Transcript
Ferrule fuse-links 8x31 gG 400VAC IEC Cylindrical Fuse-Links Mersen aM and gG fuse-links cover a wide range of physical sizes and ampere ratings for 400, 500, and 690VAC for protection in electrical distribution circuits and various industrial applications. Most ratings are available in size 8x31 and size 10x38 with an optional indicator, and in size 14x51 and 22x58 with an optional striker to activate an auxiliary contact. Size 10x38 is also available with striker. All cylindrical fuse-links have ceramic bodies and silver-plated contacts. Cylindrical fuse-links “gG” are used for the protection of cables, motors and LV-networks. They limit and cut off unacceptable overcurrents and short-circuit currents up to their nominal breaking capacity. Cylindrical fuse-links “gG” also protect electrical equipment and installations against the dynamic effect of high short-currents. Our technology and process was designed to ensure highly reliable technical performance.
Features Benefits zz zz zz zz zz
eet IEC, NFC and UNE standard M Reduced size Full range protection Safest and most reliable protection system Visual indication of fuse operation
Applications zz g G type for protection of line, cable against overload and short circuit in various industrial application and electrical distribution circuits.
Standards IEC 60269-1 & -2
Voltage AC
400 VAC
Ampere Range (A)
0.5 ... 25 A
Speed/Characteristic gG I.R. AC (kA)
20 kA
Body Material
Ceramic
Contact Materials
Silver plated copper
Product Size
8x31 mm
Low Voltage IEC Fuses / DS-LFCY8GG-05-1115_EN www.ep.mersen.com
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
Technical data overview
1
Ferrule fuse-links 8x31 gG 400VAC Product range Size 8,5x31,5 400 VAC without indicator Catalog number FR8GG40V0.5
Reference Rated voltage AC Rated breaking Rated current In number (IEC) capacity AC
FR8GG40V0.5 P218191
400 V
0.5 A
20 kA
Power dissipation at In
Weight
0.55 W
4.4 g
FR8GG40V1
C218709
400 V
1 A
20 kA
0.35 W
4.4 g
FR8GG40V2
Q219227
400 V
2 A
20 kA
0.45 W
4.4 g
FR8GG40V6
A211025
400 V
6 A
20 kA
0.83 W
4.4 g
FR8GG40V8
B213096
400 V
8 A
20 kA
1 W
4.4 g
FR8GG40V10
A214613
400 V
10 A
20 kA
1.2 W
4.4 g
FR8GG40V16
P216650
400 V
16 A
20 kA
1.7 W
4.4 g
FR8GG40V20
F217677
400 V
20 A
20 kA
2 W
4.4 g
FR8GG40V25
D218710
400 V
25 A
20 kA
2.4 W
4.4 g
Size 8,5x31,5 400VAC with indicator
FR8GG40V2I
Reference Rated voltage AC number (IEC)
Rated current In
Rated breaking capacity AC
Power dissipation at In
Weight
FR8GG40V2I
B222204
400 V
2 A
20 kA
0.45 W
4.4 g
FR8GG40V4I
X222959
400 V
4 A
20 kA
0.65 W
4.4 g
FR8GG40V6I
V201291
400 V
6 A
20 kA
0.83 W
4.4 g
FR8GG40V8I
B211026
400 V
8 A
20 kA
1 W
4.4 g
FR8GG40V12I C213097
400 V
12 A
20 kA
1.3 W
4.4 g
FR8GG40V16I Y214105
400 V
16 A
20 kA
1.7 W
4.4 g
FR8GG40V20I J215127
400 V
20 A
20 kA
2 W
4.4 g
FR8GG40V25I S216147
400 V
25 A
20 kA
2.4 W
4.4 g
Low Voltage IEC Fuses / DS-LFCY8GG-05-1115_EN www.ep.mersen.com
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
Catalog number
2
Ferrule fuse-links 8x31 gG 400VAC Time current characteristic curves Size 8x32 400V gG 10000 7000 5000 3000 2000 1000 700 500 300 200 100 70
0.5 A
50 30 20 10
1A
7 5 3 2 1
2A
0.7 0.5 0.3 0.2
0.07 0.05 0.03 0.02 0.01 0.007 0.005 0.003 0.002 0.001 0.0007 0.0005 0.0003
RMS value of prearc current (A) +/- 8%
Low Voltage IEC Fuses / DS-LFCY8GG-05-1115_EN www.ep.mersen.com
1000
700
500
300
200
100
70
50
30
20
10
7
5
3
2
1
0.7
0.5
0.3
0.1
0.0001
0.2
0.0002
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
4A
0.1
3
Ferrule fuse-links 8x31 gG 400VAC Time current characteristic curves Size 8x32 400V gG 10000 7000 5000 3000 2000 1000 700 500
6A
300 200
8A
100 70 50
10 A
30 20
12 A
10 7 5
16 A
3 2
20 A
1 0.7 0.5
25 A
0.3 0.2
0.05 0.03 0.02 0.01 0.007 0.005 0.003 0.002 0.001 0.0007 0.0005 0.0003
RMS value of prearc current (A) +/- 8%
Low Voltage IEC Fuses / DS-LFCY8GG-05-1115_EN www.ep.mersen.com
10000
7000
5000
3000
2000
1000
700
500
300
200
100
70
50
30
20
10
7
5
3
1
0.0001
2
0.0002
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.1 0.07
4
Ferrule fuse-links 8x31 gG 400VAC Current limiting diagram Size 8x32 400V gG 2000
lm = 2.3 lp
1000
4A
Maximum peak let thru current (Ic)(A)
700
2A
500 300
1A
200
0.5 A
100 70 50 30 20
10 7 5
70000
100000
50000
30000
20000
7000
10000
5000
3000
2000
700
1000
500
300
200
70
100
50
30
20
10
7
5
3
2
2
1
3
50 Hz RMS symetrical prospective current (Ip)(A)
3000
1000
25 A 20 A 16 A 12 A 10 A 8A
700
6A
lm = 2.3 lp
500
300 200
100 70
50 Hz RMS symetrical prospective current (Ip)(A)
Low Voltage IEC Fuses / DS-LFCY8GG-05-1115_EN www.ep.mersen.com
100000
70000
50000
30000
20000
10000
7000
5000
3000
2000
1000
700
500
300
200
100
70
50
30
30
20
50
10
Maximum peak let thru current (Ic)(A)
2000
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
Size 8x32 400V gG
5
Ferrule fuse-links 8x31 gG 400VAC Pre-arcing and operating I2t characteristics Size 8x32 400V gG 100 70 50 30
400V 230V pre-arcing I²t
Rated current (A)
20 10 7 5 3 2 1 0,7 0,5 0,3 0,2 0,1
4
2
0.5
0,05
1
0,07
Size 8x32 400V gG 3000 2000
400V 230V
Rated current (A)
1000 700 500 300 200
100 70 50 30
Low Voltage IEC Fuses / DS-LFCY8GG-05-1115_EN www.ep.mersen.com
25
20
16
12
10
8
10
6
20
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
pre-arcing I²t
6
Ferrule fuse-links 8x31 gG 400VAC Dimensions Size 8x31 gG without indicator
Size 8x31 gG with indicator
(1001204)
(1001203)
6.3
6.3
Visual indicator
Ø 8.4
+0.2 0
+0.2 0
6.3
6.3
31.5 ± 0.5
31.5 ± 0.5
Ø 8.4
Dimensions in mm
Low Voltage IEC Fuses / DS-LFCY8GG-05-1115_EN www.ep.mersen.com
MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
Dimensions in mm
7