Transcript
6
5
3
4
2
1
Enhanced Series Enclosure Features • 44 RMU, 19” EIA 310-D Compliant
TOP DESIGNED FOR VARIETY OF REMOVABLE TOP PANELS
D
• Fully Welded Steel Construction #16 Gauge Steel
D
• Universal M6 Cage Nut Rails Standard (10/32 Tapped Rails Available) #12 Gauge Steel • Rack Mounting Hardware Included • Rails are Infinitely Adjustable, Front to Rear (Max. Rail Spacing is Cabinet Depth minus 2 inches) • Rails with RMU Markings
12 GAUGE MOUNTING RAILS - 44 RMU, 19" 310-D COMPLIANT - 0.375" SQ. CAGE NUT (STANDARD) - OPTIONAL RAILS TAPPED #10/ 32
C
• TRC (True Rail Count) Rails This certifies that the number of RMU are true and all accessible within the door opening.
C
• Total of Three 10/32 x 1.5” Copper Plated Grounding Studs (One in bottom, two in top) • Weight Capacity: 1500 lbs. on levelers, bolted to floor, or on heavy duty casters
CABLE TIE-DOWN SLOTS
• Durable Powder Coat Finish • Field Reversible Door Hinges (No Additional Hardware Required) B
• Optional Features: • Cable Lacing Bars • Ganging Hardware (No Tools Required) • Anti-tip Legs • Variety of Top, Bottom, & Side Panels
1.50" DIA. CABLE PASS THROUGH HOLES
B
NETWORK / GANGING HOLES RAILS ARE FULLY ADJUSTABLE FRONT-TO-REAR A
INTERPRET DRAWING PER ASME Y14.5M-1994
10/32 x 1.5” COPPER PLATED GROUNDING STUD, QTY (3) DOORS CAN BE EITHER RIGHT OR LEFT-HAND HINGED
DIMENSIONAL LIMITS APPLY AFTER APPLICATION OF FINISH DRAWING NOT TO SCALE
TOLERANCE UNLESS OTHERWISE NOTED: ANGULAR +/- 1~ .XXXX +/- .010 .XXX +/- .015 .XX +/- .030 .X FOR REF. ONLY
THIRD ANGLE PROJECTION
6
5
UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES
4
NOTICE:
PART NUMBER:
TITLE
8401E2932
Use of this document is subject to QTY PER UNIT: 1 MATERIAL TYPE: a confidentiality and nondisclosure agreement with Great Lakes Case MATERIAL GAUGE: & Cabinet Co., Inc. (GLCC) and may FINISH: not be reproduced, disclosed or utilized in whole or in part without DRAWN DATE 8/21/2002 prior written authorization from GLCC. CA CHECKED & APP.
3
WSS
DATE
5-25-05
2
BASE UNIT ASSEMBLY - 84" H X 29" W X 32" D E CABINET
GREAT LAKES CASE & CABINET CO., INC. P.O. BOX 551 EDINBORO, PA 16412 PHONE (814) 734-7303 FAX (814) 734-3907 E-MAIL
[email protected]
DWG NO:
8401E2932
REV
13
S H EET: 1 OF 2 1
A
6
5
3
4
2
1
25.61
44 R MU, 12 G AUGE RAIL, 0.375 SQ. CAGE NUT (SHOWN) OR TAPPED #10/ 32 D
78.24
19.87
D
S L I D I N G R A I L S F OR INFINITE ADJUSTMENT FR ONT TO R EAR
C
1.50" DIA. CABLE PASS THROUGH HOLES 18.31 CENTERS
1/2"-13 LEVELER HOLE 1/2"-13 CASTER HOLE
VERTICAL/HORIZONTAL TIE-DOWN SLOTS
11.75
0.75" DIA. ANCHOR HOLES
14.00
84.00
TOP VIEW
B
29.00
32.00 RIGHT SIDE VIEW
FRONT VIEW
INTERPRET DRAWING PER ASME Y14.5M-1994 DIMENSIONAL LIMITS APPLY AFTER APPLICATION OF FINISH
A
DRAWING NOT TO SCALE
TOLERANCE UNLESS OTHERWISE NOTED: ANGULAR +/- 1~ .XXXX +/- .010 .XXX +/- .015 .XX +/- .030 .X FOR REF. ONLY
THIRD ANGLE PROJECTION
6
5
UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS ARE IN INCHES
4
16.76 29.00
17.75 OPENING
C
1.75 x 3.76 KNOCKOUT
14.75
B
27.95 32.00 BOTTOM VIEW
NETWORK / GANGING HOLES
NOTICE:
PART NUMBER:
TITLE
8401E2932
Use of this document is subject to QTY PER UNIT: 1 MATERIAL TYPE: a confidentiality and nondisclosure agreement with Great Lakes Case MATERIAL GAUGE: & Cabinet Co., Inc. (GLCC) and may FINISH: not be reproduced, disclosed or utilized in whole or in part without DRAWN DATE 8/21/2002 prior written authorization from GLCC. CA CHECKED & APP.
3
WSS
DATE
5-25-05
2
BASE UNIT ASSEMBLY - 84" H X 29" W X 32" D E CABINET
GREAT LAKES CASE & CABINET CO., INC. P.O. BOX 551 EDINBORO, PA 16412 PHONE (814) 734-7303 FAX (814) 734-3907 E-MAIL
[email protected]
DWG NO:
8401E2932
REV
13
S H EET: 2 OF 2 1
A