmut Certified
Melting Time – Current Data 1/4 - 3 Amperes, 600 Volts AC 3-2/10 - 15 Amperes, 500 Volts AC
• AC: 1/4 to 3A 600VAC, 10kA I.R. 3-2/10 to 15A 500VAC, 10kA I.R.
Ampere Rating
Catalog Number
Reference Number
1/4 1/2 6/10 3/4 1 1-1/4 1-1/2 1-6/10 2 2-1/2 3 3-2/10 3-1/2 4 5 6 7 8 9 10 12 15
A6Y1/4-2B A6Y1/2-2B A6Y6/10-2B A6Y3/4-2B A6Y1-2B A6Y1-1/4-2B A6Y1-1/2-2B A6Y1-6/10-2B A6Y2-2B A6Y2-1/2-2B A6Y3-2B A6Y3-2/10-2B A6Y3-1/2-2B A6Y4-2B A6Y5-2B A6Y6-2B A6Y7-2B A6Y8-2B A6Y9-2B A6Y10-2B A6Y12-2B A6Y15-2B
Y222546 J219865 T214722 X218819 H218300 X217784 J219336 T211134 W201913 H212688 R212167 K211655 S213203 K213702 Q214213 X215231 B215741 F216757 P223067 V200854 H201395
TIME IN SECONDS
Standard Fuse Ampere Ratings
CURRENT IN AMPERES 12/04
GPUS68
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x38 US) Fast Acting ATM
Amp-trap® midget fast-acting ATM fuses are rated 600 volts AC, with a 100kA interrupting rating. These ratings give the ATM a wide range of applications not covered by other midget fuses. In addition, ratings of 30/35, 30/40 and 30/50 amperes are offered for specific applications such as capacitor protection. These ATM fuses must still be considered 30A fuses because of their dimensions, but are able to withstand much higher inrush currents and tougher duty cycles. (Not for Branch Circuit Protection).
Features /Benefits
Highlights
• For supplemental protection of small motors and transformers • Extended ratings for special protection of capacitors and circuits with high inrush currents • 500VDC ratings for a wide variety of applications • UltraSafeTM fuse holder: refer to Fuse Blocks and Fuse Holders section for details,Catalog Number and Reference Number
• Fast Acting • Special Ratings (above 30A)
Ratings
• UL Listed to Standard 248-14 (1/10 to 30A) • DC listed to UL Standard 248-14 (1/10 to 30A) • CSA Certified to Standard C22.2 No. 248.14 (1/10 to 30A)
• AC: 1/10 to 30A 600VAC, 100kA I.R.; 35 to 50A 600VAC, 10kA I.R. • DC: 1/10 to 30A 500VDC, 100kA I.R.
Applications • Supplemental protection of a wide variety of circuits up to 600VAC and 500VDC with100kA I.R.
Approvals
Melting Time – Current Data 1/10 30/50 Amperes, 600 Volts AC Standard Fuse Ampere Ratings, Reference Numbers Ampere Rating
TIME IN SECONDS
1/10 1/8 2/10 1/4 1/2 3/4 1 1-1/2 2 3 4 5 6 8 10 12 15 20 25 30 30/35 30/40 30/50
Catalog Number
Reference Number
ATM1/10 ATM1/8 ATM2/10 ATM1/4 ATM1/2 ATM3/4 ATM1 ATM1-1/2 ATM2 ATM3 ATM4 ATM5 ATM6 ATM8 ATM10 ATM12 ATM15 ATM20 ATM25 ATM30 ATM30/35* ATM30/40* ATM30/50*
L218303 M219868 X211137 M219339 A218822 W213206 W217277 A217787 Z201916 L212691 E215744 K216255 J216760 B217788 B222549 Y200857 L201398 N211658 V212170 N213705 T214216* X214725* A215234*
*Not continuous current rated devices CURRENT IN AMPERES GPUS69
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) Fast Acting 6JX
600VAC - 500VDC 100000 A.I.R Current limiting Ferraz Shawmut 6JX Midget Fuses are recommended for applications requiring very precise operating characteristics and where high available fault currents demand high interrupting capacities. Typical applications include control circuit, lighting circuit, small motor and control transformer protection.
