Transcript
Failure Modes, Effects and Diagnostic Analysis Project: 9116 Universal converter
Customer:
PR electronics A/S Rønde Denmark
Contract No.: PR electronics 06/03-19 Report No.: PR electronics 06/03-19 R024 Version V1, Revision R0; May 2010 Stephan Aschenbrenner, Piotr Serwa
The document was prepared using best effort. The authors make no warranty of any kind and shall not be liable in any event for incidental or consequential damages in connection with the application of the document. © All rights on the format of this technical report reserved.
Management summary This report summarizes the results of the hardware assessment carried out on the 9116 Universal converter. Table 1 shows the input/output configurations of the 9116 Universal converter that have been assessed. Table 1: Overview of assessed configurations of the 9116 Universal converter FMEDA name
HW/SW version Configuration description
[C1]
3w Pt100 Aout
9116-1-V3R0
Resistance / RTD temperature / TC temperature inputs, Current Output
[C2]
3w Pt100 Relay
9116-1-V3R0
Resistance / RTD temperature / TC temperature inputs, Relay Output
[C3]
Current Aout
9116-1-V2R0
Current Input, Current Output
[C4]
Current Relay
9116-1-V2R0
Current input, Relay output
[C5]
Voltage Aout
9116-1-V2R0
Voltage input, Current Output
[C6]
Voltage Relay
9116-1-V2R0
Voltage input, Relay output
The hardware assessment consists of a Failure Modes, Effects and Diagnostics Analysis (FMEDA). A FMEDA is one of the steps taken to achieve functional safety assessment of a device per IEC 61508. From the FMEDA, failure rates are determined and consequently the Safe Failure Fraction (SFF) can be calculated for the subsystem. For full assessment purposes, all requirements of IEC 61508 must be considered. For safety applications only the described input/output configurations are considered. All other possible input/output configurations are not covered by this report. The failure rates used in this analysis are from the exida Electrical & Mechanical Component Reliability Handbook for Profile 1 1. The analysis was carried out with the basic failure rates from the Siemens standard SN 29500. However, as the comparison between these two databases has shown that the differences are within an acceptable tolerance the failure rates of the exida database are listed. The 9116 Universal converter is considered a Type B2 subsystem with a hardware fault tolerance of 0. For Type B subsystems with a hardware fault tolerance of 0 the SFF has to be ≥ 90% for SIL 2 subsystems according to table 2 of IEC 61508-2. It is important to realize that the “no effect” failures and the “annunciation” failures are included in the “safe” failure category according to IEC 61508:2000. Note that these failures on its own will not affect system reliability or safety, and should not be included in spurious trip calculations. It is assumed that the connected safety logic solver is configured per the NAMUR NE43 signal ranges, i.e. the 9116 Universal converter with 4..20 mA current output communicates detected faults by an alarm output current ≤ 3,6mA or ≥ 21mA. Assuming that the application program in the safety logic solver does not automatically trip on these failures, these failures are classified as dangerous detected failures. The following tables show how the above stated requirements are fulfilled.
1
For details, see Appendix 3.
2
Type B subsystem:
“Complex” subsystem (using micro controllers or programmable logic); For details, see 7.4.3.1.3 of IEC 61508-2.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 2 of 8
Table 2: Summary for [C1] - IEC 61508 failure rates
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
278
Fail safe undetected
0
No effect
278
Fail Dangerous Detected (DD)
352
Fail detected (detected by internal diagnostics)
226
Fail low (detected by safety logic solver)
96
Fail high (detected by safety logic solver)
5
Annunciation detected
25 43 3
Fail Dangerous Undetected (DU) Fail dangerous undetected
42
Annunciation undetected
1
No part
877
Total failure rate (safety function)
673 FIT
SFF 4
93%
DCD
89%
MTBF SIL AC 5
74 Years SIL 2
The failure rates are valid for the useful life of the interface module (see Appendix 2).
3
This value corresponds to a PFH of 4.30E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 4 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 5 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. © exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 3 of 8
Table 3: Summary for [C2] - IEC 61508 failure rates
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
359
Fail safe undetected
107
No effect
252
Fail Dangerous Detected (DD)
230
Fail detected (detected by internal diagnostics)
209
Annunciation detected
21 62 6
Fail Dangerous Undetected (DU) Fail dangerous undetected
61
Annunciation undetected
1
No part
899
Total failure rate (safety function) SFF
651 FIT
7
90%
DCD
79%
MTBF SIL AC 8
74 Years SIL 2
The failure rates are valid for the useful life of the interface module (see Appendix 2).
6
This value corresponds to a PFH of 6.20E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 7 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 8 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. © exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 4 of 8
Table 4: Summary for [C3] - IEC 61508 failure rates
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
444
Fail safe undetected
0
No effect
444
Fail Dangerous Detected (DD)
554
Fail detected (detected by internal diagnostics)
317
Fail low (detected by safety logic solver)
207
Fail high (detected by safety logic solver)
5
Annunciation detected
25 42 9
Fail Dangerous Undetected (DU) Fail dangerous undetected
41
Annunciation undetected
1
No part
510
Total failure rate (safety function)
1040 FIT
SFF 10
95%
DCD
93%
MTBF SIL AC 11
74 Years SIL 2
The failure rates are valid for the useful life of the interface module (see Appendix 2).
9
This value corresponds to a PFH of 4.20E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 10 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 11 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled. © exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 5 of 8
Table 5: Summary for [C4] - IEC 61508 failure rates
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
1 1
Fail Safe Undetected (SU)
636
Fail safe undetected
218
No effect
418
Fail Dangerous Detected (DD)
320
Fail detected (detected by internal diagnostics)
299
Annunciation detected
21 62 12
Fail Dangerous Undetected (DU) Fail dangerous undetected
61
Annunciation undetected
1
No part
533
Total failure rate (safety function) SFF
1019 FIT
13
93%
DCD
83%
MTBF SIL AC 14
74 Years SIL 2
The failure rates are valid for the useful life of the interface module (see Appendix 2).
