GOLD & COMPACT Energy-efficient, compact and flexible air handling units
Air handling units with unbeatable advantages Saves space Swegon’s air handling units have compact dimensions and what’s more sharp duct bends can be connected directly to the air handling unit without pressure losses. This saves you space in the fan room.
Optimum operating economy Energy-saving fans, efficient heat recovery and full control of temperatures, airflows and operating times provide optimum operating economy.
Economical control functions A large number of functions, including communication, are integrated into the control system and are ready to be activated via a hand-held micro terminal. Several of the functions provide unique opportunities for saving energy.
Fast installation and Plug-and-play The work of installing the air handling units can be done quickly and easily and for the accessories, such as cooling units and air heaters, there are ready-to-use control functions and all connections are made using cables with quick-fit connectors. Plug-andplay!
Contents ALLMÄNT GOLD & COMPACT
2
2
Technical Description
5
Complements and accessories
6
Overview – Airflows
8
Sizing - GOLD RX
9
Sizing - GOLD PX
13
Sizing - GOLD CX
14
Sizing - GOLD SD
16
Sizing - GOLD LP
18
Technical Description
19
Complements and accessories
20
Overview – Airflows
21
Sizing - COMPACT Unit
22
Sizing - COMPACT Top
22
Sizing - COMPACT Air
23
Sizing - COMPACT Heat
23
Revolutionary control system in the new GOLD version E
The user interface is available in a large number of languages, selected on the handheld terminal.
Groundbreaking step
User friendly multi-touch screen
With the new GOLD version E, Swegon takes a groundbreaking step in the further development of the air handling unit, which for some time has been seen as standard in the industry.
The new handheld terminal, IQnavigator, features a multi-touch screen and is very simple and easy-to-use. Commissioning and settings are performed with an intuitive user interface, and informative help texts. Set and read values for component parts in GOLD are presented in a flow chart on the screen. On a specific log page it is possible to select one or more parameters to be read in a diagram with a timeline and a size axis. The parameters can be read in real time or as logged values.
Revolutionary control system The most striking new feature is the revolutionary control system, IQlogic. In addition to several smart and user friendly functions, significantly greater options are provided for communication and remote control through main control systems, laptops, tablets or mobile phones. Communication between a handheld terminal and the GOLD unit can occur wirelessly via WLAN. It is just as easy to use a computer, tablet or mobile phone via Wi-Fi.
GOLD LP and COMPACT For GOLD LP and COMPACT the control system is designed for small air handling units. 3
Exceptional energy efficiency Energy-efficient fans of international calibre! Swegon’s fans are of the new generation of energy-efficient fans. The motors are of EC type and have been developed on a new platform that offers the best energy efficiency on the market. Swegon’s EC motors can achieve a peak efficiency of more than 90%. This is more than 10 percentage units better than traditional AC motors with frequency inverters and the difference becomes greater the more the speed of rotation is regulated to decelerate. Every improvement in motor efficiency can be directly translated into a reduction in operating costs. Several new fan sizes have been added for GOLD, which gives greater freedom to choose exactly the right unit size and fan variant to suit the needs of the installation.
Optimized heat recovery and cooling energy recovery Swegon’s rotary heat exchangers (GOLD RX/LP and COMPACT) offer unbeatable temperature efficiency, up to 85%. The rotary heat exchanger recovers cooling energy just as efficiently and version RECOsorptic also recovers moisture. This reduces the costs for cooling equipment.
Energy-efficient Fans
Rotary heat exchanger
However, in some applications, the airflow paths must be completely separate from one another. Such applications call for the use of a cross-flow plate heat exchanger (GOLD PX) or coil heat exchangers (GOLD CX/SD) as alternatives. Both have an effective freeze protection function that measures both the temperature and the humidity, which provides high efficiency. GOLD PX can be chosen with RECOfrost, a newly developed anti-frost system that takes energy efficiency for this type of heat exchanger to a completely new level. Cross-flow plate heat exchanger
Plug-and-play saves time and money Fast installation, limited space requirement and Plug-and-play type accessories connection mean low installation costs. Here are a few examples: • The air handling units are complete with direct-driven supply air and extract air fans, supply air and extract air filters, heat exchanger and built-in control equipment. • The air handling units have short installation length and are easy to handle at the building site. If needed, they can be simply split into sections for transport within the site. The cables between the sections have quick-fit connectors. • The air handling units take up little space and the fans are designed to manage sharp duct bends arranged directly from the unit without pressure losses. Several of the air handling units can also be ordered with top-mounted duct connection spigots. • Quick-fit connectors are used for connecting the hand-held micro terminal, supply air temperature sensor, air heater and communication. Other accessories and external functions are connected to an easily accessible row of wiring terminals. 4
Example of a space-saving and compact installation of GOLD with cooling unit
Technical Description
General Points - GOLD The GOLD RX/PX/CX/LP one-piece units are complete air handling units with direct-driven supply air and extract air fans, supply air and extract air filters and heat exchanger. The heat exchanger is either a rotary heat exchanger (RX/LP), plate heat exchanger (PX) or coil heat exchangers (CX). The GOLD SD single-direction units are supply air/extract air handling units with one direct-driven supply air or extract air fan. Optional filters are available for all sizes. Coil heat exchangers and unmounted pipework packages can be selected for the size 12-120 units. The casing is composed of cover panels and inspection doors. The exterior colour of the GOLD RX/PX/CX/SD is beige (NCS S2005-Y30R) and that of the GOLD LP is white (NCS S0502-G).
