XGSL
GATE OPERATOR THREE PHASE ONLY
WIRING TYPE
S2
FIELD WIRING AND ADJUSTMENTS THESE INSTRUCTIONS SHOULD BE USED FOR T H R E E P H A S E M O D E L X G S L G ATE OPERATORS WITH TYPE S2 CONTROL WIRING. (THE WIRING TYPE IS THE LAST SUFFIX OF THE MODEL NUMBER.)
ELECTRICAL ENCLOSURE COMPONENT LAYOUT FAMILIARIZE YOURSELF WITH COMPONENTS BEFORE PROCEEDING SWITCH 2 LED INDICATOR LIGHT
J1 TERMINAL STRIP
SWITCH 1
RADIO RECEIVER TERMINAL STRIP
S2 CONTROL BOARD
RESET BUTTO N
DRAWING NUMBER:
1615 I M P O R TA N T: THESE INSTRUCTIONS ARE INTENDED FOR PROFESSIONAL GATE OPERATOR INSTALLERS AND LICENSED ELECTRICIANS ONLY. ANY QUESTIONS ABOUT THESE INSTRUCTIONS SHOULD BE DIRECTED TO THE OPERATOR SUPPLIER OR THE MANUFACTURER.
M A N U FACTURED and DISTRIBUTED BY:
L I N K CONTROLS, INC.
2111 LAKELAND AVENUE
RONKONKOMA, NY 11779
PH:(516) 467-2585
MADE IN U.S.A.
FAX:(516) 467-7811
USE ENTRAPMENT PROTECTION EQUIPMENT SUCH AS SENSING EDGES WITH THIS GATE OPERATOR. WITHOUT SUCH EQUIPMENT, SERIOUS INJURY OR DEATH MAY RESULT. REFER TO SAFETY INSTRUCTIONS PROVIDED WITH O P E R ATOR FOR MORE INFORMATION.
W ARNING
SECTION 1 - MASTER/SLAVE CONNECTIONS INSTRUCTIONS:
ANY STANDARD OPERATOR MAY BE CONFIGURED AS A MASTER OR A SLAVE. IF YOUR INSTALLATION DOES NOT REQUIRE A MASTER/SLAVE SYSTEM, SKIP THIS SECTION AND PROCEED TO SECTION 2 (Control Adjustments). STEP 1 DETERMINE WHICH OPERATOR WILL BE THE MASTER UNIT.
STEP 3 DETERMINE CLOSE TIME SETTING FOR MASTER & SLAVE.
SWITCH 1
ON
SWITCH 2 PLACE POLE #4 IN APPROPRIATE POSITION. ON = MASTER UNIT OFF = SLAVE UNIT
4 3 2 1
ON
SWITCH 1
ON
ON
4 3 2 1
SLAVE UNIT Set all poles of switch 2 to the ON position.
STEP 4 INTERCONNECT MASTER ANS SLAVE UNITS AS SHOWN BELOW. AND ADD JUMPER ON J1 TERMINAL OF SLAVE UNIT ONLY.
STEP 2 DETERMINE WHICH UNIT WILL OPEN TO THE RIGHT (from inside looking out). 4 3 2 1
SWITCH 2 MASTER UNIT Set time as desired by using table in section 2 (Control Adjustments)
4 3 2 1
J1 TERMINAL (SLAVE UNIT) 1 2 3 4 5 6 7 8
PLACE POLE #2 IN APPROPRIATE POSITION. ON = OPEN LEFT OFF = OPEN RIGHT
9
10 11 12 13 14 15 16
9
10 11 12 13 14 15 16
JUMPER J1 TERMINAL (MASTER UNIT) 1 2 3 4 5 6 7 8
SECTION 3 - CONTROL EQUIPMENT INSTRUCTIONS:
CONNECT WIRES FROM YOUR CONTROL DEVICE TO THE TERMINAL NUMBERS ON THE J1 TERMINAL STRIP DESIGNATED BY THE BOX(ES) ABOVE EACH WIRE. IF MORE THAN ONE BOX IS SHOWN, REFER TO THE “OPEN AND CLOSE CONTROL OPTIONS” ON THE RIGHT TO SELECT THE CORRECT BOX FOR YOUR APPLICATION. THE CONNECTOR BLOCK MAY BE REMOVED FOR EASE OF WIRING IF DESIRED.