12 This value corresponds to a PFH of 6.20E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 13 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 14 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 6 of 8
Table 6: Summary for [C5] - IEC 61508 failure rates
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
395
Fail safe undetected
0
No effect
395
Fail Dangerous Detected (DD)
479
Fail detected (detected by internal diagnostics)
350
Fail low (detected by safety logic solver)
99
Fail high (detected by safety logic solver)
5
Annunciation detected
25 56 15
Fail Dangerous Undetected (DU) Fail dangerous undetected
55
Annunciation undetected
1
No part
620
Total failure rate (safety function)
930 FIT
SFF 16
93%
DCD
89%
MTBF SIL AC 17
74 Years SIL 2
The failure rates are valid for the useful life of the interface module (see Appendix 2).
15 This value corresponds to a PFH of 5.60E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 16 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 17 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 7 of 8
Table 7: Summary for [C6] - IEC 61508 failure rates
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
1 1
Fail Safe Undetected (SU)
480
Fail safe undetected
111
No effect
369
Fail Dangerous Detected (DD)
353
Fail detected (detected by internal diagnostics)
332
Annunciation detected
21 76 18
Fail Dangerous Undetected (DU) Fail dangerous undetected
75
Annunciation undetected
1
No part
642
Total failure rate (safety function) SFF
910 FIT
19
91%
DCD
82%
MTBF SIL AC 20
74 Years SIL 2
The failure rates are valid for the useful life of the interface module (see Appendix 2).
18 This value corresponds to a PFH of 7.60E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 19 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 20 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 8 of 8
Table of Contents Management summary .................................................................................................... 2 1 Purpose and Scope ................................................................................................. 10 2 Project management ................................................................................................ 11 2.1 2.2 2.3 2.4
exida .............................................................................................................................11 Roles and parties ..........................................................................................................11 Standards / Literature used...........................................................................................11 Reference documents ...................................................................................................11 2.4.1 Documentation provided by the customer ..........................................................11 2.4.2 Documentation generated by exida ...................................................................12
3 Description of the analyzed subsystem.................................................................... 13 4 Failure Modes, Effects, and Diagnostic Analysis ..................................................... 15 4.1 Description of the failure categories..............................................................................15 4.2 Methodology – FMEDA, Failure rates ...........................................................................16 4.2.1 FMEDA ...............................................................................................................16 4.2.2 Failure rates .......................................................................................................16 4.2.3 Assumptions.......................................................................................................17 4.3 Results ..........................................................................................................................17 4.3.1 9116 Universal converter, configuration 3w Pt100 Aout ....................................18 4.3.2 9116 Universal converter, configuration 3w Pt100 Relay ..................................19 4.3.3 9116 Universal converter, configuration Current Aout .......................................20 4.3.4 9116 Universal converter, configuration Current Relay .....................................21 4.3.5 9116 Universal converter, configuration Voltage Aout .......................................22 4.3.6 9116 Universal converter, configuration Voltage Relay .....................................23
5 Using the FMEDA results......................................................................................... 24 5.1 Example PFDAVG calculation .........................................................................................24
6 Terms and Definitions .............................................................................................. 26 7 Status of the document ............................................................................................ 27 7.1 Liability ..........................................................................................................................27 7.2 Releases .......................................................................................................................27
Appendix 1
Possibilities to reveal dangerous undetected faults during proof test ..... 28
Appendix 1.1 Possible proof tests to detect dangerous undetected faults ........................31
Appendix 2
Impact of lifetime of critical components on the failure rate .................... 32
Appendix 3
Description of the considered profiles ..................................................... 33 Appendix 3.1 exida electronic database: ..........................................................................33
Appendix 4
Using the FMEDA results ....................................................................... 34
Appendix 4.1 9116 Universal converter with thermocouple ..............................................34 Appendix 4.2 9116 Universal converter with RTD .............................................................37 © exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 9 of 41
1 Purpose and Scope This document describes the results of the FMEDA carried out on the 9116 Universal converter (9116B2). Table 1 shows the input/output configurations of the 9116 Universal converter that have been assessed. The FMEDA is part of a full functional safety assessment according to IEC 61508. The information in this report can be used to evaluate whether a sensor subsystem, including the 9116 Universal converter meets the average Probability of Failure on Demand (PFDAVG) / Probability of dangerous Failure per Hour (PFH) requirements and the architectural constraints / minimum hardware fault tolerance requirements per IEC 61508. It does not consider any calculations necessary for proving intrinsic safety.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 10 of 41
2 Project management 2.1 exida exida is one of the world’s leading knowledge companies specializing in automation system safety and availability with over 300 years of cumulative experience in functional safety. Founded by several of the world’s top reliability and safety experts from assessment organizations and manufacturers, exida is a partnership company with offices around the world. exida offers training, coaching, project oriented consulting services, internet based safety engineering tools, detail product assurance and certification analysis and a collection of on-line safety and reliability resources. exida maintains a comprehensive failure rate and failure mode database on process equipment.
2.2 Roles and parties PR electronics A/S
Manufacturer of the 9116 Universal converter.
exida
Performed the hardware assessment and reviewed the FMEDA provided by the customer.
PR electronics A/S contracted exida with the review of the FMEDA of the devices mentioned above.
