Eco Commercial Fans Installation Instructions
Original Instructions
2
Contents General Description and Physical Specification
2-3
Wall Mounting Installation
4
Window Mounting Installation
5
Ceiling/Panel Mounting Installation
6
Pitched Roof Installation
7
Flat Roof Installation
8
Refurbishment Installation
9
Wiring Instructions
10
Integral Sensor and Remote Sensor/Remote Switch Installation
11
Superduct Fan Installation
12-13
Cleaning and Maintenance
14
CE Declaration
15
General Description and Physical Specification • Warning: The appliance is not intended for use by young children or infirm persons unless they have been adequately supervised by a responsible person to ensure that they can use the appliance safely. Young children should be supervised to ensure they do not play with the appliance. • Observe appropriate safety precautions if working on steps or ladders. Wear eye protection when breaking out wall or window materials etc. • When installing wall mounted fans, ensure that there are no buried cables or pipes in the way. It is recommended that this fan is mounted 2.3m above floor level. • A clearance of 75mm to be allowed on at least one side of the fan for the removal of the internal grille. • Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel burning appliances (for duct and partition fans). • This fan shall not be mounted above or closer than 1 metre to a cooker of other heat source where it could be affected by excessive heat or moisture or sited where it would be suject to a direct source of heat in excess of 40˚C. • After the fan is installed, its control system shall be in accordance with EN60335-2-80.
Greenwood Airvac
Technical Services Tel: 01903 777135
3
Dimensions 12” Fan
9” Fan
Front
6” Fan Front
Front 342mm
420mm
342mm
420mm Surface cable entry
Recessed cable entry
269mm
Surface cable entry
Surface cable entry
Rear
Rear
Rear
Recessed cable entry
214.5mm*
175mm*
Recessed cable entry
137.5mm*
171mm*
206.5mm*
134.5mm*
342mm
413mm * To centre of duct
Side
272mm
269mm * To centre of duct
Side
130mm
169. 4mm
* To centre of duct
Side
128mm
Spigot Sizes for Ducted Applications
ck Ceiling Adaptor
sa Single Spigot Adaptor
sp Single Spigot
idk Induct Kit
CD12
350mm
350mm
350mm 350mm
CD9
250mm
250mm
250mm 250mm
CD6
200mm
200mm
200mm 200mm
Fan Specifications 220-240 ~ 50Hz / 1Ph IPX4: CD12: 100 watts CD9: 50 watts CD6: 38 Watts Cable size required: 3 core 1.5mm2 / 4 core 1.5mm2. Supply should be fused at 3 Amp. The sound pressure of the Eco Commercial Fan is less than 70 dB(A).
Technical Services Tel: 01903 777135
Greenwood Airvac
4
Wall Mounting
Complete Kits CD12WA l CD9WA l CD6WA
1 EG12 l EG9 l EG6 ED12 l ED9 l ED6 Individual Units CD12 l CD9 l CD6
2
6
10
3
7
11
4
8
12
5
9
13
Wiring – Page 10
Min. duct length 200mm
D
Eco 12” D = 410 x 410 mm Eco 9” D = 330 x 330 mm Eco 6” D = 260 x 260 mm
Greenwood Airvac
Technical Services Tel: 01903 777135
5
Window Mounting
Complete Kits CD12WA l CD9WA l CD6WA
1
ED12 l ED9 l ED6 Individual Units
CD12 l CD9 l CD6
2
6
10
3
7
11
4
8
12
5
9
13
Wiring – Page 10
D
Eco 12” D = 337 mm Eco 9”
D = 260 mm
Eco 6”
D = 184 mm
Technical Services Tel: 01903 777135
Greenwood Airvac
6
Ceiling/Panel Mounting
Complete Kits CD12CK l CD9CK l CD6CK
1 D