Dimensions
6JX fuses can be mounted in the UltraSafeTM fuse holder. Refer to Fuse Blocks and Fuse Holders section for details, Reference Number and Catalog Number.
Standard Fuse Ampere Ratings, Reference Numbers Test specifications INF = 110% IN t Ø 4 Hours IF = 135% IN t ≤ 1 Hour IF= 200% IN t ≤ 120 Sec. UL LISTED CSA CERTIFIED
Ampere Reference Rating Number 0,100 0,125 0,200 0,250 0,300 0,500 0,750 1 1,5 2 2,5 3 3,5
Metting Time-current Data
12/04
GPUS70
C079651J D079652J K079681J L079682J T082334J R083068J Q079686J S083069J S080838J K082326J A080293J F082690J E079745J
Catalog Number
Ampere Rating
6JX0,1 6JX0,125 6JX0,2 6JX0,25 6JX0,3 6JX0,5 6JX0,75 6JX1 6JX1,5 6JX2 6JX2,5 6JX3 6JX3,5
4 5 6 7 8 9 10 12 15 20 25 30
Reference Catalog Number Number E083471J X089398J B082686J W079783J B080294J R079848J E082689J W089397J F082805J S079849J K079865J S079895J
6JX4 6JX5 6JX6 6JX7 6JX8 6JX9 6JX10 6JX12 6JX15 6JX20 6JX25 6JX30
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x38 US) Fast Acting OTM
One-time OTM midget fuses provide low-cost protection for 250 volt AC general purpose lighting, heating, control circuits, etc. where time delay is not required. (Not for Branch Circuit Protection).
Features /Benefits • Low cost and fully rated for economy without compromise • UltraSafe TM fuse holder: refer to Fuse Blocks and Fuse Holders section for details, Catalog Number and Reference Number
Ratings
Highlights • Fast Acting • 250 VAC Rated
Applications
• AC: 1 to 30A 250VAC, 10kA I.R.
• Supplemental protection of circuits up to 250VAC and 10kA
Melting Time – Current Data 1-30 Amperes, 250 Volts AC
Approvals • UL Listed to Standard 248-14 • CSA Certified to Standard C22.2 No. 248.14
Standard Fuse Ampere Ratings, Reference Numbers
GPUS71
Ampere Rating
Catalog Number
Reference Number
1 2 3 4 5 6 8 10 15 20 25 30
OTM1 OTM2 OTM3 OTM4 OTM5 OTM6 OTM8 OTM10 OTM15 OTM20 OTM25 OTM30
E215721 Y217256 A218799 N219846 C222527 T223048 Z200835 L216233 J216737 B217765 M218281 M219316
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) Fast Acting GGU
125 volt AC rated GGU fuses have midget fuse dimensions (1-1/2” long x 13/32” diameter). Ratings 3 through 15 amperes have glass bodies for easy checking of fuse link status. Ratings 20, 25, and 30 amperes have ceramic bodies, allowing use in higher ambient temperature conditions than other similar fuses. (Not for Branch Circuit Protection).
