Original Operating Instructions
AERO
AEROVITAL
Wall mounted ventilator with heat recovery.
Window systems Door systems Comfort systems
Original operating instructions AEROVITAL
Contents Target group of this documentation................................................................................................................................................. 4 Intended use..................................................................................................................................................................................... 4 Safety notices................................................................................................................................................................................... 5 Scope of delivery............................................................................................................................................................................. 5 Installation........................................................................................................................................................................................ 6 Unit description..............................................................................................................................................................................12 Function..........................................................................................................................................................................................14 Commissioning...............................................................................................................................................................................15 Operation (general)......................................................................................................................................................................15 Program overview..........................................................................................................................................................................17 Programming..................................................................................................................................................................................18 Care and maintenance..................................................................................................................................................................20 Accessories....................................................................................................................................................................................22 Technical data................................................................................................................................................................................23 Dimensions.....................................................................................................................................................................................24 Liability...........................................................................................................................................................................................25 Feedback on documentation.........................................................................................................................................................25 EU Declaration of Conformity.......................................................................................................................................................26
03.2016
3
AEROVITAL
Original operating instructions
Target group of this documentation This documentation is intended for use by specialists only. All work described in this document is to be performed by experienced professionals with training and practice in the assembly, installation and maintenance of ventilation units. Safe and proper assembly of this unit is not possible without expert knowledge.
Intended use • Use the AEROVITAL only for the ventilation of closed rooms (kitchen, bathroom, living room and bedroom). • The AEROVITAL is not suitable for dehumidification (e. g. for drying new buildings). • The unit must always be installed by an experienced specialist, in accordance with the installation and planning documents of SIEGENIA. The installation instructions in this document must be complied with at all times. • Be sure to attach the supplied SIEGENIA weather grille to protect the unit from the outside. • Do not install the unit in contaminated rooms and ensure that no hazardous substances can be drawn in. • The unit is not suitable for use in swimming pools and/or damp locations. • The AEROVITAL may only be mounted in a vertical position. The unit may not be installed on diagonal surfaces (e. g. walls/ceilings). • If the unit is to be used in a room with a heating unit that draws air from the room, prior authorisation must be obtained from the proper authorities, such as the officially appointed district chimney sweep. • Only operate and/or store the AEROVITAL at temperatures between -15 °C and +40 °C. • Use the device only with original accessories from SIEGENIA. • Observe the safety regulations for working with ladders, steps, overhead work and work at particular heights. • Use the device only when it is in a technically sound condition. • Do not modify the unit‘s components in any way. • Please do not put any objects on top of the unit. • Do not use the unit as a seat. • Ensure that the air can flow in and out freely at the two outer sides. Do not hang any textiles, paper or similar objects over the air inlets or outlets and do not place any objects directly in front of or next to the unit. Do not insert objects into the openings of the unit. • Do not remove any covers or unit components except as described in the chapter „Maintenance“. Do not remove the cover of the connecting clamps inside the unit. • The device must be checked by a specialist in the event of a fault.
4
03.2016
Original operating instructions AEROVITAL
Safety notices • This unit can be used by children aged 8 and above as well as by people with physical, sensory or mental difficulties or with a lack of experience and knowledge as long as they are supervised or have been instructed in how to use the unit safely and understand the resulting risks. Children must not play with the unit. Cleaning and user maintenance must not be carried out by children without supervision. Electrically operated device. Risk of fatal injury from electric shock or fire. To prevent personal injury or damage to property, always comply with the following instructions:
› ›
Only insert the Euro plug of the standard connecting cable into a suitable 230 V AC socket.
›
nly a qualified electrician may perform any work on the 230 V AC mains power supply that is required in order to O connect the device.
› › ›
All-pole safety isolation is required if the customer is fitting the mains cable.
›
hould a solid object or any liquid get inside the device, stop operation immediately and disconnect the device from the S mains power supply.
I f the mains connection cable for the device is damaged, it must be replaced by SIEGENIA, the company‘s customer service department, or similarly qualified personnel in order to prevent personal injury or damage to property.