Eco 12” D = 430 x 430 mm Eco 9” D = 340 x 340 mm
CK12 l ck9 l ck6 Individual Units
Eco 6” D = 270 x 270 mm
5 CD12 l CD9 l CD6
2
6
9
7
10
8
11
3
Wiring – Page 10
4
Greenwood Airvac
Technical Services Tel: 01903 777135
7
Pitched Roof Installation Complete Kits CD12PR l CD9PR l CD6PR EXPLODED VIEW
Weather Terminal (WT12/WT9/WT6) Lead Flashing
Wall Fixing Plate (WFP12/WFP9/WFP6)
Spacer (WS12/WS9/WS6)
Single Spigot Adapter (SA12/SA9/SA6)
Weather Terminal Worm Drive Fixing Clips
The Installation is made by screwing (8. off 5 mm dia. screws not provided) a Wall Fixing Plate (WFP6/9/12) to suitably spaced purlins/ trimmers and weather-sealing this to the structure with a lead or zinc apron. The trimmed opening size is:– l
6” Fan = 320 x 320 mm
l
9” Fan = 385 x 385 mm
l
12” Fan = 450 x 450 mm
To complete the water-tightness of the installation, drill out the 4 dimpled hole positions (6 mm dia.) in the base of the Weather Terminal (WT6/9/12), place this centrally on the Fixing Plate, with its lower Flexible Ducting
edge sealed by silicon mastic, and then, using the M5 screws, washers and seals provided, attach the Weather Terminal to the Spacer Moulding (WS6/9/12). With the installation now weather-tight, the Fan may be fitted into the Spacer as convenient. Once the Fan is fitted, the Spigot Adaptor (SA6/9/12) may be screwed to its lower face and ducting attached as required. On 6” Fans, the Spigot Adaptor may be replaced by a Multi-Spigot Adaptor (MS6) which will accept up to 4 – 100 mm dia. individual ducts.
Dimensions Weather Terminal
Wall Fixing Plate
Plan
Plan WT12: 506 x 506mm WT9: 425 x 425mm WT6: 360 x 360mm
Side
WT12: 185mm WT9: 180mm WT6: 170mm
WFP12: 550 x 550mm WFP9: 475 x 475mm WFP6: 400 x 400mm
WFP12: 337mm dia. WFP9: 260mm dia. WFP6: 185mm dia.
Side
Single Spigot Adaptor
Spacer
Plan
Plan WS12: 425 x 425mm WS9: 341 x 341mm WS6: 271 x 271mm
SA12: 430 x 430mm SA9: 345 x 345mm SA6: 275 x 275mm
Side
SA12: 70mm SA9: 70mm SA6: 70mm
WFP12: 2mm WFP9: 2mm WFP6: 2mm
Side
WS12: 137mm WS9: 123mm WS6: 126mm
SA12: 350mm dia. SA9: 250mm dia. SA6: 200mm dia.
Technical Services Tel: 01903 777135
Greenwood Airvac
8
Flat Roof Installation Complete Kits CD12FR l CD9FR l CD6FR EXPLODED VIEW
Roof Terminal RT6 / RT9 / RT12
Spacer WS6 / WS9 / WS12 Roof Felt
Roof Felt
AxB O/all Finished Curb
Roof Slab
Fan
Ceiling Panel
Roof Slab
Roof Slab Ceiling Panel
Ceiling Panel
Grille
150 mm
Roof Felt
CxD Ceiling Opening
The Installation is made by constructing a timber or builders-work curb to the dimensions shown below:
A B C D (max.) (max.) (max.) (max.)
CD6 610mm 610mm 300mm 300mm
centrally and squarely over the curb and screw the Terminal to the curb using 6mm Wood Screws and Sealing Washers. Offer the Spacer (WS6, WS9 or WS12) to the underside of the secured Terminal and attach using the 4.off M5 screws provided.
Attach the fan to the Spacer, again using the screws provided, and complete the electrical CD12 695mm 695mm 450mm 450mm wiring as required. CD9 610mm 610mm 450mm 450mm
To complete the installation, drill out the 8.off dimpled holes in the base of the Roof Terminal (RT6, RT9 or RT12), position the Terminal
The ceiling opening should be closed using a suitable 300 x 300mm grille (CD6 fan) or 450 x 450mm grille (CD9 or CD12 fans).
