Devices, Inc. APPLICATION MANUAL 2005
RIB
®
By Yorkland Controls
www.yorkland.net
Feel free to contact Yorkland Controls at 1-877-733-3833
RELAY & CURRENT SENSOR IN ONE
1
Directly start/stop load and current sensing all in one package. (No external ring is needed) Controller Digital Out
Load
Start/Stop Relay Current Sensor Circuitry Solid State Transducer Switch
Digital In
INTERNAL 20 AMP
INTERNAL 10 AMP
INTERNAL 5 AMP
RIBX24BF RIBX24SBF RIBX24BA RIBX24SBA
RIBXLCF RIBXLSF RIBXLCA RIBXLSA
RIBXLCEA RIBXLSEA
60 Hz ac
MOTOR STARTER
2
Allows relay to control a motor starter while sensing current flowing to the motor. EXTERNAL SENSOR RING
3-Phase Line Voltage
MOTOR STARTER
CONTROLLER Digital Out
MOTOR
RIBXLCRA RIBXCLRF RIBXLSRA RIBXLSRF
24 Vac
EXTERNAL SENSOR RING
Start/Stop Relay Current Sensor Circuitry
Digital In
Solid State Switch
Transducer
SENSOR ONLY FOR 1.25 AMP TO 150 AMP LOAD
3
Use sensor only devices without relay where start/stop is not required. EXTERNAL SENSOR RING 3-Phase Line Voltage
MOTOR STARTER
MOTOR
CONTROLLER Digital Out Current Sensor Circuitry Digital In
2005
Solid State Switch
RIBXRA RIBXRF RIBMXRA RIBMXRF
EXTERNAL SENSOR RING
Transducer
APPLICATION MANUAL AM578B
www.yorkland.net
PAGE 1
PANEL MOUNTED RELAY & INTERNAL SENSOR
4
Start/Stop Relays with Internal Current Sensors measure current flow through the relay contacts, no external ring is needed. Senses current as low as .50 mA. INTERNAL 20 AMP
PANEL
RIBMX24BF RIBMX24SBF RIBMX24BA RIBMX24SBA
CONTROLLER 5 or 20 Amp MAX LOAD
Digital In Digital Out
RIBMX Start/Stop Relay Current Sensor Circuitry Solid State Switch
Transducer
60 Hz ac
INTERLOCKING LOADS
5
Some RIBX current sensor relays can be used to sense 1 or more loads to turn on another. Laundromat Exhaust Fan
60 Hz ac
24 Vac Source
RIBX Start/Stop Relay Current Sensor Circuitry Solid State Switch
EXTERNAL SENSOR
Dryer 1
Transducer
EXTERNAL 10 AMP RIBXLCRF RIBXLCRA RIBXLCJF RIBXLCJA RIBXLSRF RIBXLSRA RIBXLSJF RIBXLSJA
Dryer 2
INTERLOCKING LOADS (NO TRANSFORMER)
6
Self-powered Current Sensors of the RIBX Series and relays of the Dry Contact Input RIB Series may be applied to interlock Load 2 to Load 1. Current sensing may be internal or external
LOCAL POWER 120, 240, 277 Vac
LOAD 1
LOAD WIRE
RIBX SERIES
Low Voltage (Class II)
Current Sensor Only Current Sensor Status
DRY CONTACT INPUT RIB SERIES
DRY CONTACT INPUT RELAYS
CURRENT SENSORS
RIB21CDC RIB01BDC RIB01SBDC RIB02BDC RIB02SBDC RIBM01ZNDC RIBM02ZNDC RIBM013PNDC
RIBXKF RIBXKTF RIBXKA RIBXKTA RIBXGA RIBXGF RIBXGTA RIBXGTF RIBXGFL RIBXGTFL RIBXF RIBXA
LOAD 2
APPLICATION MANUAL AM578B 2005
RIBXRF RIBXRA RIBXJF RIBXJA RIBMXF RIBMXA RIBMXRF RIBMXRA RIBMXJF RIBMXJA
G
DAMPER MOTOR CONTROL
7
Damper motor control with true-HOA. The damper motor can be stopped in mid position for debugging. When auto/manual selector is in auto, relay controls the load. When in manual, use the manual switch to control the load. 24 Vac From Controller Auto / Manual Selector
Wh/Blu
Auto
Line (120 Vac)
Man
Wh/Yel Manual Switch
Wh/Blk (not used)
Open
N/C Closed
Open (120 Vac)
ORANGE N/O Closed
YELLOW
Damper Motor
Neutral
BLUE
10 & 15 AMP
20 AMP
RIBU1SC RIBH1SC RIBTU1SC RIBTH1SC RIBMU1SC RIBMH1SC
RIB2401SBC RIB2402SBC RIBT2401SBC RIBT2402SBC RIBM2401SBC RIBM2402SBC
Close (120 Vac)
RIBU1S VS. RIBU1SC
8
Stock model RIBU1SC for relay control applications that require true-HOA on either N/O or N/C. No jumpers and no wrong orders. RIBU1S has a lower cost but if N/C is desired on relay, it must be specified when ordering.
