Transcript
®
stored energy solutions for a demanding world
GFM Series
Model: GFM1500 The GFM range of gel technology batteries offers outstanding performance including a 15+ years design life. The GFM series is designed by using the polymer gel electrolyte and compliant with the latest IEC60896-21/22 standard. This GFM series also offers 100% capacity out of the box and is capable of handing deep discharges for complete peace of mind. The multiple installations to both horizontally and vertically are easily accessible due to the flexible connectors design.
Specifications Battery Model
GFM1500 2V
Nominal Voltage
3HR( 370A, 1. 80V) 1125AH Width Height
10HR( 150A,1. 80V) 1500AH Length
O
Capacity( 25 C ) Dimensions
265. 5mm
229mm
1HR( 825A, 1. 75V) 825AH Total Height
555mm
Approx. Weight
566mm
93kg
Internal Resistance
0.15mΩ
Max Charge Current Allowed
375A
O
Ch arge Voltage( 25 C )
Cycle use
Float use
2. 35V / cell
2. 25V / cell O
O
O
O
Operation ( maximum ): -40 C to 5 5 C( -40 F to 1 31 F) O O O O Operation ( recommended ): 15 C to 25 C( 59 F to 77 F) O O O Storage: -20 C to 40 C( -4 F to 104 O F)
Temperature Ranges
Terminal
M8 Female
Terminal Hardware Torque
15 ± 1. 0Nm
Container Material
ABS (V0 optional)
Constant Current Discharge Characteristics Units: Amperes (25OC, 77OF) End voltage per cell
1.60V 1.65V 1.70V 1.75V 1.80V 1.85V 1.90V
5min
15min
30min
1hr
2hr
3hr
5hr
6hr
8hr
10hr
24hr
48hr
100hr
2182.6 2046.7 1923.5 1814.5 1714.2 1471.7
1836.5 1728.6 1635.8 1539.6 1435.9 1221.4
1492.4 1361.0 1244.6 1147.6 1074.5 944.7
983.5 928.2 882.0 826.8 784.5 698.4
605.6 588.4 568.2 547.3 530.8 478.5
444.6 432.6 413.2 403.7 391.2 362.1
287.8 284.2 277.1 272.4 264.3 249.4
247.9 245.0 239.1 235.5 229.3 218.3
194.1 192.4 189.7 187.1 182.0 176.2
159.2 158.3 155.8 154.5 152.4 146.2
73.8 72.7 72.4 71.7 70.2 68.2
39.4 39.1 38.8 38.3 37.6 35.8
22.1 21.8 21.4 20.8 20.2 19.5
1205.4
964.3
785.0
574.0
400.0
321.9
225.9
197.0
158.8
133.2
63.7
33.5
18.0
8hr 424.3 408.6 399.7 384.9 375.0 362.7 339.3
10hr 346.4 338.1 328.1 323.2 318.3 305.9 283.7
Discharge Data with Constant Power E n d v o lta g e p e r c e ll
1.60V 1.65V 1.70V 1.75V 1.80V 1.85V 1.90V
5min 4239.5 4032.1 3876.5 3755.5 3651.8 3321.0 2930.9
15min 3550.6 3407.4 3286.4 3163.0 3014.8 2745.7 2382.7
Copyright © Tysonic Battery
30min 2827.2 2674.1 2607.4 2518.5 2429.6 2160.5 1822.2
1hr 2013.2 1860.2 1771.4 1702.3 1662.9 1512.4 1302.7
O
O
Units:Watts per cell (25 C, 77 F) 2hr 1299.0 1191.6 1157.1 1116.1 1095.4 1006.6 873.4
3hr 962.2 903.0 870.9 838.8 809.2 766.3 710.5
4hr 767.3 727.8 703.1 688.3 666.1 640.5 596.3
5hr 635.5 613.3 599.5 584.7 568.4 541.8 506.3
6hr 542.8 525.5 515.1 503.3 488.5 462.6 432.2
24hr 156.2 153.2 150.2 148.8 146.5 140.6 131.7
www.tysonicbattery.com
®
stored energy solutions for a demanding world
GFM Series
Model: GFM1500 265.5
229
M8
20bolt
555 566
washer valve terminal
cover
shell
86
C h a rg e C a p a city
C h a rg e C u rre n t
C h a rg e V o lta g e
108
86
(%)
(CA)
(V)
Charge Characteristic
Self-discharge Characteristic
Constant Charge At 0.10CA2.35V(٢٥OC) Charge Voltage
100
Capacity(%)
Charge Capacity
100 %Discharge 50 %Discharge
75
10 OC(50 OF)
50 40 OC (104 OF)
30 OC (86 OF)
3
9
20 OC(68 OF)
25 Charge Current
Time(hour)
6
12
15
18
21
24
27
Storage Time(month) Relationship Between Charging Voltage and Temperature
C ha r gi n g V o lt a g e ( V )
Capacity(%)
Temperature Effects on Capacity
Cycle use
TYSONIC BATTERY INC. 1032 East Main Street . Alhambra, CA 91801 USA Toll Free: 877-897-6648 . Tel: (626) 289-5962 . Fax: (626) 576-2503 http://www.tysonicbattery.com . Email:
[email protected]
Standby use