Dimensions Weather Terminal
Spacer
Plan
Plan WS12: 425 x 425mm WS9: 341 x 341mm WS6: 271 x 271mm
RT12: 506 x 506mm RT9: 425 x 425mm RT6: 360 x 360mm
Side
Side
WS12: 137mm WS9: 123mm WS6: 126mm
RT12: 185mm RT9: 180mm RT6: 170mm RT12: 742 x 742mm RT9: 657 x 657mm RT6: 657 x 657mm
Greenwood Airvac
Technical Services Tel: 01903 777135
9
Refurbishment Installation Complete Kits CD12RE l CD9RE l CD6RE
Replacing existing Greenwood Eco Fans
Replacing existing Greenwood Eco fan
The fan is fixed as the previous fan into the existing channels on the wall liner. The picture frame can be used if desired, however the metal brackets are not required.
Replacing existing T series Fans The brackets supplied with the kit can be aligned with the screw fixing holes of the previous fan. This then positions the receiving nut on the bracket in the correct location to allow fixing of the Greenwood refurbishment fan.
Wiring details – Greenwood Eco Fans When replacing Greenwood fans in many cases the wiring will remain the same, however if the existing controller is of the RC1 or RC2 type installed with CX fans, then the switch functionally changes. The RC1 switch becomes an intake/off/extract switch operating the fan on high speed only. The RC2 switch maintains the on/off/auto functions, but at installation the direction is selected.
Replacing existing T series fan
Wiring details – T series Fans A Greenwood CD fan can be used to replace a Vent Axia ‘T’ Series fan, retaining the original controller, providing the controller is of the ‘Ecotronic 130’, ‘Rangemaster’ or ‘T’ Series Controller type.
This arrangement will give the following operating features: • Adjustable speed • Adjustable minimum speed
Vent Axia Ecotronic 130 or Rangemaster Controller
Greenwood Eco Type CD Reversible Fan
Vent Axia Ecotronic 130 or Rangemaster Controller
Greenwood Eco TypeL5 CD Reversible Fan L4
• Extract/intake
L5 L3
• Fan off – shutter closed.
Limitations are: • Control of single fan only • Integral sensors not possible
230v ~ 50hz 230v ~ 50hz
• Fan off – shutter open
L4 L2 L3 L1
N
L2 N
L
Double-Pole N Isolator
L
• Automatic ECO setting not available.
Double-Pole Isolator
Max 5 amp Max 5 amp
This arrangement will give the following operating features: • Single speed • On/off.
Limitations are: • Control of single fan only • Integral sensors not possible • Automatic ECO setting not available. NB. All electrical products must be wired and installed by a qualified electrician in accordance with IEE and local regulations which apply. The fans must be connected to mains power by using a fused double pole isolating switch having a contact separation of at least 3mm. Technical Services Tel: 01903 777135
Double-Pole Isolator 230v ~ 50hz 230v ~ 50hz
• Extract/intake
N
N1
L3
L1
L2
L
N
N1
L3
L1
L2
N
Greenwood Eco Type CD Reversible Fan
Vent Axia T-Sereis Controller
Greenwood Eco TypeL5 CD Reversible Fan L4
L Max 5 amp
L1
Vent Axia T-Sereis Controller
Max 5 amp
L N Double-Pole Isolator
L
N
L
L
N
N
L2
L5 L3
L1
L4 L2
L2 L3
L3 L1
L1 N
L2 N
L3
L1
N
N
NB. The ‘T’ Series controller speed capacitor must be removed from the controller before use with a Greenwood ECO fan. Greenwood Airvac
10
Wiring Instructions 1
2
Double-Pole Max 3 amp Isolator
L N Double-Pole Isolator
L All electrical products should be wired and installed by a qualified electrician, N in accordance with IEE or local regulations CXPC Fan Unit which apply.