Features /Benefits
Ratings
• Glass body on 3-15A makes status of fusible element clearly visible • All ratings 125VAC - higher than competitors • Ceramic body on 20-30A allows use in higher temperature applications • Fast acting for protection of circuits up to 30A and 125VAC • UltraSafe TM fuse holder: refer to Fuse Blocks and Fuse Holders section for details, Catalog Number and Reference Number
• AC: 3 to 30A 125VAC, 10kA I.R
Highlights • Fast Acting
Applications • General Purpose • 125 Volt AC Circuits • Supplemental Protection
Approvals Melting Time – Current Data 3-30 Amperes, 125 Volts AC
• UL Listed to Standard 248-14 (3 to 15A) • UL Recognized Component Guide No. JDYX2 (20 to 30A)
TIME IN SECONDS
Standard Fuse Ampere Ratings, Reference Numbers
CURRENT IN AMPERES 12/04
GPUS72
Ampere Rating
Catalog Number
Reference Number
3 4 5 8 10 15 20 25 30
GGU3 GGU4 GGU5 GGU8 GGU10 GGU15 GGU20 GGU25 GGU30
Q212442 K213472 E213973 Q214489 K201673 S205475 A211416 C211924 A212957
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x35 US) Fast Acting SBS Unique dimensions for today’s smaller equipment and components Fast-acting general purpose SBS fuses were developed in response to the industry’s demand for smaller equipment and components. They are the only fuses in their size with a full 600 volt AC rating for all ampere ratings by Underwriters Laboratories standard 198G and CSA No. 59.2, and are the only fuses of this size with an interrupting rating of 100kA RMS, compared to 10kA on other brands. Features /Benefits SBS fuses are 1-3/8” long, smaller by 1/8” than most standard midget fuses and are available in 22 ampere • Small unique physical size for maximum ratings, from 2/10A to 30A. design flexibility and non-interchangeability (Not for Branch Circuit Protection). with ther fuse classes • Fiberglass body provides dimensional stabilRatings Applications ity in harsh industrial environments • AC: 2/10 to 30A • Control Circuits • UltraSafeTM fuse holder: refer to Gear and 600VAC, • Lighting Ballasts Fuse Gear section for details, Catalog 100kA I.R. • Meter Circuits Number and Reference Number • Electronic Circuits
Standard Fuse Ampere Ratings, Highlights Reference Numbers
Catalog Reference Catalog Reference Ampere Ampere Rating Number Number Rating Number Number 2/10 SBS2/10 Y219349 4 SBS4 J201925 4/10 SBS4/10 G211146 5 SBS5 Z211668 1/2 SBS1/2 T216769 6 SBS6 E212179 3/4 SBS3/4 J200867 7 SBS7 X212701 8/10 SBS8/10 H214735 8 SBS8 E214226 1 SBS1 G214734 10 SBS10 G217287 1-1/2 SBS1-1/2 K215243 12 SBS12 G217287 1-6/10 SBS1-6/10 N215752 15 SBS15 X218313 1-8/10 SBS1-8/10 T216263 20 SBS20 X219877 2 SBS2 K218831 25 SBS25 M222559 3 SBS3 D223080 30 SBS30 W201407 Cross Reference: SBS will replace Bussmann BBS, Littelfuse BLS fuses
Approvals
• Fast Acting • General Purpose • Unique Dimensions
• UL Listed to Standard 248-14 • CSA Certified to Standard C22.2 No. 248.14
Melting Time – Current Data 2/10 - 30 Amperes, 600 Volts AC
TIME IN SECONDS
MAXIMUM INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-thru Current Data 3/4 - 30 Amperes, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
CURRENT IN AMPERES GPUS73
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) PC Mount PCF
Fast acting fuses for direct mounting on printed circuit boards Ferraz Shawmut’s new PCF series of fast-acting direct-mountable fuses addresses the increasing need for electrical protection at the PC board as current and voltage requirements push higher. These fuses help printed circuit board manufacturers reduce parts by eliminating clips and fuse blocks and allowing automated assembly. PCF fuses can be used for the protection of main frame power boards, small circuit breakers with low interrupting ratings and other critical components. PCF fuses bring greatly increased ampere, voltage and interrupting ratings to the board itself and are UL Component Recognized.
