Transcript
Multi-Conductor, Unshielded, Non-Plenum Product Construction
NEC Type FPLR
CONDUCTOR: s
Solid bare copper
INSULATION: NO. OF COND.
AWG. SIZE
NOM. JACKET WALL
s
WEIGHT
JACKET: s
COND. STRAND
INCHES
MM
INCHES
MM
INCHES
POUNDS
Solid Solid Solid Solid
0.010 0.010 0.010 0.010
0.25 0.25 0.25 0.25
0.015 0.015 0.015 0.015
0.38 0.38 0.38 0.38
0.150 0.175 0.210 0.230
16 lbs. 29 lbs. 41 lbs. 53 lbs.
18 AWG CONDUCTORS s
W181P-1604 W184C-1602 W186C-1654 W188C-1667
2 4 6 8
18 18 18 18
s s
Solid Solid
0.010 0.010
0.25 0.25
0.015 0.015
0.38 0.38
0.172 0.202
23 lbs. 42 lbs.
14 AWG CONDUCTORS W141P-1607 2 14 W144C-1651 4 14
Solid Solid
0.013 0.013
0.33 0.33
0.015 0.015
0.38 0.38
0.210 0.248
36 lbs. 66 lbs.
s s s s s
0.013 0.013
0.33 0.33
0.015 0.015
0.38 0.38
0.244 0.288
53 lbs. 99 lbs.
Wiring of fire alarms Smoke detectors Voice communications Burglar alarms Fire protective circuits Suggested voltage rating: 300 volts
COMPLIANCES: s
Solid Solid
Premium grade, Red PVC, other jacket colors may be available – consult sales office Suitable for use from 20˚C to + 75˚C Round constructions have sequential footage markings to facilitate installation Includes ripcord on round constructions
APPLICATIONS: s
16 AWG CONDUCTORS W161P-1601 2 16 W164C-1614 4 16
12 AWG CONDUCTORS W121P-1624 2 12 W124C-1656 4 12
Premium grade, color coded, S-R PVC
NOMINAL O.D.
FIRE ALARM/ LIFE SAFETY
PART NUMBER
NOM. INSUL. THICKNESS
s s s
UL Type FPLR (UL: 75˚C, 300V) NEC Article 760 California State Fire Marshall Approved Designed to meet UL 1666 Flame Test
PACKAGING:
Color Code Chart NO. OF COND.
COLOR
NO. OF COND.
COLOR
1 2 3
Black Red Brown
5 6 7
Orange Yellow Violet
4
Blue
8
Gray
s s
1000’ (305m) Reels Other put-ups available– consult Customer Service
Multi-Conductor, Shielded, Non-Plenum
Product Construction
NEC Type FPLR
CONDUCTOR: s
Solid bare copper
INSULATION: s
Premium grade, color coded, S-R PVC
SHIELD:
PART NUMBER
NO. OF COND.
AWG. SIZE
s
COND. STRAND
NOM. INSUL. THICKNESS INCHES MM
NOM. JACKET WALL INCHES MM
NOMINAL O.D. INCHES
WEIGHT POUNDS
Solid Solid
0.010 0.010
0.015 0.015
0.158 0.183
19 lbs. 32 lbs.
JACKET:
18 AWG CONDUCTORS W181P-1603 W184C-1605
2 4
18 18
0.25 0.25
0.38 0.38
s s s
16 AWG CONDUCTORS W161P-1606 2 16 W164C-1628 4 16
Solid Solid
0.010 0.010
0.25 0.25
0.015 0.015
0.38 0.38
0.180 0.210
26 lbs. 42 lbs.
14 AWG CONDUCTORS W141P-1600 2 14 W144C-1650 4 14
Solid Solid
0.013 0.013
0.33 0.33
0.015 0.015
0.38 0.38
0.218 0.253
41 lbs. 76 lbs.
12 AWG CONDUCTORS W121P-1653 2 12 W124C-1659 4 12
s
Overall Flexfoil® polyester supported aluminum foil Stranded tinned copper drain wire
s
APPLICATIONS: s s s s
Solid Solid
0.013 0.013
0.33 0.33
0.015 0.015
0.38 0.38
0.252 0.293
56 lbs. 115 lbs.
s s
s
NO. OF COND.
COLOR
NO. OF COND.