GOLD RX
The GOLD has built-in control equipment that can be operated from the hand-held micro terminal with plain-text touch screen display or via communication. The electrical and control system is completely integrated into the air handling unit. The microprocessor-based equipment controls and regulates temperatures, airflows and other functions. A large number of functions are built into the system and are simple to activate. If additional functional sections such as dampers and air coolers are required, they can be installed in the ductwork (uninsulated duct accessories) or can be docked directly to the air handling unit (insulated duct accessories).
Application
GOLD PX
The GOLD units are designed for use in comfort ventilation applications. Depending on the variant selected, GOLD units can be utilised in buildings such as office buildings, schools, day nurseries, public buildings, shops, residential buildings, etc. GOLD units equipped with plate/coil heat exchanger (PX/CX) and separate supply air and extract air handling units (SD) can also be used for the ventilation of moderately humid buildings; however not where the humidity is continuously high, such as in indoor water parks. The separate GOLD supply air and extract air handling units (SD) are designed for applications in which the supply air and extract air flows need to be completely separated from one another or where, due to limited available space, separate units for supply air and/or extract air are needed.
GOLD CX
The GOLD RX/PX/CX/SD units can be installed outdoors and then must be equipped with the following accessories: roof, air intake section and exhaust air hood. The GOLD is designed and tested for temperatures, in the surroundings and the air stream, from -40°C to +40°C.
Certification Swegon AB has a certified Quality Assurance System that conforms to ISO 9001 Standard and a certified Environmental Management System to ISO 14001. The GOLD air handling system is also certificated by Eurovent. 12 sizes of GOLD RX for air flows up to 2.5 m3/s (9,000 m3/h) have also received Passive House certification.
N° 06.06.319. Range: GOLD
www.eurovent-certification.com www.certiflash.com
GOLD SD
GOLD LP
5
Complements and accessories
Duct accessories, GOLD Duct accessories are available for a complete installation, such asdampers, air heaters for pre- and post- heating, air coolers, prefilters and sound attenuators. As alternatives, most of the duct accessories are provided for connection with full cross sectional area, i.e. Full face. This reduces pressure losses, which saves electric power supplied to the fans. The accessories for Full face are integrated into an insulated casing, which reduces the installation costs and facilitates installation outdoors. Examples of insulated duct accessories
Examples of uninsulated duct accessories and Full face connection
Outdoor installation, GOLD The GOLD RX/PX/CX/SD units can be installed outdoors with the following accessories: roof, air intake section and exhaust air hood. The roof is supplied in kit form, complete with the necessary assembly parts and sealing strips. Visible parts are made of sheet steel, painted in a beige colour tone, NCS S2005Y30R. Roofs cannot be used on air handling units with top air connection spigots. GOLD air handling units with roof and insulated duct accessories
Hoods, GOLD • Outdoor air hood, sizes 04-40. • Exhaust air hood, sizes 04-40. • Dual-purpose hood, sizes 04-08. • Exterior wall hood, sizes 04-08. Outdoor air hood
6
Exhaust air hood
Dual-purpose hood
Exterior wall hood
Complements and accessories
DX cooling units Cooling unit COOL DX/COOL DX Top COOL DX Top
The COOL DX/COOL DX Top are internally fully wired, charged with refrigerant and the unit is trial run. The cooling unit can be docked to the GOLD or it can be installed as a stand-alone unit. Only one electric power supply and one communication cable (with quick-fit connector) between the COOL DX/COOL DX Top and the GOLD are required. All control is performed via GOLD.
GOLD RX Top
CELEST+ in version LE/HP is a highly efficient chiller for small installations and is available in six sizes up to 30 kW cooling capacity. It is possible to connect several chillers to the same GOLD unit and in doing so dimension the capacity from 9 kW and above. The speed regulated compressors are controlled exactly according to the cooling requirement via SMART Link DX.
Cooling units for minor applications
COOL DX
GOLD
Chillers and heat pumps Best energy class Swegon has a complete program of chillers and heat pumps for the production of cold or hot water. The units are energy efficient and conform to the best energy class. They are certified by Eurovent. They are available in several different versions and in various sizes and are designed for in- or outdoor installation.
