Transcript
GPC14H
2- to 5-Ton Packaged Air Conditioner
Up to 14 SEER
Cooling Capacity: 24,000 - 57,500 BTU/H Contents
Nomenclature......................................... 2 Product Specifications............................ 3 Expanded Cooling Data.......................... 5 Airflow Data.......................................... 18 Heater Kit Specifications ..................... 20 Dimensions........................................... 22 Wiring Diagram..................................... 23 Accessories........................................... 24
Standard Features • Energy-efficient compressor • EEM blower motor • Quiet horizontal discharge • Copper tube / aluminum fin condenser coil • Totally enclosed, permanently lubricated condenser fan motor • Fully charged system • 5 kW to 20 kW electric heat kit available as a field-installed option • AHRI Certified; ETL Listed
Cabinet Features • Heavy-gauge galvanized-steel cabinet with attractive Architectural Gray powder-paint finish • Fully insulated blower compartment with convenient access panels • Louvered condenser coil protection • One footprint; three heights
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.
SS-GPC14H
www.goodmanmfg.com
9/14 Supersedes 11/13
Product Specifications
Nomenclature G 1
C 3
14 4,5
36 6,7
M 8
4 9
1 10
A 11
* 12
Brand G Goodman® brand
Engineering Minor Revision
Product Category P Packaged Unit Type H Heat Pump C Air CondiJoner
Engineering Major Revision
Efficiency 13 13 SEER 14 14 SEER Nominal Capacity 24 2 Tons 30 2½ tons 36 3 Tons
2
P 2
Voltage Designator 1 208-‐230/1/60 3 208-‐230/3/60 Refrigerant 4 R-‐410A
15 15 SEER 16 16 SEER
ConfiguraDon H Horizontal M MulJ-‐posiJon
42 3½ Tons 48 4 Tons 60 5 Tons
www.goodmanmfg.com
SS-GPC14H
Product Specifications
Specifications GPC14 24H41C*
GPC14 24H41D*
GPC14 24H41E*
GPC14 30H41C*
GPC14 30H41D*
GPC14 30H41E*
23,600 17,700 14.0 / 12.0 76 5732583
23,600 17,700 14.0 / 12.0 76 6892353
23,600 17,700 14.0 / 12.0 76 7428120
28,400 21,600 14.0 / 12.0 76 5677886
28,400 21,600 14.0 / 12.0 76 6892355
28,400 21,600 14.0 / 12.0 76 7428122
EEM 10 x 8 875 800 1.5 5 ½ - 1050
EEM 10 x 8 875 800 1.5 5 ½ - 1050
EEM 10 x 8 875 800 1.5 5 ½ - 1050
EEM 10 x 8 1,050 950 1.86 5 ½ - 1050
EEM 10 x 8 1,050 950 1.86 5 ½ - 1050
EEM 10 x 8 1,050 950 1.86 5 ½ - 1050
4.66 3/ 16 0.057 20 x 20 x 1 X ¾" 60
4.66 3/ 16 0.057 20 x 20 x 1 X ¾" 60
5.25 3/ 14 0.055 20 x 20 x 1 X ¾" 51
5.25 3/ 16 0.062 20 x 25 x 1 X ¾" 61
5.25 3/ 16 0.062 20 x 25 x 1 X ¾" 61
5.25 3/ 14 0.063 20 x 25 x 1 X ¾" 46
Condenser Fan / Coil Horsepower - RPM RLA/LRA Fan Diameter/ # Fan Blades Face Area (ft²) Rows Deep/ Fins per Inch
1/6 - 815 1.1 / 1.7 22 / 2 12.3 1 / 26
1/6 - 815 1.1 / 1.7 22 / 2 12.3 1 / 26
1/6 - 815 1.1 / 1.7 22 / 2 9.3 1 / 27
1/6 - 815 1.1 / 1.7 22 / 2 12.3 1 / 26
1/6 - 815 1.1 / 1.7 22 / 2 12.3 1 / 26
1/6 - 815 1.1 / 1.7 22 / 2 9.3 1 / 27
Compressor Quantity / Type Stage Compressor RLA/LRA
1 / Rotary Single 7.7/37
1 / Rotary Single 7.7/37
1 / Rotary Single 7.7/37
1 / Scroll Single 12.8 / 64
1 / Scroll Single 12.8 / 64
1 / Scroll Single 14.1/ 64
Electrical Data Voltage-Phase (60 Hz) Indoor Blower FLA Outdoor Fan RLA Total Unit Amps Min. Circuit Ampacity¹ Max. Overcurrent Protection (amps)²
208/230-1 1.5 1.1 10.3 12.2 15
208/230-1 3.8 1.1 12.6 15 20
208/230-1 3.8 1.1 12.6 15 20
208/230-1 1.86 1.1 15.76 19 30
208/230-1 3.8 1.1 17.7 21 30
208/230-1 3.8 1.1 19 23 35
305 310
305 310
300 305
310 315
310 315
305 310
Models Cooling Capacity Cooling Capacity (BTU/h) Sensible BTU/h SEER / EER Decibels AHRI Numbers Evaporator Motor Type Wheel (D x W) Cooling CFM Fan-Only CFM RLA No. of Speeds Horsepower - RPM Evaporator Coil Face Area (ft²) Rows Deep/ Fins per Inch Indoor Orifice Size Filter Size (") All-aluminum coil Drain Size (NPT) Refrigerant Charge (oz.)
Ship Weight (lbs) Operating Weight (lbs)
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.
SS-GPC14H
www.goodmanmfg.com
3
Product Specifications
Specifications (cont.) GPC14 36H41C*
GPC14 36H41D*
GPC14 42H41C*
GPC14 42H41D*
GPC14 42H41E*
GPC14 48H41C*
35,600 27,100 14.0 / 12.0 78 5677887
35,600 27,100 14.0 / 12.0 78 6892357
40,000 30,400 14.0 / 12.0 78 5677888
40,000 30,400 14.0 / 12.0 78 6892358
40,000 30,400 14.0 / 12.0 78 7428124
46,000 35,300 14.0 / 12.0 80 5677889
EEM 10 x 8 1,200 1,100 1.86 5 ½ - 1050
EEM 10 x 8 1,200 1,100 1.86 5 ½ - 1050
EEM 10 x 8 1,200 1,200 2.9 5 ½ - 1050
EEM 10 x 8 1,200 1,200 2.9 5 ½ - 1050
EEM 10 x 8 1,300 1,200 2.9 5 ½ - 1050
EEM 10 x 8 1,600 1,400 2.9 5 ¾ - 1050
5.25 3/ 14 0.068 25 x 25 x 1 X ¾" 65
5.25 3/ 14 0.068 25 x 25 x 1 X ¾" 65
6.2 4/ 14 0.072 (2) 20 x 20 x 1 X ¾" 94
6.20 4/ 14 0.072 (2) 20 x 20 x 1 X ¾" 94
6.20 4/ 14 0.076 (2) 20 x 20 x 1 X ¾" 70
6.2 4/ 14 0.078 (2) 20 x 20 x 1 X ¾" 90
Condenser Fan / Coil Horsepower - RPM RLA/LRA Fan Diameter/ # Fan Blades Face Area (ft²) Rows Deep/ Fins per Inch
¼ - 830 1.5 / 3.0 22 / 3 12.3 1 / 26
¼ - 830 1.5 / 3.0 22 / 3 12.3 1 / 26
¼ - 1075 1.4 / 2.9 22 / 4 16 1 / 28
¼ - 1075 1.4 / 2.9 22 / 4 16 1 / 28
¼ - 1075 1.4 / 2.9 22 / 4 12.3 1 / 27
¼ - 1075 1.4 / 2.9 22 / 4 19.5 1 / 28
Compressor Quantity / Type Stage Compressor RLA/LRA
1 / Scroll Single 16.7 / 79
1 / Scroll Single 16.7 / 79
1 / Scroll Single 17.9 / 112
1 / Scroll Single 17.9 / 112
1 / Scroll Single 17.9 / 112
1 / Scroll Single 19.9 / 109
208/230-1 1.86 1.5 20.06 24.2 40
208/230-1 3.8 1.5 22 26 40
208/230-1 2.9 1.4 22.2 26.6 40
208/230-1 3.8 1.4 23.1 28 45
208/230-1 3.8 1.4 23.1 28 45
208/230-1 2.9 1.4 24.2 29.1 45
315 320
315 320
360 365
360 365
350 355
370 375
Models Cooling Capacity Cooling Capacity (BTU/h) Sensible BTU/h SEER / EER Decibels AHRI Numbers Evaporator Motor Type Wheel (D x W) Cooling CFM Fan-Only CFM RLA No. of Speeds Horsepower - RPM Evaporator Coil Face Area (ft²) Rows Deep/ Fins per Inch Indoor Orifice Size Filter Size (") All-aluminum coil Drain Size (NPT) Refrigerant Charge (oz.)
Electrical Data Voltage-Phase (60 Hz) Indoor Blower FLA Outdoor Fan RLA Total Unit Amps Min. Circuit Ampacity¹ Max. Overcurrent Protection (amps)² Ship Weight (lbs) Operating Weight (lbs)
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.
4
www.goodmanmfg.com
SS-GPC14H
Product Specifications
Specifications (cont.) GPC14 48H41D*
GPC14 48H41E*
GPC14 60H41C*
GPC14 60H41D*
GPC14 60H41E*
46,000 35,300 14.0 / 12.0 80 6892361
46,000 35,300 14.0 / 12.0 80 7428126
57,500 40,800 14.0 / 12.0 80 5677890
57,500 40,800 14.0 / 12.0 80 6892362
57,500 40,800 14.0 / 11.5 80 7428128
EEM 10 x 8 1,600 1,400 2.9 5 ¾ - 1050
EEM 10 x 8 1,600 1,400 2.9 5 ¾ - 1050
EEM 11 x 8 1,600 1,700 2.9 5 ¾ - 1050
EEM 11 x 8 1,600 1,700 2.9 5 ¾ - 1050
EEM 11 x 8 1,600 1,700 2.9 5 ¾ - 1050
6.20 4/ 14 0.078 (2) 20 x 20 x 1 X ¾" 90
6.20 4/ 14 0.076 (2) 20 x 20 x 1 X ¾" 85
7 4/ 14 0.086 (2) 20 x 25 x 1 X ¾" 110
7.00 4/ 14 0.086 (2) 20 x 25 x 1 X ¾" 110
7.00 4/ 14 0.086 (2) 20 x 25 x 1 X ¾" 103
¼ - 1075 1.4 / 2.9 22 / 4 19.5 1 / 28
¼ - 1075 1.4 / 2.9 22 / 4 16 1 / 27
¼ - 1075 1.4 / 2.9 22 / 4 17 2 /28
¼ - 1075 1.4 / 2.9 22 / 4 17 2 /28
¼ - 1075 1.4 / 2.9 22 / 4 15 2 /27
Compressor Quantity / Type Stage Compressor RLA/LRA
1 / Scroll Single 19.9 / 109
1 / Scroll Single 19.9 / 109
1 / Scroll Single 26.4 / 134
1 / Scroll Single 26.4 / 134
1 / Scroll Single 26.4 / 134
Electrical Data Voltage-Phase (60 Hz) Indoor Blower FLA Outdoor Fan RLA Total Unit Amps Min. Circuit Ampacity¹ Max. Overcurrent Protection (amps)²
208/230-1 5.4 1.4 26.7 32 50
208/230-1 5.4 1.4 26.7 32 50
208/230-1 2.9 1.4 30.7 37.3 60
208/230-1 5.4 1.4 33.2 40 60
208/230-1 5.4 1.4 33.2 40 60
370 375
365 370
375 380
375 380
370 375
Models Cooling Capacity Cooling Capacity (BTU/h) Sensible BTU/h SEER / EER Decibels AHRI Numbers Evaporator Motor Type Wheel (D x W) Cooling CFM Fan-Only CFM RLA No. of Speeds Horsepower - RPM Evaporator Coil Face Area (ft²) Rows Deep/ Fins per Inch Indoor Orifice Size Filter Size (") All-aluminum coil Drain Size (NPT) Refrigerant Charge (oz.) Condenser Fan / Coil Horsepower - RPM RLA/LRA Fan Diameter/ # Fan Blades Face Area (ft²) Rows Deep/ Fins per Inch
Ship Weight (lbs) Operating Weight (lbs)
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted. Note: Always check the S&R plate for electrical data on the unit being installed.