COLOR
s
1 2 3 4
Black Red Brown Blue
5 6 7 8
Orange Yellow Violet Gray
s
YOUR WIRE AND CABLE CONNECTION
Wiring of fire alarms Smoke alarms Voice communications Burglar alarms Fire protective circuits Suggested voltage rating: 300 volts
COMPLIANCES: s
Color Code Chart
Premium grade, Red PVC, other jacket colors may be available – consult sales office Suitable for use from 0°C to + 75°C Sequential footage markings to facilitate installation Includes ripcord
UL Type FPLR (UL: 75°C, 300V) NEC Article 760 California State Fire Marshall Approved Designed to Meet UL 1666 Flame Test
PACKAGING: s s
1000’ (305m) Reels Other put-ups available– consult Customer Service
[email protected] Sales@Connectt-Ai Air. r.co com co m
11
Mid-Capacitance, Shielded, Non-Plenum
Product Construction
NEC Type FPL for Microprocessor Controlled Systems
INSULATION:
CONDUCTOR: s
s s
Solid bare copper Premium grade color coded polypropylene Color code: see chart below
SHIELD:
FIRE ALARM/ LIFE SAFETY
s s
100% Flexfoil® aluminum/polyester, 25% overlap, minimum Stranded tinned copper drain wire
JACKET: s
PART NUMBER
NOM. INSUL. THICKNESS
NOM. JACKET WALL
NOMINAL O.D.
NO. OF COND.
AWG. SIZE
COND. STRAND
INCHES
MM
INCHES
MM
INCHES
2 2 2
18 16 14
Solid Solid Solid
0.014 0.016 0.018
0.36 0.41 0.46
0.020 0.020 0.020
0.51 0.51 0.51
0.182 0.214 0.287
NOMINAL PF/FT A*
B*
WEIGHT POUNDS
s
APPLICATIONS: s
W181P-1608 W161P-1609 W141P-1649
27.0 49.0 22 lbs. 29.0 52.0 30 lbs. 31.0 55.5 47 lbs.
s s s s
*A – Capacitance between conductors *B – Capacitance between one conductor and other conductors connected to shield
Color Code Chart NO. OF COND.
1 2 3 4
COLOR
Black Red Brown Blue
PVC, red Temperature range: 0°C to + 60°C
s
Addressable fire alarm systems Fire alarm systems Voice communications Smoke detectors Pull boxes Suggested voltage rating: 300 volts
COMPLIANCES: s s s s
UL Type FPL (UL: 60°C, 300V) NEC Article 760 California State Fire Marshall Approved Passes UL 70,000 BTU Vertical Tray Flame Test
PACKAGING: s 1000’ s
Mid-Capacitance, Unshielded, Non-Plenum
(30 m) reels Other put-ups available– consult Customer Service
Product Construction CONDUCTOR: s
NEC Type FPL for Microprocessor Controlled Systems
18 thru 12 AWG fully annealed solid bare copper per ASTM B3
INSULATION: s
Premium grade color coded polypropylene s Color code: see chart below
JACKET: s s
PVC, red Temperature range: – 20°C to + 60°C
APPLICATIONS:
PART NUMBER
W181P-1617 W161P-1647 W141P-1656
NOM. INSUL. THICKNESS
NOM. JACKET WALL
NO. OF COND.
AWG. SIZE
COND. STRAND
INCHES
MM
INCHES
MM
2 2 2
18 16 14
Solid Solid Solid
0.014 0.016 0.018
0.36 0.41 0.46
0.020 0.020 0.020
0.51 0.51 0.51
NOMINAL O.D.
Addressable fire alarm systems Fire alarm systems s Voice communications s Smoke detectors s Pull boxes s Suggested voltage rating: 300 volts s
INCHES
NOM. C-C CAP. PF/FT*
WEIGHT POUNDS
0.177 0.206 0.240
16.5 17.5 18.0
22 lbs. 30 lbs. 38 lbs.
s
COMPLIANCES: s
UL Type FPL (UL: 60°C, 300V) NEC Article 760 s California State Fire Marshall Approved s Passes UL 70,000 BTU Vertical Tray Flame Test s
Color Code Chart NO. OF COND.
1 2 3 4
12
CONNECT-AIR WIRE AND CABLE
COLOR
Black Red Brown Blue
PACKAGING: 1000’ (305m) Reels 500’ (152m) Reels s Other put-ups available– consult Customer Service s s
Multi-Conductor, Shielded, Direct Burial
Product Construction
NEC Type FPL / PLTC 300V
INSULATION:
CONDUCTOR: s
s s
Stranded copper per ASTM B3 PVC with nylon Color code: see chart below
SHIELD: s
JACKET: s s
PART NUMBER
W181P-1676 W161P-1661 W141P-1662
NO. OF COND.