Air/Water chillers
Air/Water heat pumps
Water/Water chillers and heat pumps
Air/Water multifunctional units
7
Sizing
Overview – Airflows, GOLD GOLD RX
3
Min. 1) m /s
3
SFPv ≤ 2.0 at 200 Pa 2)
m /h
3
m /s
3
m /h
04 05 07 08 11 12 14 20 25 30 35 40 50 60 70 80 100 120
0.08 0.08 0.08 0.20 0.20 0.20 0.20 0.30 0.30 0.50 0.50 0.75 0.60 1.00 1.00 1.50 1.50 2.50
290 290 290 720 720 720 720 1080 1080 1800 1800 2700 2160 3600 3600 5400 5400 9000
0.42 0.42 0.69 0.77 1.00 1.14 1.65 1.80 2.25 2.35 3.50 3.80 4.75 5.00 6.60 6.85 10.00 10.30
1510 1510 2480 2770 3600 4100 5940 6480 8100 8460 12600 13680 17100 18000 23760 24660 36000 37080
m3/s
m /h
m3/s
m3/h
0.45 0.65 0.75 1.00 1.10 1.40 1.65 2.10 2.50 3.20 3.90 5.00 5.00 6.50 7.50 9.50 11.00 14.00
1620 2340 2700 3600 3960 5040 5940 7560 9000 11520 14040 18000 18000 23400 27000 34200 39600 50400
0.45 0.65 0.75 1.00 1.10 1.40 1.65 2.10 2.50 2.81 3.90 3.90 5.00 6.00 7.50 8.31 11.00 13.04
1620 2340 2700 3600 3960 5040 5940 7560 9000 10120 14040 14040 18000 21600 27000 29920 39600 46940
m3/s
m3/h
m3/s
m3/h
m3/s
m3/h
m3/s
m3/h
04 05 07 08 11 12 14 20 25 30
0.08 0.08 0.08 0.20 0.20 0.20 0.20 0.30 0.30 0.50
290 290 290 720 720 720 720 1080 1080 1800
0.45 0.47 0.71 0.79 1.01 1.14 1.65 2.00 2.45 2.55
1620 1690 2560 2840 3640 4100 5940 7200 8820 9180
0.45 0.65 0.75 1.00 1.10 1.40 1.65 2.10 2.50 3.20
1620 2340 2700 3600 3960 5040 5940 7560 9000 11520
0.45 0.53 0.75 0.83 1.05 1.20 1.65 1.85 2.40 2.32
1620 1910 2700 2930 3780 4320 5940 6660 8640 11520
35 40 50 60 70 80 100 120
GOLD SD
Min. m3/s m3/h 1)
0.50 0.75 1.00 1.00 1.50 1.50 1.50 2.50
1800 2700 3600 3600 5400 5400 5400 9000
Min. m3/s m3/h 1)
Fan+Filter 04 0.08 290 05 0.08 290 07 0.08 290 08 0.20 720 Fan+Filter+Coil h. exch. 11 0.20 720 12 0.20 720 14 0.20 720 20 0.30 1080 25 0.30 1080 30 0.50 1800 35 0.50 1800 40 0.75 2700 50 0.60 2160 60 1.00 3600 70 1.00 3600 80 1.50 5400 100 1.50 5400 120 2.50 9000
GOLD LP 05 08
8
Min. 1) 3 m /s m3/h 0.08 0.08
290 290
SFPv ≤ 2.0 at 200 Pa 2)
Max. Ecodesign 2) 3) 3
GOLD PX
GOLD CX
Min. 1)
Max.
SFPv ≤ 2.0 at 200 Pa m3/s m3/h 3.78 3.90 5.00 5.95 7.30 8.00 11.00 11.70
2)
13610 14040 18000 21420 26280 28800 39600 42120
SFPv ≤ 1.0 at 200 Pa m3/s m3/h
Max.
Max. m3/s m3/h 3.90 3.90 5.00 6.50 7.50 9.50 11.00 14.00
2)
14040 14040 18000 23400 27000 34200 39600 50400
Max. m3/s m3/h
Max. Ecodesign 2) 3)
Max. Ecodesign m3/s m3/h
2) 3)
3.88 3.90 5.00 6.02 7.48 7.86 11.00 12.68
13970 14040 18000 21670 26930 28300 39600 45650
Max. Ecodesign m3/s m3/h
2) 3)
0.60 0.80 0.80 1.19
2160 2880 2880 4280
0.60 0.80 0.80 1.20
2160 2880 2880 4320
0.60 0.66 0.80 1.07
2160 2380 2880 3850
1.05 1.20 1.65 2.10 2.50 3.19 3.90 4.00 5.00 6.50 7.30 8.00 11.00 11.70
3780 4320 5940 7560 9000 11480 14040 14400 18000 23400 26280 28800 39600 42120
1.20 1.80 1.80 2.80 2.80 4.00 4.00 5.00 5.60 8.00 8.00 12.00 12.00 18.00
4320 6480 6480 10080 10080 14400 14400 18000 20160 28800 28800 43200 43200 64800
1.20 1.41 1.80 2.25 2.80 3.47 4.00 4.92 5.60 6.99 7.79 7.86 11.48 12.69
4320 5080 6480 8100 10080 12490 14400 17710 20160 25160 28040 28300 41330 45680
SFPv ≤ 2.0 at 200 Pa 2)
SFPv ≤ 2.0 at 200 Pa m3/s m3/h 0.41 0.62
1470 2230
Max. m3/s m3/h 0.53 0.74
1900 2600
Max. Ecodesign m3/s m3/h 0.50 0.74
1800 2600
All the sizing data specified in this brochure are meant for use as an overview. Exact sizing can be carried out in the web-based ProUnit air handling unit selection software. Contact your nearest Swegon representative for data calculations or use the program yourself at www.swegon.com.
Dimensions specified in this brochure Width
Height (including junction hood and base beams)
Length
Supplied with or without end wall panel The air handling unit can be ordered without end connection panel for the required direction of airflow and with insulated duct accessories that are designed for Full face connection.
Without end wall panel With end wall panel
Division at the building site All the air handling units as from size 11 can be divided into sections for transport within the building site. The length of the longest section is given in the dimension tables.
Arrows for airflows in this brochure Outdoor air
Supply air
Extract air
Exhaust air
1) Applies for airflow regulation. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). 2) Whenever applicable, the value specified for capacity variant 1 applies. 3) Full face
Sizing
GOLD RX sizes 04/05, 07/08 Duct connection options A: Specify left-hand or right-hand version when placing orders. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site via the handheld terminal. B: Specify with or without end wall panel for each airflow direction when placing orders.
Right-hand version
C: The air handling unit can be installed upended.
Bottom beam/Base frame/Base If the air handling unit is installed horizontally, it must be mounted on a bottom beam (option), stand (accessory) or some other form of base support, so that its inspection doors can be opened.