SS-GPC14H
www.goodmanmfg.com
5
6
www.goodmanmfg.com
24.5 0.84 21 1.48 6.6 225 111 23.8 0.80 21 1.47 6.6 223 110 22.0 0.77 22 1.43 6.4 216 107
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
720
820
920
59 24.1 0.74 18 1.47 6.6 223 110 23.4 0.71 19 1.45 6.5 220 109 21.6 0.68 19 1.42 6.4 214 106
Airflow MBh S/T ∆T kW 920 Amps HI PR LO PR MBh S/T ∆T kW 820 Amps HI PR LO PR MBh S/T ∆T 720 kW Amps HI PR LO PR
25.2 0.75 19 1.51 6.8 242 119 24.5 0.72 20 1.50 6.7 240 117 22.6 0.69 20 1.46 6.6 232 114
63 25.0 0.62 15 1.50 6.7 240 117 24.3 0.59 16 1.49 6.7 237 116 22.4 0.57 16 1.45 6.5 230 113 27.3 0.57 16 1.56 7.0 255 129 26.5 0.54 16 1.55 6.9 253 128 24.5 0.52 16 1.51 6.7 245 124
67 27.4 0.43 12 1.55 6.9 253 128 26.6 0.41 12 1.53 6.9 250 127 24.5 0.39 12 1.50 6.7 243 123 29.3 0.37 11 1.61 7.2 266 138 28.5 0.35 11 1.60 7.1 264 136 26.3 0.34 11 1.56 7.0 256 132
71 23.9 0.87 21 1.60 7.1 252 118 23.2 0.83 22 1.58 7.0 250 117 21.5 0.80 22 1.54 6.9 242 113
59 23.5 0.77 18 1.58 7.0 250 117 22.9 0.73 19 1.57 7.0 247 115 21.1 0.71 19 1.53 6.8 240 112 24.7 0.78 19 1.63 7.2 271 125 23.9 0.74 20 1.62 7.2 269 124 22.1 0.72 20 1.58 7.0 261 120
63 24.4 0.64 16 1.62 7.2 269 124 23.7 0.61 16 1.61 7.1 266 123 21.9 0.59 16 1.56 7.0 258 119
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
75
70
IDB
65
26.7 0.59 16 1.69 7.5 287 137 25.9 0.56 16 1.67 7.4 284 135 23.9 0.54 17 1.63 7.2 275 131
67 26.7 0.44 12 1.67 7.4 284 135 26.0 0.42 12 1.66 7.3 281 134 24.0 0.41 12 1.62 7.2 273 130 28.6 0.38 11 1.74 7.7 299 146 27.8 0.36 11 1.73 7.6 296 144 25.7 0.35 11 1.69 7.5 287 140
71 23.4 0.89 21 1.70 7.6 287 122 22.7 0.85 22 1.69 7.6 284 121 20.9 0.82 22 1.64 7.4 276 118
59 23.0 0.79 18 1.69 7.6 284 121 22.3 0.75 19 1.67 7.5 281 120 20.6 0.72 19 1.63 7.3 273 116 24.1 0.80 19 1.74 7.8 309 130 23.4 0.76 20 1.73 7.7 306 129 21.6 0.74 20 1.68 7.5 297 125
26.0 0.61 16 1.80 8.0 326 142 25.3 0.58 16 1.78 8.0 323 141 23.3 0.56 17 1.74 7.8 313 136
22.8 0.92 21 1.79 8.1 327 129 22.1 0.88 22 1.78 8.0 324 127 20.4 0.85 22 1.73 7.8 314 123
23.5 0.83 19 1.84 8.3 352 137 22.8 0.79 20 1.82 8.2 348 135 21.0 0.76 20 1.77 8.0 338 131
25.4 0.62 16 1.90 8.5 371 149 24.7 0.60 16 1.88 8.4 368 148 22.8 0.57 17 1.83 8.2 357 143
27.3 0.40 11 1.96 8.8 387 159 26.5 0.38 11 1.95 8.7 383 157 24.4 0.37 12 1.90 8.5 372 153
71 21.7 0.96 21 1.87 8.6 368 135 21.0 0.91 22 1.86 8.5 364 133 19.4 0.88 22 1.81 8.3 353 129
59 21.3 0.84 18 1.86 8.5 364 133 20.7 0.80 19 1.84 8.4 360 132 19.1 0.78 19 1.79 8.2 350 128 22.3 0.86 19 1.92 8.7 396 143 21.7 0.82 20 1.90 8.7 392 142 20.0 0.79 20 1.85 8.5 380 138
63 22.1 0.70 16 1.90 8.7 392 142 21.4 0.67 16 1.88 8.6 388 140 19.8 0.65 16 1.83 8.4 376 136 24.1 0.65 16 1.98 9.0 418 156 23.4 0.62 16 1.96 8.9 414 155 21.6 0.60 16 1.91 8.7 401 150
67 24.2 0.49 12 1.96 8.9 414 155 23.5 0.47 12 1.95 8.9 409 153 21.7 0.45 12 1.90 8.6 397 149
105
25.9 0.42 11 2.05 9.3 436 167 25.2 0.40 11 2.03 9.2 431 165 23.2 0.38 11 1.98 9.0 418 160
71 20.1 0.97 19 1.94 9.0 406 139 19.5 0.92 20 1.92 8.9 402 138 18.0 0.89 20 1.87 8.7 390 134
59 19.7 0.85 17 1.92 8.9 402 138 19.2 0.81 17 1.91 8.9 398 137 17.7 0.78 18 1.86 8.6 386 132 20.7 0.86 18 1.99 9.2 437 148 20.1 0.82 19 1.97 9.1 433 147 18.5 0.79 19 1.92 8.9 420 142
63 20.5 0.71 15 1.97 9.1 433 147 19.9 0.68 15 1.95 9.1 428 145 18.3 0.65 15 1.90 8.8 416 141 22.4 0.65 15 2.05 9.5 462 162 21.7 0.62 15 2.04 9.4 457 160 20.0 0.60 15 1.98 9.2 443 155
67 22.4 0.49 11 2.04 9.4 457 160 21.8 0.47 11 2.02 9.3 452 159 20.1 0.45 12 1.97 9.1 439 154
115
24.0 0.42 10 2.13 9.8 481 172 23.3 0.40 10 2.11 9.7 477 171 21.5 0.39 11 2.05 9.5 462 166
71 -
Shaded area reflects ACCA (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
28.0 0.39 11 1.86 8.3 340 151 27.1 0.37 11 1.85 8.2 337 150 25.1 0.36 11 1.80 8.0 327 145
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 23.8 26.1 22.4 23.2 25.5 0.66 0.46 0.81 0.68 0.47 16 12 18 16 12 1.73 1.78 1.78 1.82 1.88 7.7 8.0 8.0 8.2 8.4 306 323 323 348 368 129 141 127 135 148 23.1 25.3 21.8 22.6 24.7 0.63 0.43 0.77 0.65 0.45 16 12 19 16 12 1.71 1.77 1.76 1.80 1.87 7.7 7.9 8.0 8.1 8.4 303 320 320 345 364 128 139 126 134 146 21.3 23.4 20.1 20.8 22.8 0.60 0.42 0.75 0.62 0.43 16 13 19 17 13 1.67 1.72 1.72 1.76 1.82 7.5 7.7 7.8 7.9 8.2 294 310 311 334 353 124 135 122 130 142
Product Specifications
Expanded Cooling Data — GPC1424H41**
SS-GPC14H
SS-GPC14H
www.goodmanmfg.com
25.4 0.97 25 1.50 6.7 229 114 24.6 0.92 25 1.49 6.7 227 113 22.7 0.89 26 1.45 6.5 220 109
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
720
820
920
59 25.0 0.92 23 1.49 6.7 227 113 24.2 0.88 24 1.48 6.6 225 111 22.4 0.85 24 1.44 6.5 218 108
Airflow MBh S/T ∆T kW 920 Amps HI PR LO PR MBh S/T ∆T kW 820 Amps HI PR LO PR MBh S/T ∆T 720 kW Amps HI PR LO PR
25.9 0.93 24 1.54 6.9 247 121 25.1 0.89 25 1.52 6.8 244 120 23.2 0.86 25 1.49 6.7 237 116
63 25.5 0.87 22 1.52 6.8 244 120 24.8 0.83 23 1.51 6.8 242 119 22.8 0.80 23 1.47 6.6 235 115 27.1 0.84 23 1.59 7.1 261 132 26.3 0.80 24 1.57 7.0 258 131 24.3 0.77 24 1.53 6.9 250 127
67 27.2 0.70 19 1.57 7.0 258 131 26.4 0.67 20 1.56 7.0 256 129 24.4 0.65 20 1.52 6.8 248 126 28.9 0.68 20 1.64 7.3 272 141 28.1 0.65 21 1.63 7.2 269 139 25.9 0.63 21 1.59 7.1 261 135
71 29.1 0.53 15 1.63 7.2 269 139 28.3 0.50 16 1.61 7.2 267 138 26.1 0.48 16 1.57 7.0 259 134 24.8 1.00 25 1.62 7.2 257 120 24.1 0.96 26 1.61 7.2 255 119 22.2 0.92 26 1.57 7.0 247 115
59 24.4 0.96 23 1.61 7.2 255 119 23.7 0.91 24 1.60 7.1 252 118 21.8 0.88 25 1.56 6.9 245 114 25.3 0.97 24 1.66 7.4 277 128 24.5 0.92 25 1.65 7.3 274 127 22.6 0.89 26 1.60 7.1 266 123
63 24.9 0.90 22 1.65 7.3 274 127 24.2 0.86 23 1.63 7.2 272 125 22.3 0.82 24 1.59 7.1 263 122
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
85
80
IDB
65
26.5 0.87 23 1.72 7.6 292 140 25.7 0.83 24 1.70 7.5 290 138 23.7 0.80 24 1.66 7.3 281 134
67 26.6 0.73 19 1.70 7.5 290 138 25.8 0.70 20 1.69 7.5 287 137 23.8 0.67 20 1.64 7.3 278 133 28.2 0.71 20 1.77 7.8 305 149 27.4 0.68 21 1.76 7.8 302 147 25.3 0.65 21 1.71 7.6 293 143
71 28.4 0.55 16 1.76 7.8 302 147 27.6 0.52 16 1.74 7.7 299 146 25.5 0.50 16 1.70 7.5 290 141 24.2 1.00 24 1.73 7.8 293 125 23.5 0.98 26 1.72 7.7 290 124 21.7 0.95 26 1.67 7.5 281 120
59 23.8 1.00 24 1.72 7.7 290 124 23.1 0.94 24 1.70 7.6 287 122 21.3 0.90 25 1.66 7.5 278 119 24.7 0.99 24 1.77 7.9 315 133 24.0 0.95 25 1.76 7.9 312 131 22.1 0.91 26 1.71 7.7 303 128
25.8 0.90 23 1.83 8.2 333 145 25.1 0.85 24 1.81 8.1 329 144 23.2 0.82 24 1.77 7.9 319 139
23.6 1.00 24 1.83 8.2 333 131 22.9 1.00 26 1.81 8.2 330 130 21.2 0.98 26 1.76 8.0 320 126
24.1 1.00 24 1.87 8.4 359 140 23.4 0.98 26 1.85 8.3 355 138 21.6 0.94 26 1.80 8.1 345 134
25.2 0.92 23 1.93 8.7 379 152 24.5 0.88 24 1.91 8.6 375 151 22.6 0.85 25 1.86 8.4 364 146
26.9 0.75 20 2.00 9.0 395 162 26.1 0.72 21 1.98 8.9 391 161 24.1 0.69 21 1.93 8.7 380 156
71 27.1 0.58 16 1.98 8.9 391 161 26.3 0.55 16 1.96 8.8 387 159 24.3 0.53 16 1.91 8.6 376 154 22.4 1.00 22 1.91 8.7 375 137 21.8 1.00 24 1.89 8.6 371 136 20.1 1.00 26 1.84 8.4 360 132
59 22.0 1.00 22 1.89 8.6 371 136 21.4 1.00 24 1.87 8.6 368 135 19.8 0.97 24 1.82 8.3 357 131 22.9 1.00 23 1.95 8.9 404 146 22.2 1.00 25 1.93 8.8 400 145 20.5 0.98 26 1.88 8.6 388 140
63 22.5 1.00 23 1.93 8.8 400 145 21.9 0.94 23 1.92 8.7 396 143 20.2 0.91 23 1.87 8.5 384 139 24.0 0.96 23 2.02 9.2 426 160 23.3 0.91 24 2.00 9.1 422 158 21.5 0.88 24 1.95 8.9 409 153
67 24.1 0.80 19 2.00 9.1 422 158 23.4 0.76 20 1.98 9.0 418 156 21.6 0.74 20 1.93 8.8 405 152
105
25.6 0.78 20 2.09 9.5 445 170 24.8 0.74 21 2.07 9.4 440 168 22.9 0.72 21 2.01 9.2 427 163
71 25.7 0.60 15 2.07 9.4 440 168 25.0 0.57 16 2.05 9.3 436 167 23.1 0.55 16 2.00 9.1 423 162 20.8 1.00 21 1.97 9.2 414 142 20.2 1.00 23 1.96 9.1 410 141 18.6 1.00 24 1.91 8.9 398 137
59 20.4 1.00 20 1.96 9.1 410 141 19.8 1.00 22 1.94 9.0 406 139 18.3 0.97 23 1.89 8.8 394 135 21.2 1.00 21 2.02 9.4 446 151 20.6 1.00 23 2.00 9.3 442 150 19.0 0.99 24 1.95 9.1 428 145
63 20.9 1.00 21 2.00 9.3 442 150 20.3 0.95 22 1.99 9.2 437 148 18.7 0.91 22 1.93 9.0 424 144 22.2 0.97 21 2.09 9.7 471 165 21.5 0.92 22 2.07 9.6 466 163 19.9 0.89 23 2.02 9.3 452 159
67 22.3 0.81 18 2.07 9.6 466 163 21.6 0.77 19 2.05 9.5 462 162 20.0 0.74 19 2.00 9.3 448 157
115
23.7 0.78 19 2.16 10.0 491 176 23.0 0.75 19 2.15 9.9 486 174 21.2 0.72 20 2.09 9.7 472 169
71 23.8 0.60 14 2.15 9.9 486 174 23.1 0.58 15 2.13 9.8 482 172 21.4 0.56 15 2.07 9.6 467 167
Shaded area reflects AHRI (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
27.6 0.73 20 1.89 8.4 347 154 26.8 0.69 21 1.88 8.4 344 153 24.7 0.67 21 1.83 8.2 333 148
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 24.3 26.0 27.8 23.2 23.7 25.3 0.92 0.75 0.56 1.00 0.95 0.77 22 19 16 23 23 20 1.76 1.81 1.88 1.81 1.85 1.91 7.9 8.1 8.4 8.2 8.3 8.6 312 329 344 330 355 375 131 144 153 130 138 151 23.6 25.2 27.0 22.5 23.0 24.6 0.88 0.71 0.53 0.97 0.91 0.74 23 20 16 24 23 20 1.74 1.80 1.86 1.79 1.84 1.90 7.8 8.0 8.3 8.1 8.3 8.5 309 326 340 327 352 371 130 142 151 129 137 149 21.8 23.3 24.9 20.8 21.3 22.7 0.85 0.69 0.51 0.93 0.87 0.71 24 20 16 25 24 21 1.70 1.75 1.81 1.75 1.79 1.85 7.6 7.8 8.1 7.9 8.1 8.3 300 316 330 317 341 360 126 138 147 125 133 145
Product Specifications
Expanded Cooling Data — GPC1424H41** (cont.)