AWG. SIZE
COND. STRAND
2 2 2
18 16 14
7/26 7/24 19/27
NOM. INSUL. THICKNESS INCHES
MM
NOM. JACKET WALL INCHES
0.015 0.005 0.040 0.015 0.005 0.040 0.015 0.005 0.040
NOMINAL O.D.
MM
INCHES
WEIGHT POUNDS
1.02 1.02 1.02
0.310 0.328 0.350
48 lbs. 58 lbs. 75 lbs.
s
APPLICATIONS: s s s s s
Color Code Chart NO. OF COND.
PVC, Black Temperature range: – 20°C to + 105°C dry locations, 75°C wet locations Includes ripcord
FIRE ALARM/ LIFE SAFETY
s
100% Flexfoil® aluminum/polyester foil, 25% overlap, minimum Stranded tinned copper drain wire
COLOR
1 2 3
Black Red Brown
4
Blue
Fire alarm systems Smoke detectors Fire protective circuits Burglar alarms Suggested voltage rating: 300 volts
COMPLIANCES: s s s
UL Type PLTC/FPLR (UL: 105°C, 300V) NEC Article 760 California State Fire Marshall Approved
FEATURES: s s s
Sunlight and moisture resistant jacket Sequentially footage marked Water blocked construction
PACKAGING: s s
1000’ (305m) Reels Other put-ups available– consult Customer Service
Product Construction
Multi-Conductor, Unshielded, Direct Burial
CONDUCTOR: s
Stranded bare copper
INSULATION:
NEC Type FPL / PLTC 300V
s s
PVC with nylon Color code: see chart below
JACKET: s s s
PVC, Black Temperature range: – 20°C to + 105°C dry locations, 75°C wet locations Includes ripcord
APPLICATIONS: s
PART NUMBER
NOM. INSUL. THICKNESS
NOM. JACKET WALL
NOMINAL O.D.
s
NO. OF COND.
AWG. SIZE
COND. STRAND
INCHES
MM
INCHES
MM
INCHES
WEIGHT POUNDS
2 4 2 2 4
18 18 16 14 14
7/26 7/26 7/24 19/27 19/27
0.015 0.015 0.015 0.015 0.015
0.005 0.005 0.005 0.005 0.005
0.040 0.040 0.040 0.040 0.040
1.02 1.02 1.02 1.02 1.02
0.270 0.327 0.295 0.310 0.395
37 lbs. 59 lbs. 48 lbs. 59 lbs. 98 lbs.
s s s
W181P-1679 W184C-1693 W161P-1657 W141P-1663 W144C-1699
Fire alarm systems Voice communications Smoke detectors Burglar Alarms Suggested voltage rating: 300 volts
COMPLIANCES: s s s
UL Type PLTC/FPLR (UL: 105°C, 300V) NEC Article 760 California State Fire Marshall Approved
FEATURES: s
Color Code Chart
s
Sunlight and moisture resistant jacket Sequentially footage marked Water blocked construction
COLOR
s
1 2 3
Black Red Brown
PACKAGING:
4
Blue
NO. OF COND.
YOUR WIRE AND CABLE CONNECTION
s s
1000’ (305m) Reels Other put-ups available– consult Customer Service
[email protected] Sales@Connectt-Ai Air. r.co com co m
13
Multi-Conductor, Type MC FPLP/MC 300V/600V
Product Construction
Red Fire Alarm/Control Cable™
ARMOR: s
Galvanized interlocking Steel Strip (red-striped)
CONDUCTORS:
FIRE ALARM/ LIFE SAFETY
s
Solid copper
CONDUCTOR INSULATION: s
AFC Cable Systems
ASSEMBLY:
Multi-Conductor, Unshielded, Type MC PART NUMBER
NO. OF COND.
s
2 4
COND. STRAND
NOMINAL O.D.
WEIGHT
18 18
Solid Solid
0.410 0.430
115 lbs. 130 lbs.
s
Solid Solid
0.420 0.440
130 lbs. 155 lbs.
14 AWG CONDUCTORS W141P-1607MC 2 14 W144C-1651MC 4 14
Solid Solid
0.470 0.510
175 lbs. 230 lbs.
s
s s
s
Multi-Conductor, Type CI COND. STRAND
NOMINAL O.D.
