Transcript
Fire Detection System Manual
Fogmaker North America
Post address: 150 Gordon Dr Exton, PA 19341
P/N 18136
Delivery address: 150 Gordon Dr Exton, PA 19341
Page 1
Tel: 610-265-3610 Fax: 610-265-8327
[email protected] www.FMNA.net
Rev. H
Fire Detection System Installation and Operation Manual MADE IN THE USA
READ THIS MANUAL CAREFULLY AND SAVE FOR FUTURE REFERENCE. KEEP THIS MANUAL WITH THE SYSTEM.
Introduction The fire detection system. It has the ability to monitor pressure switches/IR-Thermal switches/ and other contact type inputs. These inputs will control the indicators on the display to alert a user of service needed or in case of a fire. They also control the engine shutdown relay and one input has its own separate output. This output switches system voltage out if a condition occurs. Read this owner’s manual completely before installation. Failure to read and follow these instructions can result in damage to the unit voiding the warranty.
CAUTION: NO POWER ON/OFF SWITCH IS PROVIDED FOR THIS UNIT. TO FUNCTION AS INTENDED, THE CONTROL PANEL MUST BE CONNECTED TO A CORRECT POWER SOURCE (5 amp or greater), AND FOR MAXIMUM EFFECTIVENESS, BE POWERED AT ALL TIMES A DANGER MAY BE PRESENT. IF POWER IS ON AND LEFT UNATTENDED FOR AN EXTENDED PERIOD OF TIME, BATTERY POWER MAY BE DIMINISHED.
Manual Display Controls / Indicator Fire Detection OK - Green when there is no fire detected or service required Service Required – Orange when pressure has dropped in detector bottle or piston accumulator. Fire – Red when pressure lost or fire detected/occurred.
Display Installation The Control panel should be mounted in a convenient location, preferably where the visual indicators may be readily seen. To install the display, you must first cut a rectangular opening 4 1/8” x 2 1/4”. Secure the display at the four corners with #6 screws.
Wiring the control panel The display has three connectors for external connections and one pink wire for battery back-up. See diagram below for connections. See the table for connector pin outs. FM-US-400018 has an in line fuse on the positive cable.
P/N 18136
Page 2
Rev. H
Optional Equipment FM-US-400021 FM-US-400010
Rechargeable battery backup unit for 10-54 Vdc Bracket for surface mounting.
Connector
Pin A
Function Gnd from display 50 Bar in switch (if 50 Bar is open & 14 Bar is closed then service lights. If 50 Bar & 14 Bar are open then fire lights, siren sounds, relay activation) 5 Bar in switch (if 5 Bar is open & 14 Bar is closed then service lights. If 5 Bar & 14 Bar are open then fire lights, siren sounds, relay activation) Relay Option (if disconnected no relay delay on fire, if connected to system voltage 15 second delay on relay) 14 Bar in switch (if 14 Bar is open & 50 or 5 Bar is closed then service lights. If 14 Bar & 50 or 5 Bar are open then fire lights, siren sounds, relay activation)
B
Primary Fire Connector
C D
E
F
H
Power Connector
A
IR-Thermal switch input. (if closed fire lights, siren sounds, relay activation)
B
A
B
Switched system voltage on closed IR-Thermal switch
Grn
18 18
Br O R
Bl
18 18 18 18
Bl
R
18
18
Power (10V-54V)
Pink
18
Ground input for display
A
Blk
18
NC output for Engine relay NO output for Engine relay Common input for the Engine relay. Relay is triggered by 50Bar, 5Bar, IR-Thermal
Y
IR-Thermal Connector
Gauge 18
G
Color W
Battery Backup input wire (or secondary supply connection)
Blk
Pink
18
18
Testing Display Mode If no alarm conditions are present, holding either button down for 4 seconds will initiate a self test sequence. During this sequence all LED’s will cycle along with the engine relay and siren.
Engine Relay The engine relay is controlled by the fire system and has (C,NO,NC) dry contacts for multiple wiring options. If the “Fire” light comes on the relay will turn on immediately. If the green wire is connected to system voltage the relay will turn on after 15 seconds. See connector table.) P/N 18136
Page 3
Rev. H
IR-Thermal Relay This relay has the common tied to system voltage and is normally open. When a ground is present at the IRThermal input the relay closes sending out system voltage. This will activate the relay switch.
Button Operation Either button can be used for each system. When there are no alarm conditions holding either button for 4 seconds will initiate a self test sequence. If the siren is sounding, holding either button in for 1 second will mute the siren for 15 seconds. If the engine relay is activated holding either button will reset the relay for 250mS to signal the bus’s monitoring system. If the green wire is connected to system voltage and the engine relay is activated, holding either button for 5 seconds will cause the relay to reset for 15 seconds allowing the vehicle to start. See connector table. Testing the operation of the fire suppression system: 1. Connect all wires and arm the fire suppression system. Turn on the bus. After the automatic system test runs if everything is connected and the bottles charged to the correct pressure the green “SYSTEM OK” light should be illuminated.
2. Disconnect the connection between the 50 bar pressure switch and the wire harness. This is labeled “EXT PR SW”. The “SERVICE REQUIRED” light will be illuminated. Reconnect after this is verified.
3. Disconnect the connection between the 14 bar pressure switch and the wire harness. This is labeled “DET CYL PR SW”. The “SERVICE REQUIRED” light will be illuminated. Reconnect after this is verified.
4. Disconnect the connections between the 14 bar pressure switch and the 50 bar pressure switch. The “FIRE “light will be illuminated. The siren will sound. The relay will activate (unless the green wire is connected to system voltage. See connector table.). Press Silence reset button for 1 second to silence the alarm. To restart the bus hold the Silence reset button for 4 seconds to reset the 15 second timer.
If system is equipped with the optional 5 bar pressure switch: 1. Disconnect the connection between the 5 bar pressure switch and the wire harness. This is labeled “5 BAR SW”. The “SERVICE REQUIRED” light will be illuminated. Reconnect after this is verified. 2. Disconnect the connections between the 5 bar pressure switch and the 14 bar switch. The “FIRE “light will be illuminated. The siren will sound. The relay will activate (unless the green wire is connected to system voltage. See connector table.). 3. Disconnect the connections between the 14 bar pressure switch, the 50 bar pressure switch and the 5 bar pressure switch. The “FIRE “light will be illuminated. The siren will sound. The relay will activate (unless the green wire is connected to system voltage. See connector table.). Specifications Voltage ………………………………………… +12VDC Nominal (10VDC to 54VDC) Alarm ………………………………………… Visual @ 20% of LEL Relay @ 50% of LEL Relay.................. ……………………………… 1 amp max Display Current ……………………………….. 50 mA
WARNING The FM-US-400018 is Fire & Methane. This device is meant to serve as a supplement warning only. It is NOT intended to replace standard safety practices which should be carried out around explosive gases (i.e. inspect all compartments, check all gas fittings and connections, smell for methane gas fumes, etc…) To function properly the FMUS-400018 must be powered at all times. Before installing in applications which may appear different than those outlined in this manual, contact the manufacturer. This device is not intended for use in aircraft. There are no user or field serviceable parts in this product. The FM-US-400018 must be returned to the manufacturer for any repair or trouble shooting beyond what is recommended in this manual. Installation shall be done by qualified P/N authorized 18136 to do so by the authorities having Pagejurisdiction 4 H the product is personnel for the particular application Rev. in which being used. Electrical wiring shall be in accordance with applicable codes. Improper wiring, including all wire connections, may render the unit inoperable, damage components, or cause a fire, and will void all warranties