Current local regulations (such as those of the VDE in Germany) must be observed. R elevant country-specific regulations must be strictly followed for all work carried out on the voltage supply system or house wiring system.
Scope of delivery AEROVITAL
Pipe
Remote control
Drilling template
Top and bottom blower unit
4 Screws 5 x 120 4 Dowel S8 ORIGINAL BETRIEBSANLEITUNG
Weather grille
AERO
AEROVITAL
Original operating instructions
Fenstersysteme Türsysteme Komfortsysteme
Adhesive tape
03.2016
5
AEROVITAL
Original operating instructions
Installation Risk of damage to property by drilling through concealed cables or pipes!
›
Before installing the unit, use a suitable cable and pipe detector at the installation location to identify the presence of concealed cables or pipes in the wall (such as water pipes).
Step 1 (only for in-wall mounting): preparation of wall recess 1. Make the wall recess according to the adjacent diagram. Note: The surface must be level (plastered).
462 m
75
mm
min. 350 mm
75 mm
437 mm
m
Step 2: Marking drill holes With in-wall mounting and permanent electrical connection 1. Cut out the drilling template along the dotted line for in-wall mounting. 2. Cut out an opening in the drilling template at the point marked with a cross and draw the end of the cable through the opening. 3. Align the drilling template with a spirit level, if necessary, and fix into place. 4. Mark four fastening drill holes and core drill hole on the wall. Notes: • The surface must be level (plastered).
300 mm 150 mm
• The entire free cable length should be 300 mm, of which 150 mm must be without outer sheathing.
6
03.2016
Original operating instructions AEROVITAL
On-wall mounting 1. Align the drilling template with a spirit level and fix into place. 2. Mark four fastening drill holes and core drill hole on the wall. Notes: • The surface must be level (plastered). • The maximum distance from the outer edge of the template to the next socket should not exceed 300 mm.
Step 3: Drilling the core hole and mounting holes 1. Drill core hole (ø 120+3). Using a hammer drill at an angle of approx. 2° to 5°, drill a hole through to the outside wall. +3
ø120
2. Drill the four marked mounting holes (all drill holes ø 8 mm, at least 45 mm deep). 3. Insert four S8 dowels (included in delivery) into the drilled holes. Note: depending on the type of wall (e.g. plasterboard), suitable dowels may need to be provided by the customer for inserting into the drill holes.
Step 4: Trimming the PVC ventilation pipe 1. Trim pipe according to the formula: X = Y – 43 mm (on-wall mounting) X = Y – 118 mm (in-wall mounting)
03.2016
X
Y
Y
on-wall mounting
in-wall mounting
7
AEROVITAL
Original operating instructions
Step 5: Fixing the pipe to the socket piece 1. Push the pipe side with the recessed middle bar onto the socket piece of the ventilation unit until the pipe is firmly seated. 2. Fix the transition point with the adhesive tape included in the delivery. Pipe and socket piece must be firmly connected.
Step 6: Removing the front panel 1. Insert screwdriver into the left and then the right opening of the front panel until the underlying snap connection is released at both sides.
2. Fold the front panel forwards, unhinge and set down on the side.
8
03.2016
Original operating instructions AEROVITAL
Step 7: Routing the cables With permanent electrical connection (a) 1. Lift the ventilation unit and push a small section of the attached pipe into the wall opening. 2. Draw the cable through the opening at the rear of the ventilation unit.
a
For socket connection (b) 1. Route the connecting cable in the cable duct in a clockwise or anticlockwise direction. Note: The cable must be neatly laid in the cable duct to prevent it from being squeezed or carried through during the installation.
b
Step 8: Screwing the ventilation unit to the wall 1. Lift the ventilation unit and push the attached pipe through the wall opening. 2. Press the ventilation unit firmly against the wall and fasten with four screws. 3. Seal around the connection of the ventilation unit to the wall with permanently elastic sealing compound.
03.2016
9
AEROVITAL
Original operating instructions
Step 9: Connecting the cable to the clamping block (only for permanent electrical connection) 1. Remove screws and cover. 2. Connect the cable to the clamping block. 3. Put on the cover and screw firmly into place. Note: Route the cable through the top breakthrough on the terminal box.