NO. OF AWG. COND. SIZE
COND. STRAND
NOMINAL O.D.
CONDUCTOR: s
WEIGHT
18 18
Solid Solid
0.390 0.445
82 lbs. 127 lbs.
W181P-1603CI W184C-1605CI
2 4
18 18
Solid Solid
0.310 0.355
s
54 lbs. 77 lbs.
14 AWG CONDUCTORS W141P-1607CI 2 14 W144C-1651CI 4 14
Solid Solid Solid* Solid*
0.350 0.400 0.390 0.445
64 lbs. 96 lbs.
16 AWG CONDUCTORS W161P-1606CI 2 16 W164C-1628CI 4 16
Solid Solid
0.330 0.375
82 lbs. 127 lbs.
14 AWG CONDUCTORS W141P-1600CI 2 14 W144C-1650CI 4 14
Solid* Solid*
0.370 81 lbs. 0.425 126 lbs.
2-hour fire rated – FPLR-CI
COMPLIANCES: s
16 AWG CONDUCTORS W161P-1601CI 2 16 W164C-1614CI 4 16
Solid copper
APPLICATIONS:
18 AWG CONDUCTORS
18 AWG CONDUCTORS 2 4
PART NUMBER
300V (FPLP) 600V (MC)
CI Product Construction
Multi-Conductor, Shielded, Type CI WEIGHT
FPLP: 105° (dry) MC: 90° (dry)
MAXIMUM VOLTAGE RATING: s
NO. OF AWG. COND. SIZE
Cable tray installations per NEC NFPA 262 (formerly U.L. 910) Plenum rated – Type FPLP
MAXIMUM TEMPERATURE RATING: s
Multi-Conductor, Unshielded, Type CI
Fire Alarm/Control Type MC – FPLP
COMPLIANCES:
s
W181P-1604CI W184C-1602CI
Bare or insulated green
APPLICATIONS:
16 AWG CONDUCTORS W161P-1601MC 2 16 W164C-1614MC 4 16
PART NUMBER
Polyester assembly tape
GROUNDING:
AWG. SIZE
18 AWG CONDUCTORS W181P-1604MC W184C-1602MC
TFN and/or THHN
s
63 lbs. 96 lbs.
UL 2196 NFPA 262 (formerly U.L. 910)
MAXIMUM VOLTAGE RATING: s
FPL – 300V
*May be stranded construction. Consult your sales representative.
CIC Product Construction
Multi-Conductor, Type CIC Multi-Conductor, Unshielded, Type CIC PART NUMBER
NO. OF COND.
AWG. SIZE
COND. STRAND
NOMINAL O.D.
WEIGHT
18 AWG CONDUCTORS W181P-1604CIC W184C-1602CIC
2 4
PART NUMBER
NO. OF COND.
s
18 18
Solid Solid
0.330 0.370
AWG. SIZE
COND. STRAND
NOMINAL O.D.
WEIGHT
18 18
Solid Solid
0.330 0.385
57 lbs. 81 lbs.
W181P-1603CIC W184C-1605CIC
62 lbs. 94 lbs.
16 AWG CONDUCTORS W161P-1606CIC 2 16 W164C-1628CIC 4 16
Solid Solid
0.350 0.400
66 lbs. 99 lbs.
14 AWG CONDUCTORS W141P-1600CIC 2 14
Solid* 0.400
85 lbs.
W144C-1650CIC
Solid* 0.450 130 lbs.
16 AWG CONDUCTORS W161P-1601CIC 2 16 W164C-1614CIC 4 16
Solid Solid
0.330 0.400
14 AWG CONDUCTORS W141P-1607CIC 2 14 W144C-1651CIC 4 14
Solid* Solid*
0.390 80 lbs. 0 440 125 lbs.
CONNECT-AIR WIRE AND CABLE
4
s
2-hour fire rated – FPL/-NPLF
COMPLIANCES:
53 lbs. 76 lbs.
2 4
Solid copper
APPLICATIONS:
18 AWG CONDUCTORS
*May be stranded construction. Consult your sales representative.
14
CONDUCTOR:
Multi-Conductor, Shielded, Type CIC
14
s s
UL 2196 NFPA 262 (formerly U.L. 910)
MAXIMUM VOLTAGE RATING: s s
FPL – 300V NPLR – 150V
NOTE: 2-hour rated cable must be installed in conduit for any high-rise building over 75 feet, any federal building, and areas of assembly (1000 or more people).