2.3 Standards / Literature used The services delivered by exida were performed based on the following standards / literature. [N1] IEC 61508-2:2000
Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems
[N2] Electrical & Mechanical Component Reliability Handbook, 2nd Edition, 2008
exida L.L.C, Electrical & Mechanical
Component Reliability Handbook, Second Edition, 2008, ISBN 978-0-9727234-6-6
2.4 Reference documents 2.4.1 Documentation provided by the customer [D1]
9116 CPU failure distribution estimation.xls of 2009.12.21
[D2]
9116 Circuit Description V2R0.doc of Circuit description 11.02.10
[D3]
9116-1-02-PDF.pdf of 2009.12.16
Circuit schematics and layout diagrams (91161-2)
[D4]
9116-1-03-PDF.pdf of 2010.01.26
Circuit schematics and layout diagrams (91161-3)
[D5]
9116V100_DK.pdf of 2007.05.09
Users’ manual (in Danish)
[D6]
9116 Derating Analysis V0R8.xls of Derating analysis 23.03.10
[D7]
9116 FMEDA 3W V0R8.xls of 23.03.10
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
Pt100
Failure distribution for used CPUs
Relay FMEDA results file generated by customer for 3w Pt100 Aout PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 11 of 41
[D8]
9116 FMEDA 3w Pt100 Aout V0R8.xls FMEDA results file generated by customer for of 23.03.10 3w Pt100 Relay
[D9]
9116 FMEDA Current Aout V0R8.xls of FMEDA results file generated by customer for 23.03.10 3w Current Aout
[D10] 9116 FMEDA Current Relay V0R8.xls FMEDA results file generated by customer for of 23.03.10 3w Current Relay [D11] 9116 FMEDA Voltage Aout V0R8.xls FMEDA results file generated by customer for of 23.03.10 3w Voltage Aout [D12] 9116 FMEDA Voltage Relay V0R8.xls FMEDA results file generated by customer for of 23.03.10 3w Voltage Relay [D13] 9116V001.pdf of 2010.03.17
Users’ manual (multilingual), from PRelectronics website.
[D14] 9116 Hardware Fault Insertion Test Hardware Fault Insertion Test Report Report V2R0.doc of11.02.10 [D15] 9116 Safety Manual V0R9.pdf
Safety Manual
2.4.2 Documentation generated by exida [R1]
9116 FMEDA 3w Pt100 Aout - Review Review of FMEDA by Stephan Aschenbrenner SA.xls
[R2]
9116 FMEDA 3W Pt100 Relay - Review of FMEDA by Stephan Aschenbrenner Review SA.xls
[R3]
Review and Feedback 05.02.10.txt
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
Review comments by Stephan Aschenbrenner
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 12 of 41
3 Description of the analyzed subsystem The 9116 Universal converter converts various sensor input signals to either (1) a 4..20 mA current output, or to (2) a relay output. The hardware for the 9116 Universal converter is divided into 4 major modules. Each of these modules is then divided in sub modules. In this document, all component functions of each sub module will be described. The general description of the modules is as follows:
MAIN SUPPLY: Power supply circuit with external supply connection or from Power Rail. Additionally, this block contains the Status signal latching relay and the Power Rail status output.
MAIN CPU: Contains the Main CPU circuit with front LEDS and interface to 4501 and Output.
INPUT: Measurement circuits with ADC and a P to transfer measured values to Output. The input is isolated from the other modules with Ex-quality.
OUPUT: Contains the Output P which handles all the main calculations, output current, output relay setting and the Ex isolation and power supply for Input.
Figure 1: 9116 Universal converter circuit diagram As shown by Figure 2, the 9116 Universal converter has the following inputs: Input for RTD, TC, Ohm, potentiometer, mA and V. it has the following outputs: active mA output, passive mA output and relay output.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 13 of 41
Figure 2: 9116 Universal converter block diagram
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 14 of 41
4 Failure Modes, Effects, and Diagnostic Analysis The Failure Modes, Effects, and Diagnostic Analysis (FMEDA) was prepared by PR electronics A/S and reviewed by exida. The resulting FMEDAs are documented in [D7] to [D12]. When the effect of a certain component failure mode could not be analyzed theoretically, the failure modes were introduced on component level and the effects of these failure modes were examined on system level (see fault insertion test report [D14]). This resulted in failures that can be classified according to the following failure categories.
4.1 Description of the failure categories In order to judge the failure behavior of the 9116 Universal converter, the following definitions for the failure of the product were considered. Fail-Safe State
For 3w Pt100 Aout, Current Aout, Voltage Aout, the fail-safe state is defined as the output reaching the user defined threshold value. For 3w Pt100 Relay, Current Relay, Voltage Relay, the fail-safe state is defined as the output being de-energized.
Fail Safe
Failure that causes the subsystem to go to the defined fail-safe state without a demand from the process.
Fail Dangerous
A dangerous failure (D) is defined as a failure that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state) or deviates the output current by more than 2% full span.
Fail Dangerous Undetected Failure that is dangerous and that is not being diagnosed by internal diagnostics. Fail Dangerous Detected
Failure that is dangerous but is detected by internal diagnostics and causes the output signal to go to the predefined alarm state.
Fail High
A fail high failure (H) is defined as a failure that causes the output signal to go to the over-range or high alarm output current (> 21mA).
Fail Low
A fail low failure (L) is defined as a failure that causes the output signal to go to the under-range or low alarm output current (< 3.6mA).
No Effect
A no effect failure (#) is defined as a failure of a component that is part of the safety function but has no effect on the safety function or deviates the output current by not more than 2% full span. For the calculation of the SFF it is treated like a safe undetected failure.
Annunciation
Failure that does not directly impact safety but does impact the ability to detect a future fault (such as a fault in a diagnostic circuit). Annunciation failures are divided into annunciation detected (AD) and annunciation undetected (AU) failures. For the calculation of the SFF they are treated as “Dangerous Undetected” failures.
No Part
Component that plays no part in implementing the safety function but is part of the circuit diagram and is listed for completeness. When calculating the SFF this failure mode is not taken into account. It is also not part of the total failure rate.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 15 of 41
The failure categories listed above expand on the categories listed in IEC 61508, which are only safe and dangerous, both detected and undetected. The reason for this is that not all failure modes have effects that can be accurately classified according to the failure categories listed in IEC 61508:2000. The “No Effect” and “Annunciation Undetected” failures are provided for those who wish to do reliability modeling more detailed than required by IEC 61508. In IEC 61508:2000 the “No Effect” failures are defined as safe undetected failures even though they will not cause the safety function to go to a safe state. Therefore, they need to be considered in the Safe Failure Fraction calculation.
