Preview only show first 10 pages with watermark. For full document please download

Heat Exchanger Cleaning Technical Service Bulletin

   EMBED


Share

Transcript

Bulletin Number: TBG-42 | Model: GB142 series boilers Technical service bulletin Heat Exchanger Cleaning  Heat Exchanger Cleaning Procedure  Switch off the power supply of the heating system on the circuit breaker.  Set the main switch on the BC10 to “0” (Off).  Remove the casing.  Close the gas shut-off valve (see fig. 1, pos. 1). Remove the cable plug from the gas control valve (see fig. 3). Figure 3 Figure 1  Closed Remove both cable plugs [Fig.4, pos.1] from the fan unit. Figure 4 Open  Loosen the union nut of the gas control valve (see fig. 2, pos. 1). Figure 2 1  Pull down on both retaining clips [Fig.5, pos.1] to open and remove the burner cover. Figure 5 1 1. 1 of 3 1. Bulletin Number: TBG-42 | GB142 Heat Exchanger Cleaning  Remove the burner gasket (see fig. 6, pos. 1).  Remove the gas/air distributor plate (see fig. 6, pos. 2).  Remove the orifice plate (only applies to Logamax plus GB142-24/30 and GB142-60) (see fig. 6, pos. 3). Note that the orifice plate of the GB142-60 has a different shape.  Remove the burner (see fig. 6, pos. 4). Technical service bulletin  Remove both the hot surface ignitor and the ionization electrode from heat exchanger [Fig.8]. Figure 8 Figure 6 1 2  Paint or spray Heat Exchanger with mineral oil  Re-assemble all parts in reverse order of disassembly. 3 4 WARNING It is important to inspect the rubber gaskets. Replace brittle, discolored, split or worn rubber gaskets.  Switch on the heating system using the main switch.  Disconnect the hot surface ignitor and ionization electrode plugs.  Press the “Chimney Sweep” button until the decimal point is displayed. Leave the boiler on for approx. 10 minutes.  Loosen the fastening screws [Fig.7, pos.1].  Switch off the heating system using the main switch.  Pull the ground cable from the hot surface ignitor [Fig.7, pos.2].  Dismantle the boiler again and flush the heat exchanger with water.  Dismantle the mounting plate [Fig.7, pos.3].  Pull the condensate trap from the condensate plate (fig. 9, pos. 1). Figure 7 Figure 9 3 1 2 1 1 4 2 3  Pull the internal condensate bypass pipe (if installed) from the condensate trap (see fig. 9, pos. 2). 2 of 3 Data subject to change without notice | BTC 435002109 A | 07.2013 Buderus Bulletin Number: TBG-42 | GB142 Heat Exchanger Cleaning  Loosen the condensate trap from the connection (fig. 9, pos. 3) and remove it.  Use a bristle brush to clean the condensate trap.  Flush the condensate trap.  Open latches [Fig. 10, pos.1] on the condensate collector. Technical service bulletin Figure 10 1 1  Remove the condensate collector.  Remove the baffle plate and clean it using compressed air [Fig. 11]. If necessary brush fins with a stiff nylon brush.  Figure 11  Check the condensate trap gasket for damage and replace it if necessary.  Fill the condensate trap with water before re-installing it.  Reassemble all parts in reverse order of disassembly. NOTICE For heavy build up, repeat procedure. NOTICE Recommended cleaning interval is every 2 years. 3 of 3 Data subject to change without notice | BTC 435002109 A| 07.2013 Bosch Thermotechnology Corp. 50 Wentworth Ave Londonderry, NH 03053 Tel: (800) 283-3787 Fax: (603) 965-7581 www.buderus.us Buderus