Multi-Conductor, Unshielded, Plenum
Product Construction CONDUCTOR:
NEC Type FPLP
s
18 thru 12 AWG fully annealed solid bare copper per ASTM B3
INSULATION: s
Premium grade, color coded, Plenum Rated PVC
JACKET: AWG. SIZE
COND. STRAND
18 AWG CONDUCTORS W181P-2600 2 18 W184C-2607 4 18 W186C-2651 6 18
Solid Solid Solid
0.010 0.010 0.010
0.25 0.25 0.25
0.015 0.015 0.015
0.38 0.38 0.38
0.155 0.175 0.211
17 lbs. 30 lbs. 57 lbs.
16 AWG CONDUCTORS W161P-2601 2 16 W164C-2637 4 16
Solid Solid
0.010 0.010
0.25 0.25
0.015 0.015
0.38 0.38
0.172 0.202
24 lbs. 45 lbs.
14 AWG CONDUCTORS W141P-2611 2 14 W144C-2640 4 14
Solid Solid
0.012 0.012
0.30 0.30
0.015 0.015
0.38 0.38
0.210 0.243
36 lbs. 66 lbs.
12 AWG CONDUCTORS W121P-2613 2 12 W124C-2641 4 12
Solid Solid
0.012 0.012
0.30 0.30
0.015 0.015
0.38 0.38
0.244 0.284
52 lbs. 100 lbs.
PART NUMBER
NO. OF COND.
NOM. JACKET WALL INCHES MM
NOMINAL O.D. INCHES
WEIGHT POUNDS
Premium grade, Red Plenum Rated PVC, other jacket colors may be available – consult sales office s Suitable for use from 0°C to + 75°C s Sequential footage markings to facilitate installation s Includes ripcord
APPLICATIONS:
FIRE ALARM/ LIFE SAFETY
s
NOM. INSUL. THICKNESS INCHES MM
s
Wiring of fire alarms Smoke detectors s Voice communications s Burglar alarms s Fire protective circuits s Suggested voltage rating: 300 volts s
COMPLIANCES:
Color Code Chart
s
UL Type FPLP (UL: 75°C, 300V) NEC Article 760 s California State Fire Marshall Approved s Designed to meet UL 910 flame test s
PACKAGING:
NO. OF COND.
COLOR
NO. OF COND.
COLOR
s
1 2 3
Black Red Brown
4 5 6
Blue Orange Yellow
s
1000’ (305m) Reels Other put-ups available– consult Customer Service
Product Construction
Multi-Conductor, Shielded, Plenum
CONDUCTOR:
NEC Type FPLP
INSULATION:
s
s
Solid bare copper Premium grade, color coded, Plenum Rated PVC
SHIELD: s s
100% aluminum foil/polyester Stranded tinned copper drain wire
JACKET:
PART NUMBER
NO. OF COND.
AWG. SIZE
s
COND. STRAND
NOM. INSUL. THICKNESS INCHES MM
NOM. JACKET WALL INCHES MM
NOMINAL O.D. INCHES
WEIGHT POUNDS
Solid Solid Solid
0.010 0.010 0.010
0.015 0.015 0.015
0.155 0.183 0.216
21 lbs. 34 lbs. 47 lbs.
18 AWG CONDUCTORS W181P-2601 W184C-2621 W186C-2644
2 4 6
18 18 18
0.25 0.25 0.25
0.38 0.38 0.38
Premium grade, Red Plenum Rated PVC, other jacket colors may be available – consult sales office s Suitable for use from 0°C to + 75°C s Sequential footage markings to facilitate installation s Includes ripcord
APPLICATIONS: s
16 AWG CONDUCTORS W161P-2602 2 16 W164C-2604 4 16
Solid Solid
0.010 0.010
0.25 0.25
0.015 0.015
0.38 0.38
0.180 0.210
28 lbs. 49 lbs.
14 AWG CONDUCTORS W141P-2605 2 14 W144C-2642 4 14
Solid Solid
0.012 0.012
0.30 0.30
0.015 0.015
0.38 0.38
0.210 0.248
43 lbs. 76 lbs.