Ratings
Applications
• AC: 1 to 30A 600VAC, 100kA I.R. • DC: 1 to 30A 500VDC, 100kA I.R. L/R ≤10ms
• Protection of main frame power boards, circuit breakers, components
Highlights
Approvals
• Fast Acting • PC Board Mount • Three Mounting Styles
• UL Recognized Components
Melting Time – Current Data
Standard Fuse Ampere Ratings, Ref. Numbers Ampere Rating
Catalog Number
Reference Number
Ampere Rating
Catalog Number
Reference Number
N212256 V218909 P212257 F218390 D219952 G201486 G211744
8 10 12 15 20 25 30
PCF8-R PCF10-R PCF12-R PCF15-R PCF20-R PCF25-R PCF30-R
P213292 E213789 T215826 Q217364 V222635 F201485 Q215317
8 10 12 15 20 25 30
PCF8-H PCF10-H PCF12-H PCF15-H PCF20-H PCF25-H PCF30-H
C212775 N213291 N214809 B216845 C219951 P200941 F213790
8 10 12 15 20 25 30
PCF8-S PCF10-S PCF12-S PCF15-S PCF20-S PCF25-S PCF30-S
G213791 N214303 Y216336 Y217877 J223154 Q211223 V215827
Slot Mount 1 2 3 4 5 6 7
PCF1-R PCF2-R PCF3-R PCF4-R PCF5-R PCF6-R PCF7-R
TIME IN SECONDS
Double Hole Mount 1 2 3 4 5 6 7
PCF1-H PCF2-H PCF3-H PCF4-H PCF5-H PCF6-H PCF7-H
E211742 E218389 F211743 Z217878 K219429 Q200942 R211224
Surface Mount 1 2 3 4 5 6 7
CURRENT IN AMPERES 12/04
GPUS74
PCF1-S PCF2-S PCF3-S PCF4-S PCF5-S PCF6-S PCF7-S
A212773 J219428 B212774 W218910 W222636 T202026 Q212258
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x38 US) PC Mount PCS
Semiconductor protection fuses for direct mounting on printed circuit boards Ferraz Shawmut's new PCS series of extremely fast-acting, direct-mountable fuses addresses the increasing need for electrical protection at the PC board as current and voltage requirements push higher. These fuses help printed circuit board manufacturers reduce parts by eliminating clips and fuse blocks and allowing automated assembly. PCS fuses are AC and DC rated and are extremely current-limiting. They will protect semiconductors, main frame boards, circuit breakers with low interrupting rating and other critical components. PCS fuses bring I2t protection, higher voltage and interrupting ratings to the board itself and are UL Component Recognized.
Ratings
Applications
• AC: 5 to 30A 600VAC, 200kA I.R.
• Protection of semiconductors, circuit breakers, critical components
• DC: 5 to 30A 600VAC, 100kA I.R. L/R ≤ 10 ms
Approvals
Highlights
• UL Recognized Components
• Extremely Fast Acting • PC Board Mount • Three Mounting Styles
Standard Fuse Ampere Ratings Ampere Rating
Melting Time – Current Data
Catalog Number
Reference Number
PCS5-R PCS8-R PCS10-R PCS12-R PCS15-R PCS20-R PCS25-R PCS30-R
B217880 M219431 Z216337 A217879 L219430 K223155 V202027 R212259
Slot Mount 5 8 10 12 15 20 25 30 TIME IN SECONDS
Double Hole Mount 5 8 10 12 15 20 25 30
PCS5-H PCS8-H PCS10-H PCS12-H PCS15-H PCS20-H PCS25-H PCS30-H
S217366 Y218912 P214304 R217365 X218911 X222637 H201487 H211745
PCS5-S PCS8-S PCS10-S PCS12-S PCS15-S PCS20-S PCS25-S PCS30-S
H218392 F219954 C216846 G218391 E219953 R200943 S211225 D212776
Surface Mount 5 8 10 12 15 20 25 30
CURRENT IN AMPERES
GPUS75
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) PC Mount PCS
I2t at 600VDC,100kA, L/R = 10 ms Ampere Rating
Clearing I2t (A2s)
5 8 10 12 15 20 25 30
40 42 70 90 110 200 260 520