4.2 Methodology – FMEDA, Failure rates 4.2.1 FMEDA A Failure Modes and Effects Analysis (FMEA) is a systematic way to identify and evaluate the effects of different component failure modes, to determine what could eliminate or reduce the chance of failure, and to document the system under consideration. An FMEDA (Failure Mode Effect and Diagnostic Analysis) is an FMEA extension. It combines standard FMEA techniques with extensions to identify online diagnostics techniques and the failure modes relevant to safety instrumented system design. It is a technique recommended to generate failure rates for each important category (safe detected, safe undetected, dangerous detected, dangerous undetected, fail high, fail low) in the safety models. The format for the FMEDA is an extension of the standard FMEA format from MIL STD 1629A, Failure Modes and Effects Analysis.
4.2.2 Failure rates The failure rate data used by exida in this FMEDA are from the exida Electrical & Mechanical Component Reliability Handbook for Profile 1. The rates were chosen in a way that is appropriate for safety integrity level verification calculations. The rates were chosen to match operating stress conditions typical of an industrial field environment similar to exida Profile 1. It is expected that the actual number of field failures due to random events will be less than the number predicted by these failure rates. For hardware assessment according to IEC 61508 only random equipment failures are of interest. It is assumed that the equipment has been properly selected for the application and is adequately commissioned such that early life failures (infant mortality) may be excluded from the analysis. Failures caused by external events however should be considered as random failures. Examples of such failures are loss of power or physical abuse. The assumption is also made that the equipment is maintained per the requirements of IEC 61508 or IEC 61511 and therefore a preventative maintenance program is in place to replace equipment before the end of its “useful life”. The user of these numbers is responsible for determining their applicability to any particular environment. Accurate plant specific data may be used for this purpose. If a user has data collected from a good proof test reporting system that indicates higher failure rates, the higher numbers shall be used. Some industrial plant sites have high levels of stress. Under those conditions the failure rate data is adjusted to a higher value to account for the specific conditions of the plant.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 16 of 41
4.2.3 Assumptions The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis of the 9116 Universal converter.
Failure rates are constant, wear out mechanisms are not included.
Propagation of failures is not relevant.
The device is installed per manufacturer’s instructions.
Failures during parameterization are not considered.
Sufficient tests are performed prior to shipment to verify the absence of vendor and/or manufacturing defects that prevent proper operation of specified functionality to product specifications or cause operation different from the design analyzed.
The Mean Time To Restoration (MTTR) after a safe failure is 24 hours.
External power supply failure rates are not included.
The time of a connected safety PLC to react on a dangerous detected failure and to bring the process to the safe state is identical to MTTR.
Only the described versions are used for safety applications.
Only one input and one output are part of the considered safety function.
The application program in the safety logic solver is configured according to NAMUR NE43 to detect under-range and over-range failures and does not automatically trip on these failures; therefore these failures have been classified as dangerous detected failures.
Materials are compatible with process conditions.
The measurement / application limits (including pressure and temperature ranges) are considered.
Short circuit and lead breakage detection are activated.
The worst-case internal fault detection time is 30 seconds.
4.3 Results For the calculation of the Safe Failure Fraction (SFF) and total the following has to be noted: total = SD + SU + DD + DU SFF = 1 – DU / total DCD = DD / (DD + DU) MTBF = MTTF + MTTR = (1 / (total + no part)) + 24 h
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 17 of 41
4.3.1 9116 Universal converter, configuration 3w Pt100 Aout The FMEDA carried out on the 9116 Universal converter, configuration 3w Pt100 Aout ([C1]) leads under the assumptions described in section 4.2.3 to the following failure rates:
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
278
Fail safe undetected
0
No effect
278
Fail Dangerous Detected (DD)
352
Fail detected (detected by internal diagnostics)
226
Fail low (detected by safety logic solver)
96
Fail high (detected by safety logic solver)
5
Annunciation detected
25 43 21
Fail Dangerous Undetected (DU) Fail dangerous undetected
42
Annunciation undetected
1
No part
877
Total failure rate (safety function)
673 FIT
SFF 22
93%
DCD
89%
MTBF SIL AC 23
74 Years SIL 2
21 This value corresponds to a PFH of 4.30E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 22 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 23 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 18 of 41
4.3.2 9116 Universal converter, configuration 3w Pt100 Relay The FMEDA carried out on the 9116 Universal converter, configuration 3w Pt100 Relay ([C2]) leads under the assumptions described in section 4.2.3 to the following failure rates:
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
359
Fail safe undetected
107
No effect
252
Fail Dangerous Detected (DD)
230
Fail detected (detected by internal diagnostics)
209
Annunciation detected
21 62 24
Fail Dangerous Undetected (DU) Fail dangerous undetected
61
Annunciation undetected
1
No part
899
Total failure rate (safety function) SFF
651 FIT
25
90%
DCD
79%
MTBF SIL AC 26
74 Years SIL 2
24 This value corresponds to a PFH of 6.20E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 25 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 26 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 19 of 41
4.3.3 9116 Universal converter, configuration Current Aout The FMEDA carried out on the 9116 Universal converter, configuration Current Aout ([C3]) leads under the assumptions described in section 4.2.3 to the following failure rates:
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
444
Fail safe undetected
0
No effect
444
Fail Dangerous Detected (DD)
554
Fail detected (detected by internal diagnostics)
317
Fail low (detected by safety logic solver)
207
Fail high (detected by safety logic solver)
5
Annunciation detected
25 42 27
Fail Dangerous Undetected (DU) Fail dangerous undetected
41
Annunciation undetected
1
No part
510
Total failure rate (safety function)
1040 FIT
SFF 28
95%
DCD
93%
MTBF SIL AC 29
74 Years SIL 2
27 This value corresponds to a PFH of 4.20E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 28 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 29 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 20 of 41