12 AWG CONDUCTORS W121P-2645 2 12 W124C-2641 4 12
Wiring of fire alarms Smoke detectors s Voice communications s Burglar alarms s Fire protective circuits s Suggested voltage rating: 300 volts s
COMPLIANCES: s
UL Type FPLP (UL: 75°C, 300V) NEC Article 760 s California State Fire Marshall Approved s Designed to meet UL 910 Flame Test s
Solid Solid
0.012 0.012
0.30 0.30
0.015 0.015
0.38 0.38
0.252 0.300
57 lbs. 114 lbs.
PACKAGING: 1000’ (305m) Pull-Pac® Cartons (18 and 16 AWG items only) s 1000’ (305m) reels s 500’ (152m) spools or reels s Other put-ups available– consult Customer Service s
Color Code Chart NO. OF COND.
COLOR
NO. OF COND.
COLOR
1 2 3
Black Red Brown
4 5 6
Blue Orange Yellow
YOUR WIRE AND CABLE CONNECTION
[email protected] Sales@Connectt-Ai Air. r.co com co m
15
Mid-Capacitance, Shielded, Plenum
Product Construction CONDUCTOR:
NEC Type FPLP for Microprocessor Controlled Systems
s
Solid bare copper
INSULATION: s
Premium grade color coded Fluoropolymer s Color code: see chart below
FIRE ALARM/ LIFE SAFETY
SHIELD: s
PART NUMBER
W181P-2620 W161P-2634 W141P-2635
NO. OF COND.
AWG. SIZE
COND. STRAND
NOM. INSUL. THICKNESS INCHES MM
2 2 2
18 16 14
Solid Solid Solid
0.014 0.016 0.018
0.36 0.41 0.46
NOM. JACKET WALL INCHES MM
NOMINAL O.D. INCHES
0.015 0.015 0.020
0.172 22 lbs. 31.0 56.0 0.203 35 lbs. 33.0 59.0 0.247 35 lbs. 35.0 63.0
0.38 0.38 0.51
NOMINAL CAP.* PF/FT A* B*
WEIGHT LBS
s
100% aluminum/polyester foil Stranded tinned copper drain wire
JACKET: Premium grade, Red Plenum Rated PVC Temperature range: 0°C to + 75°C s Includes ripcord s s
APPLICATIONS: s
*A – Capacitance between conductors *B – Capacitance between one conductor and other conductors connected to shield
Addressable fire alarm systems Fire alarm systems s Voice communications s Smoke detectors s Pull boxes s Suggested voltage rating: 300 volts s
Color Code Chart NO. OF COND.
1 2 3 4
COLOR
Black Red Brown Blue
COMPLIANCES: s
UL Type FPLP (UL: 75°C, 300V) NEC Article 760 s California State Fire Marshall Approved s Designed to Meet UL 910 Flame Test s
PACKAGING: s s
Mid-Capacitance, Unshielded, Plenum
Product Construction CONDUCTOR: s
NEC Type FPLP for Microprocessor Controlled Systems
1000’ (30 m) Reels Other put-ups available– consult Customer Service
Solid bare copper
INSULATION: s
Premium grade color coded Fluoropolymer s Color code: see chart below
JACKET: s
Premium grade, Red Plenum Rated PVC Temperature range: 0°C to + 75°C s Includes ripcord s
PART NUMBER
NO. OF COND.
AWG. SIZE
COND. STRAND
NOM. INSUL. THICKNESS INCHES MM
NOM. JACKET WALL INCHES MM
NOMINAL O.D. INCHES
WEIGHT POUNDS
NOMINAL C-CAP. PF/FT*
2 2 2 2
18 16 14 12
Solid Solid Solid Solid
0.014 0.016 0.018 0.020
0.015 0.015 0.020 0.020
0.172 0.196 0.242 0.282
18 lbs. 31 lbs. 43 lbs. 63 lbs.
19.0 20.0 20.0 22.0
APPLICATIONS: s
W181P-2622 W161P-2633 W141P-2646 W121P-2643
0.36 0.41 0.46 0.46
0.38 0.38 0.51 0.51
* Capacitance between conductors
Addressable fire alarm systems Fire alarm systems s Voice communications s Smoke detectors s Pull boxes s Suggested voltage rating: 300 volts s
COMPLIANCES: s
Color Code Chart NO. OF COND.
1 2 3 4
16
CONNECT-AIR WIRE AND CABLE
COLOR
Black Red Brown Blue
UL Type FPLP (UL: 75°C, 300V) NEC Article 760 s California State Fire Marshall Approved s Designed to Meet UL 910 Flame Test s
PACKAGING: s s
1000’ (305m) Reels Other put-ups available– consult Customer Service