7
8
www.goodmanmfg.com
28.3 0.84 19 1.76 8.0 237 109 27.5 0.80 20 1.75 7.9 234 108 26.1 0.77 21 1.72 7.8 230 106
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
900
1020
1145
59 27.8 0.74 17 1.75 7.9 234 108 27.0 0.71 17 1.73 7.9 232 107 25.7 0.68 18 1.70 7.7 227 105
Airflow MBh S/T ∆T kW 1145 Amps HI PR LO PR MBh S/T ∆T kW 1020 Amps HI PR LO PR MBh S/T ∆T 900 kW Amps HI PR LO PR
29.1 0.75 18 1.80 8.1 255 116 28.3 0.72 18 1.79 8.1 252 115 26.9 0.69 19 1.76 8.0 247 112
63 28.8 0.62 14 1.78 8.1 252 115 28.0 0.59 15 1.77 8.0 250 114 26.6 0.57 15 1.74 7.9 245 111 31.5 0.57 14 1.86 8.4 269 127 30.6 0.54 15 1.84 8.3 266 125 29.1 0.52 15 1.81 8.2 261 123
67 31.6 0.43 11 1.84 8.3 266 125 30.7 0.41 11 1.83 8.2 264 124 29.1 0.39 12 1.80 8.1 258 122 33.9 0.37 10 1.92 8.6 281 135 32.9 0.35 10 1.90 8.6 278 133 31.2 0.34 11 1.87 8.4 272 131
71 27.6 0.87 19 1.90 8.5 266 115 26.8 0.83 20 1.89 8.5 263 114 25.5 0.80 21 1.85 8.3 258 112
59 27.2 0.77 17 1.89 8.5 263 114 26.4 0.73 17 1.87 8.4 260 113 25.1 0.70 18 1.84 8.3 255 111 28.5 0.78 18 1.94 8.7 286 122 27.6 0.74 19 1.93 8.6 283 121 26.3 0.71 19 1.90 8.5 277 119
63 28.2 0.64 15 1.93 8.6 283 121 27.4 0.61 15 1.91 8.6 280 120 26.0 0.59 16 1.88 8.4 275 118
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
75
70
IDB
65
30.8 0.59 15 2.01 9.0 302 134 29.9 0.56 15 1.99 8.9 299 132 28.4 0.54 16 1.96 8.7 293 130
67 30.9 0.44 11 1.99 8.9 299 132 30.0 0.42 11 1.97 8.8 296 131 28.5 0.41 12 1.94 8.7 290 128 33.1 0.38 10 2.08 9.2 315 142 32.1 0.36 10 2.06 9.2 312 141 30.5 0.35 11 2.02 9.0 305 138
71 27.0 0.90 19 2.03 9.2 302 120 26.2 0.85 20 2.01 9.1 299 118 24.9 0.82 21 1.97 8.9 293 116
59 26.5 0.79 17 2.01 9.1 299 118 25.8 0.75 17 1.99 9.0 296 117 24.5 0.72 18 1.96 8.9 290 115 27.8 0.80 18 2.07 9.4 325 127 27.0 0.76 19 2.05 9.3 322 126 25.6 0.73 19 2.02 9.1 315 124
30.1 0.61 15 2.14 9.6 343 139 29.2 0.58 15 2.12 9.5 340 138 27.7 0.55 16 2.09 9.4 333 135
26.3 0.92 20 2.14 9.7 344 126 25.6 0.88 20 2.12 9.6 341 124 24.3 0.84 21 2.08 9.5 334 122
27.1 0.83 18 2.18 9.9 370 134 26.3 0.79 19 2.17 9.8 367 132 25.0 0.76 19 2.13 9.7 359 130
29.3 0.63 15 2.26 10.2 391 146 28.5 0.60 15 2.24 10.1 387 145 27.1 0.57 16 2.20 10.0 379 142
31.5 0.40 10 2.34 10.5 408 155 30.6 0.38 11 2.32 10.5 404 154 29.0 0.37 11 2.28 10.3 396 151
71 25.0 0.96 19 2.23 10.2 387 132 24.3 0.91 20 2.21 10.2 383 130 23.1 0.88 21 2.17 10.0 376 128
59 24.6 0.84 17 2.21 10.2 383 130 23.9 0.80 17 2.19 10.1 379 129 22.7 0.77 18 2.15 9.9 372 127 25.8 0.86 18 2.28 10.5 417 140 25.0 0.82 18 2.26 10.4 412 139 23.8 0.78 19 2.22 10.2 404 136
63 25.5 0.70 14 2.26 10.4 412 139 24.7 0.67 15 2.24 10.3 408 137 23.5 0.64 15 2.20 10.1 400 135 27.9 0.65 15 2.36 10.8 440 153 27.1 0.62 15 2.34 10.7 435 151 25.7 0.59 16 2.30 10.5 427 148
67 27.9 0.49 11 2.34 10.7 435 151 27.1 0.47 11 2.32 10.6 431 150 25.8 0.45 12 2.28 10.4 422 147
105
29.9 0.42 10 2.44 11.1 459 163 29.0 0.40 10 2.42 11.0 454 161 27.6 0.38 11 2.38 10.9 445 158
71 23.2 0.97 18 2.31 10.8 428 136 22.5 0.92 19 2.29 10.7 423 135 21.4 0.88 19 2.25 10.5 415 132
59 22.8 0.85 16 2.29 10.7 423 135 22.1 0.81 16 2.27 10.6 419 134 21.0 0.78 17 2.23 10.4 411 131 23.9 0.87 17 2.36 11.0 460 145 23.2 0.83 17 2.34 10.9 456 144 22.0 0.79 18 2.30 10.7 447 141
63 23.6 0.71 13 2.34 10.9 456 143 22.9 0.68 14 2.32 10.8 451 142 21.8 0.65 14 2.28 10.7 442 139 25.8 0.65 14 2.44 11.3 486 158 25.1 0.62 14 2.42 11.3 481 157 23.8 0.60 15 2.38 11.1 472 154
67 25.9 0.49 10 2.42 11.3 481 157 25.1 0.47 11 2.40 11.2 476 155 23.9 0.45 11 2.36 11.0 467 152
115
27.7 0.42 9 2.53 11.7 507 169 26.9 0.40 10 2.51 11.6 502 167 25.6 0.38 10 2.46 11.4 492 164
71 -
Shaded area reflects ACCA (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
32.3 0.39 10 2.21 9.9 358 148 31.3 0.37 11 2.20 9.9 354 147 29.8 0.36 11 2.16 9.7 347 144
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 27.5 30.1 25.9 26.8 29.4 0.66 0.46 0.81 0.68 0.47 15 11 17 15 11 2.05 2.12 2.12 2.16 2.24 9.3 9.5 9.6 9.8 10.1 322 340 341 367 387 126 138 124 132 145 26.7 29.3 25.1 26.1 28.5 0.63 0.43 0.78 0.65 0.45 15 11 18 15 12 2.04 2.10 2.10 2.15 2.22 9.2 9.5 9.5 9.8 10.0 319 336 337 363 383 125 136 123 131 143 25.4 27.8 23.9 24.7 27.1 0.60 0.42 0.74 0.62 0.43 16 12 18 16 12 2.00 2.07 2.06 2.11 2.18 9.1 9.3 9.4 9.6 9.9 312 330 330 356 376 122 133 121 128 140
Product Specifications
Expanded Cooling Data — GPC1430H41**
SS-GPC14H
SS-GPC14H
www.goodmanmfg.com
29.3 0.97 23 1.79 8.1 241 111 28.5 0.92 24 1.78 8.0 239 110 27.0 0.89 24 1.75 7.9 234 108
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
900
1020
1145
59 28.8 0.92 21 1.78 8.0 239 110 28.0 0.88 22 1.76 8.0 237 109 26.6 0.84 23 1.73 7.9 232 107
Airflow MBh S/T ∆T kW 1145 Amps HI PR LO PR MBh S/T ∆T kW 1020 Amps HI PR LO PR MBh S/T ∆T 900 kW Amps HI PR LO PR
29.9 0.93 22 1.83 8.3 260 118 29.0 0.89 23 1.81 8.2 257 117 27.6 0.85 24 1.78 8.1 252 115
63 29.4 0.87 20 1.81 8.2 257 117 28.6 0.83 21 1.80 8.1 255 116 27.1 0.79 22 1.77 8.0 250 114 31.3 0.84 21 1.89 8.5 274 129 30.4 0.80 22 1.87 8.4 272 128 28.9 0.77 23 1.84 8.3 266 125
67 31.4 0.71 18 1.87 8.4 272 128 30.5 0.67 19 1.86 8.4 269 127 29.0 0.64 19 1.83 8.2 264 124 33.4 0.68 18 1.95 8.8 286 138 32.4 0.65 19 1.94 8.7 283 136 30.8 0.63 20 1.90 8.6 278 133
71 33.6 0.53 14 1.94 8.7 283 136 32.6 0.50 15 1.92 8.6 281 135 31.0 0.48 15 1.89 8.5 275 132 28.6 1.00 23 1.93 8.7 271 117 27.8 0.96 24 1.92 8.6 268 116 26.4 0.92 25 1.89 8.5 263 114
59 28.1 0.96 22 1.92 8.6 268 116 27.3 0.91 22 1.90 8.5 266 115 25.9 0.87 23 1.87 8.4 260 113 29.2 0.97 23 1.98 8.8 292 125 28.3 0.92 24 1.96 8.8 289 124 26.9 0.89 24 1.93 8.6 283 121
63 28.7 0.90 21 1.96 8.8 289 124 27.9 0.86 22 1.94 8.7 286 123 26.5 0.82 22 1.91 8.6 280 120
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
85
80
IDB
65
30.6 0.87 21 2.04 9.1 308 136 29.7 0.83 22 2.03 9.0 305 135 28.2 0.80 23 1.99 8.9 299 132
67 30.7 0.73 18 2.03 9.0 305 135 29.8 0.70 19 2.01 9.0 302 134 28.3 0.67 19 1.97 8.8 296 131 32.6 0.71 19 2.11 9.4 321 145 31.7 0.68 19 2.09 9.3 318 144 30.1 0.65 20 2.06 9.2 312 141
71 32.8 0.55 14 2.09 9.3 318 144 31.9 0.52 15 2.08 9.2 315 142 30.3 0.50 15 2.04 9.1 309 140 27.9 1.00 22 2.06 9.3 308 122 27.1 0.98 24 2.04 9.2 305 121 25.8 0.94 25 2.01 9.1 299 118
59 27.5 1.00 22 2.04 9.2 305 121 26.7 0.94 23 2.03 9.2 302 120 25.3 0.90 23 1.99 9.0 296 117 28.5 0.99 23 2.11 9.5 332 130 27.7 0.95 24 2.09 9.4 328 129 26.3 0.91 24 2.05 9.3 322 126
29.8 0.90 21 2.18 9.8 350 142 29.0 0.86 22 2.16 9.7 347 140 27.5 0.82 23 2.12 9.5 340 138
27.3 1.00 22 2.17 9.9 351 128 26.5 1.00 24 2.15 9.8 348 127 25.1 0.97 25 2.12 9.6 341 124
27.8 1.00 22 2.22 10.1 378 136 27.0 0.98 24 2.20 10.0 374 135 25.6 0.94 25 2.16 9.8 367 132
29.1 0.93 22 2.30 10.4 399 149 28.3 0.88 22 2.28 10.3 395 147 26.8 0.85 23 2.24 10.1 387 145
31.1 0.75 19 2.38 10.7 416 159 30.1 0.72 19 2.36 10.6 412 157 28.6 0.69 20 2.32 10.5 404 154
71 31.3 0.58 15 2.36 10.6 412 157 30.4 0.55 15 2.34 10.5 408 155 28.8 0.53 16 2.30 10.4 400 152 25.9 1.00 21 2.27 10.4 395 134 25.1 1.00 23 2.25 10.3 391 133 23.9 1.00 24 2.21 10.2 383 130
59 25.5 1.00 20 2.25 10.3 391 133 24.7 1.00 22 2.23 10.2 387 132 23.5 0.96 23 2.19 10.1 379 129 26.4 1.00 21 2.32 10.6 425 143 25.6 1.00 23 2.30 10.6 421 142 24.4 0.97 24 2.26 10.4 412 139
63 26.0 1.00 21 2.30 10.6 421 142 25.3 0.94 21 2.28 10.5 417 140 24.0 0.90 22 2.24 10.3 408 137 27.7 0.96 21 2.40 11.0 449 156 26.8 0.92 22 2.38 10.9 444 155 25.5 0.88 23 2.34 10.7 435 151
67 27.8 0.80 18 2.38 10.9 444 155 27.0 0.77 19 2.36 10.8 440 153 25.6 0.73 19 2.32 10.6 431 150
105
29.5 0.78 18 2.48 11.3 468 166 28.6 0.74 19 2.46 11.2 463 165 27.2 0.71 20 2.42 11.0 454 161
71 29.7 0.60 14 2.46 11.2 463 165 28.8 0.57 15 2.44 11.1 459 163 27.4 0.55 15 2.40 11.0 450 160 24.0 1.00 19 2.35 11.0 436 139 23.3 1.00 21 2.33 10.9 432 138 22.1 1.00 23 2.29 10.7 423 135
59 23.6 1.00 19 2.33 10.9 432 138 22.9 1.00 21 2.31 10.8 428 136 21.7 0.97 22 2.27 10.6 419 134 24.5 1.00 20 2.40 11.2 470 148 23.7 1.00 21 2.38 11.1 465 146 22.6 0.98 23 2.34 10.9 456 143
63 24.1 1.00 19 2.38 11.1 465 146 23.4 0.95 20 2.36 11.0 460 145 22.2 0.91 21 2.32 10.8 451 142 25.6 0.97 20 2.49 11.5 496 161 24.9 0.92 21 2.46 11.4 491 160 23.6 0.88 21 2.42 11.3 481 157
67 25.7 0.81 17 2.46 11.4 491 160 25.0 0.77 17 2.44 11.3 486 158 23.7 0.74 18 2.40 11.2 476 155
115
27.3 0.79 17 2.57 11.9 517 172 26.5 0.75 18 2.55 11.8 512 170 25.2 0.72 18 2.51 11.6 502 167
71 27.5 0.61 13 2.55 11.8 512 170 26.7 0.58 14 2.53 11.7 507 169 25.4 0.55 14 2.48 11.5 497 165
Shaded area reflects AHRI (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
31.8 0.73 19 2.25 10.1 365 151 30.9 0.69 19 2.23 10.0 362 150 29.4 0.66 20 2.19 9.9 354 147
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 28.1 30.0 32.1 26.8 27.4 29.3 0.92 0.75 0.56 1.00 0.95 0.77 21 18 14 22 21 18 2.09 2.16 2.23 2.15 2.20 2.28 9.4 9.7 10.0 9.8 10.0 10.3 328 347 362 348 374 395 129 140 150 127 135 147 27.2 29.1 31.1 26.0 26.6 28.4 0.88 0.71 0.53 0.97 0.91 0.74 22 19 15 23 22 19 2.07 2.14 2.21 2.14 2.18 2.26 9.4 9.6 9.9 9.7 9.9 10.2 325 343 358 344 370 391 127 139 148 126 134 146 25.9 27.7 29.6 24.7 25.3 27.0 0.84 0.68 0.51 0.93 0.87 0.71 22 19 15 23 22 19 2.04 2.10 2.18 2.10 2.15 2.22 9.2 9.5 9.8 9.5 9.8 10.0 319 336 351 337 363 383 125 136 145 123 131 143
Product Specifications
Expanded Cooling Data — GPC1430H41** (cont.)