Step 10: Inserting the blower units 1. Insert the top and bottom blower unit and press slightly against the contacts. Note: The blower units are retained in this position after the front panel has been mounted.
Yellow round label Spring-loaded PVC pin
Step 11: Inserting the foam strips 1. Press the foam strips into the hollow cavity between the casing and the top blower unit. Note: The second foam strip must not project over the front edge of the front panel.
10
03.2016
Original operating instructions AEROVITAL
Step 12: Closing the front panel and testing the function 1. Hook the front panel into the ventilation unit. 2. Press the front panel with both your hands until you hear the snap connection engage. 3. Plug the Euro plug into the socket, or switch on the fuse of the electrical circuit in the case of permanent electrical connection. 4. Press the On/Off button beside the display to test the function of the ventilation unit. 5. After the successful test, switch off the device. Note: Check the correct seating of the front panel if the ventilation unit is not functioning.
Step 13: Mounting the weather grille 1. Apply permanently elastic sealing compound to the outer edge of the pipe and mount the weather grille. 2. Press the weather grille firmly against the pipe. Two clamps must be seated above the middle bar and one below. Notes: • Ensure that the lamella of the weather grille are facing downwards. • There must not be any gaps at the transition point between the pipe and the house wall.
03.2016
11
AEROVITAL
Original operating instructions
Unit description AEROVITAL 1. Housing base 2. Display 3. Infrared receiver 4. Button 5. Housing frame 6. Front panel 7. Air inlet and outlet with closing caps 8. Cable duct 9. Socket piece 10. Mains cable with Euro plug
1.
2.
3.
4.
5.
6. 7.
8.
1.
5.
7.
9. 10.
12
03.2016
Original operating instructions AEROVITAL
Infrared control 1. Infrared transmitter (range approx. 5 m at direct visual contact to the AEROVITAL) 2. Reduce air flow (P1) Reduce humidity/temperature values and basic ventilation level (P2/P3) 3. Increase air flow (P1) Increase humidity/temperature values and basic ventilation level (P2/P3) 4. On / Off Programmable function buttons 5. P1: Pollen protection (manual control) 6. P2: Humidity control 7. P3: Humidity and/or room temperature control
1. 2.
3. 4.
5.
7. 6.
Display All symbols will not be displayed simultaneously in normal mode.
Room temperature in degrees Celsius (measuring range from 0°C to 99°C) Relative room humidity in % (measuring range from 30% to 90%) Air flow level (ten possible levels) Mode of operation (programs) P1 Manual ventilation (pollen protection) P2 Automatic ventilation (humidity control) P3 Automatic ventilation (humidity and/or room temperature control) Operation of blower units Filter replacement required Note! The filter is monitored by the current consumption of the unit. If the unit is continually operated at air flow level 1 or 2, the AEROVITAL-processor will switch to air flow level 5 for approx. two minutes every 8 hours in order to check the filter for measuring reasons. The unit then automatically switches back to the previously set air flow level.
03.2016
13
AEROVITAL
Original operating instructions
Function Features • Simultaneous aeration and deaeration • Filters pollen and dust • Filtering of exhaust air • Heat recovery • Sound absorption of external noise • Low internal noise Ventilation In ventilation mode, the AEROVITAL aerates and deaerates simultaneously. To achieve this, the unit has two internal separate air routes and two separate blower units. Room air is drawn into the two top air inlets (a), filtered, guided through the heat exchanger and discharged to the outside. Fresh air is drawn from outside, filtered, guided through the heat exchanger and conveyed into the room through the two bottom air outlets (b).
a a
b b
Ventilation elements The heat exchanger absorbs part of the heat in the discharged room air and heats up the fresh air supplied. You can fold out the heat exchanger to exchange the filter unit in the heat exchanger.