120 Vac
24 Vac From Controller Orange
Wh/Blu
RIBU1S
Wh/Yel
Orange
LOAD RIBU1SC is an alternative to the RIBU1S that allows one item to be ordered - no need to specify N/O or N/C.
120 Vac
24 Vac From Controller Wh/Blu
RIBU1SC
Wh/Yel
Yellow Orange (N/O)
10 & 15 AMP
20 AMP
RIBU1SC RIBH1SC RIBTU1SC RIBTH1SC RIBMU1SC RIBMH1SC
RIB2401SBC RIB2402SBC RIBT2401SBC RIBT2402SBC RIBM2401SBC RIBM2402SBC
LOAD
Blue (N/C) N/O or N/C, you choose
DRY CONTACT INPUT RELAYS
9
Does not require a transformer to power the relay. Safe, low voltage, Class II wiring can be run to a dry contact switch on the door (or any place desired).
Class II Wiring RIB21CDC
120 Vac Power
Light Fixture Junction Box Closet Light
Line Neutral
Class II Wiring
Dry-Contact Door Switch
Closet Door
RIB21CDC
BLACK YELLOW RED ORANGE
ENCLOSED RELAYS
TRACK RELAYS
RIB21CDC RIB01BDC RIB01SBDC RIB02BDC RIB02SBDC
RIBM01ZNDC RIBM02ZNDC RIBM013PNDC
Light Fixture Junction Box
Blue (Not Used)
2005
APPLICATION MANUAL AM578B
www.FUNCTIONALDEVICES.com
PAGE 3
10
LIMIT EXTRA TRANSFORMERS WITH DRY CONTACT INPUT RELAYS
Eliminate the expense of extra transformer(s) and associated wiring. BEFORE Enclosure D Controller R Cont. Pwr. Y C O N T A C T S
120 Vac
24 Vac
40 VA
24 Vac
100 VA
D.O.1 D.O.2
Enclosure Controller
C O N T A C T S
11
ENCLOSED RELAYS
TRACK RELAYS
RIB21CDC RIB01BDC RIB01SBDC RIB02BDC RIB02SBDC
RIBM01ZNDC RIBM02ZNDC RIBM013PNDC
D.O.3
AFTER D R Y
RIBU1C's
Dry Contact Input RIB's
120 Vac
24 Vac
Cont. Pwr.
40 VA
D.O.1 D.O.2 D.O.3
DETECT WATER LEVELS WITH DRY CONTACT INPUT RELAYS
If the water touches the wires, the relay will turn on (closes COMMON to N/O and opens COMMON to N/C). Uses UL Approved low-voltage to sense water and activate relay. Dry Contact Input Relay CONTROL CIRCUIT
120-277 Vac Power
R E L A Y
LOAD
TRACK RELAYS
RIB21CDC RIB01BDC RIB01SBDC RIB02BDC RIB02SBDC
RIBM01ZNDC RIBM02ZNDC RIBM013PNDC
Any typical non-corrosive probes may be used.