9
10
www.goodmanmfg.com
36.4 0.84 21 2.39 10.3 238 111 35.4 0.81 22 2.37 10.3 236 110 32.7 0.78 22 2.32 10.0 229 107
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1052
1201
1350
59 35.8 0.74 18 2.37 10.3 236 110 34.8 0.71 19 2.35 10.2 234 109 32.1 0.68 19 2.30 9.9 227 106
Airflow MBh S/T ∆T kW 1350 Amps HI PR LO PR MBh S/T ∆T kW 1201 Amps HI PR LO PR MBh S/T ∆T 1052 kW Amps HI PR LO PR
37.5 0.76 19 2.44 10.5 257 119 36.4 0.72 20 2.42 10.5 254 117 33.6 0.69 20 2.36 10.2 246 114
63 37.1 0.62 16 2.42 10.5 254 117 36.1 0.59 16 2.40 10.4 251 116 33.3 0.57 17 2.35 10.1 244 113 40.6 0.57 16 2.52 10.8 271 129 39.4 0.55 16 2.50 10.8 268 128 36.4 0.53 17 2.44 10.5 260 124
67 40.7 0.43 12 2.50 10.8 268 128 39.5 0.41 12 2.48 10.7 266 127 36.5 0.40 13 2.42 10.4 258 123 43.6 0.37 11 2.60 11.2 283 138 42.3 0.35 11 2.58 11.1 280 137 39.1 0.34 12 2.52 10.8 271 132
71 35.6 0.88 21 2.58 11.1 268 118 34.6 0.84 22 2.56 11.0 265 117 31.9 0.81 22 2.49 10.7 257 113
59 35.0 0.77 18 2.56 11.0 265 117 34.0 0.73 19 2.54 10.9 262 115 31.4 0.71 19 2.47 10.6 254 112 36.7 0.78 20 2.63 11.3 288 125 35.6 0.75 20 2.61 11.2 285 124 32.8 0.72 21 2.55 10.9 276 120
63 36.3 0.64 16 2.61 11.2 285 124 35.2 0.61 17 2.59 11.1 282 123 32.5 0.59 17 2.53 10.8 274 119
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
75
70
IDB
65
39.7 0.59 16 2.72 11.6 304 137 38.5 0.57 17 2.70 11.5 301 135 35.6 0.55 17 2.63 11.2 292 131
67 39.8 0.45 12 2.70 11.5 301 135 38.6 0.43 13 2.67 11.4 298 134 35.6 0.41 13 2.61 11.2 289 130 42.6 0.38 11 2.81 12.0 317 146 41.3 0.36 12 2.79 11.9 314 144 38.2 0.35 12 2.72 11.6 304 140
71 34.7 0.90 21 2.74 11.9 304 122 33.7 0.86 22 2.72 11.8 301 121 31.1 0.83 22 2.65 11.5 292 118
59 34.2 0.79 18 2.72 11.8 301 121 33.2 0.75 19 2.70 11.7 298 120 30.6 0.73 19 2.63 11.4 289 116 35.8 0.80 20 2.80 12.1 327 130 34.7 0.77 20 2.78 12.0 324 129 32.1 0.74 21 2.71 11.8 314 125
38.7 0.61 16 2.89 12.5 346 142 37.6 0.58 17 2.87 12.4 342 141 34.7 0.56 17 2.80 12.1 332 137
33.9 0.93 21 2.89 12.6 347 129 32.9 0.88 22 2.86 12.5 343 127 30.4 0.85 23 2.79 12.2 333 123
34.9 0.83 20 2.95 12.9 373 137 33.9 0.79 21 2.93 12.8 369 135 31.3 0.76 21 2.85 12.5 358 131
37.8 0.63 16 3.05 13.3 394 149 36.7 0.60 17 3.02 13.2 390 148 33.9 0.58 17 2.95 12.8 378 143
40.6 0.40 11 3.15 13.7 411 159 39.4 0.38 12 3.12 13.6 407 157 36.3 0.37 12 3.05 13.3 394 153
71 32.2 0.96 21 3.01 13.3 390 135 31.3 0.92 22 2.98 13.2 386 133 28.9 0.88 22 2.91 12.9 374 129
59 31.7 0.85 18 2.98 13.2 386 133 30.7 0.81 19 2.96 13.1 382 132 28.4 0.78 19 2.88 12.8 371 128 33.2 0.86 19 3.08 13.6 420 143 32.2 0.82 20 3.05 13.5 415 142 29.7 0.79 21 2.97 13.2 403 138
63 32.8 0.71 16 3.05 13.5 415 142 31.9 0.67 16 3.02 13.4 411 141 29.4 0.65 17 2.95 13.1 399 136 35.9 0.65 16 3.18 14.0 443 157 34.8 0.62 17 3.15 13.9 439 155 32.2 0.60 17 3.07 13.6 425 150
67 36.0 0.49 12 3.15 13.9 439 155 34.9 0.47 12 3.13 13.8 434 153 32.2 0.45 13 3.05 13.5 421 149
105
38.5 0.42 11 3.29 14.5 462 167 37.4 0.40 11 3.26 14.4 457 165 34.5 0.39 12 3.18 14.0 444 160
71 29.8 0.97 20 3.12 14.0 431 139 29.0 0.93 21 3.09 13.9 426 138 26.7 0.89 21 3.01 13.6 414 134
59 29.3 0.85 17 3.09 13.9 426 138 28.5 0.81 18 3.06 13.8 422 137 26.3 0.78 18 2.98 13.5 409 133 30.7 0.87 18 3.19 14.4 464 148 29.8 0.83 19 3.16 14.2 459 147 27.5 0.80 19 3.08 13.9 445 142
63 30.4 0.71 15 3.16 14.2 459 147 29.5 0.68 15 3.13 14.1 454 145 27.2 0.66 16 3.05 13.8 441 141 33.2 0.66 15 3.29 14.8 489 162 32.3 0.63 15 3.27 14.7 485 160 29.8 0.60 16 3.18 14.3 470 155
67 33.3 0.49 11 3.26 14.7 485 160 32.3 0.47 12 3.24 14.5 480 159 29.9 0.45 12 3.15 14.2 465 154
115
35.7 0.42 10 3.41 15.3 510 172 34.6 0.40 11 3.38 15.2 505 171 32.0 0.39 11 3.29 14.8 490 166
71 -
Shaded area reflects ACCA (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
41.6 0.39 11 2.99 12.9 361 151 40.4 0.37 12 2.97 12.8 357 150 37.2 0.36 12 2.89 12.5 346 145
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 35.4 38.8 33.3 34.6 37.9 0.66 0.46 0.82 0.68 0.47 16 12 19 16 12 2.78 2.87 2.86 2.93 3.02 12.0 12.4 12.5 12.8 13.2 324 342 343 369 390 129 141 127 135 148 34.4 37.7 32.4 33.5 36.8 0.63 0.44 0.78 0.65 0.45 17 13 19 17 13 2.76 2.85 2.84 2.90 3.00 11.9 12.3 12.4 12.7 13.1 321 339 340 365 386 128 139 126 134 146 31.7 34.8 29.9 31.0 33.9 0.61 0.42 0.75 0.63 0.43 17 13 20 17 13 2.69 2.77 2.77 2.83 2.92 11.7 12.0 12.1 12.4 12.7 311 329 329 355 374 124 135 122 130 142
Product Specifications
Expanded Cooling Data — GPC1436H41**
SS-GPC14H
SS-GPC14H
www.goodmanmfg.com
37.7 0.97 25 2.43 10.5 243 114 36.6 0.93 26 2.41 10.4 241 113 33.8 0.89 26 2.35 10.2 234 109
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1052
1201
1350
59 37.1 0.93 23 2.41 10.4 241 113 36.0 0.88 24 2.39 10.3 238 111 33.2 0.85 25 2.33 10.1 231 108
Airflow MBh S/T ∆T kW 1350 Amps HI PR LO PR MBh S/T ∆T kW 1201 Amps HI PR LO PR MBh S/T ∆T 1052 kW Amps HI PR LO PR
38.5 0.94 25 2.48 10.7 262 121 37.4 0.89 26 2.46 10.6 259 120 34.5 0.86 26 2.40 10.4 251 116
63 37.9 0.87 22 2.46 10.6 259 120 36.8 0.83 23 2.44 10.6 257 119 34.0 0.80 24 2.38 10.3 249 115 40.3 0.85 23 2.56 11.0 276 132 39.1 0.81 24 2.54 10.9 274 131 36.1 0.78 25 2.48 10.7 265 127
67 40.5 0.71 20 2.54 10.9 274 131 39.3 0.67 20 2.52 10.8 271 129 36.3 0.65 21 2.46 10.6 263 126 43.0 0.69 20 2.65 11.4 288 141 41.7 0.65 21 2.62 11.3 285 139 38.5 0.63 21 2.56 11.0 277 135
71 43.3 0.53 16 2.62 11.3 285 139 42.0 0.50 16 2.60 11.2 283 138 38.8 0.49 16 2.54 10.9 274 134 36.9 1.00 25 2.62 11.2 273 120 35.8 0.96 26 2.60 11.1 270 119 33.0 0.93 27 2.53 10.9 262 115
59 36.2 0.96 24 2.60 11.1 270 119 35.2 0.92 25 2.58 11.1 268 118 32.5 0.88 25 2.51 10.8 260 114 37.6 0.97 25 2.68 11.5 294 128 36.5 0.93 26 2.65 11.4 291 127 33.7 0.89 26 2.59 11.1 282 123
63 37.0 0.90 23 2.65 11.4 291 127 35.9 0.86 24 2.63 11.3 288 125 33.2 0.83 24 2.57 11.0 279 122
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
85
80
IDB
65
39.4 0.88 24 2.76 11.8 310 140 38.2 0.84 24 2.74 11.7 307 138 35.3 0.81 25 2.67 11.4 298 134
67 39.6 0.73 20 2.74 11.7 307 138 38.4 0.70 21 2.72 11.6 304 137 35.4 0.67 21 2.65 11.3 295 133 42.0 0.71 20 2.86 12.2 323 149 40.8 0.68 21 2.83 12.1 320 147 37.6 0.65 21 2.76 11.8 311 143
71 42.3 0.55 16 2.83 12.1 320 147 41.1 0.52 16 2.81 12.0 317 146 37.9 0.50 17 2.74 11.7 308 141 36.0 1.00 25 2.79 12.1 310 125 34.9 0.98 26 2.76 12.0 307 124 32.2 0.95 27 2.70 11.7 298 120
59 35.4 1.00 24 2.76 12.0 307 124 34.3 0.94 25 2.74 11.9 304 122 31.7 0.91 25 2.67 11.6 295 119 36.7 1.00 25 2.85 12.3 334 133 35.6 0.95 26 2.83 12.2 331 132 32.9 0.92 26 2.75 11.9 321 128
38.4 0.90 24 2.94 12.7 353 145 37.3 0.86 24 2.92 12.6 349 144 34.4 0.83 25 2.84 12.3 339 139
35.1 1.00 24 2.93 12.8 354 131 34.1 1.00 26 2.91 12.7 350 130 31.5 0.98 27 2.84 12.4 340 126
35.8 1.00 24 3.00 13.1 380 140 34.7 0.98 26 2.98 13.0 377 138 32.1 0.95 26 2.90 12.7 365 134
37.5 0.93 24 3.10 13.5 402 152 36.4 0.89 25 3.07 13.4 398 151 33.6 0.85 25 3.00 13.0 386 146
40.0 0.75 21 3.21 13.9 419 162 38.8 0.72 21 3.18 13.8 415 161 35.8 0.69 22 3.10 13.5 402 156
71 40.3 0.58 16 3.18 13.8 415 161 39.1 0.55 17 3.15 13.7 411 159 36.1 0.53 17 3.07 13.4 398 154 33.4 1.00 23 3.06 13.6 398 137 32.4 1.00 25 3.03 13.4 394 136 29.9 1.00 26 2.96 13.1 382 132
59 32.8 1.00 22 3.03 13.4 394 136 31.8 1.00 24 3.01 13.3 390 135 29.4 0.97 25 2.93 13.0 378 131 34.0 1.00 23 3.13 13.9 428 146 33.0 1.00 25 3.10 13.7 424 145 30.5 0.98 26 3.02 13.4 411 140
63 33.5 1.00 23 3.10 13.7 424 145 32.5 0.94 23 3.08 13.6 420 143 30.0 0.91 24 3.00 13.3 407 139 35.6 0.96 23 3.23 14.3 452 160 34.6 0.92 24 3.21 14.2 447 158 31.9 0.89 25 3.12 13.8 434 153
67 35.8 0.81 20 3.21 14.2 447 158 34.7 0.77 20 3.18 14.0 443 157 32.1 0.74 21 3.10 13.7 430 152
105
38.0 0.78 20 3.34 14.8 471 170 36.9 0.75 21 3.32 14.6 467 168 34.0 0.72 21 3.23 14.3 453 163
71 38.3 0.60 16 3.32 14.6 467 168 37.1 0.57 16 3.29 14.5 462 167 34.3 0.55 17 3.20 14.2 448 162 30.9 1.00 21 3.17 14.3 439 142 30.0 1.00 23 3.14 14.2 435 141 27.7 1.00 24 3.06 13.8 422 137
59 30.4 1.00 21 3.14 14.2 435 141 29.5 1.00 23 3.12 14.0 431 139 27.2 0.98 23 3.04 13.7 418 135 31.5 1.00 21 3.24 14.6 473 151 30.6 1.00 23 3.21 14.5 468 150 28.2 0.99 24 3.13 14.1 454 145
63 31.0 1.00 21 3.21 14.5 468 150 30.1 0.95 22 3.19 14.4 464 148 27.8 0.92 22 3.10 14.0 450 144 33.0 0.97 22 3.35 15.0 499 165 32.0 0.93 23 3.32 14.9 494 164 29.6 0.89 23 3.24 14.5 480 159
67 33.1 0.81 18 3.32 14.9 494 164 32.2 0.77 19 3.29 14.8 489 162 29.7 0.75 19 3.21 14.4 475 157
115
35.2 0.79 19 3.47 15.6 521 176 34.2 0.75 20 3.44 15.4 516 174 31.5 0.72 20 3.35 15.0 500 169
71 35.4 0.61 15 3.44 15.4 516 174 34.4 0.58 15 3.41 15.3 511 172 31.8 0.56 15 3.32 14.9 495 167
Shaded area reflects AHRI (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
41.0 0.73 20 3.04 13.1 368 154 39.8 0.70 21 3.02 13.0 364 153 36.7 0.67 22 2.94 12.7 353 148
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 36.1 38.6 41.3 34.5 35.3 37.7 0.92 0.75 0.56 1.00 0.95 0.78 23 20 16 24 23 20 2.83 2.92 3.02 2.91 2.98 3.07 12.2 12.6 13.0 12.7 13.0 13.4 331 349 364 350 377 398 132 144 153 130 138 151 35.1 37.5 40.1 33.5 34.2 36.6 0.88 0.72 0.54 0.97 0.91 0.74 24 21 16 25 24 21 2.80 2.89 2.99 2.89 2.95 3.05 12.1 12.5 12.9 12.6 12.9 13.3 327 346 361 347 373 394 130 142 151 129 137 149 32.4 34.6 37.0 30.9 31.6 33.8 0.85 0.69 0.52 0.93 0.88 0.71 24 21 17 25 24 21 2.73 2.82 2.92 2.81 2.88 2.97 11.9 12.2 12.6 12.3 12.6 12.9 318 335 350 336 362 382 126 138 147 125 133 145
Product Specifications
Expanded Cooling Data — GPC1436H41** (cont.)