MASTER/SLAVE UNITS:
D O N OT BYPASS STOP BU T TO N. IF STOP BUTTON IS NOT INSTALLED, OR WIRED INCORRECTLY, A PERSON MAY NOT BE ABLE TO STOP THE GATE IN AN EMERGENCY. SERIOUS INJURY OR DEATH MAY RESULT. REFER TO SAFETY INSTRUCTIONS PROVIDED WITH OPERATOR FOR MORE INFORMATION.
W ARNING 1
WIRE ALL CONTROLS TO MASTER UNIT ONLY (DETERMINED BY SWITCH 1 POLE 4).
2
9 or 8
AN OPEN CONTROL, WHEN CONNECTED TO TERMINAL NUMBER:
5
ANY OPEN CONTROL will open gate if fully closed and reverse gate when closing
3
ANY OPEN & CLOSE CONTROL will open gate if fully closed, close gate if fully open, and reverse gate when closing.
4 7 or 4 or 1
O P E N A N D C LO S E O P T I O N S
5
6
9 or 8 or 2
5
3
7 or 4 or 1
5
3
STO P
STO P
OFF ON
(See Note #1) 10
5
SENSING EDGE TO REVERSE will reverse gate if edge is struck when gate is closing
8
- Will only require a momentary pulse on the control each time control is used, but WILL NOT set or reset close timer
2
- EMERGENCY OPEN (See Note #2)
A CLOSE CONTROL, WHEN CONNECTED TO TERMINAL NUMBER:
9 or 8 or 2
CLOSE
CLOSE
5
- Will only require a momentary pulse on the control each time control is used, and will set or reset close timer.
7
- Will only require a momentary pulse on the control each time control is used.
4
- Will require constant pressure on the control to keep gate moving.
1
- EMERGENCY CLOSE (See Note #2)
OPEN
OPEN
STA N D A R D 3 BUTTON CONTROL
9
3 BUTTON CONTROL WITH KEYED LOCK-OUT Key Switch will lock-out all controls, including close timer.
6
5
3
STO P
SENSING EDGE TO STO P will stop gate if edge is struck when gate is moving in either direction (wire in series w/ STOP button)
NOTES: 1) VEHICLE & PERSONNEL SENSORS Vehicle sensors and personnel sensors may also be connected to terminals 10 & 5 (in parallel to the sensing edge) to function as safety devices. Actuation of the device will reverse the gate if it is closing. 2) EMERGENCY OPEN/CLOSE Connections from O P EN and CLOSE controls may be made to terminals 2 and 1 respectively to by-pass the main control board in case of board failure. When these connections are made, controls will require constant pressure to keep door moving. On Master/Slave pairs, the controls will only operate the Master unit. To operate the slave in emergency mode, seperate Open and Close controls must be temporarily connected to the Slave as per diagram 3 at left. Disconnect these controls to return to normal operation.
CAUTION Sensing edge and all other components may be disabled in this mode.
W ARNING
L O C ATE ALL CONTROLS OUT OF REACH OF CHILDREN; AND SO THAT THE PERSON OPERATING THE CONTROL WILL HAVE CLEAR VIEW OF THE MOVING GATE, BUT WILL NOT BE ABLE TO REACH OR TOUCH THE GATE. REFER TO THE SAFETY INSTRUCTIONS PROVIDED WITH THE OPERATOR FOR MORE INFORMATION.
SECTION 2 - CONTROL ADJUSTMENTS INSTRUCTIONS: READ THIS SECTION IN ITS ENTIRETY AND MAKE NECESSARY ADJUSTMENTS BY SETTING THE SWITCH POLES AS DESCRIBED BELOW. SWITCH 1
ON
4 3 2 1
SWITCH 2
NOTE: On MASTER/SLAVE units, POLE #3 setting for Master and Slave must correspond.