4.3.4 9116 Universal converter, configuration Current Relay The FMEDA carried out on the 9116 Universal converter, configuration Current Relay ([C4]) leads under the assumptions described in section 4.2.3 to the following failure rates:
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
1 1
Fail Safe Undetected (SU)
636
Fail safe undetected
218
No effect
418
Fail Dangerous Detected (DD)
320
Fail detected (detected by internal diagnostics)
299
Annunciation detected
21 62 30
Fail Dangerous Undetected (DU) Fail dangerous undetected
61
Annunciation undetected
1
No part
533
Total failure rate (safety function) SFF
1019 FIT
31
93%
DCD
83%
MTBF SIL AC 32
74 Years SIL 2
30 This value corresponds to a PFH of 6.20E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 31 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 32 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 21 of 41
4.3.5 9116 Universal converter, configuration Voltage Aout The FMEDA carried out on the 9116 Universal converter, configuration Voltage Aout ([C5]) leads under the assumptions described in section 4.2.3 to the following failure rates:
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
0 0
Fail Safe Undetected (SU)
395
Fail safe undetected
0
No effect
395
Fail Dangerous Detected (DD)
479
Fail detected (detected by internal diagnostics)
350
Fail low (detected by safety logic solver)
99
Fail high (detected by safety logic solver)
5
Annunciation detected
25 56 33
Fail Dangerous Undetected (DU) Fail dangerous undetected
55
Annunciation undetected
1
No part
620
Total failure rate (safety function)
930 FIT
SFF 34
93%
DCD
89%
MTBF SIL AC 35
74 Years SIL 2
33 This value corresponds to a PFH of 5.60E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 34 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 35 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 22 of 41
4.3.6 9116 Universal converter, configuration Voltage Relay The FMEDA carried out on the 9116 Universal converter, configuration Voltage Relay ([C6]) leads under the assumptions described in section 4.2.3 to the following failure rates:
exida Profile 1 Failure category
Failure rates (in FIT)
Fail Safe Detected (SD) Fail safe detected
1 1
Fail Safe Undetected (SU)
480
Fail safe undetected
111
No effect
369
Fail Dangerous Detected (DD)
353
Fail detected (detected by internal diagnostics)
332
Annunciation detected
21 76 36
Fail Dangerous Undetected (DU) Fail dangerous undetected
75
Annunciation undetected
1
No part
642
Total failure rate (safety function) SFF
910 FIT
37
91%
DCD
82%
MTBF SIL AC 38
74 Years SIL 2
36 This value corresponds to a PFH of 7.60E-08 1/h. A fault reaction time of 30 seconds requires that a connected device can detect the output state within a time that allows reacting within the process safety time. 37 The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only. 38 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 23 of 41
5 Using the FMEDA results The following section describes how to apply the results of the FMEDA. It is the responsibility of the Safety Instrumented Function designer to do calculations for the entire SIF. exida recommends the accurate Markov based exSILentia tool for this purpose. The following results must be considered in combination with PFDAVG values of other devices of a Safety Instrumented Function (SIF) in order to determine suitability for a specific Safety Integrity Level (SIL).
5.1
Example PFDAVG calculation
An average Probability of Failure on Demand (PFDAVG) calculation is performed for a single (1oo1) 9116 Universal converter considering a proof test coverage of 95% (see Appendix 1.1) and a mission time of 10 years. The failure rate data used in this calculation are displayed in sections 4.3.1 to 4.3.6. The resulting PFDAVG values for a variety of proof test intervals are shown in Table 8. Table 8: PFDAVG values Configuration
T[Proof] = 1 year
T[Proof] = 2 years
T[Proof] = 5 years
3w Pt100 Aout
PFDAVG =
2,82E-04
PFDAVG =
4,63E-04
PFDAVG =
1,00E-03
3w Pt100 Relay
PFDAVG =
4,03E-04
PFDAVG =
6,63E-04
PFDAVG =
1,44E-03
Current Aout
PFDAVG =
2,77E-04
PFDAVG =
4,52E-04
PFDAVG =
9,76E-04
Current Relay
PFDAVG =
4,00E-04
PFDAVG =
6,56E-04
PFDAVG =
1,42E-03
Voltage Aout
PFDAVG =
3,66E-04
PFDAVG =
5,99E-04
PFDAVG =
1,30E-03
Voltage Relay
PFDAVG =
4,89E-04
PFDAVG =
8,04E-04
PFDAVG =
1,75E-03
For SIL2 applications, the PFDAVG value needs to be < 1.00E-02. This means that for a SIL2 application, the PFDAVG for a 1-year Proof Test Interval is within the range 3% - 5% of the allowed range. Figure 3 shows the time-dependent value of PFDAVG.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 24 of 41
Figure 3: PFDAVG(t)
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 25 of 41
6 Terms and Definitions DCD
Diagnostic Coverage of dangerous failures (DCD = dd / (dd + du))
FIT
Failure In Time (1x10-9 failures per hour)
FMEDA
Failure Modes, Effects, and Diagnostic Analysis
HFT
Hardware Fault Tolerance
Low demand mode
Mode, where the frequency of demands for operation made on a safetyrelated system is no greater than one per year and no greater than twice the proof test frequency.
MTTR
Mean Time To Restoration
PFDAVG
Average Probability of Failure on Demand
SFF
Safe Failure Fraction summarizes the fraction of failures, which lead to a safe state and the fraction of failures which will be detected by diagnostic measures and lead to a defined safety action.
SIF
Safety Instrumented Function
SIL
Safety Integrity Level
Type B subsystem
“Complex” subsystem (using micro controllers or programmable logic); for details see 7.4.3.1.3 of IEC 61508-2
T[Proof]
Proof Test Interval
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 26 of 41
7 Status of the document 7.1 Liability exida prepares FMEDA reports based on methods advocated in International standards. Failure rates are obtained from a collection of industrial databases. exida accepts no liability whatsoever for the use of these numbers or for the correctness of the standards on which the general calculation methods are based. Due to future potential changes in the standards, best available information and best practices, the current FMEDA results presented in this report may not be fully consistent with results that would be presented for the identical product at some future time. As a leader in the functional safety market place, exida is actively involved in evolving best practices prior to official release of updated standards so that our reports effectively anticipate any known changes. In addition, most changes are anticipated to be incremental in nature and results reported within the previous three year period should be sufficient for current usage without significant question. Most products also tend to undergo incremental changes over time. If an exida FMEDA has not been updated within the last three years and the exact results are critical to the SIL verification you may wish to contact the product vendor to verify the current validity of the results.