The filter unit consists of a cassette filter (filter grade F7) which filters over 97% of the pollen from the fresh air and a fleece filter which filters the room air. The two filters reduce the contamination of the heat exchanger and the blower units. Required filter exchange is indicated by the symbol „ “ in the display of the AEROVITAL. The performance of the supply air and the exhaust air blower unit and consequently the air flow is variable in ten levels. If the AEROVITAL is switched off, the two blower units are out of operation.
14
03.2016
Original operating instructions AEROVITAL
Commissioning Electrically operated unit. Risk of fatal injury from electric shock or fire.
›
The AEROVITAL is connected directly to the 230-V AC mains power supply. However, the voltage is transformed to 12 V low voltage in the unit. In case of overload, a safety device (thermal overload protection) in the transformer disconnects the unit from 230 V AC mains power supply and automatically switches on again when the overload has been rectified.
›
A safety switch is also integrated for maintenance purposes. If the front panel is removed, the safety switch cuts off the supply voltage.
To prevent personal injury or damage to property, always comply with the following instructions:
› ›
The power supply terminals supply 230 V AC even when the front panel has been removed. Do not remove the cover of the connecting clamps behind the top housing unit.
Following the successful installation and electrical connection of the AEROVITAL, the unit can be commissioned. • The Euro plug of the mains cable must be properly connected to the 230 V AC mains power supply via a power socket. If the unit has been permanently connected to the 230 V AC mains power supply, the safety device belonging to this electrical circuit must be switched on. • Remove any transport and mounting aids prior to the commissioning.
Operation (general) Closing flaps
› ›
Open the closing flaps (a), before the AEROVITAL is switched on. Shut the closing flaps (b), before the AEROVITAL is switched off for a longer period.
a b
03.2016
15
AEROVITAL
Original operating instructions
Basic functions • The infrared receiver receives the signals from the remote control and transmits these to the unit control.
AEROVITAL
• The activated air flow levels are indicated by the corresponding number of bars in the display.
Infrared receiver Button
• On activation, the AEROVITAL always starts in pollen protection program P1. After voltage breakdown (e. g. power failure), the AEROVITAL will automatically start in the most recently used program (P1, P2 or P3). • During the commissioning, the AEROVITAL starts at air flow level 5 (factory setting). Later, the unit will start at the most recent set air flow level when switched on. Buttons on the unit Set the required air flow level by briefly pressing the button. Switch sequence Unit is switched off
Air flow level 2
Air flow level 4
Air flow level 10
Unit is switched off
...
Remote control The desired function can be carried out when the corresponding button is briefly pressed. Button Function
Comments
Switch on unit
• Unit always starts in pollen protection program P1
Switch off unit
• Ventilation unit off
Increase air flow level
• Air flow is increased in stages (max. level 10) • Function is only available in program P1
Increase desired air humidity or room temperature and • Function is only available in program P2 and P3 basic ventilation level Reduce air flow level
• Air flow is reduced in stages (min. level 1) • Function is only available in program P1
Increase desired air humidity or room temperature and • Function is only available in program P2 and P3 basic ventilation level
16
03.2016
Original operating instructions AEROVITAL
Program overview • Three programs can be selected which can be programmed via remote control. • If a longer pause occurs during the programming (approx. 30 seconds), without the programming having been completed, the AEROVITAL will automatically switch back to the most recent operating mode. Changed values will not be saved. Program P1
P2
Function P3 Manual control of air flow level Humidity control If the air humidity in the room falls below the set value, the unit will automatically switch to basic ventilation. If the air humidity in the room exceeds the set value, the air flow level will automatically increase. Attention! If, however, the outside air has a higher humidity than the room air, the AEROVITAL will only operate in basic ventilation mode. • Background: Otherwise the air humidity in the room would continue to rise due to the humid outside air. • Recommendation: On especially humid days, manual control of the unit is recommended because outside air will still enter the room via the basic ventilation. Room temperature control If the room temperature falls below the set value, the unit will automatically switch to basic ventilation. If the room temperature exceeds the set value, the air flow level will automatically increase. Attention! If, however, the outside air has a higher temperature than the room air, the AEROVITAL will only operate in basic ventilation mode. • Background: Otherwise the room temperature would continue to rise due to the warm outside air. • Recommendation: On especially hot days, manual control of the unit is recommended because outside air will still enter the room via the basic ventilation. Humidity and room temperature control If the air humidity in the room and the room temperature fall below the set value, the unit will automatically switch to basic ventilation. If the air humidity in the room and the room temperature exceed the set value, the air flow level will automatically increase. Attention! If, however, the outside air has a higher humidity than the room air or if the outside air has a higher temperature than the room air, the AEROVITAL will only operate in basic ventilation mode. • Background: Otherwise the air humidity in the room or the room temperature would continue to rise due to the humid or hot outside air. • Recommendation: On especially humid or hot days, manual control of the unit is recommended because outside air will still enter the room via the basic ventilation.