Max 3 amp
L N
L connected to mains power by using a fused The fans must be N switch having a contact separation of at double pole isolating least 3mm. For other siting appliances please refer to supplier data sheets CX Fan Unit available on requested. L5 Always isolate appliance from the mains before cleaning. L4 CX L3 Fan Unit Do not use solvents to clean the fan. L2 L5 L1 L4 N L3
Isolator
L4
L L2 Switch RC1 L3
Max 3 amp
N NL L4 L2
L N
L3
L2 L1 N
Fan with Automatic operation by Remote Sensor N N Link L2 – L4 for Extract
Remote Sensor
230v ~ 50hz 230v ~ 50hz
L1 L2 N
Double-Pole Max Isolator 3 amp
L N Double-Pole Isolator
Remote Sensor L1 L2 N
Max 3 amp
L N
Link L2 – L3 for Intake
CD Fan Unit
CD Fan Unit
Link L2 – L4 for Extract L5
Link L2 – L3 for Intake L5
L4 CD Fan L3 Unit
L4 CD Fan L3 Unit L5 L2 L4 L1
L5 L2 L4 L1
L3 N L2
L3 N L2
L1
L1
N
N
Link L2 – L4
Link L2 – L3
Only required if Fan unit is to be Fan SWL without Controller switched by Integral Sensor for Extract for Intake
CD Fan Unit Only required if Fan unit is to be
230v ~ 50hz 230v ~ 50hz
SWL
L N Double-Pole Isolator
Max 3 amp
L N SWL
Only required if Fan unit is to be
Remote Sensor
230v ~ 50hz 230v ~ 50hz 230v ~ 50hz
Only required if L1 Fan unit L2is toNbe SWL 2-position Fan with Switch
Double-Pole Max Isolator 3 amp
Remote Sensor L1 L2 N
L N Double-Pole
L L N N
Max Max Double-Pole Isolator 3 amp 3 amp Isolator
L
Double-Pole Max Isolator 3 amp
L Double-Pole Max N Isolator 3 amp L N
Link L2 – L4 for Extract L5
L4 CD Fan L3 Unit
L5 L2 L4 L1
L5 L2 L4 L1
L3 N L2
L3 N L2
L1
L1
N
N Link L2 – L3 for Intake
CD Fan Unit
CD Fan Unit
Link L2 – L4 for Extract L5
Link L2 – L3 for Intake L5
L4 L4 CD Fan CD Fan L3 Unit L3 Unit At Installation, set link on Terminal Block Cover L5to L3 to give intake or L2 L5 L2 L4 to give extract. L4 L4 L1 L1 L3 N L2
L3 N L5L2 L4L1 L3 N L2 L1 N
L1 N
N
CD Fan Unit
Switch RC3 L4 Switch L L3 RC3 L2 L4 LN L3L1 N Switch L2 RC3 N L1 L4 N L L3 L2 N L1 N
Fan with Remote Switch RC4 and Remote Remote L1 L2 NSensor
Link L2 – L3 for Intake L5
Link L2 – L4 for Extract
Double-Pole Max Isolator 3 amp
L N
CD Fan Unit
L4 CD Fan L3 Unit
Double-Pole Max Isolator 3 amp
Fan with Remote Switch RC3
230v ~ 50hz 230v ~ 50hz 230v ~ 50hz
Double-Pole Max Isolator 3 amp
L N Double-Pole
Double-Pole Max Isolator 3 amp
Sensor
Switch RC4
L1 L2 N Remote L4 Sensor Switch L L3 RC4 L L2 Double-Pole Max N Isolator 3 amp L4 LN L3L1 L1 L2 N Remote N L Sensor Switch L2 RC4 N L1 N Double-Pole Max L4 N Isolator 3 amp L L3 L L2 N N L1 Only required if Fan unit is to be fitted withN integral ‘TA’ Timer SWL
230v ~ 50hz 230v ~ 50hz 230v ~ 50hz
Switch RC1 230v ~ 50hz 230v ~ 50hz
CXPC Fan Unit
N.B:
SWL
Only requiredMax if Fan unit is to be fitted with integral ‘TA’ Timer Double-Pole
L4 Fan with Isolator Remote3 amp Switch RC4 Switch L and Integral Sensor L3 RC4 L2 L4 L1 N L3 Only required if Fan unit is to be fittedLwith integral ‘TA’ Timer N Switch L2 RC4 L1 N Double-Pole Max L4 N Isolator 3 amp L L3 L2 N L1 N