Left-hand version GOLD RX size
Length mm
Width mm
Height mm
Weight kg
Duct connection mm
04
1500
825
1011
214-243
05
1500
825
1011
07
1600
995
08
1600
995
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Ø 315
0.08
0.42
0.45
0.45
1x230V, 10A or 3x400V, 10A
214-243
Ø 315
0.08
0.42
0.65
0.65
1x230V, 101)/162)A or 3x400V, 10A
1176
262-301
Ø 400
0.08
0.69
0.75
0.75
x230V, 101)/162)A or 3x400V, 10A
1176
270-309
Ø 400
0.20
0.77
1.00
1.00
1x230V, 16A1) or 3x400V, 10A1)2)
1) Capacity variant 1. 2) Capacity variant 2.
GOLD RX Top, sizes 04/05, 07/08 Duct connection options A: The GOLD is supplied in a right-hand version. The unit can be changed to the left-hand version at the building site via the handheld terminal.
Bottom beam/Base frame/Base If the air handling unit is installed horizontally, it must be mounted on a bottom beam (option), stand (accessory) or some other form of base support, so that its inspection doors can be opened.
1)
GOLD RX Top size
Length mm
Width mm
Height mm
Weight kg
Duct connection mm
04
1500
825
1011
247
05
1500
825
1011
07
1600
995
08
1600
995
Right-hand version
Left-hand version
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Ø 315
0.08
0.38
0.45
0.45
1x230V, 10A or 3x400V, 10A
247
Ø 315
0.08
0.38
0.65
0.57
1x230V, 10A or 3x400V, 10A
1176
306
Ø 400
0.08
0.65
0.75
0.75
1x230V, 10A or 3x400V, 10A
1176
310
Ø 400
0.20
0.711)
1.00
0.92
1x230V, 16A or 3x400V, 10A
0.71 m3/s refers to air handling units in the right-hand version. For air handling units in the left-hand version, the value is 0.77 m3/s.
9
Sizing
GOLD RX, sizes 11/12 Duct connection options A: Specify left-hand or right-hand version when placing orders. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site via the handheld terminal.
Fan arrangement 1
Fan arrangement 2
Right-hand version
B: Specify with or without end wall panel for each airflow direction when placing orders. C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Fan arrangement 2
Fan arrangement 1
Left-hand version GOLD RX size
Length mm
Width mm
Height mm
Weight kg
Duct connection mm
1860
The longest section when sectionalizing mm 655
11
1199
1486
444-496
12
1860
655
1199
1486
466-518
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Ø 500
0.20
1.00
1.10
1.10
1x230V, 16A1) or 3x400V, 10A1)2)
Ø 500
0.20
1.14
1.40
1.40
3x400V, 10A
1) Capacity variant 1. 2) Capacity variant 2.
GOLD RX Top, sizes 11/12 Duct connection options A: The GOLD is supplied in a right-hand version. The unit can be changed to the left-hand version at the building site via the handheld terminal.
Right-hand version
Left-hand version
GOLD RX Top size
Length The longest secmm tion when sectionalizing mm 1860 655
11 12
1860
655
Width mm
Height mm
Weight kg
Duct connection mm
1199
1486
488
1199
1486
504
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Ø 500
0.20
0.94
1.10
1.10
1x230V, 16A or 3x400V, 10A
Ø 500
0.20
1.041)
1.40
1.25
3x400V, 10A
1) 1.04 m /s refers to air handling units in the right-hand version. For air handling units in the left-hand version, the value is 1.08 m3/s. 3
10
Sizing
GOLD RX sizes 14/20, 25/30, 35/40 *
Duct connection options
*
A: Specify left-hand or right-hand version when placing orders. If the air handling unit is supplied with all the end connection panels, the version can be changed at the building site via the handheld terminal. B: Specify with or without end wall panel for each airflow direction when placing orders.
Fan arrangement 1
Fan arrangement 2
Right-hand version
C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
*
*
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units). E: Specify air intake from above for outdoor air or extract air when placing orders (sizes 14-30, not for outdoor units). Fan arrangement 1
Left-hand version
* Sizes 14-30 GOLD RX size
Length mm
The longest section when sectionalizing mm
Width Height mm mm
Weight kg
Duct connection Min mm
14
2080
765
1400
1586
521-589
1000x400
20
2080
765
1400
1586
557-625
25
2220
835
1600
1786
30
2220
835
1600
1786
35
2446
948
1990
40
2446
948
1990
Fan arrangement 2
Airflow m3/s
Power connection
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
0.20
1.65
1.65
1.65
3x400V, 10A
1000x400
0.30
1.80
2.10
2.10
3x400V, 101)/162)A
666-746
1200x500
0.30
2.25
2.50
2.50
3x400V, 101)/162)A
706-786
1200x500
0.50
2.35
3.20
2.81
3x400V, 20A
2085
956-1070
1400x600
0.50
3.50
3.90
3.90
3x400V, 20A
2085
1006-1120
1400x600
0.75
3.80
3.901/5.002
3,90
3x400V, 201)/252)A
1) Capacity variant 1. 2) Capacity variant 2.
11
Sizing
GOLD RX, sizes 50/60 and 70/80 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Fan arrangement 1
Fan arrangement 2
Right-hand version
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Delivery The GOLD RX 70/80 units are supplied as two units. The one unit consists of the centre section with heat exchanger and the fan/filter section where the fan is located in the upper level. The other unit consists of a fan/filter section in which the fan is placed in the lower level. GOLD RX size
Length mm
The longest section when sectionalizing mm
Width mm
Height mm
Weight kg
Duct connection mm
50
2670
1050
2318
2353
1294-1418
60
2670
1050
2318
2353
70
3120
1275
2637
80
3120
1275
2637
Fan arrangement 1
Fan arrangement 2
Left-hand version Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
1600x800
0.60
4.75
5.00
5.00
3x400V, 201)/322)A
1374-1498
1600x800
1.00
5.00
6.50
6.50
3x400V, 321)/502)A
2740
2059-2211
1800x1000
1.00
6.60
7.50
7.50
3x400V, 321)/502)A
2740
2159-2435
1800x1000
1.50
6.85
9.50
8.31
3x400V, 501)/802)A
1) Capacity variant 1. 2) Capacity variant 2.