03.2016
17
AEROVITAL
Original operating instructions
Programming P1 Pollen protection The air flow level can be set manually using the buttons (see „Basic functions“ auf Seite 16).
or
the remote control, or with the button on the AEROVITAL
P2 Humidity control The AEROVITAL ventilates continually in basic ventilation and automatically elevates the air flow level as soon as the defined humidity values are exceeded. • The air flow level (1 to 4) for the basic ventilation is freely selectable • The desired room humidity can be set at between 30% and 90%. Example of programming The AEROVITAL should operate at air flow level 2 in basic ventilation mode and increase the air flow level automatically from a room humidity of 58%. Step
Button (press briefly)
Function
1
P2
A flashing value of the relative air humidity will appear in the display. Factory setting: 55%.
Keep pressed down for approx. 5 seconds 2
3
4
5
or Press briefly or keep pressed down P2
or Press briefly or keep pressed down P2
Display
The numerical value is increased (+) or reduced (—) in increments
A flashing blower symbol will appear in the display.
The air flow level is increased (+) or reduced (—) in increments
The new values will be stored (the display will briefly flash 2x).
• The program (P2) will now run with the newly set values. • The display shows the current measured values for room temperature and room humidity. • When the P2 button is pressed briefly, the programmed values will be displayed for approx. 3 seconds.
18
03.2016
Original operating instructions AEROVITAL
P3 Humidity and/or room temperature control The AEROVITAL ventilates continually in basic ventilation and automatically elevates the air flow level as soon as the defined values are exceeded. • The air flow level (1 to 4) for the basic ventilation is freely selectable • The desired room humidity can be set at between 30% and 90%. • The desired room temperature can be set at between 10°C and 50°C. • If only the room humidity is to be controlled, the room temperature must be set at 0°C. • If only the room temperature is to be controlled, the room humidity must be set at 0%. Example of programming The AEROVITAL should operate at air flow level 2 in basic ventilation mode and increase the air flow level automatically from a room humidity of 65% or a room temperature of 25°C. Step
Button (press briefly)
Function
1
P3
A flashing value of the room temperature will appear in the display. Factory setting: 0°C
Keep pressed down for approx. 5 seconds 2
3
4
5
6
7
or Press briefly or keep pressed down P3
or Press briefly or keep pressed down P3
or Press briefly or keep pressed down P3
Display
The numerical value is increased (+) or reduced (—) in increments
A flashing value of the relative air humidity will appear in the display. Factory setting: 55%. The numerical value is increased (+) or reduced (—) in increments
A flashing blower symbol will appear in the display.
The air flow level for the basic ventilation is increased (+) or reduced (—) in increments
The new values will be stored (the display will briefly flash 2x).
• The program (P3) will now run with the newly set values. • The display shows the current measured values for room temperature and room humidity. • When the P3 button is pressed briefly, the programmed values will be displayed for approx. 3 seconds.
03.2016
19
AEROVITAL
Original operating instructions
Care and maintenance Electrically operated unit. Risk of fatal injury from electric shock or fire. To prevent personal injury or damage to property, always comply with the following instructions:
›
Disconnect the mains plug out from the socket before you clean or service the unit. Do not pull on the cable to disconnect the unit from the mains power supply.
›
Switch off all poles of the feeder on units with permanent connection to 230 V AC mains power supply. The fuses may need to be removed.