7.2 Releases Version History: V1R0: Review comments incorporated; May 18, 2010 V0R1: Initial version; March 31, 2010 Authors: Stephan Aschenbrenner, Piotr Serwa Review: V0R1: Hans Jørgen Eriksen (PR electronics A/S); April 15, 2010 Rachel Amkreutz (exida); May 17, 2010 Release status: Released to PR electronics A/S as part of a complete functional safety assessment according to IEC 61508.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 27 of 41
Appendix 1 Possibilities to reveal dangerous undetected faults during proof test According to section 7.4.3.2.2 f) of IEC 61508-2, proof tests shall be undertaken to reveal dangerous faults, which are undetected by diagnostic tests. This means that it is necessary to specify how dangerous undetected faults that have been noted during the FMEDA can be detected during proof testing. Table 9 shows the importance analysis of the dangerous undetected faults and indicates how these faults can be detected during proof testing. Appendix 1 shall be considered when writing the safety manual as it contains important safety related information. Table 9: Importance analysis for 9116 Universal converter 3w Pt100 Aout Component
% of total du
IC106-FLASH
24,43%
IC104
17,34%
Z201
14,49%
IC203-RAM
9,15%
IC106-CPU
6,20%
Z104
4,77%
T103
3,58%
IC203-CPU
3,43%
C112
2,38%
C114
2,38%
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
Detection through 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 28 of 41
Table 10: Importance analysis for 9116 Universal converter 3w Pt100 Relay Component
% of total du
RE201
32,56%
IC106-FLASH
16,69%
IC104
11,84%
Z201
9,90%
IC203-RAM
6,25%
IC106-CPU
4,23%
Z104
3,26%
T103
2,44%
IC203-CPU
2,34%
C112
1,63%
Detection through 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range
Table 11: Importance analysis for 9116 Universal converter Current Aout Component
% of total du
IC106-FLASH
25,20%
IC104
17,89%
Z201
14,95%
IC203-RAM
9,44%
IC106-CPU
6,39%
Z104
4,92%
IC203-CPU
3,54%
IC106-RAM
2,21%
Z116, Z117, Z118, Z119, Z120, Z121
2,03%
C24
1,48%
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
Detection through 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 29 of 41
Table 12: Importance analysis for 9116 Universal converter Current Relay Component
% of total du
RE201
33,05%
IC106-FLASH
16,94%
IC104
12,02%
Z201
10,05%
IC203-RAM
6,35%
IC106-CPU
4,30%
Z104
3,31%
IC203-CPU
2,38%
IC106-RAM
1,49%
Z116, Z117, Z118, Z119, Z120, Z121
1,36%
Detection through 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range
Table 13: Importance analysis for 9116 Universal converter Voltage Aout Component
% of total du
IC106-FLASH
18,73%
IC104
13,29%
Z201
11,11%
Z109
10,87%
IC203-RAM
7,02%
IC106-CPU
4,75%
IC107
4,39%
Z104
3,65%
Z129, Z130, Z131
3,01%
IC203-CPU
2,63%
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
Detection through 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 30 of 41
Table 14: Importance analysis for 9116 Universal converter Voltage Relay Component
% of total du
RE201
26,82%
IC106-FLASH
13,75%
IC104
9,76%
Z201
8,15%
Z109
7,98%
IC203-RAM
5,15%
IC106-CPU
3,49%
IC107
3,22%
Z104
2,68%
Z129, Z130, Z131
2,21%
Detection through 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range 100% functional test with different expected output signals over the entire range
Appendix 1.1 Possible proof tests to detect dangerous undetected faults A possible proof test is described in section 10 of the safety manual ([D15]) for the 9116 Universal converter. This test will detect approximately 95% of possible “du” failures in the transmitter and the connected sensing element.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 31 of 41
Appendix 2 Impact of lifetime of critical components on the failure rate According to section 7.4.7.4 of IEC 61508-2, a useful lifetime, based on experience, should be assumed. Although a constant failure rate is assumed by the probabilistic estimation method (see section 4.2.3) this only applies provided that the useful lifetime39 of components is not exceeded. Beyond their useful lifetime, the result of the probabilistic calculation method is meaningless, as the probability of failure significantly increases with time. The useful lifetime is highly dependent on the component itself and its operating conditions – temperature in particular (for example, electrolyte capacitors can be very sensitive). This assumption of a constant failure rate is based on the bathtub curve, which shows the typical behavior for electronic components. Therefore, it is obvious that the PFDAVG calculation is only valid for components that have this constant domain and that the validity of the calculation is limited to the useful lifetime of each component. It is assumed that early failures are detected to a huge percentage during the installation period and therefore the assumption of a constant failure rate during the useful lifetime is valid. Table 15 shows which components with reduced useful lifetime are contributing to the dangerous undetected failure rate and therefore to the PFDAVG calculation and what their estimated useful lifetime is. Table 15: Useful lifetime of components with reduced useful lifetime contributing to λdu FMEDA
Type
32 Pt100 Relay,
Relay (w. FE) - Plastic-sealed, RE201 (Relay) low gas emission, tempered plastic, single contacts (alloy on silver basis), >20cN
Current Relay, Voltage Relay
Name
Useful lifetime Approximately 100.000 switching cycles
Assuming one demand per year for low demand mode applications and additional switching cycles during installation and proof testing, the relays do not have a real impact on the useful lifetime. When plant experience indicates a shorter useful lifetime than indicated in this appendix, the number based on plant experience should be used.
39 Useful lifetime is a reliability engineering term that describes the operational time interval where the failure rate of a device is relatively constant. It is not a term that covers product obsolescence, warranty, or other commercial issues.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 32 of 41
Appendix 3 Description of the considered profiles Appendix 3.1 exida electronic database: Profile
Profile according to IEC 60654-1
1 2 3
B2 C3 C3
Ambient Temperature [°C] Average Mean (external) (inside box) 30 25 25
60 30 45
Temperature Cycle [°C / 365 days] 5 25 25
PROFILE 1: Cabinet mounted equipment typically has significant temperature rise due to power dissipation but is subjected to only minimal daily temperature swings. PROFILE 2: Low power electrical (two-wire) field products have minimal self-heating and are subjected to daily temperature swings. PROFILE 3: General (four-wire) field products may have moderate self-heating and are subjected to daily temperature swings.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 33 of 41
Appendix 4 Using the FMEDA results The 9116 Universal converter together with a temperature sensing device becomes a temperature sensor assembly. Therefore, when using the results of this FMEDA in a SIL verification assessment, the failure rates and failure modes of the temperature sensing device must be considered.