GOLD RX, sizes 100/120 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders. D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 1
Fan arrangement 2
Right-hand version
Delivery The GOLD RX 100/120 air handling units are delivered in five separate subunits: two fan sections, two filter sections and one heat exchanger section. The heat exchanger section can also be supplied split into two casing sections and rotor, in which case the rotor is supplied tilted in a transport cradle (transport height = 2930 mm). After assembling the heat exchanger section, install the five units at the building site. GOLD Length RX mm size
The longest section when sectionalizing mm
Width Height mm mm
Weight kg
Duct connection3) mm
Fan arrangement 1
Fan arrangement 2
Left-hand version Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
100
3322
1126
3340
3440
3540-3900
2400x1200
1.50
10.00
11.00
11.00
3x400V, 501)/802)A
120
3322
1126
3340
3440
3746-4168
2400x1200
2.50
10.30
14.00
13.04
3x400V, 801)/1252)A
Capacity variant 1. 2) Capacity variant 2. 3) Duct connection 2500 x 800 mm on the units with a fan outlet for upward air discharge.
12
Sizing
GOLD PX, sizes 04/05, 07/08 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. Left-hand version GOLD PX size
Length mm
Width mm
Height mm
Weight kg
Duct connection mm
04
2000
905
1191
291-337
05
2000
905
1191
07
2230
1075
08
2230
1075
Right-hand version
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Ø 315
0.08
0.45
0.45
0.45
1x230V, 10A or 3x400V, 10A
291-337
Ø 315
0.08
0.47
0.65
0.53
1x230V, 101)/162)A or 3x400V, 10A
1356
360-419
Ø 400
0.08
0.71
0.75
0.75
1x230V, 101)/162)A or 3x400V, 10A
1356
369-428
Ø 400
0.20
0.79
1.00
0.83
1x230V, 16A1) or 3x400V, 10A1)2)
1) Capacity variant 1. 2) Capacity variant 2.
GOLD PX, sizes 11/12 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. Left-hand version GOLD PX size
Length mm
11
2510
The longest section when sectionalizing mm 1200
12
2510
1200
Width Height mm mm
Weight kg
Duct connection mm
Right-hand version
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
1279
1486
552-646
Ø 500
0.20
1.01
1.10
1.05
1x230V, 16A1) or 3x400V, 10A1)2)
1279
1486
574-668
Ø 500
0.20
1.14
1.40
1.20
3x400V, 10A
1) Capacity variant 1. 2) Capacity variant 2.
GOLD PX, sizes 14/20 and 25/30 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. C: Specify air intake from above for supply air and/or extract air when placing orders (not for outdoor units).
Left-hand version
GOLD PX size
Length mm
The longest section when sectionalizing mm
Width mm
Height mm
Weight kg
Duct connection mm
14
2830
1300
1480
1586
667-773
20
2830
1300
1480
1586
25
3220
1550
1680
30
3220
1550
1680
Right-hand version
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
1000x400
0.20
1.65
1.65
1.65
3x400V, 10A
703-809
1000x400
0.30
2.00
2.10
1.85
3x400V, 101)/162)A
1786
905-1058
1200x500
0.30
2.45
2.50
2.40
3x400V, 101)/162)A
1786
945-1098
1200x500
0.50
2.55
3.20
2.32
3x400V, 161)/202)A
1) Capacity variant 1. 2) Capacity variant 2.
13
Sizing
GOLD CX, size 35/40 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Fan arrangement 1
Fan arrangement 2
Fan arrangement 1
Fan arrangement 2
Right-hand version
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Left-hand version GOLD CX size
Length mm
The longest section when sectionalizing mm
Width Height mm3) mm
35
2719
948
2961
40
2719
948
2961
Weight kg
Duct connection mm
2085
1635-1749
2085
1685-1799
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
1400x600
0.50
3.78
3.90
3.88
3x400V, 201)/252)A
1400x600
0.75
3.90
3.901/5.002
3.90
3x400V, 201)/322)A
1) Capacity variant 1. 2) Capacity variant 2. 3) Including pipework package
GOLD CX, sizes 50/60 and 70/80 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. C: The arrangement of the functional sections can be vertically reversed. Specify this by selecting fan arrangement 1 or 2 when placing orders.
Fan arrangement 1
Fan arrangement 2
Fan arrangement 1
Fan arrangement 2
Right-hand version
D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Delivery The GOLD CX 50/60 units are supplied as two units, 70/80 as three units.
Left-hand version GOLD CX size
Length mm
The longest section when sectionalizing mm
Width mm3)
Height mm
Weight kg
Duct connection mm
50
2956
1050
3305
2353
2170-2294
60
2956
1050
3305
2353
70
3454
1275
3650
80
3454
1275
3650
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
1600x800
1.00
5.00
5.00
5.00
3x400V, 251)/322)A
2250-2374
1600x800
1.00
5.95
6.50
6.02
3x400V, 401)/502)A
2740
3156-3308
1800x1000
1.50
7.30
7.50
7.48
3x400V, 401)/632)A
2740
3256-3532
1800x1000
1.50
8.00
9.50
7.86
3x400V, 631)/802)A
1) Capacity variant 1. 2) Capacity variant 2. 3) Including pipework package
14
Airflow m3/s
Sizing
GOLD CX, size 100/120 Duct connection options A: Specify left-hand or right-hand version when placing orders. B: Specify with or without end wall panel for each airflow direction when placing orders. Fan arrangement 1
C: The arrangement of the functional sections can vary. Specify this by selecting fan arrangement 1, 2, 4 or 5 when placing orders. For fan arrangement 4 and 5, you should also specify: supply air in upper or lower level. D: Specify upper fan outlet for upward air discharge when placing orders (not for outdoor units).