Cleaning Important: When cleaning the AEROVITAL, do not allow liquids to get inside the unit. • Never use cleaning agents that are aggressive or contain solvents or sharp-edged objects, as these may damage the surfaces of the casing. • Never clean the unit with a high-pressure cleaner or steam-jet cleaner. • Clean the AEROVITAL with a cloth moistened with a mild soap solution or cleaning agent. Battery replacement remote control If, when a button is pressed, no function is carried out, the batteries must be replaced. 1. Open the cover of the battery compartment and remove the used batteries. Note: The battery compartment is located at the rear of the remote control. 2. Used batteries must be disposed of in an environmentally safe manner. 3. Insert the new batteries (see marking at the base of the battery compartment for the direction). Note: 2 batteries, e. g. type Micro, type LR03 or equivalent 4. Close the battery compartment.
20
03.2016
Original operating instructions AEROVITAL
Replacing the filter • The filter should be replaced whenever this is indicated in the display - every 6 months, at the latest. • Only use genuine filters from SIEGENIA. You can purchase replacement filters from SIEGENIA or from specialist retailers. Caution! Only activate and remove the specified unit components. 1. Insert a screwdriver into the left and then the right opening of the front panel until the underlying snap connection is released at both sides.
2. Fold the front panel forwards, unhinge and set down on the side.
3. Fold the heat exchanger forwards.
03.2016
21
AEROVITAL
Original operating instructions
4. Remove the filter from the heat exchanger and dispose of it in the household waste.
5. Insert the new filter into the heat exchanger. Note: The front cardboard strip on the filter cassette must be inserted between the two aluminium edges (a + b). The upper edge of the cardboard strip must close under the top aluminium edge. The bottom edge of the fleece filter must be pressed behind the bottom aluminium edge (c). 6. Reassemble the AEROVITAL in the reverse order. Note: Check the correct seating of the front panel if the AEROVITAL does not function at once after the filter exchange.
a b
c
Accessories
22
Material description
Material number
Spare filter F7 (three-layer, synthetic composite filter)
L5300220-096110
03.2016
Original operating instructions AEROVITAL
Technical data AEROVITAL Internal noise (measured according to DIN EN ISO 3745) Power consumption Heat recovery efficiency (DiBT) Sound absorption (measured according to DIN EN 10140-2) Electrical connection Protection class Weight Fresh air filter
Level 1 Level 4 Level 10 Level 1 Level 4 Level 10 max. 73 % Dn,e,w = 51 dB
LPA = 23 dB (A) LPA = 30 dB (A) LPA = 40 dB (A) 10 watts 17 watts 32 watts
230 V∼ / 0,17 A II 12,5 kg Filter grade F7 (3-layer, synthetic composite filter)
Product fiche (in accordance with EU regulation 1254/2014) a producer b model identifier c energy consumption (SEC) energy consumption class (SEC class) (per climate zone: warm / average / cold) d typology e type of drive f heat recovery system g thermal efficiency h maximum flow rate i electric power input j sound power level k reference flow rate l reference pressure difference m specific power input n control factor / control typology o maximum internal and external leakage rates (internal / external leakage) p mixing rate (inside / outside) q instructions to change filter r instructions to install supply/exhaust grilles (with unidirectional ventilation systems) s dis-assembly instructions t the airflow sensitivity to pressure variations (at + 20 Pa and - 20 Pa) u the indoor/outdoor air tightness v the annual electricity consumption (in kWh electricity/a) w the annual heating saved (in kWh primary energy/a)
03.2016
SIEGENIA AEROVITAL ― 9,5 kWh/(m² · a); F ― 30,6 kWh/(m² · a); B ― 67,5 kWh/(m² · a); A+ RVU / BVU variable speed drive recuperative 54 % 60 m³/h 32 W 42 dB (A) 43 m³/h ― 0,51 W/(m³/h) 1,21 / 0,65 ―1%/7% 1,9 % / 21 % „Replacing the filter“ see page 21 ― ― 15 % / 14 % 2,5 m³/h 3,4 kWh/a 17,4 kWh/a 38,5 kWh/a 75,4 kWh/a
23
AEROVITAL
Original operating instructions
Dimensions
24
03.2016
Original operating instructions AEROVITAL