11
12
www.goodmanmfg.com
40.5 0.82 21 2.70 11.5 244 110 39.3 0.78 22 2.68 11.4 241 109 36.3 0.75 23 2.62 11.1 234 106
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1116
1274
1432
59 39.8 0.72 18 2.68 11.4 241 109 38.6 0.69 19 2.66 11.3 239 108 35.7 0.66 20 2.60 11.0 232 105
Airflow MBh S/T ∆T kW 1432 Amps HI PR LO PR MBh S/T ∆T kW 1274 Amps HI PR LO PR MBh S/T ∆T 1116 kW Amps HI PR LO PR
41.7 0.73 20 2.76 11.8 262 117 40.5 0.70 20 2.74 11.7 260 116 37.3 0.68 21 2.67 11.4 252 112
63 41.3 0.60 16 2.74 11.7 260 116 40.1 0.58 17 2.72 11.6 257 115 37.0 0.55 17 2.65 11.3 249 111 45.1 0.56 16 2.85 12.2 277 128 43.8 0.53 17 2.82 12.0 274 127 40.4 0.51 17 2.76 11.7 266 123
67 45.2 0.42 12 2.82 12.0 274 127 43.9 0.40 13 2.80 11.9 272 125 40.5 0.38 13 2.73 11.6 263 122 48.4 0.36 11 2.94 12.6 289 136 47.0 0.34 12 2.91 12.5 286 135 43.4 0.33 12 2.84 12.1 277 131
71 39.5 0.85 22 2.91 12.4 274 116 38.4 0.81 22 2.89 12.3 271 115 35.4 0.78 23 2.82 12.0 263 112
59 38.9 0.75 19 2.89 12.3 271 115 37.7 0.71 19 2.86 12.2 268 114 34.8 0.69 20 2.79 11.9 260 111 40.7 0.76 20 2.97 12.7 294 124 39.5 0.73 21 2.95 12.6 291 123 36.5 0.70 21 2.88 12.3 283 119
63 40.3 0.63 16 2.95 12.6 291 122 39.1 0.60 17 2.92 12.5 289 121 36.1 0.57 17 2.85 12.2 280 118
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
75
70
IDB
65
44.1 0.58 16 3.07 13.1 311 135 42.8 0.55 17 3.04 13.0 308 134 39.5 0.53 17 2.97 12.6 299 130
67 44.1 0.43 12 3.04 13.0 308 134 42.9 0.41 13 3.02 12.9 305 132 39.6 0.40 13 2.94 12.5 296 128 47.3 0.37 11 3.17 13.6 324 144 45.9 0.35 12 3.14 13.4 321 142 42.4 0.34 12 3.07 13.1 311 138
71 38.6 0.87 22 3.09 13.4 311 121 37.5 0.83 22 3.07 13.3 308 120 34.6 0.80 23 2.99 13.0 299 116
59 38.0 0.77 19 3.07 13.3 308 120 36.8 0.73 19 3.04 13.2 305 118 34.0 0.71 20 2.97 12.8 296 115 39.7 0.78 20 3.16 13.7 335 129 38.6 0.74 21 3.14 13.6 331 127 35.6 0.72 21 3.06 13.3 322 124
43.0 0.59 16 3.27 14.2 354 140 41.8 0.56 17 3.24 14.0 350 139 38.5 0.54 17 3.16 13.7 340 135
37.7 0.90 22 3.26 14.3 354 127 36.6 0.86 23 3.23 14.2 351 126 33.7 0.83 23 3.15 13.8 340 122
38.8 0.81 20 3.33 14.6 381 135 37.6 0.77 21 3.30 14.5 378 134 34.7 0.74 21 3.22 14.1 366 130
42.0 0.61 16 3.44 15.1 403 147 40.7 0.58 17 3.41 15.0 399 146 37.6 0.56 17 3.32 14.6 387 142
45.0 0.39 11 3.55 15.7 420 157 43.7 0.37 12 3.52 15.5 416 156 40.4 0.36 12 3.44 15.1 403 151
71 35.8 0.93 21 3.39 15.2 399 133 34.7 0.89 22 3.37 15.1 395 132 32.1 0.86 23 3.28 14.7 383 128
59 35.2 0.82 19 3.37 15.1 395 132 34.1 0.78 19 3.34 14.9 391 130 31.5 0.76 20 3.25 14.5 379 127 36.8 0.84 20 3.47 15.5 429 142 35.8 0.80 21 3.44 15.4 425 140 33.0 0.77 21 3.35 15.0 412 136
63 36.5 0.69 16 3.44 15.4 425 140 35.4 0.65 17 3.41 15.3 420 139 32.7 0.63 17 3.33 14.9 408 135 39.9 0.63 16 3.59 16.0 453 155 38.7 0.60 17 3.56 15.9 449 153 35.7 0.58 17 3.47 15.5 435 148
67 39.9 0.48 12 3.56 15.9 448 153 38.8 0.45 13 3.53 15.8 444 151 35.8 0.44 13 3.44 15.3 431 147
105
42.8 0.41 11 3.71 16.6 472 165 41.5 0.39 12 3.68 16.5 468 163 38.3 0.37 12 3.58 16.0 454 158
71 33.1 0.94 20 3.51 16.1 440 138 32.2 0.90 21 3.48 15.9 436 136 29.7 0.87 21 3.40 15.5 423 132
59 32.6 0.83 17 3.48 15.9 436 136 31.6 0.79 18 3.45 15.8 432 135 29.2 0.76 18 3.37 15.3 419 131 34.1 0.84 18 3.59 16.4 474 146 33.1 0.80 19 3.56 16.3 469 145 30.6 0.78 20 3.47 15.9 455 141
63 33.8 0.69 15 3.56 16.3 469 145 32.8 0.66 16 3.53 16.1 465 144 30.3 0.64 16 3.44 15.7 451 139 36.9 0.64 15 3.71 17.0 501 160 35.9 0.61 16 3.68 16.8 496 158 33.1 0.59 16 3.59 16.4 481 154
67 37.0 0.48 11 3.68 16.8 495 158 35.9 0.46 12 3.65 16.7 491 157 33.2 0.44 12 3.56 16.2 476 152
115
39.6 0.41 10 3.84 17.6 522 170 38.5 0.39 11 3.81 17.4 517 169 35.5 0.38 11 3.71 17.0 501 164
71 -
Shaded area reflects ACCA (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
46.2 0.38 11 3.37 14.7 369 150 44.8 0.36 12 3.35 14.6 365 148 41.4 0.35 12 3.26 14.2 354 144
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 39.3 43.1 37.0 38.4 42.0 0.64 0.44 0.79 0.66 0.46 16 12 19 16 12 3.14 3.24 3.23 3.30 3.41 13.6 14.0 14.2 14.5 15.0 331 350 351 377 399 127 139 126 134 146 38.2 41.8 35.9 37.3 40.8 0.61 0.42 0.76 0.63 0.44 17 13 20 17 13 3.11 3.21 3.20 3.27 3.38 13.5 13.9 14.1 14.4 14.8 328 346 347 374 395 126 138 124 132 145 35.2 38.6 33.2 34.4 37.7 0.59 0.41 0.73 0.61 0.42 17 13 20 17 13 3.03 3.13 3.12 3.19 3.30 13.1 13.6 13.7 14.0 14.4 318 336 337 363 383 122 133 121 128 140
Product Specifications
Expanded Cooling Data — GPC1442H41**
SS-GPC14H
SS-GPC14H
www.goodmanmfg.com
41.9 0.94 25 2.75 11.7 249 112 40.7 0.90 26 2.72 11.6 246 111 37.6 0.87 27 2.66 11.3 239 108
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1116
1274
1432
59 41.2 0.90 24 2.72 11.6 246 111 40.0 0.86 25 2.70 11.5 244 110 36.9 0.83 25 2.64 11.2 236 107
Airflow MBh S/T ∆T kW 1432 Amps HI PR LO PR MBh S/T ∆T kW 1274 Amps HI PR LO PR MBh S/T ∆T 1116 kW Amps HI PR LO PR
42.7 0.91 25 2.80 12.0 268 119 41.5 0.87 26 2.78 11.9 265 118 38.3 0.84 26 2.71 11.6 257 115
63 42.1 0.84 23 2.78 11.9 265 118 40.9 0.81 24 2.76 11.8 262 117 37.7 0.78 24 2.69 11.5 255 114 44.7 0.82 24 2.89 12.4 283 130 43.4 0.78 25 2.87 12.3 280 129 40.1 0.76 25 2.80 11.9 271 125
67 45.0 0.69 20 2.87 12.3 280 129 43.7 0.66 21 2.85 12.2 277 128 40.3 0.63 21 2.78 11.8 269 124 47.7 0.67 20 2.99 12.8 295 139 46.3 0.64 21 2.96 12.7 292 138 42.8 0.61 22 2.89 12.4 283 133
71 48.1 0.51 16 2.96 12.7 292 138 46.7 0.49 17 2.94 12.6 289 136 43.1 0.47 17 2.87 12.3 280 132 40.9 0.98 26 2.96 12.6 279 119 39.7 0.93 27 2.93 12.5 276 117 36.7 0.90 27 2.86 12.2 268 114
59 40.2 0.93 24 2.93 12.5 276 117 39.1 0.89 25 2.91 12.4 274 116 36.1 0.86 25 2.84 12.1 265 113 41.7 0.94 25 3.02 12.9 300 126 40.5 0.90 26 3.00 12.8 297 125 37.4 0.87 27 2.92 12.5 288 121
63 41.1 0.88 23 3.00 12.8 297 125 39.9 0.83 24 2.97 12.7 294 124 36.8 0.80 24 2.90 12.4 286 120
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
85
80
IDB
65
43.7 0.85 24 3.12 13.3 317 138 42.4 0.81 25 3.09 13.2 314 136 39.2 0.78 25 3.02 12.9 305 132
67 43.9 0.71 20 3.09 13.2 314 136 42.6 0.68 21 3.07 13.1 311 135 39.4 0.66 21 2.99 12.7 302 131 46.6 0.69 21 3.22 13.8 331 147 45.3 0.66 22 3.20 13.7 327 145 41.8 0.64 22 3.12 13.3 318 141
71 47.0 0.53 16 3.20 13.7 327 145 45.6 0.51 17 3.17 13.6 324 144 42.1 0.49 17 3.09 13.2 315 140 40.0 1.00 26 3.15 13.7 317 123 38.8 0.96 27 3.12 13.5 314 122 35.8 0.92 27 3.04 13.2 305 118
59 39.3 0.96 24 3.12 13.5 314 122 38.1 0.91 25 3.09 13.4 311 121 35.2 0.88 26 3.02 13.1 302 117 40.7 0.97 25 3.21 14.0 342 131 39.6 0.92 26 3.19 13.9 338 130 36.5 0.89 27 3.11 13.5 328 126
42.7 0.87 24 3.32 14.4 361 143 41.4 0.83 25 3.29 14.3 357 142 38.2 0.80 25 3.21 13.9 346 138
39.0 1.00 25 3.31 14.6 361 130 37.9 0.99 27 3.28 14.4 358 128 34.9 0.95 27 3.20 14.1 347 124
39.7 1.00 25 3.39 14.9 389 138 38.6 0.95 27 3.36 14.8 385 136 35.6 0.92 27 3.27 14.4 374 132
41.6 0.90 24 3.50 15.4 411 150 40.4 0.86 25 3.47 15.2 407 149 37.3 0.83 25 3.38 14.8 395 145
44.4 0.73 21 3.62 15.9 428 160 43.1 0.70 22 3.58 15.8 424 159 39.8 0.67 22 3.49 15.4 411 154
71 44.7 0.56 16 3.58 15.8 424 159 43.4 0.54 17 3.55 15.7 420 157 40.1 0.52 17 3.46 15.2 407 152 37.0 1.00 24 3.45 15.5 407 136 36.0 1.00 26 3.42 15.3 403 134 33.2 0.99 27 3.34 14.9 391 130
59 36.4 1.00 23 3.42 15.3 403 134 35.3 0.98 25 3.40 15.2 399 133 32.6 0.94 25 3.31 14.8 387 129 37.8 1.00 24 3.53 15.8 438 144 36.7 0.99 26 3.50 15.7 433 143 33.8 0.95 27 3.41 15.3 420 139
63 37.2 0.96 23 3.50 15.7 433 143 36.1 0.92 24 3.47 15.5 429 142 33.3 0.88 24 3.38 15.1 416 137 39.5 0.94 24 3.65 16.3 462 158 38.4 0.89 25 3.62 16.2 458 156 35.4 0.86 25 3.52 15.8 444 151
67 39.7 0.78 20 3.62 16.2 458 156 38.6 0.75 21 3.59 16.0 453 155 35.6 0.72 21 3.50 15.6 439 150
105
42.2 0.76 21 3.77 16.9 482 168 41.0 0.72 21 3.74 16.8 477 166 37.8 0.70 22 3.64 16.3 463 161
71 42.5 0.58 16 3.74 16.8 477 166 41.2 0.56 17 3.71 16.6 473 165 38.1 0.54 17 3.61 16.2 458 160 34.3 1.00 22 3.57 16.3 449 140 33.3 1.00 24 3.54 16.2 445 139 30.7 1.00 25 3.45 15.8 432 135
59 33.7 1.00 22 3.54 16.2 445 139 32.7 0.99 23 3.51 16.1 440 138 30.2 0.95 24 3.43 15.6 427 134 35.0 1.00 22 3.65 16.7 484 149 34.0 1.00 24 3.62 16.6 479 148 31.3 0.96 25 3.53 16.1 464 143
63 34.5 0.97 21 3.62 16.6 479 148 33.5 0.92 22 3.59 16.4 474 146 30.9 0.89 23 3.50 16.0 460 142 36.6 0.94 22 3.78 17.3 511 163 35.6 0.90 23 3.75 17.1 506 161 32.8 0.87 23 3.65 16.7 490 157
67 36.8 0.79 19 3.75 17.1 506 161 35.7 0.75 19 3.71 17.0 501 160 33.0 0.73 20 3.62 16.5 486 155
115
39.1 0.77 19 3.91 17.9 533 174 37.9 0.73 20 3.87 17.8 527 172 35.0 0.70 20 3.77 17.3 511 167
71 39.4 0.59 15 3.87 17.8 527 172 38.2 0.56 16 3.84 17.6 522 170 35.3 0.54 16 3.74 17.1 506 165
Shaded area reflects AHRI (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
45.5 0.71 21 3.43 14.9 376 153 44.2 0.68 22 3.40 14.8 372 151 40.8 0.65 22 3.32 14.4 361 147
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 40.1 42.9 45.8 38.3 39.2 41.8 0.90 0.73 0.55 1.00 0.93 0.75 23 20 16 25 23 20 3.19 3.29 3.40 3.28 3.36 3.47 13.9 14.3 14.8 14.4 14.8 15.2 338 357 372 358 385 407 130 142 151 128 136 149 39.0 41.6 44.5 37.2 38.0 40.6 0.86 0.70 0.52 0.94 0.88 0.72 24 21 17 25 24 21 3.16 3.27 3.37 3.26 3.33 3.44 13.7 14.2 14.7 14.3 14.6 15.1 335 354 369 354 381 403 129 140 150 127 135 148 36.0 38.4 41.1 34.3 35.1 37.5 0.83 0.67 0.50 0.91 0.85 0.69 24 21 17 26 25 21 3.08 3.18 3.29 3.18 3.25 3.35 13.4 13.8 14.3 13.9 14.3 14.7 325 343 358 344 370 391 125 136 145 123 131 143
Product Specifications
Expanded Cooling Data — GPC1442H41** (cont.)