Appendix 4.1 9116 Universal converter with thermocouple The failure mode distributions for thermocouples (TC) vary in published literature but there is strong agreement that open circuit or “burn-out” failure is the dominant failure mode. While some estimates put this failure mode at 99%+, a more conservative failure rate distribution suitable for SIS applications is shown in Table 16 and Table 17 when thermocouples are supplied with the 9116 Universal converter. The drift failure mode is primarily due to T/C aging. The 9116 Universal converter will detect a thermocouple burn-out failure and drive its output to the specified failure state. Table 16: Typical failure rates for thermocouples (with extension wire) Failure Mode Distribution Open Circuit (Burn-out) Short Circuit (Temperature measurement in error) Drift (Temperature Measurement in error)
Low Stress 900 FIT 50 FIT 50 FIT
High Stress 18000 FIT 1000 FIT 1000 FIT
Table 17: Typical failure rates for thermocouples (close coupled) Failure Mode Distribution Open Circuit (Burn-out) Short Circuit (Temperature measurement in error) Drift (Temperature Measurement in error)
Low Stress 95 FIT 4 FIT 1 FIT
High Stress 1900 FIT 80 FIT 20 FIT
A complete temperature sensor assembly consisting of the 9116 Universal converter and a temperature sensing device can be modeled by considering a series subsystem where a failure occurs if there is a failure in either component. For such a system, failure rates are added. Table 18: Thermocouple fault classification Failure mode
Classification
Open circuit
Dangerous detected
Short circuit
Dangerous undetected
Drift
Dangerous undetected
As a result, the failure rate contribution for the thermocouple is as follows.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 34 of 41
Table 19: Thermocouple (with extension wire) Low stress environment
High stress environment
dd = 900 FIT
dd = 18000 FIT
du = 50 FIT + 50 FIT = 100 FIT
du = 1000 FIT + 1000 FIT = 2000 FIT
su = 0 FIT
su = 0 FIT
sd = 0 FIT
sd = 0 FIT
Table 20: Thermocouple (close coupled) Low stress environment
High stress environment
dd = 95 FIT
dd = 1900 FIT
du = 4 FIT + 1 FIT = 5 FIT
du = 80 FIT + 20 FIT = 100 FIT
su = 0 FIT
su = 0 FIT
sd = 0 FIT
sd = 0 FIT
This results in a failure rate distribution and SFF as shown below for a 9116 Universal converter together with a thermocouple with current output or relay output. The failure rates for the 9116 Universal converter with the thermocouple are sums of corresponding failure rates of the converter and of the thermocouple.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 35 of 41
Table 21: 9116 Universal converter with thermocouple Transmitter 3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Relay
3w Pt100 Relay
3w Pt100 Relay
3w Pt100 Relay
Extension wire With
With
Without
Without
With
With
Without
Without
Environment Low stress
High stress
Low stress
High stress
Low stress
High stress
Low stress
High stress
SD
SU
DD
DU
0 FIT +
0 FIT +
900 FIT +
100 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
1 210 FIT
142 FIT
0 FIT +
0 FIT +
18 000 FIT +
2 000 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
18 310 FIT
2 042 FIT
0 FIT +
0 FIT +
95 FIT +
5 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
405 FIT
47 FIT
0 FIT +
0 FIT +
1 900 FIT +
100 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
2 210 FIT
142 FIT
0 FIT +
0 FIT +
900 FIT +
100 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
1 161 FIT
161 FIT
0 FIT +
0 FIT +
18 000 FIT +
2 000 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
18 261 FIT
2 061 FIT
0 FIT +
0 FIT +
95 FIT +
5 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
356 FIT
66 FIT
0 FIT +
0 FIT +
1 900 FIT +
100 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
2 161 FIT
161 FIT
SFF
91%
90%
93%
94%
90%
90%
91%
93%
These numbers could be used in safety instrumented function SIL verification calculations for this set of assumptions.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 36 of 41
Appendix 4.2 9116 Universal converter with RTD The failure mode distribution for an RTD depends on the application with the key variables being stress level, presence (or not) of extension wire and wire configuration (2-wire/3-wire or 4wire). The key stress variables are high vibration and frequent temperature cycling as these are known to cause cracks in the substrate leading to broken lead connection welds. Failure rate distributions are shown in Table 22, Table 23, Table 24 and Table 25. The 9116 Universal converter will detect open circuit, short circuit and a certain percentage of drift RTD failures and drive their output to the specified failure state. Table 22: Typical failure rates for 4-Wire RTDs (with extension wire) RTD Failure Mode Distribution Open Circuit (Burn-out) Short Circuit (Temperature measurement in error) Drift (Temperature Measurement in error)
Low Stress 410 FIT 20 FIT 70 FIT 40
High Stress 8200 FIT 400 FIT 1400 FIT 41
Table 23: Typical failure rates for 4-Wire RTDs (close coupled) RTD Failure Mode Distribution Open Circuit (Burn-out) Short Circuit (Temperature measurement in error) Drift (Temperature Measurement in error)
Low Stress 41.5 FIT 2.5 FIT 6 FIT 42
High Stress 830 FIT 50 FIT 120 FIT 43
Table 24: Typical failure rates for 2-Wire and 3-Wire RTDs (with extension wire) RTD Failure Mode Distribution Open Circuit (Burn-out) Short Circuit (Temperature measurement in error) Drift (Temperature Measurement in error)
Low Stress 370.5 FIT 9.5 FIT 95 FIT
High Stress 7410 FIT 190 FIT 1900 FIT
Table 25: Typical failure rates for 2-Wire and 3-Wire RTDs (close coupled) RTD Failure Mode Distribution Open Circuit (Burn-out) Short Circuit (Temperature measurement in error) Drift (Temperature Measurement in error)
Low Stress 37.92 FIT 1.44 FIT 8.64 FIT
High Stress 758.4 FIT 28.8 FIT 172.8 FIT
A complete temperature sensor assembly consisting of the 9116 Universal converter and a temperature sensing device can be modeled by considering a series subsystem where a failure occurs if there is a failure in either component. For such a system, failure rates are added.