I2t at 600VAC, 100kA Ampere Rating
Melting I2t (A2s)
Clearing I2t (A2s)
5 8 10 12 15 20 25 30
5 6.5 10 17 26 41 69 132
60 70 110 150 180 330 440 860
Watts Loss Data Ampere Rating
Watts Loss @ 80% Rating (w)
Watts Loss @ 100%Rating (w)
5 10 15 20 25 30
0.5 0.9 1.9 2.6 2.9 3.0
0.7 1.5 3.0 4.4 5.3 5.8
MAX. INSTANTANEOUS PEAK LET-THRU AMPERES
Peak Let-Thru Current Data – PCS5 to 30-R, H or S, 600 Volts AC
AVAILABLE CURRENT IN RMS SYMMETRICAL AMPERES
12/04
GPUS76
General Purpose US US Fuses General Purpose Fuses Midget Fuses (10x38 US) PC Mount PCT
TIME DELAY FUSES FOR DIRECT MOUNTING ON PRINTED CIRCUIT BOARDS Ferraz Shawmut’s new PCT series of time-delay, direct-mountable fuses addresses the increasing need for electrical protection at the PC board as current and voltage requirements push higher. These fuses help printed circuit board manufacturers reduce parts by eleminiating clips and fuse blocks and allowing automated assembly. PCT fuses can be used for the protection of main frame power boards, small circuit breakers with low interrupting ratings and other components. PCT fuses bring protection with time delay, greatly increased ampere, voltage and interrupting ratings to the board itself and are UL Component Recognized
Ratings
Applications
• AC: 1 to 30A 500VAC, 100kA
• Protection of main frame power boards, circuit breakers, components
Highlights
Approvals
• Time Delay • PC Board Mount • Three Mounting Styles
• UL Recognized Components
Melting Time – Current Data
Standard Fuse Ampere Ratings, Ref. Numbers Ampere Rating
Catalog Number
Reference Number
Ampere Rating
Catalog Number
Reference Number
L223156 S215319 Z222639 K211747 S213295 Q214811 C216340
8 10 12 15 20 25 30
PCT8-R PCT10-R PCT12-R PCT15-R PCT20-R PCT25-R PCT30-R
D217882 D202081 S212260 J213793 T217367 Z218913 K201489
8 10 12 15 20 25 30
PCT8-H PCT10-H PCT12-H PCT15-H PCT20-H PCT25-H PCT30-H
V217368 J201488 J211746 R213294 D216847 J218393 T200945
8 10 12 15 20 25 30
PCT8-S PCT10-S PCT12-S PCT15-S PCT20-S PCT25-S PCT30-S
K218394 T211226 E212777 R214306 C217881 N219432 N202090
1 2 3 4 5 6 7
TIME IN SECONDS
TIME IN SECONDS
Slot Mount
CURRENT IN AMPERES
PCT1-R PCT2-R PCT3-R PCT4-R PCT5-R PCT6-R PCT7-R
Double Hole Mount 1 2 3 4 5 6 7 CURRENT IN AMPERES
Y222638 P214810 G219955 V211227 F212778 S214307 X215829
Surface Mount 1 2 3 4 5 6 7
GPUS77
PCT1-H PCT2-H PCT3-H PCT4-H PCT5-H PCT6-H PCT7-H
PCT1-S PCT2-S PCT3-S PCT4-S PCT5-S PCT6-S PCT7-S
S200944 B216339 M223157 T212261 K213794 T215320 E216848
12/04
General Purpose General Purpose US Fuses US Fuses Midget Fuses (10x38 US) PC Mount Mechanics PCx
PCF1-R thru PCF30-R PCS5-R thru PCS30-R PCT1-R thru PCT30-R
FOR .062 (1.6) NOMINAL
MOUNTING HOLE DETAIL
CIRCUIT BOARD THICKNESS
Double Hole Mount (Round Holes) “H” terminal
PCF1-H thru PCF30-H PCS5-H thru PCS30-H PCT1-H thru PCT30-H
MOUNTING HOLE DETAIL
FOR .062 (1.6) NOMINAL CIRCUIT BOARD THICKNESS
Surface (Screw) Mount “S” terminal
PCF1-S thru PCF30-S PCS5-S thru PCS30-S PCT1-S thru PCT30-S
MAXIMUM RECOMMENDED SCREW SIZE #6 (3.5mm)
WWW.CABLEJOINTS.CO.UK
THORNE & DERRICK UK 12/04
TEL 0044 191 490 1547 FAX 0044 477 5371 TEL 0044 117 977 4647 FAX 0044 977 5582 GPUS78 WWW.THORNEANDDERRICK.CO.UK