Water Pan
12
ENCLOSED RELAYS
MONITORING SWITCH POSITION WITH A CONTROLLER
Digital In 1 and 2 of the controller can be used to monitor the position of the HOA switch. The controller can be programmed to log the status of the HOA and provide a warning if the switch is in an override position. CONTROLLER Digital Out Common
10-30Vac/dc Common
RIB
60 Hz ac
120 Vac Not Used
Digital In 1 Digital In 2 Common
PAGE 4
Closed SWITCH Auto Pole #2 Common
SWITCH Pole #1
Auto Common
ENCLOSED RELAYS 10 AMP
TRACK RELAYS 15 AMP
RIBU1SM RIBH1SM
RIBMU1SM RIBMH1SM RIBMNU1SM RIBMNH1SM
LOAD
www.FUNCTIONALDEVICES.com
DI1 Open Open Closed Closed
DI2 Open Closed Open Closed
RESULT Overridden Off Auto Overridden On Error Condition
APPLICATION MANUAL AM578B 2005
HIGH VOLTAGE OPTOISOLATED RELAYS
13
Optoisolated relays help isolate noisy loads from the controller. Good for controlling power relays from analog outputs. 60 Hz ac
CONTROLLER
Power Supply Digital Out (or Analog Out)
Opto Input
R E L A Y
LOAD
ENCLOSED RELAYS
TRACK RELAYS
RIBTE01B RIBTE02B RIBTE01SB RIBTE02SB RIBTE01P RIBTE02P
RIBME2401B RIBME2402B RIBME2401SB RIBME2402SB RIBME2401P RIBME2402P
OPTO RIB
14
LOW VOLTAGE OPTOISOLATED RELAYS
Optoisolated relays help isolate noisy loads from the controller. Good for controlling power relays from analog outputs. 60 Hz ac
CONTROLLER
Power Supply
24 Vac/dc
Opto Input
Digital Out
R E L A Y
LOAD
ENCLOSED RELAYS
TRACK RELAYS
RIBTELC RIBTELS RIBTE24B RIBTE24SB RIBTE24P
RIBME2401B RIBME2402B RIBME2401SB RIBME2402SB RIBME2401P RIBME2402P
OPTO RIB
15
POLARIZED RELAYS
For fire alarm systems, smoke control systems, etc. Relays are polarized to work in a supervised system and may be turned on and off by reversing polarity.
LOAD
LOAD
RIB24C-FA
RIB24C-FA
+-
+-
ENCLOSED RELAYS
TRACK RELAYS
RIB12C-FA RIB24C-FA RIB24S-FA RIBT24B-FA RIB24P-FA
RIBMN12C-FA RIBMN24C-FA RIBMN12S-FA RIBMN24S-FA
END OF LINE RESISTOR
CONTROLLER
SIGNALING CIRCUIT
2005
APPLICATION MANUAL AM578B
www.FUNCTIONALDEVICES.com
PAGE 5
CONDENSE WORK SPACE & WIRING (POWER CONTROL)
16
Power Control Centers allow you to save large amounts of time, space, and wiring throughout your panel. BEFORE
AFTER
There is a lot of extra wiring in this enclosure which not only takes up space but also increases the difficulty and time associated with installation.
By using one of Functional Devices' Power Control Centers you will greatly reduce installation time, as well as save space in your enclosure.
CONDUIT ENCLOSURE
ENCLOSED 10 AMP
PSPT2RB4 PSPW2RB4
PSPT2RB10 PSPW2RB10
CONDUIT
Power Control Center is pre-wired ENCLOSURE
SWITCH
To remainder of panel
H N G H N G
FUSE
SUB-PANEL
ENCLOSED 4 AMP
SWITCH, BREAKER & INDICATOR LIGHT
To remainder of panel
SUB-PANEL
CONDENSE WORK SPACE & WIRING (POWER SUPPLIES)
17
The PSC, PSH, and PSB Series Power Supplies allow you to save large amounts of time, space, and wiring throughout your panel. BEFORE
By using one of Functional Devices' Power Supplies you will greatly reduce installation time, as well as save space in your enclosure.
CONDUIT ENCLOSURE H N G H N G
FUSE
24 Vac
18
To remainder of panel
Any “B10” models in the PSC, PSH, or PSB Power Supply Series’
CONDUIT
Power Supplies are pre-wired ENCLOSURE
SWITCH
SUB-PANEL
POWER SUPPLIES
AFTER
There is a lot of extra wiring in this enclosure which not only takes up space but also increases the difficulty and time associated with installation.
24Vac Switch/Breaker
120Vac from 10A Switch & CB to remainder of panel
24Vac
24Vac Indicator
POWER SUPPLY MAIN POWER 10A Switch/CB & Indicator Light SUB-PANEL
SWITCH IN A BOX ENCLOSED CONTROLS
Pre-labeled 20A switches are great for new installations or last minute corrections to controls jobs. Switch labels may be custom selected when ordering. 2 POSITION SUMMER WINTER
COOL (Summer)
HEAT (Winter)
To A/C Power In
2 POSITION
3 POSITION
SIB04S SIB05S
SIB02S SIBLS
3 POSITION 24VAC
HAND OFF AUTO
CONTACTOR
COIL
CONTROLLER DIGITAL OUT
PAGE 6
24Vac Transformer DO Front Controller
Hand Off Auto
Contactor Coil
www.FUNCTIONALDEVICES.com
APPLICATION MANUAL AM578B 2005
AM578B APPLICATION MANUAL 2005
www.FUNCTIONALDEVICES.com
APPLICATION NOTES FOR RIB® RELAYS, CURRENT SENSORS, POWER SUPPLIES, & POWER CONTROL UNITS