40
It is assumed that 65 FIT are detectable if the 4-wire RTD is correctly used. It is assumed that 1300 FIT are detectable if the 4-wire RTD is correctly used. 42 It is assumed that 3.5 FIT are detectable if the 4-wire RTD is correctly used. 43 It is assumed that 70 FIT are detectable if the 4-wire RTD is correctly used. 41
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 37 of 41
Table 26: Fault classification for 4-Wire RTD Failure mode
Classification
Open circuit
Dangerous detected
Short circuit
Dangerous detected
Drift
Most of it is dangerous detected, remaining part dangerous undetected (assuming a correct use of 4-wire RTD)
Table 27: 4-Wire RTD (with extension wire) Low stress environment
High stress environment
dd = 410 FIT + 20 FIT + 65 FIT = 495 FIT
dd = 8200 FIT + 400 FIT + 1300 FIT = 9900 FIT
du = 5 FIT
du = 100 FIT
su = 0 FIT
su = 0 FIT
sd = 0 FIT
sd = 0 FIT
Table 28: 4-Wire RTD (close coupled) Low stress environment
High stress environment
dd = 41.5 FIT + 2.5 FIT + 3.5 FIT = 47.5 FIT
dd = 830 FIT + 50 FIT + 70 FIT = 950 FIT
du = 2.5 FIT
du = 50 FIT
su = 0 FIT
su = 0 FIT
sd = 0 FIT
sd = 0 FIT
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 38 of 41
Table 29: Fault classification for 2-Wire and 3-Wire RTD Failure mode
Classification
Open circuit
Dangerous detected
Short circuit
Dangerous detected
Drift
Dangerous undetected
Table 30: 2-Wire and 3-Wire RTD (with extension wire) Low stress environment
High stress environment
dd = 370.5 FIT + 9.5 FIT = 380 FIT
dd = 7410 FIT + 190 FIT = 7600 FIT
du = 95 FIT
du = 1900 FIT
su = 0 FIT
su = 0 FIT
sd = 0 FIT
sd = 0 FIT
Table 31: 2-Wire and 3-Wire RTD (close coupled) Low stress environment
High stress environment
dd = 37.92 FIT + 1.44 FIT = 39.36 FIT
dd = 758.4 FIT + 28.8 FIT = 787.2 FIT
du = 8.64 FIT
du = 172.8 FIT
su = 0 FIT
su = 0 FIT
sd = 0 FIT
sd = 0 FIT
This results in a failure rate distribution and SFF as shown below for a 9116 Universal converter together with a RTD with current output or relay output. The failure rates for the 9116 Universal converter with the RTD are sums of corresponding failure rates of the converter and of the RTD.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 39 of 41
Table 32: 9116 Universal converter with 4-Wire RTD Transmitter 3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Relay
3w Pt100 Relay
3w Pt100 Relay
3w Pt100 Relay
Extension wire
Environment
With
Low stress
With
Without
Without
With
With
Without
Without
High stress
Low stress
High stress
Low stress
High stress
Low stress
High stress
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
SD
SU
DD
DU
0 FIT +
0 FIT +
495 FIT +
5 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
805 FIT
47 FIT
0 FIT +
0 FIT +
9 900 FIT +
100 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
10 210 FIT
142 FIT
0 FIT +
0 FIT +
48 FIT +
3 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
358 FIT
45 FIT
0 FIT +
0 FIT +
950 FIT +
50 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
1 260 FIT
92 FIT
0 FIT +
0 FIT +
495 FIT +
5 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
756 FIT
66 FIT
0 FIT +
0 FIT +
9 900 FIT +
100 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
10 161 FIT
161 FIT
0 FIT +
0 FIT +
48 FIT +
3 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
309 FIT
64 FIT
0 FIT +
0 FIT +
950 FIT +
50 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
1 211 FIT
111 FIT
SFF
95%
98%
93%
94%
94%
98%
90%
93%
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 40 of 41
Table 33: 9116 Universal converter with 2-Wire and 3-Wire RTD Transmitter 3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Aout
3w Pt100 Relay
3w Pt100 Relay
3w Pt100 Relay
3w Pt100 Relay
Extension wire
Environment
With
Low stress
With
Without
Without
With
With
Without
Without
High stress
Low stress
High stress
Low stress
High stress
Low stress
High stress
SD
SU
DD
DU
0 FIT +
0 FIT +
380 FIT +
95 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
690 FIT
137 FIT
0 FIT +
0 FIT +
7 600 FIT +
1 900 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
7 910 FIT
1 942 FIT
0 FIT +
0 FIT +
39 FIT +
9 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
349 FIT
51 FIT
0 FIT +
0 FIT +
787 FIT +
173 FIT +
0 FIT =
321 FIT =
310 FIT =
42 FIT =
0 FIT
321 FIT
1 097 FIT
215 FIT
0 FIT +
0 FIT +
380 FIT +
95 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
641 FIT
156 FIT
0 FIT +
0 FIT +
7 600 FIT +
1 900 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
7 861 FIT
1 961 FIT
0 FIT +
0 FIT +
39 FIT +
9 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
300 FIT
70 FIT
0 FIT +
0 FIT +
787 FIT +
173 FIT +
0 FIT =
329 FIT =
261 FIT =
61 FIT =
0 FIT
329 FIT
1 048 FIT
234 FIT
SFF
88%
80%
92%
86%
86%
80%
90%
85%
These numbers could be used in safety instrumented function SIL verification calculations for this set of assumptions.
© exida.com GmbH Stephan Aschenbrenner, Piotr Serwa
PR 9116 06-03-19 R024 V1R0.doc; May 18, 2010 Page 41 of 41