13
14
www.goodmanmfg.com
46.9 0.85 21 2.42 13.3 235 112 45.5 0.81 22 2.39 13.2 233 111 42.0 0.78 22 2.32 12.8 226 108
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1386
1582
1777
59 46.1 0.75 18 2.39 13.2 232 111 44.8 0.72 19 2.37 13.1 230 110 41.3 0.69 19 2.30 12.7 223 106
Airflow MBh S/T ∆T kW 1777 Amps HI PR LO PR MBh S/T ∆T kW 1582 Amps HI PR LO PR MBh S/T ∆T 1386 kW Amps HI PR LO PR
48.3 0.76 19 2.48 13.5 253 119 46.9 0.73 20 2.46 13.4 250 118 43.3 0.70 20 2.38 13.1 243 114
63 47.8 0.63 15 2.46 13.4 250 118 46.4 0.60 16 2.43 13.3 248 117 42.8 0.58 16 2.36 13.0 240 113 52.3 0.58 16 2.58 13.9 267 130 50.8 0.55 16 2.56 13.8 264 129 46.8 0.53 17 2.48 13.5 256 125
67 52.4 0.43 12 2.55 13.8 264 129 50.9 0.41 12 2.53 13.7 262 127 46.9 0.40 12 2.45 13.4 254 124 56.1 0.37 11 2.68 14.4 278 138 54.5 0.35 11 2.66 14.3 276 137 50.3 0.34 11 2.58 13.9 267 133
71 45.8 0.88 21 2.65 14.2 263 118 44.5 0.84 22 2.63 14.1 261 117 41.1 0.81 22 2.55 13.8 253 114
59 45.1 0.78 18 2.63 14.1 261 117 43.7 0.74 19 2.60 14.0 258 116 40.4 0.72 19 2.52 13.6 251 112 47.2 0.79 19 2.72 14.5 284 126 45.8 0.75 20 2.70 14.4 281 125 42.3 0.73 20 2.62 14.1 272 121
63 46.7 0.65 16 2.70 14.4 281 125 45.3 0.62 16 2.67 14.3 278 123 41.8 0.60 17 2.59 13.9 270 120
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
75
70
IDB
65
51.1 0.60 16 2.83 14.9 299 137 49.6 0.57 16 2.80 14.8 296 136 45.8 0.55 17 2.72 14.5 288 132
67 51.2 0.45 12 2.80 14.8 296 136 49.7 0.43 12 2.78 14.7 293 135 45.8 0.41 13 2.69 14.3 285 131 54.8 0.39 11 2.95 15.5 312 146 53.2 0.37 11 2.92 15.3 309 145 49.1 0.35 12 2.83 14.9 300 141
71 44.7 0.91 21 2.86 15.3 300 123 43.4 0.86 22 2.83 15.2 297 122 40.1 0.83 22 2.75 14.8 288 118
59 44.0 0.80 18 2.83 15.2 297 122 42.7 0.76 19 2.80 15.1 294 120 39.4 0.73 19 2.72 14.7 285 117 46.0 0.81 19 2.94 15.6 322 131 44.7 0.77 20 2.91 15.5 319 129 41.3 0.75 20 2.82 15.1 310 126
49.8 0.61 16 3.05 16.1 341 143 48.4 0.59 16 3.02 16.0 337 141 44.7 0.56 17 2.93 15.6 327 137
43.6 0.94 21 3.04 16.3 341 129 42.4 0.89 22 3.01 16.1 338 128 39.1 0.86 22 2.92 15.7 328 124
44.9 0.84 19 3.13 16.6 367 137 43.6 0.80 20 3.10 16.5 364 136 40.3 0.77 21 3.00 16.1 353 132
48.6 0.63 16 3.25 17.1 388 150 47.2 0.60 17 3.22 17.0 384 149 43.6 0.58 17 3.12 16.6 373 144
52.2 0.41 11 3.38 17.7 405 160 50.7 0.39 11 3.35 17.6 401 158 46.8 0.37 12 3.25 17.1 389 153
71 41.5 0.97 21 3.20 17.2 384 135 40.2 0.93 22 3.17 17.1 380 134 37.1 0.89 22 3.07 16.6 369 130
59 40.8 0.85 18 3.17 17.1 380 134 39.6 0.81 19 3.14 16.9 376 133 36.5 0.79 19 3.04 16.5 365 129 42.7 0.87 19 3.29 17.6 413 144 41.4 0.83 20 3.25 17.5 409 143 38.2 0.80 20 3.16 17.0 397 138
63 42.2 0.71 16 3.25 17.4 409 143 41.0 0.68 16 3.22 17.3 405 141 37.9 0.66 16 3.12 16.9 393 137 46.2 0.66 16 3.42 18.1 436 157 44.9 0.63 16 3.38 18.0 432 156 41.4 0.60 17 3.28 17.5 419 151
67 46.3 0.49 12 3.38 18.0 432 156 44.9 0.47 12 3.35 17.8 428 154 41.5 0.45 13 3.25 17.4 415 149
105
49.6 0.42 11 3.55 18.8 455 167 48.1 0.40 11 3.52 18.6 451 166 44.4 0.39 11 3.41 18.1 437 161
71 38.4 0.98 19 3.34 18.1 424 140 37.3 0.93 20 3.30 18.0 420 139 34.4 0.90 21 3.20 17.5 407 134
59 37.8 0.86 17 3.30 18.0 420 139 36.7 0.82 18 3.27 17.8 416 137 33.8 0.79 18 3.17 17.4 403 133 39.5 0.88 18 3.43 18.6 457 149 38.4 0.84 19 3.39 18.4 452 147 35.4 0.81 19 3.29 17.9 438 143
63 39.1 0.72 15 3.39 18.4 452 147 38.0 0.69 15 3.36 18.2 447 146 35.1 0.66 15 3.26 17.8 434 142 42.8 0.66 15 3.56 19.1 482 163 41.5 0.63 15 3.53 19.0 477 161 38.3 0.61 16 3.42 18.5 463 156
67 42.9 0.50 11 3.52 19.0 477 161 41.6 0.48 12 3.49 18.8 473 159 38.4 0.46 12 3.38 18.3 458 155
115
45.9 0.43 10 3.70 19.8 503 173 44.6 0.41 11 3.67 19.6 498 171 41.2 0.39 11 3.56 19.1 483 166
71 -
Shaded area reflects ACCA (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
53.5 0.39 11 3.18 16.7 355 152 51.9 0.38 11 3.15 16.5 352 151 47.9 0.36 12 3.05 16.1 341 146
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 45.6 49.9 42.9 44.5 48.7 0.67 0.46 0.82 0.69 0.48 16 12 18 16 12 2.91 3.02 3.01 3.09 3.22 15.5 16.0 16.1 16.5 17.0 319 337 338 364 384 129 141 128 136 148 44.3 48.5 41.7 43.2 47.3 0.64 0.44 0.79 0.66 0.45 16 12 19 16 12 2.88 2.99 2.98 3.06 3.19 15.4 15.9 16.0 16.3 16.8 316 334 335 360 380 128 140 127 135 147 40.8 44.8 38.5 39.9 43.7 0.61 0.42 0.76 0.63 0.44 17 13 19 17 13 2.79 2.90 2.89 2.97 3.09 15.0 15.5 15.6 15.9 16.4 307 324 324 349 369 124 136 123 131 143
Product Specifications
Expanded Cooling Data — GPC1448H41**
SS-GPC14H
SS-GPC14H
www.goodmanmfg.com
48.6 0.98 25 2.47 13.5 240 114 47.2 0.94 26 2.44 13.4 237 113 43.5 0.90 26 2.37 13.1 230 110
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1386
1582
1777
59 47.7 0.94 23 2.44 13.4 237 113 46.4 0.89 24 2.42 13.3 235 112 42.8 0.86 24 2.34 12.9 228 109
Airflow MBh S/T ∆T kW 1777 Amps HI PR LO PR MBh S/T ∆T kW 1582 Amps HI PR LO PR MBh S/T ∆T 1386 kW Amps HI PR LO PR
49.5 0.95 24 2.53 13.8 258 122 48.1 0.90 25 2.51 13.7 255 120 44.4 0.87 26 2.43 13.3 248 117
63 48.8 0.88 22 2.51 13.7 255 120 47.4 0.84 23 2.48 13.5 253 119 43.7 0.81 23 2.41 13.2 245 116 51.9 0.85 23 2.63 14.2 272 133 50.3 0.81 24 2.61 14.1 270 131 46.5 0.79 24 2.53 13.7 261 127
67 52.1 0.71 19 2.61 14.1 270 131 50.6 0.68 20 2.58 13.9 267 130 46.7 0.66 20 2.50 13.6 259 126 55.3 0.69 20 2.74 14.6 284 141 53.7 0.66 21 2.71 14.5 281 140 49.6 0.64 21 2.63 14.2 273 136
71 55.7 0.53 15 2.71 14.5 281 140 54.1 0.51 16 2.68 14.4 278 139 49.9 0.49 16 2.60 14.1 270 134 47.4 1.00 25 2.71 14.4 269 121 46.1 0.97 26 2.68 14.3 266 119 42.5 0.93 26 2.60 14.0 258 116
59 46.6 0.97 23 2.68 14.3 266 119 45.3 0.92 24 2.65 14.2 264 118 41.8 0.89 25 2.57 13.9 256 115 48.4 0.98 25 2.78 14.8 289 128 47.0 0.94 26 2.75 14.6 286 127 43.3 0.90 26 2.67 14.3 278 123
63 47.6 0.91 22 2.75 14.6 286 127 46.3 0.87 23 2.72 14.5 284 126 42.7 0.84 24 2.64 14.2 275 122
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
85
80
IDB
65
50.7 0.89 23 2.89 15.2 305 140 49.2 0.84 24 2.86 15.1 302 139 45.4 0.81 25 2.77 14.7 293 135
67 50.9 0.74 19 2.86 15.1 302 139 49.4 0.71 20 2.83 15.0 299 137 45.6 0.68 21 2.75 14.6 290 133 54.0 0.72 20 3.01 15.7 319 149 52.5 0.68 21 2.98 15.6 315 148 48.4 0.66 21 2.89 15.2 306 143
71 54.4 0.55 16 2.98 15.6 315 148 52.8 0.53 16 2.95 15.5 312 146 48.8 0.51 16 2.86 15.1 303 142 46.3 1.00 24 2.92 15.6 306 125 45.0 0.99 26 2.89 15.4 303 124 41.5 0.96 26 2.80 15.1 294 120
59 45.5 1.00 24 2.89 15.4 303 124 44.2 0.95 24 2.86 15.3 300 123 40.8 0.91 25 2.78 14.9 291 119 47.2 1.00 24 3.00 15.9 329 133 45.8 0.96 26 2.97 15.8 326 132 42.3 0.92 26 2.88 15.4 316 128
49.4 0.91 23 3.12 16.4 347 146 48.0 0.87 24 3.09 16.3 344 144 44.3 0.83 25 2.99 15.8 334 140
45.2 1.00 23 3.11 16.5 348 132 43.9 1.00 26 3.08 16.4 345 130 40.5 0.99 27 2.98 16.0 334 127
46.1 1.00 24 3.19 16.9 375 140 44.7 0.99 26 3.16 16.8 371 139 41.3 0.95 26 3.06 16.3 360 135
48.2 0.94 23 3.32 17.4 396 153 46.8 0.89 24 3.28 17.3 392 152 43.2 0.86 25 3.18 16.8 380 147
51.5 0.76 20 3.45 18.0 413 163 50.0 0.72 21 3.42 17.9 409 161 46.1 0.70 21 3.31 17.4 396 157
71 51.8 0.59 16 3.42 17.9 409 161 50.3 0.56 16 3.38 17.7 405 160 46.4 0.54 17 3.28 17.3 392 155 42.9 1.00 22 3.27 17.5 392 138 41.7 1.00 24 3.23 17.4 388 137 38.5 1.00 26 3.14 16.9 376 133
59 42.2 1.00 22 3.23 17.4 388 137 41.0 1.00 24 3.20 17.2 384 135 37.8 0.98 25 3.10 16.8 373 131 43.8 1.00 23 3.35 17.9 422 147 42.5 1.00 25 3.32 17.7 417 145 39.2 0.99 26 3.22 17.3 405 141
63 43.1 1.00 22 3.32 17.7 417 145 41.9 0.95 23 3.29 17.6 413 144 38.6 0.92 24 3.19 17.2 401 140 45.8 0.97 23 3.49 18.5 445 160 44.5 0.93 24 3.45 18.3 441 159 41.1 0.89 24 3.35 17.8 428 154
67 46.1 0.81 19 3.45 18.3 441 159 44.7 0.78 20 3.42 18.1 436 157 41.3 0.75 20 3.31 17.7 423 152
105
48.9 0.79 20 3.63 19.1 464 171 47.5 0.75 21 3.59 18.9 460 169 43.8 0.73 21 3.48 18.4 446 164
71 49.2 0.61 15 3.59 18.9 460 169 47.8 0.58 16 3.56 18.8 455 167 44.1 0.56 16 3.45 18.3 441 162 39.8 1.00 21 3.40 18.5 433 143 38.6 1.00 22 3.37 18.3 429 141 35.6 1.00 24 3.27 17.8 416 137
59 39.1 1.00 20 3.37 18.3 429 141 37.9 1.00 22 3.34 18.1 424 140 35.0 0.99 23 3.24 17.7 412 136 40.5 1.00 21 3.49 18.9 466 152 39.4 1.00 23 3.46 18.7 461 150 36.3 1.00 24 3.36 18.2 447 146
63 39.9 1.00 21 3.46 18.7 461 150 38.8 0.96 22 3.43 18.6 457 149 35.8 0.93 22 3.32 18.1 443 144 42.5 0.98 22 3.63 19.5 492 166 41.2 0.94 22 3.60 19.3 487 164 38.0 0.90 23 3.49 18.8 472 159
67 42.7 0.82 18 3.60 19.3 487 164 41.4 0.78 19 3.56 19.1 482 163 38.2 0.75 19 3.45 18.6 468 158
115
45.3 0.80 19 3.78 20.2 513 177 44.0 0.76 19 3.74 20.0 508 175 40.6 0.73 20 3.63 19.5 493 170
71 45.6 0.61 14 3.74 20.0 508 175 44.3 0.58 15 3.70 19.8 503 173 40.9 0.56 15 3.59 19.3 488 168
Shaded area reflects AHRI (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
52.8 0.74 20 3.24 17.0 362 155 51.2 0.70 21 3.21 16.8 359 154 47.3 0.68 21 3.11 16.4 348 149
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 46.5 49.7 53.1 44.4 45.4 48.5 0.93 0.76 0.57 1.00 0.96 0.78 22 20 16 23 23 20 2.97 3.09 3.21 3.08 3.16 3.28 15.8 16.3 16.8 16.4 16.8 17.3 326 344 359 345 371 392 132 144 154 130 139 152 45.2 48.2 51.6 43.1 44.1 47.1 0.89 0.72 0.54 0.98 0.92 0.75 23 20 16 25 24 20 2.94 3.05 3.18 3.05 3.13 3.25 15.6 16.1 16.7 16.3 16.6 17.1 323 341 355 341 367 388 131 143 152 129 137 150 41.7 44.5 47.6 39.8 40.7 43.4 0.86 0.70 0.52 0.94 0.89 0.72 24 21 16 25 24 21 2.85 2.96 3.08 2.95 3.03 3.15 15.3 15.7 16.3 15.9 16.2 16.7 313 330 345 331 356 376 127 139 148 125 133 146
Product Specifications
Expanded Cooling Data — GPC1448H41** (cont.)