L Double-Pole Max N Isolator 3 amp
SWL
L N L N
L5 L4 CD Fan Unit L3 L5 L2 L4 L1 L3 N CD L2 Fan Unit L5 L1 L4 N L3 L2 L1 N CD Fan Unit L5 L4 CD Fan Unit L3 L5 L2 L4 L1 L3 N CD L2 Fan Unit L5 L1 L4 N L3 L2 L1 N CD Fan Unit
Switch RC4
230v ~ 50hz 230v ~ 50hz 230v ~ 50hz
230v ~ 50hz 230v ~ 50hz
4
3
L5 L4 CD Fan Unit L3 L5 L2 L4 L1 L3 N CD L2 Fan Unit L5 L1 L4 N L3 L2 L1 N
CD Fan Unit
Greenwood Airvac
Technical Services Tel: 01903 777135
11
Integral Sensor 1
4
7
2
5
8
3
6
9
Remote Sensor/Remote Switch 1
3
5
2
4
6
> 1.5m
> 200mm
Technical Services Tel: 01903 777135
Greenwood Airvac
Superduct Fan SD100
SD150
SD200
SD250
80mm
80mm
80mm
80mm
Dimensions SD100 Front
Front
44mm
Front
44mm
242mm
272mm
344mm
80mm
80mm
80mm
Side
Surface cable entry
Side
Surface cable entry
Front Front Front Front
272mm 272mm 272mm 272mm
242mm mm 242mm
344mm
SD250
44mm44mm 44mm44mm
Front Front Front Front
344mm 344mm 344mm 344mm
344mm 344mm 344mm 344mm
80mm80mm 80mm80mm
80mm80mm 80mm80mm
SideSide SideSide
Front Front Front Front
344mm 344mm 344mm 344mm
230mm 230mm 230mm 230mm
44mm44mm 44mm44mm
402mm 402mm 402mm 402mm
80mm80mm 80mm80mm
SideSide SideSide
SurfaceSurface Surface Surface cable entry cable cable entry cable entry entry
272mm 272mm 272mm 272mm
80mm80mm 80mm80mm
402mm 402mm 402mm 402mm
SideSide SideSide
SurfaceSurface Surface Surface cable entry cable cable entry cable entry entry
198mm 198mm 198mm 198mm
SD315
230mm
344mm 344mm 344mm 344mm
344mm 344mm 344mm 344mm
242mm 2mm
SD100 l SD150 l SD200 l SD250 l SD315
44mm44mm 44mm44mm
80mm80mm 80mm80mm
SurfaceSurface Surface Surface cable entry cable cable entry cable entry entry
344mm
SD315 SD315 SD315 SD315
80mm80mm 80mm80mm
272mm 272mm 272mm 272mm
SideSide SideSide
80mm
Surface cable entry
230mm
80mm80mm 80mm80mm SD200
44mm44mm 44mm44mm
Side
SD250 SD250 SD250 SD250
198mm
80mm80mm 80mm80mm SD150
Front Front Front Front
344mm
272mm
SD200 SD200 SD200 SD200
194mm
344mm
Surface cable entry
242mm
SD150 SD150 SD150 SD150
44mm
344mm
242mm
Side
Front
44mm
272mm
SurfaceSurface Surface Surface cable entry cable cable entry cable entry entry
344mm 344mm 344mm 344mm
230mm 230mm 230mm 230mm
402mm 402mm 402mm 402mm
257mm 257mm 257mm 257mm
Wiring Instructions SD100
Green/Yellow Blue Fan
N
Brown
L
Black
Green/Yellow Black Fan
N
Blue
L
Brown
Capacitor
230 V ~ 50 Hz
SD150, SD200, SD250 & SD315 230 V ~ 50 Hz
m 44mm44mm
12
Capacitor
N.B.: All electrical products should be wired and installed by a qualified electrician, in accordance with IEE or local regulations which apply. The fans must be connected to mains power by using a fused double pole isolating switch having a contact separation of at least 3mm. For other siting applications please refer to supplier data sheets, available on request. Always isolate appliance from the mains before cleaning. Do not use solvents to clean this fan.