Fan arrangement 5, supply air – upper level
Delivery
Fan arrangement 2
Fan arrangement 5, supply air - lower level
Right-hand version
The GOLD RX 100/120 air handling units are delivered in six separate subunits: two fan sections, two filter sections and two heat exchanger sections. The six sections must be fitted together at the building site. The pipework package including the control box can be ordered as accessories and are supplied in unassembled condition for wall or floor mounting.
Fan arrangement 1
Fan arrangement 4, supply air – upper level
Fan arrangement 2
Fan arrangement 4, supply air - lower level
Left-hand version GOLD Length CX mm size
The longest section when sectionalizing mm
Width Height mm mm
Weight kg
Duct connection mm4)
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
100
3396
1144
3677
3440
4374-4734
2400x1200
1.50
11.00
11.00
11.00
3x400V, 631)/802)A
120
3396
1144
3677
3440
4580-5002
2400x1200
2.50
11.70
14.00
12.68
3x400V, 801)/1252)A
1) Capacity variant 1. 2) Capacity variant 2. 4) The dimensions of the duct connection on the units with a fan outlet for upward air discharge are 2500 x 800 mm.
15
Sizing
GOLD SD, size 04/05, 07/08 Installation/duct connection options A: The air handling unit can be upended or turned upside down. The unit can also be installed with the inspection door upward, but not downward. B: Specify: with or without end connection panel when placing orders.
Bottom beam/Base frame/Base If the air handling unit is installed horizontally, it must be mounted on a bottom beam (option), stand (accessory) or some other form of base support, so that its inspection doors can be opened.
GOLD SD size
Length mm
Width mm
Height mm
Weight kg
Duct connection mm
Airflow m3/s Min
SFPv ≤ 1.0 at 200 Pa
Max
Max Ecodesign
Power connection
Fan + Filter 04
1099
825
490
105-119
Ø 315
0.08
0.60
0.60
0.60
1x230V, 10A
05
1099
825
490
105-119
Ø 315
0.08
0.80
0.80
0.66
1x230V, 10A
07
1174
995
575
113-133
Ø 400
0.08
0.80
0.80
0.80
1x230V, 10A
08
1174
995
575
117-137
Ø 400
0.20
1.19
1.20
1.07
1x230V, 10A1) 3x400V, 10A2)
1) Capacity variant 1. 2) Capacity variant 2.
GOLD SD, size 11/12 Left-hand version
Right-hand version
Duct connection options A: Specify left-hand or right-hand version when ordering.
Fan with filter, if required.
B: Specify: with or without end connection panel when placing orders.
Fan with filter, if required + Coil heat exchanger in extract air. Droplet eliminator is optional. Fan with filter, if required + Coil heat exchanger in supply air.
GOLD SD size
Length mm
The longest section when sectionalizing mm
Width mm
Height mm
Weight kg
Duct connection mm
Airflow m3/s Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Power connection
Fan + Filter + Coil heat exchanger 11
2092
1404
11993)
748
321-347
Ø 500
0.20
1.05
1.20
1.20
1x230V, 10A1) 3x400V, 10A2)
12
2092
1404
11993)
748
332-358
Ø 500
0.20
1.20
1.80
1.41
3x400V, 10A
1) Capacity variant 1. 2) Capacity variant 2. 3) Coil Heat Exchanger width + 200 mm
16
Sizing
GOLD SD, sizes 14/20,25/30,35/40,50/60,70/80, 100/120 Left-hand version
Duct connection options
Right-hand version
A: Specify left-hand or right-hand version when placing orders. Fan
B: Specify: with or without end connection panel when placing orders. C: Specify fan outlet for upward air discharge when placing orders (not applicable to outdoor units).
Fan + Filter
Delivery
Fan + Filter + Coil heat exchanger in extract air. The droplet collector is an accessory.
The size 70/80 GOLD SD units are always supplied as one unit if they each consist of a fan or fan + filter. If it consists of fan + filter + coil heat exchanger, it is supplied as two units. The GOLD SD 100/120 units are supplied as separate units for fan + filter + coil heat exchanger.
Fan + Filter + Coil heat exchanger in supply air
Units in the other sizes are always supplied as one unit.