15
16
www.goodmanmfg.com
57.3 0.81 24 3.73 15.8 241 109 55.6 0.77 25 3.70 15.7 238 108 51.3 0.75 25 3.61 15.3 231 105
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1500
1700
1900
59 56.3 0.71 21 3.70 15.7 238 108 54.7 0.68 21 3.67 15.6 236 107 50.5 0.66 22 3.58 15.2 229 103
Airflow MBh S/T ∆T kW 1900 Amps HI PR LO PR MBh S/T ∆T kW 1700 Amps HI PR LO PR MBh S/T ∆T 1500 kW Amps HI PR LO PR
59.0 0.73 22 3.82 16.2 259 116 57.3 0.69 23 3.79 16.0 256 115 52.9 0.67 23 3.69 15.6 249 111
63 58.4 0.60 18 3.78 16.0 256 115 56.7 0.57 19 3.75 15.9 254 114 52.3 0.55 19 3.66 15.5 246 110 63.9 0.55 18 3.94 16.7 273 126 62.0 0.52 19 3.91 16.5 271 125 57.2 0.51 19 3.81 16.1 263 121
67 64.0 0.41 14 3.91 16.5 271 125 62.1 0.39 14 3.88 16.4 268 124 57.3 0.38 14 3.78 16.0 260 120 68.5 0.35 12 4.07 17.2 285 135 66.5 0.34 13 4.04 17.1 282 133 61.4 0.33 13 3.94 16.7 274 129
71 56.0 0.84 24 4.03 17.0 270 115 54.3 0.80 25 4.00 16.9 267 114 50.2 0.77 25 3.90 16.4 259 110
59 55.0 0.74 21 4.00 16.9 267 114 53.4 0.71 22 3.97 16.7 265 113 49.3 0.68 22 3.87 16.3 257 109 57.6 0.75 22 4.12 17.4 291 122 55.9 0.72 23 4.09 17.3 288 121 51.6 0.69 23 3.99 16.8 279 118
63 57.0 0.62 18 4.09 17.2 288 121 55.4 0.59 19 4.06 17.1 285 120 51.1 0.57 19 3.95 16.7 276 116
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
75
70
IDB
65
62.4 0.57 18 4.26 17.9 307 134 60.6 0.54 19 4.23 17.8 304 132 55.9 0.52 19 4.12 17.3 295 128
67 62.5 0.43 14 4.23 17.8 304 132 60.7 0.41 14 4.19 17.6 301 131 56.0 0.39 14 4.08 17.2 292 127 66.9 0.37 13 4.41 18.6 320 142 65.0 0.35 13 4.37 18.4 317 141 60.0 0.34 13 4.26 17.9 307 137
71 54.6 0.86 24 4.30 18.4 307 120 53.0 0.82 25 4.26 18.2 304 118 49.0 0.79 26 4.15 17.8 295 115
59 53.7 0.76 21 4.26 18.2 304 118 52.2 0.72 22 4.23 18.1 301 117 48.1 0.70 22 4.12 17.6 292 114 56.3 0.77 22 4.40 18.8 330 127 54.6 0.74 23 4.36 18.6 327 126 50.4 0.71 24 4.25 18.2 317 122
60.9 0.58 18 4.55 19.4 349 139 59.1 0.56 19 4.51 19.2 346 137 54.6 0.54 19 4.39 18.7 335 133
53.3 0.89 24 4.53 19.6 350 126 51.8 0.85 25 4.49 19.4 346 124 47.8 0.82 26 4.38 18.9 336 121
54.9 0.80 22 4.64 20.0 376 134 53.3 0.76 23 4.60 19.9 373 132 49.2 0.73 24 4.48 19.3 361 128
59.4 0.60 18 4.79 20.7 397 146 57.7 0.58 19 4.75 20.5 394 144 53.2 0.55 19 4.63 19.9 382 140
63.8 0.39 13 4.96 21.4 415 155 61.9 0.37 13 4.92 21.2 410 154 57.1 0.36 13 4.79 20.7 398 149
71 50.6 0.92 24 4.73 20.8 393 132 49.2 0.88 25 4.69 20.6 390 130 45.4 0.85 25 4.57 20.0 378 126
59 49.8 0.81 21 4.69 20.6 390 130 48.3 0.78 22 4.65 20.4 386 129 44.6 0.75 22 4.53 19.9 374 125 52.1 0.83 22 4.84 21.3 423 140 50.6 0.79 23 4.80 21.1 419 139 46.7 0.76 23 4.67 20.5 407 134
63 51.6 0.68 18 4.80 21.1 419 139 50.1 0.65 19 4.76 20.9 415 137 46.2 0.62 19 4.63 20.3 403 133 56.4 0.63 18 5.01 21.9 447 153 54.8 0.60 19 4.96 21.7 443 151 50.6 0.58 19 4.83 21.2 429 147
67 56.5 0.47 14 4.96 21.7 443 151 54.9 0.45 14 4.92 21.5 438 150 50.7 0.43 14 4.79 21.0 425 145
105
60.6 0.40 12 5.18 22.7 466 163 58.8 0.38 13 5.14 22.5 462 161 54.3 0.37 13 5.00 21.9 448 156
71 46.9 0.93 22 4.90 21.9 435 136 45.5 0.89 23 4.86 21.7 430 135 42.0 0.86 24 4.73 21.2 418 131
59 46.1 0.82 19 4.86 21.7 430 135 44.8 0.78 20 4.82 21.6 426 133 41.3 0.75 20 4.69 21.0 413 129 48.3 0.83 21 5.02 22.5 468 145 46.9 0.80 21 4.97 22.3 463 143 43.3 0.77 22 4.84 21.7 449 139
63 47.8 0.69 17 4.97 22.3 463 143 46.4 0.65 17 4.93 22.1 459 142 42.8 0.63 18 4.80 21.5 445 138 52.3 0.63 17 5.19 23.2 494 158 50.8 0.60 18 5.14 23.0 489 157 46.8 0.58 18 5.01 22.4 474 152
67 52.4 0.47 13 5.14 23.0 489 156 50.9 0.45 13 5.10 22.8 484 155 46.9 0.44 13 4.97 22.2 470 150
115
56.1 0.41 12 5.37 24.0 515 168 54.5 0.39 12 5.32 23.8 510 167 50.3 0.37 12 5.18 23.2 495 162
71 -
Shaded area reflects ACCA (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
65.3 0.38 13 4.70 20.1 364 148 63.4 0.36 13 4.66 19.9 360 146 58.6 0.35 13 4.54 19.4 350 142
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 55.7 61.0 52.4 54.3 59.5 0.63 0.44 0.78 0.65 0.45 18 14 21 18 14 4.36 4.51 4.49 4.60 4.75 18.6 19.2 19.4 19.9 20.5 327 345 346 373 393 126 137 124 132 144 54.1 59.2 50.9 52.7 57.8 0.60 0.42 0.75 0.62 0.43 19 14 22 19 14 4.32 4.47 4.46 4.56 4.71 18.5 19.1 19.2 19.7 20.3 324 342 343 369 390 125 136 123 131 143 49.9 54.7 47.0 48.7 53.3 0.58 0.40 0.72 0.60 0.42 19 15 22 19 15 4.21 4.35 4.34 4.44 4.59 18.0 18.6 18.7 19.2 19.8 314 332 333 358 378 121 132 119 127 139
Product Specifications
Expanded Cooling Data — GPC1460H41**
SS-GPC14H
SS-GPC14H
www.goodmanmfg.com
59.3 0.93 28 3.80 16.1 245 111 57.6 0.89 29 3.77 16.0 243 110 53.2 0.86 30 3.67 15.6 236 107
MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR MBh S/T ∆T kW Amps HI PR LO PR
1500
1700
1900
59 58.3 0.89 27 3.77 16.0 243 110 56.6 0.85 28 3.73 15.8 241 109 52.3 0.82 28 3.64 15.4 233 106
Airflow MBh S/T ∆T kW 1900 Amps HI PR LO PR MBh S/T ∆T kW 1700 Amps HI PR LO PR MBh S/T ∆T 1500 kW Amps HI PR LO PR
60.5 0.90 28 3.88 16.5 264 118 58.7 0.86 29 3.85 16.3 262 117 54.2 0.83 30 3.75 15.9 254 113
63 59.6 0.84 25 3.85 16.3 262 117 57.9 0.80 26 3.82 16.2 259 116 53.4 0.77 27 3.72 15.8 251 112 63.3 0.81 26 4.01 17.0 279 129 61.5 0.78 27 3.98 16.8 276 128 56.8 0.75 28 3.88 16.4 268 124
67 63.7 0.68 22 3.98 16.8 276 128 61.8 0.65 23 3.94 16.7 273 126 57.1 0.63 23 3.84 16.2 265 123 67.6 0.66 23 4.14 17.5 291 137 65.6 0.63 24 4.11 17.4 288 136 60.6 0.61 24 4.01 17.0 279 132
71 68.1 0.51 18 4.11 17.4 288 136 66.1 0.48 18 4.08 17.2 285 135 61.0 0.47 19 3.97 16.8 277 131 58.0 0.97 29 4.10 17.3 275 117 56.3 0.92 30 4.07 17.2 273 116 51.9 0.89 30 3.97 16.7 265 113
59 57.0 0.92 27 4.07 17.2 273 116 55.3 0.88 28 4.03 17.0 270 115 51.0 0.85 28 3.93 16.6 262 112 59.1 0.93 28 4.20 17.7 296 125 57.4 0.89 29 4.16 17.5 294 124 52.9 0.86 30 4.05 17.1 285 120
63 58.2 0.87 26 4.16 17.5 294 124 56.5 0.83 27 4.13 17.4 291 122 52.2 0.80 27 4.02 17.0 282 119
75
IDB = Entering Indoor Dry Bulb Temperature High and low pressures are measured at the liquid and suction access fittings.
85
80
IDB
65
61.9 0.84 27 4.34 18.2 313 136 60.1 0.80 28 4.30 18.1 310 135 55.4 0.78 28 4.19 17.6 301 131
67 62.2 0.70 22 4.30 18.1 310 135 60.4 0.67 23 4.26 17.9 307 134 55.7 0.65 24 4.15 17.5 298 130 66.0 0.68 23 4.48 18.9 326 145 64.1 0.65 24 4.45 18.7 323 144 59.2 0.63 24 4.33 18.2 314 139
71 66.5 0.53 18 4.45 18.7 323 144 64.5 0.50 19 4.41 18.6 320 142 59.6 0.48 19 4.29 18.1 310 138 56.6 0.99 29 4.37 18.7 313 122 54.9 0.95 30 4.34 18.5 310 121 50.7 0.91 30 4.23 18.1 301 117
59 55.6 0.95 27 4.34 18.5 310 121 54.0 0.90 28 4.30 18.4 307 120 49.8 0.87 28 4.19 17.9 298 116 57.7 0.96 28 4.47 19.1 337 130 56.0 0.91 29 4.43 19.0 334 128 51.7 0.88 30 4.32 18.5 324 125
60.4 0.86 27 4.62 19.7 356 142 58.6 0.82 28 4.58 19.6 352 140 54.1 0.79 28 4.47 19.1 342 136
55.2 1.00 28 4.61 19.9 357 128 53.6 0.98 30 4.57 19.8 353 127 49.5 0.94 31 4.45 19.2 343 123
56.3 0.99 28 4.72 20.4 384 136 54.6 0.94 30 4.68 20.2 380 135 50.4 0.91 30 4.56 19.7 369 131
58.9 0.89 27 4.88 21.0 405 149 57.2 0.85 28 4.84 20.8 401 147 52.8 0.82 28 4.71 20.3 389 143
62.9 0.72 23 5.05 21.8 423 158 61.0 0.69 24 5.00 21.6 419 157 56.3 0.67 25 4.87 21.0 406 152
71 63.3 0.56 18 5.00 21.6 419 157 61.5 0.53 19 4.96 21.4 415 155 56.7 0.51 19 4.83 20.8 402 151 52.4 1.00 27 4.81 21.1 401 134 50.9 1.00 29 4.77 21.0 397 133 47.0 0.98 30 4.65 20.4 386 129
59 51.5 1.00 26 4.77 21.0 397 133 50.0 0.97 28 4.73 20.8 394 132 46.2 0.93 28 4.61 20.2 382 128 53.5 1.00 27 4.93 21.6 432 143 51.9 0.98 29 4.88 21.4 428 141 47.9 0.94 30 4.76 20.9 415 137
63 52.7 0.95 26 4.88 21.4 428 141 51.1 0.91 27 4.84 21.3 423 140 47.2 0.87 27 4.71 20.7 411 136 56.0 0.93 26 5.09 22.3 456 156 54.4 0.88 28 5.05 22.1 452 154 50.2 0.85 28 4.92 21.5 438 150
67 56.3 0.77 22 5.05 22.1 452 154 54.6 0.74 23 5.01 21.9 447 153 50.4 0.71 24 4.88 21.3 434 148
105
59.7 0.75 23 5.27 23.1 476 166 58.0 0.72 24 5.23 22.9 471 164 53.5 0.69 24 5.09 22.3 457 159
71 60.1 0.58 18 5.23 22.9 471 164 58.4 0.55 19 5.18 22.7 466 163 53.9 0.53 19 5.05 22.1 452 158 48.6 1.00 25 4.99 22.3 444 139 47.2 1.00 27 4.95 22.1 439 137 43.5 0.99 28 4.82 21.5 426 133
59 47.7 1.00 24 4.95 22.1 439 137 46.3 0.98 26 4.90 21.9 435 136 42.8 0.94 26 4.78 21.4 422 132 49.5 1.00 25 5.10 22.9 477 148 48.1 0.99 27 5.06 22.7 473 146 44.4 0.95 28 4.93 22.1 458 142
63 48.8 0.96 24 5.06 22.7 473 146 47.4 0.91 25 5.02 22.5 468 145 43.7 0.88 25 4.89 21.9 454 140 51.9 0.93 25 5.28 23.6 504 161 50.3 0.89 26 5.24 23.4 499 160 46.5 0.86 26 5.10 22.8 484 155
67 52.1 0.78 21 5.24 23.4 499 160 50.6 0.74 22 5.19 23.2 494 158 46.7 0.72 22 5.05 22.6 479 153
115
55.3 0.76 21 5.47 24.5 526 172 53.7 0.72 22 5.42 24.2 520 170 49.6 0.70 23 5.28 23.6 505 165
71 55.7 0.58 17 5.42 24.2 520 170 54.1 0.56 17 5.37 24.0 515 168 49.9 0.54 18 5.23 23.4 500 163
Shaded area reflects AHRI (TVA) conditions. kW = total system power Amps: Unit amps (comp.+ evaporator + condenser fan motors)
64.4 0.70 23 4.78 20.4 371 151 62.6 0.67 24 4.74 20.3 368 149 57.7 0.64 24 4.62 19.7 357 145
Outdoor Ambient Temperature 85 95 Entering Indoor Wet Bulb Temperature 63 67 71 59 63 67 56.8 60.7 64.9 54.3 55.4 59.2 0.89 0.72 0.54 1.00 0.92 0.75 26 22 18 28 26 23 4.43 4.58 4.74 4.57 4.68 4.84 19.0 19.6 20.3 19.8 20.2 20.8 334 352 368 353 380 401 128 140 149 127 135 147 55.2 58.9 63.0 52.7 53.8 57.5 0.85 0.69 0.52 0.93 0.87 0.71 27 23 19 28 27 24 4.40 4.55 4.70 4.53 4.64 4.80 18.8 19.4 20.1 19.6 20.0 20.7 331 349 364 350 376 398 127 139 148 126 134 146 50.9 54.4 58.2 48.6 49.7 53.1 0.82 0.66 0.50 0.90 0.84 0.69 27 24 19 29 27 24 4.28 4.43 4.58 4.42 4.52 4.67 18.3 18.9 19.6 19.1 19.5 20.1 321 339 353 339 365 386 123 135 143 122 130 141
Product Specifications
Expanded Cooling Data — GPC1460H41** (cont.)