Greenwood Airvac
Technical Services Tel: 01903 777135
1
6
11
2
7
12
3
8
13
4
9
14
5
10
15
Technical Services Tel: 01903 777135
13
Greenwood Airvac
14
Cleaning / Maintenance • Always isolate fan from mains before cleaning. • For all fan sizes remove grille and clean in warm soapy water with a non-abrasive cloth. • The impeller can be removed by carefully pulling the fan blades from either side at the same time. These are to be cleaned in the same way as the above. • The rear shutters can be cleaned but care must be taken when removing and replacing. • Ensure that the shutter blades pins are correctly seated on the outside rim. • Remove shutters via the retaining screws (3 will be found on the 6” and 9” models, 7 will be found on the 12” model). Once removed, the shutter assembly can be cleaned in warm soapy water and must be dried thoroughly before replacing. • When replacing ensure that the shutter assembly blades are fully closed and that the assembly, as a whole, is correctly seated before tightening the screws. • When the shutter assembly has been replaced, ensure that the shutter blades are free to open by placing a hand on either side of the shutter assembly blades and carefully opening. • Once the interior grille shutter assembly has been cleaned, the fan’s main housing can be wiped with a clean damp, non-abrasive cloth.
Greenwood Airvac
Technical Services Tel: 01903 777135
15
EC Declaration of Conformity/Incorporation In accordance with EN ISO 17050-1:2004
Greenwood Air Management Ltd Greenwood House, Brookside Avenue, Rustington, West Sussex, BN16 3LF, UK
We Of
In accordance with the following Directive(s): 2004/108/EC 2006/42/EC
The Electromagnetic Compatibility Directive The Machinery Directive
hereby declare that: Equipment Model Number
Ventilation Fan CD6 / ENERGY 500VE / CD9 / ENERGY 900VE / CD12 / ENERGY 1800VE
Is in conformity with the applicable requirements of the following documents Ref. No. Title BS EN ISO 12100- Safety of machinery. Basic concepts, general principles for design BS EN 60335-1
Household and similar electrical appliances. Safety. General requirements BS EN 60335-2-80 Household and similar electrical appliances. Safety. Particular requirements for fans BS EN 61000-6-1 Electromagnetic compatibility (EMC). Generic standards. Immunity for residential, commercial and light-industrial environments BS EN 61000-6-3 Electromagnetic compatibility (EMC). Generic standards. Emission standard for residential, commercial and light-industrial environments
Edition/date 2003 =A1:2009 1&2 2002+A2:2006 2003 2007 2007
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced specifications and is in accordance with the requirements of the Directive(s)
Signed by: Name:
John Barratt
(full name of signatory)
Position: Business Process Manager
(position)
Done at:
As above
(place)
On :
02 February 2012
(date)
The technical documentation for the machinery is available from the manufacturer at the above address.
Technical Services Tel: 01903 777135
Greenwood Airvac
Greenwood Air Management Ltd Greenwood House, Brookside Avenue, Rustington, West Sussex BN16 3LF Main Line Tel: +44 (0) 1903 771021 Technical Services: +44 (0) 1903 777135 Main Line Fax: +44 (0) 1903 782398 Web: www.greenwood.co.uk Email:
[email protected]
P541/132 Iss H May 2012 MCR708 PN05.10.114