GOLD Length SD mm size
The longest section when sectionalizing mm
Width Height mm mm
Weight kg
Duct connection mm
480-518
1000x400
Airflow m3/s Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
0.20
1.65
1.80
1.80
Power connection
Fan + Filter + Coil heat exchanger 14
2615
988
14004)
20
2615
988
1400
906
498-536
1000x400
0.30
2.10
2.80
2.25
3x400V, 10A
25
2720
1093
16004)
1126
626-678
1200x500
0.30
2.50
2.80
2.80
3x400V, 10A
30
2720
1093
16004)
1126
646-698
1200x500
0.50
3.19
4.00
3.47
3x400V, 10A
35
2720
1093
19904)
1226
793-861
1400x600
0.50
3.90
4.00
4.00
3x400V, 10A
40
2720
1093
19904)
1226
818-886
1400x600
0.75
4.001)/4.602)
5.001)/6.002)
4.92
3x400V, 101)/162)A
50
2687
1050
23184)
1420
1093-1155
1600x800
0.60
5.00
5.60
5.60
3x400V, 101)/162)A
60
2687
1050
2318
1420
1133-1195
1600x800
1.00
6.50
8.00
6.99
3x400V, 161)/252)A
70
3452
1327
2637
1420
1563-1639
1800x1000
1.00
7.30
8.00
7.79
3x400V, 161)/252)A
80
3452
1327
4)
2637
1420
1613-1689
1800x1000
1.50
8.00
12.00
7.86
3x400V, 251)/402)A
100
3396
1144
33404)
1720
2187-2367
2400x12003)
1.50
11.00
12.00
11.48
3x400V, 251)/402)A
120
3396
1144
3340
1720
2290-2501
2400x1200
2.50
11.70
18.00
12.69
3x400V, 401)/632)A
4)
4) 4)
4)
906
3)
3x400V, 10A
1) Capacity variant. 2) Capacity variant. 3) The dimensions of the duct connection on the units with a fan outlet for upward air discharge are 2500 x 800 mm. 4) Coil Heat Exchanger width + 200 mm
17
Sizing
GOLD LP, sizes 05, 08 Installation/duct connection options
Right-hand version
A: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by making a simple adjustment in the control equipment.
Installation Thanks to its low installation height, the GOLD LP can be installed in false ceiling voids, horizontally in an attic space or in other confined spaces. In order to save floor space, the GOLD LP can also be mounted by a wall (a floor stand is available as an accessory) as an alternative to a conventional unit arrangement. If the unit is mounted on a wall, the electric equipment cubicle must always be located upwards.
1)
Left-hand version
GOLD LP size
Length mm
Width1 1) mm
Width 2 mm
Height mm
Weight kg
Duct connection mm
05
2172
507
560
1171
247
08
2370
582
635
1329
301
Airflow m3/s SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
454x400
0.08
0.41
0.53
0.50
1x230V, 10A
533x475
0.08
0.62
0.74
0.74
3x400V, 10A
Refers to the width with the slide rails for the inspection doors removed.
Installation Examples
In a closet In suspended ceilings
Visible on the ceiling
18
Power connection
Min
In a corridor
Technical Description
General Points - COMPACT The COMPACT units are a complete air handling units with directdriven supply air and extract air fans, supply air and extract air filters, and rotary heat exchanger. The exterior colour of the visible sheet metal surfaces is white, (NCS S0502-G). The COMPACT has built-in control equipment that can be operated from the hand-held micro terminal with plain-text display. The electrical and control system is completely integrated into the air handling unit. The microprocessor-based equipment controls and regulates temperatures, airflows and other functions. A large number of functions, including communication, are built into the system and are simple to activate. If supplementary functional sections such as dampers and air coolers are required, they must be installed in the ductwork.
Application The COMPACT Unit and COMPACT Top units are designed for comfort ventilation and can be used in small premises such as offices, schools, day nurseries, public premises, shops, residential buildings, etc.The space available in smaller buildings is usually restricted. The COMPACT Unit and COMPACT Top make a very compact installation possible. The COMPACT Unit AHUs have duct connection spigots on their end panels, the traditional way, whereas the COMPACT Top units have them at the top.
COMPACT Unit
The COMPACT Air and COMPACT Heat units are designed for comfort ventilation and can be used in classrooms, day nurseries, conference halls, smaller offices, workrooms, shops, restaurants and similar public premises. The COMPACT Air and COMPACT Heat can be installed directly in the room to be ventilated. COMPACT Heat operates in normal applications like COMPACT Air but it can also be used for heating the room with BOOSTER function. The COMPACT units should be installed indoors. The COMPACT units are designed and tested for ambient temperatures of from -25°C to +40°C, and air stream temperatures of from -40°C to +40°C.
COMPACT Top
Certification Swegon AB has a certified Quality Assurance System that conforms to ISO 9001 Standard and a certified Environmental Management System to ISO 14001. The COMPACT air handling system Unit & Top are also certificated by Eurovent.
N° 09.05.426. Range: COMPACT
www.eurovent-certification.com www.certiflash.com
COMPACT Air
COMPACT Heat
19
Complements and accessories
Duct accessories, COMPACT Duct accessories are available for a complete installation, e.g. the following: • Damper • Electric or hot water air heater • Air cooler for water or direct expansion • Sound attenuator
Damper
Air heater and air cooler
Electric air heater
Air handling unit accessories, COMPACT Accessories are available for the various air handling models, e.g. the following: • Stand (Unit) • Door fastener (Unit) • Extract air connection (Air/Heat)
Louvre damper
• Cover plate between air handling unit and roof (Air/Heat) • Louvre damper (Air, included as standard in the Heat model)
Support stand
Extract air connection piece
Hoods, COMPACT • Outdoor air hood (Unit/Top) • Exhaust air hood (Unit/Top) • Dual-purpose hood (Unit/Top) • Exterior wall hood
Outdoor air hood
Exhaust air hood
Dual-purpose hood
Exterior wall hood
COMPACT control components If necessary, the built-in control equipment can be supplemented with components e.g. the following: • Air quality sensor • Presence detector • Room sensor
20
Air quality sensor
Presence detector
Sizing
Overview – Airflows, COMPACT SFPV ≤ 2.0 at 200 Pa
Min.
Max.
Max. Ecodesign
COMPACT Unit
m3/s
m3/h
02
0.08
03
0.08
COMPACT Top
m3/s
m3/h
02
0.08
290
0.2
720
0.23
830
03
0.08
290
0.23
830
0.36
1300
COMPACT Air
m3/s
m3/h
m3/s
290
0.2
720
0.23
830
290
0.25
900
0.36
1300
m3/s
Max. m3/h
Min.