17
Product Specifications
Airflow Data Model
GPC14 24H41C*
GPC14 24H41D/E*
GPC14 30H41C*
GPC14 30H41D/E*
GPC14 36H41C*
GPC14 36H41D*
GPC14 42H41C*
Speed*
Volts
Type
T1
E.S.P. (In. of H₂O) 0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
230
CFM Watts
922 74
873 85
823 96
774 107
724 118
675 129
626 140
576 151
T2, T3
230
CFM Watts
922 74
873 85
823 96
774 107
724 118
675 129
626 140
576 151
T4, T5
230
CFM Watts
1069 102
1020 113
971 124
921 135
872 146
822 157
773 168
724 179
T1
230
CFM Watts
922 74
873 85
823 96
774 107
724 118
675 129
626 140
576 151
T2, T3
230
CFM Watts
922 74
873 85
823 96
774 107
724 118
675 129
626 140
576 151
T4, T5
230
CFM Watts
1231 168
1179 180
1127 193
1074 205
1022 218
969 230
917 243
865 255
T1
230
CFM Watts
1048 97
993 109
939 122
884 134
829 147
775 159
720 172
666 184
T2, T3
230
CFM Watts
1123 123
1068 136
1014 148
959 161
905 173
850 186
796 198
741 211
T4, T5
230
CFM Watts
1244 158
1189 170
1135 183
1080 195
1026 208
971 220
917 233
862 245
T1
230
CFM Watts
1048 97
993 109
939 122
884 134
829 147
775 159
720 172
666 184
T2, T3
230
CFM Watts
1123 123
1068 136
1014 148
959 161
905 173
850 186
796 198
741 211
T4, T5
230
CFM Watts
1462 241
1409 253
1357 266
1305 278
1252 291
1200 303
1147 315
1095 328
T1
230
CFM Watts
1151 132
1097 144
1042 156
988 169
933 181
879 194
824 206
770 219
T2, T3
230
CFM Watts
1261 131
1215 144
1169 157
1123 169
1076 182
1030 194
984 207
937 220
T4, T5
230
CFM Watts
1376 170
1330 182
1284 195
1237 207
1191 220
1145 233
1099 245
1052 258
T1
230
CFM Watts
1151 132
1097 144
1042 156
988 169
933 181
879 194
824 206
770 219
T2, T3
230
CFM Watts
1261 131
1215 144
1169 157
1123 169
1076 182
1030 194
984 207
937 220
T4, T5
230
CFM Watts
1577 277
1525 290
1472 302
1420 314
1367 327
1315 339
1263 352
1210 364
T1
230
CFM Watts
1165 118
1122 130
1080 142
1037 154
995 166
953 178
910 190
868 202
T2, T3
230
CFM Watts
1258 150
1216 162
1173 175
1131 187
1088 199
1046 211
1004 223
961 235
T4, T5
230
CFM Watts
1511 239
1469 251
1427 263
1384 275
1342 287
1299 299
1257 311
1214 323
* Speed set at T2 at the factory.
18
www.goodmanmfg.com
SS-GPC14H
Product Specifications
Airflow Data (cont.) Model
GPC14 42H41D*
GPC14 42H41E*
GPC14 48H41C*
GPC14 48H41D*
GPC14 48H41E*
GPC14 60H41C*
GPC14 60H41D*
CFM Watts
0.1 1165 118
0.2 1122 130
0.3 1080 142
E.S.P. (In. of H₂O) 0.4 0.5 1037 995 154 166
0.6 953 178
0.7 910 190
0.8 868 202
230
CFM Watts
1258 150
1216 162
1173 175
1131 187
1088 199
1046 211
1004 223
961 235
T4, T5
230
CFM Watts
1645 285
1602 297
1560 309
1517 321
1475 333
1433 346
1390 358
1348 370
T1
230
CFM Watts
1181 146
1146 158
1112 174
1062 182
1022 196
977 208
937 218
891 227
T2, T3
230
CFM Watts
1410 222
1366 236
1328 250
1286 260
1248 273
1195 285
1155 296
1115 305
T4, T5
230
CFM Watts
1637 331
1605 348
1561 361
1527 374
1484 385
1436 392
1390 407
1345 417
T1
230
CFM Watts
1421 170
1367 182
1314 195
1260 208
1206 220
1152 233
1099 246
1045 258
T2, T3
230
CFM Watts
1696 287
1643 299
1589 312
1535 325
1481 337
1428 350
1374 363
1320 375
T4, T5
230
CFM Watts
1859 356
1805 368
1751 381
1698 394
1644 406
1590 419
1536 432
1483 444
T1
230
CFM Watts
1421 170
1367 182
1314 195
1260 208
1206 220
1152 233
1099 246
1045 258
T2, T3
230
CFM Watts
1696 287
1643 299
1589 312
1535 325
1481 337
1428 350
1374 363
1320 375
T4, T5
230
CFM Watts
1983 553
1928 565
1873 578
1818 591
1763 603
1708 616
1652 629
1597 641
T1
230
CFM Watts
1337 179
1297 190
1218 203
1155 210
1118 225
1088 243
1022 249
989 268
T2, T3
230
CFM Watts
1711 330
1640 341
1605 358
1537 370
1496 377
1441 394
1397 408
1347 418
T4, T5
230
CFM Watts
2002 498
1935 521
1885 516
1827 534
1767 551
1732 567
1669 571
1618 574
T1
230
CFM Watts
1507 168
1459 175
1410 183
1362 191
1314 199
1266 207
1218 214
1169 222
T2, T3
230
CFM Watts
1694 296
1646 303
1598 311
1549 319
1501 327
1453 334
1405 342
1357 350
T4, T5
230
CFM Watts
1965 481
1917 489
1869 496
1821 504
1773 512
1724 520
1676 528
1628 535
T1
230
CFM Watts
1507 168
1459 175
1410 183
1362 191
1314 199
1266 207
1218 214
1169 222
T2, T3
230
CFM Watts
1694 296
1646 303
1598 311
1549 319
1501 327
1453 334
1405 342
1357 350
T4, T5
230
CFM Watts
1919 449
1870 457
1822 465
1774 472
1726 480
1678 488
1629 496
1581 503
Speed*
Volts
Type
T1
230
T2, T3
* Speed set at T2 at the factory.
SS-GPC14H
www.goodmanmfg.com
19
Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode) Model and Heat Kit Usage GPC1424H41** HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* GPC1424H41D* HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* GPC1424H41E* HKP-05C* HKR-08C* HKP-10C* GPC1430H41** HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* GPC1430H41D* HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* GPC1430H41E* HKP-05C* HKR-08C* HKP-10C* HKP-15C* GPC1436H41** HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* GPC1436H41D* HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* GPC1442H41** HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* HKP-20C
Circuit #1
Circuit #2
Single-Point Kit
MCA¹
MOP²
MCA¹
MOP²
MCA¹
MOP²
Actual kW / BTU@ 240V
1.9 21 / 25 32 / 36 43 / 49 1.9 21 / 25 32 / 36 43 / 49 1.9 21 / 25 32 / 36 43 / 49 2.3 21 / 25 32 / 36 43 / 49 43 / 49 2.3 21 / 25 32 / 36 43 / 49 43 / 49 2.3 21 / 25 32 / 36 43 / 49 43 / 49 2.3 21 / 25 32 / 36 43 / 49 43 / 49 2.3 21 / 25 32 / 36 43 / 49 43 / 49 3.6 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49
--25 / 25 35 / 40 45 / 50 --25 / 25 35 / 40 45 / 50 --25 / 25 35 / 40 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50
--------------------------------21 / 25 --------21 / 25 --------21 / 25 --------21 / 25 --------21 / 25 --------21 / 25 43 / 49
--------------------------------25 / 25 --------25 / 25 --------25 / 25 --------25 / 25 --------25 / 25 --------25 / 25 45 / 50
-24 / 27 33 / 38 45 / 51 -29 41 54 -29 41 54 -24 / 27 34 / 39 45 / 52 67 / 77 -29 41 54 79 -29 41 54 79 -24 / 27 34 / 39 45 / 52 67 / 77 -29 41 54 79 -27 34 / 39 46 / 52 68 / 78 90 / 103
-30 / 30 40 / 40 60 / 60 -30 45 60 -30 45 60 -30 / 30 40 / 40 60 / 60 70 / 80 -30 45 60 80 -30 45 60 80 -40 / 40 40 / 40 60 / 60 70 / 80 -40 45 60 80 -40 / 40 40 / 40 60 / 60 70 / 80 90 / 110
--4.75 / 16,200 7 / 23,800 9.5 / 32,400 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800
¹ Minimum Circuit Ampacity @ 208 / 240 V ² Maximum Overcurrent Protection Device @ 208 / 240 V * Revision level that may or may not be designated C Circuit breaker option ^ Heat Kit requires three-phase power supply Note: HKP-15C* and HKP-20C* replace HKR-15C and HKR-20C respectively to meet new UL1995 requirements.
20
www.goodmanmfg.com
SS-GPC14H
Product Specifications
Heat Kit Electrical Data (Blower Only, Heat Mode) Model and Heat Kit Usage GPC1442H41D* HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* HKP-20C GPC1442H41E* HKP-05C* HKR-08C* HKP-10C* HKP-15C* HKP-20C GPC1448H41** HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* HKP-20C GPC1448H41D* HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* HKP-20C GPC1448H41E* HKP-05C* HKR-08C* HKP-10C* HKP-15C* HKP-20C GPC1460H41** HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* HKP-20C GPC1460H41D* HKR-05*, HKR-05C* HKR-08*, HKR-08C* HKR-10*, HKR-10C* HKP-15C* HKP-20C GPC1460H41E* HKP-05C* HKR-08C* HKP-10C* HKP-15C* HKP-20C
Circuit #1
Circuit #2
Single-Point Kit
MCA¹
MOP²
MCA¹
MOP²
MCA¹
MOP²
Actual kW / BTU@ 240V
3.6 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49 3.6 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49 3.6 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49 3.6 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49 3.6 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49 7.5 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49 7.5 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49 7.5 21 / 25 32 / 36 43 / 49 43 / 49 43 / 49
--25 / 25 35 / 40 45 / 50 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50 --25 / 25 35 / 40 45 / 50 45 / 50 45 / 50
--------21 / 25 43 / 49 --------21 / 25 43 / 49 --------21 / 25 43 / 49 --------21 / 25 43 / 49 --------21 / 25 43 / 49 --------21 / 25 43 / 49 --------21 / 25 43 / 49 --------21 / 25 43 / 49
--------25 / 25 45 / 50 --------25 / 25 45 / 50 --------25 / 25 45 / 50 --------25 / 25 45 / 50 --------25 / 25 45 / 50 --------25 / 25 45 / 50 --------25 / 25 45 / 50 --------25 / 25 45 / 50
-29 41 54 79 104 -29 41 54 79 104 -29 34 / 40 46 / 53 68 / 78 90 / 103 -32 43 56 81 106 -32 43 56 81 106 -37.3 37/40 48 / 54 70 / 80 92 / 105 -40 43 56 81 106 -40 43 56 81 106
-45 45 60 80 110 -45 45 60 80 110 -45 45 60 / 60 70 / 80 90 / 110 -50 50 60 90 110 -50 50 60 90 110 -60 60 60 / 60 80 / 90 100 / 110 -60 60 60 90 110 -60 60 60 90 110
--4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800 --4.75 / 16,200 7 / 23,800 9.5 / 32,400 14.25 / 48,600 19.0 / 64,800
See Notes on previous page.
SS-GPC14H
www.goodmanmfg.com
21
Product Specifications
Dimensions
A
BACK VIEW (DUCT OPENINGS)
W
B
D
Model
22
Dimensions W"
D"
H"
A"
B"
Chassis Size
GPC1424H41**
66
33
30½
22
30
Small
GPC1430H41**
66
33
30½
22
30
Small
GPC1436H41**
66
33
30½
22
30
Small
GPC1442H41C*/D*
66
33
35½
24
35
Medium
GPC1442H41E*
66
33
30½
22
30
Small
GPC1448H41C*/D*
66
33
38½
24
38¾
Large
GPC1448H41E*
66
33
35½
24
35
Medium
GPC1460H41C*/D*
66
33
38½
24
38¾
Large
GPC1460H41E*
66
33
35½
24
35
Medium
www.goodmanmfg.com
SS-GPC14H
Product Specifications
Wiring Diagram PU
NOTE #3 BK
RD
BL
RD
BK BK RD
BK T2
C T1
SEE NOTE 5
L1
YL
GND
GR
BK
60
RD
RD
YL
PU
LVJB
YL RD BR
WH
BL H
YL
BL
C F RCCF
GR
YL C L G N 1
2
WH
GR
PLF 3
6
9
2
5
8
1
4
7
BR
PU
RD SA (IF USED) SEE NOTE 4
BR
YL
BK
CM
L2 SUPPLY VOLTAGE 208-240/1/60
T1
T2
R C COMP S
H
S.A.
W2 C
RD CONTROL BOX
S C R
COMPONENT LEGEND C CM COMP EM GND LVJB PLF RCCF
C
C RCCF
F
SA TR
CM
NOTE #4
CONTACTOR CONDENSER MOTOR COMPRESSOR EVAPORATOR MOTOR EQUIPMENT GROUND LOW VOLTAGE JUNCTION BOX FEMALE PLUG / CONNECTOR RUN CAPACITOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER
IF USED NOTE #2
EM 1
BR BL
T H E R M O S T A T
EM
L1
N
Y R G W1
COMP
WH
C
YL RD GR WH
BK
PU BR BK
WH GR
3 4 5
SEE NOTE 2
2 0 8 2 4 0 / 1 /
L2
G
L 3 2 NOTE #4
208-240 3
2
1
FACTORY WIRING LINE VOLTAGE LOW VOLTAGE OPTINAL HIGH VOLTAGE FIELD WIRING HIGH VOLTAGE LOW VOLTAGE
WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
TR 24V
NOTES:
1 EM C 2
3
SEE NOTE #2
4 5
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105°C) USE COPPER CONDUCTO R ONLY. 2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW LEADS FROM EM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED. 3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER. 4. START ASSIST FACTOR EQUIPED WHEN REQUIRED 5. USE COPPER CONDUCTORS ONLY. ++ USE N.E.C. CLASS 2 WIRE
⚡
BL
24V
PU
BL
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
PU
3
240
Warning
2
208 TR
⚠
1
C
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
BK
6
PLF C
R
W2
W1
Y
G
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION
C
THERMOSTAT
208-240/1/60 0140G00407
SS-GPC14H
www.goodmanmfg.com
23
Product Specifications
Accessories Accessory Description
Small Chassis
Item Number Medium/Large Chassis
Downflow Economizer
PCE101
PCE102/103
Downflow Plenum Kit
PCP101
PCP102/103
Downflow Plenum Kit (R-8)
PCP101 R8
PCP102 R8 /103 RB
Elbow Flashing w/ R-8 Liner
PCEF101
PCEF102/103
Emergency Heat Relay
OT/EHR18-60
OT/EHR18-60
External Horizontal Filter Rack
GPGHFR101
GPGHFR102/103
Horizontal Economizer
DHZECNJPGCHM
DHZECNJPGCHL
Manual Damper
PCMD101
PCMD102/103
Horizontal Manual Damper
PCMDH101
PCMDH102/103
Motorized Damper
PCMDM101
PCMDM102/103
Outdoor Thermostat w/ Lockout Stat
OT18-60A
OT18-60A
Roof Curb
PCCP101
PCCP102/103
Square to Round
SQRPC101
SQRPC102/103
Square to Round for Horizontal Application
SQRPCH101
SQRPCH102/103
Single-Point Wiring Kits Select the single-point kit accessory based on the unit model. Model
Single-Point Kit
Model
Single-Point Kit
GPC1424***41C*
SPK-15
GPC1424***41D*
SPK-20
GPC1430***41C*
SPK-30
GPC1430***41D*
SPK-30
GPC1436***41C*
SPK-40
GPC1436***41D*
SPK-40
GPC1442***41C*
SPK-40
GPC1442***41D*
SPK-45
GPC1448***41C*
SPK-45
GPC1448***41D*
SPK-50
GPC1460***41C*
SPK-60
GPC1460***41D*
SPK-60
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2014 Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
24
www.goodmanmfg.com
SS-GPC14H