Logic
GuardPLC™ Safety Control Systems
The safety relay output module can provide dry contact enable signals as well as high current AC or DC outputs. The 8 input/8 output and 16 input/8 output digital combination modules feature both positive and negative switching outputs, for applications that use diverse outputs. The analog input module lets you distribute analog inputs for more process-oriented safety applications. All I/O modules include GuardPLC 100 Mbps Ethernet, which provides one of the fastest safety networks and machine stop times in the industry. The built-in two-port Ethernet switches make connecting I/O modules to the GuardPLC controller as easy as daisy-chaining Ethernet cable from I/O module to controller. Take advantage of all the benefits of traditional distributed I/O with GuardPLC distributed safety I/O, available for all GuardPLC systems.
Place the I/O where the devices reside. Reduce wiring costs and the time necessary to wire the machine or cell. Reduce machine or cell start up time. Increase machine and cell reliability.
9-
GuardPLC distributed I/O modules provide considerable flexibility in configuring the right mix of I/O in the right place. The 16 digital input module offers 4 pulse test source terminals, allowing users to pulse test all 16 digital inputs from the I/O module and providing PLe/Category 4 capable safety circuitry while retaining all the
Benefits
Principles
advantages of distributed I/O. The 16 digital output module is rated for 2A on every other output point, limiting the need for additional interposing safety relays for additional current and therefore saving on machine costs.
Distributed Safety I/O for GuardPLC Ethernet
General
Distributed Safety I/O for GuardPLC Ethernet
Digital Safety I/O Module Specifications 1753-IB16XOB8
1753-IB20XOB8
Description
GuardPLC Digital Combination Module
GuardPLC Digital Combination Module
GuardPLC Digital Combination Module
GuardPLC Digital Output Module
1753-OB16
Operating Voltage Range
24V DC, -15%…+20%, wss 15%1
24V DC, -15%…+20%, wss 15%1
24V DC, -15%…+20%, wss 15%1
24V DC, -15%…+20%, wss 15%1
24V DC, -15%…+20% wss 15%1
Number of Digital Inputs
16 safety
8 safety
16 safety
20 safety
—
Voltage, On-State Input, Nom.
24V DC
24V DC
24V DC
24V DC
—
—
8 positive-switching and 2 negative-switching safety
8 positive-switching and 8 negative-switching safety
8 safety
16 safety
Current, On-State Output, per Channel
—
L+ Channels 1…3, 5…7: 0.5 A @ 60 °C (140 °F) L+ Channels 4 and 8: 1 A @ 60 °C (140 °F), 2 A @ 40 °C (104 °F) L- Channels 1 and 2: 1 A @ 60 °C (140 °F), 2 A @ 40 °C (104 °F)
Channels 2, 4, 5 and 7: 0.5 A @ 60 °C (140 °F) Channels 1 and 8: 1 A @ 60 °C (140 °F), 2 A @ 40 °C (104 °F) Channels 3 and 6: 1 A @ 60 °C (140 °F)
Channels 1…3, 5…7: 0.5 A @ 60 °C (140 °F) 1 A @ 60 °C (140 °F) Channels 4 and 8: 1 A @ 2 A @ 40 °C (104 °F) 60 °C (140 °F), 2 A @ 50 °C (122 °F)
Voltage, On-State Output, Max.
—
Supply Voltage (L+)
Supply Voltage (L+)
Supply Voltage (L+)
Supply Voltage (L+)
4
2
2
—
—
0…60°C (32…140°F)
0…60°C (32…140°F)
0…60°C (32…140°F)
0…60 °C (32…140 °F)
Digital Inputs
Digital Outputs Number of Digital Outputs
10-Safety Applications
1753-IB16
11-Cat. No. Index
1753-IB8XOB8
GuardPLC Digital Input Module
Cat. No.
Number of Pulse Test Sources General Temperature, operating
0…60° C (32…140° F)
Temperature, nonoperating
-40…85 °C (-40…185 °F) -40…85 °C (-40…185 °F) -40…85 °C (-40…185 °F) -40…85 °C (-40…185 °F) -40…85 °C (-40…185 °F)
Dimensions (HxWxD), Metric
114 x 152 x 78 mm‡
114 x 152 x 78 mm‡
114 x 205 x 100 mm‡
114 x 207 x 78 mm‡
114 x 207 x 78 mm‡
Dimensions (HxWxD), Imperial
4.49 x 5 99 x 3.07 in‡
4.49 x 6.00 x 3.07 in‡
4.49 x 8.08 x 3.94 in‡
4.49 x 8.16 x 3.07 in‡
4.49 x 8.16 x 3.07 in‡
5-Programmable Safety Solutions
Pulse Test Sources
1 Requires a power supply with protective separation, conforming to IEC 61131-2 requirements.
Power
Not electrically isolated. ‡ Height including latch; width including housing screws; depth including grounding bolt and connectors.
Visit our website: www.ab.com/catalogs Publication S117-CA001A-EN-P
5-129
06_ProgSafetySolutions
5/6/2010
11:50 AM
Page 5-130
Logic
GuardPLC™ Safety Control Systems Distributed Safety I/O for GuardPLC Ethernet Digital Relay Safety Output Module Specifications 1753-OW8
Cat. No.
General
Description
GuardPLC Digital Relay Output Module
Number of Outputs
8 safety relay
Operating Voltage Range
24V DC, -15%…+20% wss 15%1
Switching Voltage
5…250 V AC/ DC
Switching Current
• UL: 24V DC @ 1A resistive load, 250V AC @ 6 A general purpose • TUV: up to 240VA (for V AC), up to 30V DC @ 90 W, up to 70V DC @ 35 W, up to 127V DC @ 30 W
Service Life, Mechanical
≥106 switching cycles
Principles
Temperature, operating
0…60 °C (32…140 °F)
Temperature, nonoperating
-40…+85 °C (-40…+185 °F)
Dimensions (HxWxD), Metric
114 x 207 x 98 mm
Dimensions (HxWxD), Imperial
4.49 x 8.16 x 3.86 in
‡ External fusing adapted. 1 Requires a power supply with protective separation, conforming to IEC 61131-2 requirements. Height including latch; width including housing screws; depth including grounding bolt and connectors.
Analog Safety I/O Module Specifications 1753-IF8XOF4
Cat. No. Description
GuardPLC Analog Combination Module
9-
10-Safety Applications
Operating Voltage Range
24V DC, -15%…+20%, wss 15%1
Number of Safety Analog Inputs
8
Input Signal Range
Nominal: 0…+10V DC or 0…20 mA (with shunt) Service: -0.1…+11.5V DC or -0.4…23 mA (with shunt)
Input Impedance
Analog Input: >2 MΩ
Input Resolution
12 bit
Accuracy
0.5%
Number of Analog Outputs (Standard)
4‡
Output Signal Range
4…20 mA 0…20 mA
Output Impedance
Current Output: 600 Ω max.
Temperature, operating
0…60°C (32…140°F)
Temperature, nonoperating
-40…85 °C (-40…185 °F)
Dimensions (HxWxD), Metric
114 x 207 x 111 mm
Dimensions (HxWxD), Imperial
4.49 x 8.16 x 4.37 in
11-Cat. No. Index
‡ Non-safety-related with common safety switch-off. 1 Requires a power supply with protective separation, conforming to IEC 61131-2 requirements.
Height including latch; width including housing screws; depth including grounding bolt, connectors, and shield plate.
5-Programmable Safety Solutions
Power Visit our website: www.ab.com/catalogs
5-130
Publication S117-CA001A-EN-P