Min.
SFPV ≤ 2.0 at 200 Pa m3/s m3/h
Max./SFPV
m3/s
m3/h
m3/s
m3/h
02
0.08
290
0.23/1.1
830/1.1
03
0.08
290
0.33/1.8
1190/1.8
COMPACT Heat
Min.
Max./SFPV
m3/s
m3/h
m3/s
m3/h
02
0.08
290
0.23/1.3
830/1.3
03
0.08
290
0.305/2.0
1100/2.0
m3/h
Max. Ecodesign m3/s 0.23 0.36
m3/h 830 1300
Max. Ecodesign m3/s 0.23 0.36
m3/h 830 1300
All the sizing data specified in this brochure are meant for use as an overview. Exact sizing can be carried out in the web-based ProUnit air handling unit selection software.
m3/s m3/h 0.23 830 0.36 1300 Max. Ecodesign m3/s m3/h 0.23 830 0.36 1300
Contact your nearest Swegon representative for data calculations or use the program yourself at www.swegon.com.
Sound level ≤ 30 dB(A) at airflow m3/s m3/h 0.231)
8301)
0.25
9001)
1)
Sound level ≤ 30 dB(A) at airflow m3/s m3/h 0.231)2)
8301)2)
0.231)2)
8301)2)
1) The sound pressure level with consideration given to a room effect of -12 dB. 2) Does not apply to operation in the BOOSTER mode.
Arrows for airflows in this brochure Outdoor air
Supply air
Extract air
Exhaust air
Dimensions specified in this brochure Width
Width
Height (including junction hood)
Height (including base beams)
Length Length Width
Width
Height (including base beams, air recirculation section and louvre damper)
Height (including base beams)
Length
Length
21
Sizing
COMPACT Unit, sizes 02, 03 Duct connection options A: The air handling unit is supplied in the right-hand version. The unit can be changed to the left-hand version at the building site by making a simple adjustment in the control equipment. B: The air handling unit can be installed upended.
Base frame/Base
Right-hand version
If the air handling unit is installed horizontally, it must be mounted on a stand (accessory) or some other form of base support, so that its inspection doors can be opened.
Left-hand version COMPACT Unit size
Length mm
Width mm
Height mm
Weight kg
Duct connection mm
02
1214
788
872
160
03
1214
788
872
160
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Ø 250
0.08
0.2
0.23
0.23
1x230V, 10A
Ø 250
0.08
0.25
0.36
0.36
1x230V, 10A
COMPACT Top, sizes 02, 03 Duct connection options A: The air handling unit is produced in one variant in which all the components are arranged at their given physical locations inside the unit. All the duct connections are arranged from the top of the air handling unit.
Base frame/Base The unit is equipped with base beams.
COMPACT Top size
Length mm
Width mm
Height mm
Weight kg
Duct connection mm
02
1103
788
1302
200
03
1103
788
1302
200
22
Airflow m3/s
Power connection
Min
SFPv ≤ 2.0 at 200 Pa
Max
Max Ecodesign
Ø 250
0.08
0.2
0.23
0.23
1x230V, 10A
Ø 250
0.08
0.23
0.36
0.36
1x230V, 10A
Sizing
COMPACT Air, sizes 02, 03 Duct connection options A: The air handling unit is produced in one variant in which all the components are arranged at their given physical locations inside the unit. All the duct connections are arranged from the top of the air handling unit.
Installation The air diffuser section can be separated from the main unit section for transport within the building site. The unit should be installed in the room to be ventilated and its electric plug should be connected to an earthed mains electric socket. The ducts for outdoor air and exhaust air should be connected to the top of the unit and should be arranged to lead out through the wall.
COMPACT Length Width Height Weight Duct Air mm mm mm kg connection size mm
Airflow m3/s Min
Max/SFPv
Available pressure for Sound Power outdoor air/exhaust air level connection Max at max. airflow ≤ 30 dB(A) Ecodesign Pa at m3/s
02
1102
788
2114
331
Ø 250
0.08
0.23/1.1
0.23
20
0.231)
1x230V, 10A
03
1102
788
2114
331
Ø 250
0.08
0.33/1.8
0.36
20
0.25
1x230V, 10A
1)
1) The sound pressure level with consideration given to a room effect of -12 dB.
COMPACT Heat, sizes 02, 03 Duct connection options A: The air handling unit is produced in one variant in which all the components are arranged at their given physical locations inside the unit. All the duct connections are arranged from the top of the air handling unit.
Installation The air diffuser section can be separated from the main unit section for transport within the building site. The unit should be installed in the room to be ventilated and should be connected to the mains power supply via a type Perilex electric plug to an appropriate power outlet. The ducts for outdoor air and exhaust air should be connected to the top of the unit and should be arranged to lead out through the wall.
COMPACT Length Width Height Weight Heat mm mm mm kg size
Duct connection mm
Airflow m3/s Min Max/SFPv
Available pressure for Sound Power outdoor air/exhaust air level connection Max at max. airflow ≤ 30 dB(A) Ecodesign Pa at m3/s
02
1102
788
2414
345
Ø 250
0.08
0.23/1.3
0.23
20
0.231)2)
3x400V, 16A
03
1102
788
2414
345
Ø 250
0.08
0.305/2.0
0.36
20
0.23
3x400V, 16A
1) 2)
1) The sound pressure level with consideration given to a room effect of -12 dB. 2) Does not apply to operation in the BOOSTER mode.
23
EN-GOLD & COMPACT overview 2016-01-25