Transcript
NEW!
NETWORK & WIRELESS FLEXIBLE BACNET THERMOSTAT FLEXSTAT DESCRIPTION The FlexStat Series of intelligent thermostats can monitor temperature/humidity/motion-sensing, and are wallmounted. In addition the FlexStat comes with BACnet MS/TP communications standard. The FlexStat simplifies networked zone control for common HVAC equipment. Example applications are packaged rooftop units, air handlers, fan coil units, and heat pumps. The on-board library of programs permits rapid configuration of a wide range of HVAC control applications via the FlexStat’s display and buttons. FEATURES • User-friendly English-language menus on a 64 x 128 pixel, dot-matrix LCD display with 5 buttons for data selection and entry • Built-in, factory-tested libraries of configurable application control sequences • Schedules can easily be set by weekdays (Mon. Fri.), weekend (Sat. - Sun.), entire week (Mon. -Sun.), individual days, and/or holidays • Six On/Off and independent heating and cooling set point periods are available per day • Three levels of password-protected access (user/ operator/administrator)
BACnet 120000 Series • Integral temperature and optional humidity and/or motion sensors • Multiple models available • 72-hour power (capacitor) backup and a real time clock for network time synchronization or full stand alone operation
SPECIFICATIONS
NETWORK & WIRELESS
13
Supply Voltage 24VAC 50/60 Hz Supply Current 13 VA Display 64 x 128 pixel dot matrix LCD Analog Input 0-12 VDC (Active/Passive) 10K thermistor (type 2 or 3) Analog Output 0-12 VDC, 20 mA (maximum) Digital Output 1 A maximum each or total of 1.5 A per bank of relays Sensor Type Humidity (optional) CMOS Temperature (with humidity) CMOS Temperature (without humidity) 10K Type 2 Motion (optional) Passive infrared with 33 feet (10 meter) range Accuracy Humidity (optional) ±2% RH (10 to 90% RH)
Temperature (with humidity) ±0.9°F (±0.5°C) Temperature (without humidity) ±0.36°F (±0.2°C) Range Humidity (optional) 0 to 100% RH Temperature (with humidity) 36° to 120°F (2.2 to 48.8°C) Temperature (without humidity) 48° to 96°F (8.8 to 35.5°C) Response Time Humidity (optional) < 4 seconds Operating Temperature 34° to 125°F (1.1 to 51.6°C) Operating Humidity 0 to 90% RH (non-condensing) Dimensions 4.1"H x 5.5"W x 1.1"D (10.6 x 14.1 x 1.1 cm) Weight 0.48 lb (0.22 kg) Approvals cULus Listed File #E145832, FCC Warranty 5 years
MOTION / OCCUPANCY SENSOR (OPTIONAL) PATTERN Top View 10 m 32.8 ft
Side View
X
10 m 32.8 ft
Y 46.5°
0°
0°
10 m 32.8 ft
756
888-397-5353 USA
55°
10 m 32.8 ft
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
NETWORK & WIRELESS FLEXIBLE BACNET THERMOSTAT FLEXSTAT
BAC-121136C
BAC-121036C
BAC-120136C
BAC-120036C
BAC-121163C
BAC-121063C
BAC-120163C
BAC-120063C
APPLICATIONS
13
NETWORK & WIRELESS
To order white instead of light almond, add W to the end of the model number (e.g., BAC-120036CW).
March 2014
WE MAKE IT EASY.
kele.com
888-397-5353 USA
757
NEW!
NETWORK & WIRELESS WIRING 6/3 & 3/6 Wiring
Input Pull-Up Switches 10K W 0-12 V
IN9 IN8 IN7 IN4 IN3
Pushed Left Pushed Right
NOTE: IN1 and IN5–6 are reserved for internal sensors
(Wiring is dependent on application)
GND IN7 +B
Inputs
IN4
–A IN3
NETWORK & WIRELESS
GND IN2 Common/–/C
Analog 8 Analog 7 Relay 6 SC 4–6 Relay 5 Relay 4
NOTE: EOL = End Of Line of BACnet MS/TP network NOTE: Inputs configurable for Type 3 (default) or Type 2 thermistors in FlexStat’s menu NOTE: IN1 and IN5–6 are reserved for internal sensors
NOTE: SC = Switched (Relay) Common Outputs
Inputs
GND IN7
MS/TP Network
+B
Inputs
IN4
–A IN3 GND
SC 1–3
IN2 24 VAC
GND 7–9
IN8
(Wiring is dependent on application)
Relay 2
Analog 9
IN9
Relay 3
Relay 1
Phase/ /R
Common/–/C Phase/ /R
Analog 8 Analog 7 Analog 6 GND 4–6 Analog 5 Analog 4 Relay 3 SC 1–3 Relay 2 Relay 1
ORDERING INFORMATION MODEL BAC-120036C BAC-120063C BAC-120136C BAC-120163C BAC-121036C BAC-121063C BAC-121136C BAC-121163C
758
GND 7–9
IN8
MS/TP Network
24 VAC
Analog 9
(Wiring Cutout in Backplate)
13
NOTE: SC = Switched (Relay) Common Outputs
IN9
Inputs
IN2
EOL Switches OFF ON
(Wiring Cutout in Backplate)
FLEXIBLE BACNET THERMOSTAT FLEXSTAT
888-397-5353 USA
DESCRIPTION 3 relays and 6 analog outputs almond 6 relays and 3 analog ouputs almond 3 relays and 6 analog outputs humidity almond 6 relays and 3 analog outputs humidity almond 3 relays and 6 analog outputs motion sensor almond 6 relays and 3 analog outputs motion sensor almond 3 relays and 6 analog outputs humidity motion sensor almond 6 relays and 3 analog outputs humidity motion sensor almond
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014