Liability Intended use Any use of this product that is not in accordance with its intended use, or any adaptation of or modification to the product and its associated components for which our express consent has not been obtained, is strictly prohibited. We accept no liability whatsoever for any material losses or injury to people caused by failure to comply with this stipulation. Product liability Our products are guaranteed – subject to correct installation and proper use – for a period of one year from the date of receipt by a company (according to our general terms and conditions) or as otherwise agreed, and for a period of two years for end consumers, in accordance with statutory provisions. As part of our ongoing improvements, we reserve the right to replace individual components or entire products. Consequential losses resulting from defects are excluded from the warranty within the limits of the law. The warranty shall become void if modifications that are not authorised by us or have not been described in this documentation are performed on the product and/or individual components, or if the product and/or individual components is/are dismantled or partly dismantled, and the defect is due to the changes made. Exclusion of liability The product and its components are subject to stringent quality controls. As a result, they function reliably and safely when used correctly. Our liability for consequential losses and/or claims for damages is excluded, except in the case of wilful misconduct or gross negligence, or where we are responsible for injury to life, limb or health. Strict liability under the German Product Liability Act (Produkthaftungsgesetz) remains unaffected. Liability for the culpable violation of significant contractual obligations also remains unaffected; liability in this case is limited to losses that are specific to the contract and that could have been foreseen. The above regulations do not imply a change in the burden of proof to the detriment of the consumer. Environmental protection Although our products do not fall within the scope of the German Electrical and Electronic Equipment Act, SIEGENIA will continue to meet the requirements of this Act and will endeavour to completely eliminate the use of substances that are hazardous to the environment as soon as this becomes technically feasible. Electrical products should not be disposed of as household waste.
Feedback on documentation We welcome your comments and suggestions on how to improve our documentation. Please email your comments to
[email protected].
03.2016
25
AEROVITAL
Original operating instructions
EU Declaration of Conformity In terms of the EG Directive Electromagnetic Compatibility 2004/108/EC and 2006/42/EC SIEGENIA-AUBI KG Hardware and ventilation technology Duisburger Straße 8 D-57234 Wilnsdorf declares that the product: Ventilation unit unit type AEROLIFE / AEROVITAL Designation of type is compliant with the following standards or normative documents: EN 55014-1 :2006 EN 55014-2 :1997+A1 EN 61000-3-2 :2006 EN 61000-3-3 :1995+A1,A2 EN 60335-1 :2010 EN 60335-2-80 :2003+A1 :2004, EN 62233 :2008 EN 62233 Br.1 :2008, EN 62233 :2008-11 EN ISO 12100:2010 RoHS 2011/65/EU This declaration is based on test reports from: EMC TestHaus Dr. Schreiber GmbH - Test protocol 14/317
Siegen, 2014-11-03
S. Bauerdick (site manager)
The technical documents will be provided by SIEGENIA-AUBI KG. This declaration certifies conformity with the directives cited but does not warrant properties in the legal sense. The safety instructions in the product documentation supplied must be followed.
26
03.2016
Head Office:
Phone: +49 271 3931-0
Industriestraße 1–3
Telefax: +49 271 3931-333
57234 Wilnsdorf
[email protected]
GERMANY
www.siegenia.com
SIEGENIA worldwide:
Hungary Phone: +36 76 500810
Austria Phone: +43 6225 8301
Italy Phone: +39 02 9353601
Belarus Phone: +375 17 3143988
Poland Phone: +48 77 4477700
Benelux Phone: +31 85 4861080
Russia Phone: +7 495 7211762
China Phone: +86 316 5998198
South Korea Phone: +82 31 7985590
France Phone: +33 3 89618131
Switzerland Phone: +41 33 3461010
You can find address details for our
Germany Phone: +49 271 39310
Turkey Phone: +90 216 5934151
international sites at: www.siegenia.com
Great Britain Phone: +44 2476 622000
Ukraine Phone: +380 44 4637979
H47.WANS003EN/2