4 3 2 1
ON
POLE #1 - MAXIMUM RUN TIME ON: Maximum run time is 90 seconds. OFF: Maximum run time is 45 seconds. POLE #2 - DIRECTION OF GATE TO OPEN ON: Open LEFT (from inside gate looking out) OFF: Open RIGHT (from inside gate looking out) POLE #3 - WARNING DEVICE (SEE NOTE IN SECTION 7) ON: Warning device will turn on three(3) seconds before gate starts to move in either direction. OFF: W arning device will only turn on three(3) seconds before timer closes gate. POLE #4 - MASTER/SLAVE - SINGLE UNIT ON: Master OFF: Slave or Single Unit
POLE SETTINGS
POLE #1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
POLE #2 ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF
4. LIMIT SWITCH ADJUSTMENT FOR REFERENCE ONLY. REFER TO THE INSTALLATION MANUAL FOR INSTRUCTIONS.
AUX. L/S-”A” (Optional)
SET CLOSE TIMER TO DESIRED TIME SETTING BY USING TABLE BELOW. APPROXIMATE TIME BEFORE CLOSING
POLE #3 POLE #4 ON ON ON ON ON ON ON ON OFF ON OFF ON OFF ON OFF ON ON OFF ON OFF ON OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF
= = = = = = = = = = = = = = = =
DISABLED 2 SEC. 3 SEC. 13 SEC. 15 SEC. 23 SEC. 33 SEC. 44 SEC. 72 SEC. 88 SEC. 107 SEC. 126 SEC. 148 SEC. 172 SEC. 198 SEC. 224 SEC.
5. LINE VOLTAGE SUPPLY CONNECT INCOMING POWER TO THE ON/OFF SWITCH AS S H O W N B E L O W. REFER TO OPERATOR NAMEPLATE FOR CORRECT VOLTAGE.
Depress this plate to release the limit nuts for adjustments.
L/S-”A”
O N /O FF SW ITC H
L/S-”B”
+
L1 L2 L3
3-PH ASE PO W ER IN 208VAC ,230VAC ,460VAC O R 575VAC (AC C O R D IN G TO O PER ATO R N AM EPLATE)
AUX. L/S-”B” (Optional)
6. RADIO RECEIVER (optional) CONNECT RADIO RECEIVER BY EITHER PHYSICALLY MOUNTING IT TO THE TERMINAL STRIP, OR BY MOUNTING IT ELSEWHERE INSIDE THE OPERATOR ENCLOSURE AND RUNNING WIRES TO THE TERMINAL STRIP. BE SURE TO CONNECT AN ANTENNA OUTSIDE THE GATE OPERATO R ENCLOSURE.
7. AUXILIARY CONTROLS (optional) IF YOUR SYSTEM INCLUDES A WARNING DEVICE, CONNECT TO J1 TERMINAL STRIP AS SHOWN BELOW. 15
POWER SOURCE
16
SOLENOID G ATE LOCK
R1 R2
13
14
R3 TER M IN AL O N TO P O F ELEC TR IC AL PAN EL 1 2 3 R AD IO R EC EIVER
O U TSID E AN TEN N A
G ND
POWER SOURCE
W ARNING DEVICE
SOLENOID TYPE GATE LOCK From fully closed, it will engage 1/4 second before gate starts to open. Connect power source for gate lock in series with lock. Be sure power source voltage matches gate lock requirements. Voltage should be 115V or less and gate lock should not draw more than 3 amps.
W ARNING DEVICE W ill turn depending on setting of switch 1 pole #3 (see section 2). Connect power source for warning device in series with device. Be sure power source voltage matches warning device requirements. Voltage should be 115V or less and gate lock should not draw more than 3 amps.
NOTE: In both of the above connections, connect power source in series with device. Be sure power source voltage matches device requirements. Voltage should be 115V or less and device should not draw more than 3 amps.
G AT E O P E R ATO R S C H E M ATIC DIAG R A M
APPLICATIONS:
NOTES: 1)
EXTERNAL OVERLOAD IS USED WHEN O/L IS NOT PRESENT IN THE M O TOR (J WIRES IN MOTOR).
2)
WIRE COLOR 208V-RED, 230V-ORANGE, 460V-VIOLET, 575V-GRAY.
LINK CONTROLS, INC.
LINK
CONTROLS
2111 LAKELAND AVE. RONKONKOMA, NY 11779 PH:(516) 467-2585 FAX:(516) 467-7811
CONTROL WIRING TYPE - S2 FIELD WIRING & ADJUSTMENTS MODEL TYPES:
XGSL
HORSEPOWER:
-
V O LTAGE/PHASE:
208V, 230V, 460V OR 575V - 3 PHASE ONLY
D R AWING NUMBER: D ATE:
1615 REVISION:
12/08/97
ECN:
B-08/08/98
G151