Preview only show first 10 pages with watermark. For full document please download

Hem Nvx User Manual Version:

   EMBED


Share

Transcript

CE HEM-NVx Range Gas-fired insertion modules for air handling units or duct sections Users Instructions WARNING Incorrect installation, unauthorised adjustments or alterations or lack of servicing and maintenance could lead to property damage, injury or death. All work must be carried out by suitably qualified operatives. Powrmatic Ltd do not take any responsibility if regulations covering the installation of this equipment are not correctly implemented. WARNING: THIS APPLIANCE MUST BE EARTHED GB & IE HEM-NVx Range Users Issue 1.0 November 2013 Users Instructions If the heater has not been left operational proceed as follows. 1. Checks before lighting the Air Heater The following preliminary checks should be made before lighting the heater(s) a) Ensure that the external controls are set to OFF. b) Turn ON the gas and electricity supplies. b) Check that all warm air delivery outlets are open. 2. Lighting the Air Heater WARNING: If it is not possible to light the heater after several attempts contact the installer or local service company. 2) Start the heater by completing the external control circuit e.g. switch the time clock to an on period, turn the room thermostat to maximum or set the BMS to call for heat. The main air fan should start. 3) The main air moving fan has to run and its air flow be proved at which point the burner ignition cycle will automatically start. If, at the end of 5 ignition attempt cycles, the burner has not lit the LOCKOUT light on the burner control panel will be illuminated. Press the reset button to reset the burner. IMPORTANT If the burner fails to light after 2 cycles of 5 attempts a service engineer should be called to ascertain the cause of failure. 3. To Shut Down the Air Heater 3.1 For Short Periods: To shut down the heater for short periods either turn the room thermostat to minimum and/or set the time clock and/or BMS to OFF. 3.2 For Long Periods: Complete step 3.1 above. Wait for 5 minutes and then turn OFF the electrical supply at the isolator. 4. Description of Operation Important: The heater must NOT be controlled by switching ON and OFF the main electrical supply to it. 4.1 Standard Units Note: On units with two burner sets the sequence below will ocurr on both burners simultaneously. Providing the main air fan is running and its air flow has been proved the ignition sequence commences each time the external controls e.g. Time clock, room thermostat, BMS etc. call for heat. The internal exhaust fan will run and, when sufficient combustion airflow is proved by the air pressure switch, the ignition spark will be generated, the main gas valves opened and the burners lit. When the external controls are satisfied the burners will be turned off . If the burners fail to light the control box will make another four attempts at ignition. 4.2 High / Lo & Modulating Units When the burners are alight the heat output will be controlled either to high fire or low fire or, in the case of modulating units, to any point between high and low fire; depending on the requirements of the space being heated and the external controls fitted. 4.4 Overheat Thermostat This operates if high temperatures within the heater are detected, the burners are turned off and a red indicator light on the front panel is illuminated. Note: Modules having two burner sets have a high limit thermostat in each burner set (either thermostat can go to limit and shut off all the burners). The fault condition must be identified and rectified and the thermostat manually reset. When the unit has cooled push the reset switch under the black cover cap on the limit thermostat, the red indicator light will go out and the unit is operational again. Note: The limit thermostat(s) can only be reset once the unit has cooled down. Unless the cause of the fault condition is readily obvious, for example a power cut whilst the heater was operating, a service engineer should be contacted. 5. Maintenance To maintain efficient, reliable and safe operation of the heater it must serviced by a qualified person at least annually and preferably at the end of the heating season. 6. IMPORTANT Free access must be maintained to and around the heater for servicing purposes and the air supply to the heater must not be restricted in any way. Combustible materials must not be stored adjacent to the heater. If at any time a gas leak is suspected turn OFF the gas supply at the meter and contact the local gas undertaking immediately. All Powrmatic heaters use gas and electricity to power them. It would be hazardous to tamper with or attempt to service unless you are a competent person in the field of Gas and Electrical work. Gas Safety (Installation & Use) (Amendment) Regulations It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualified persons* in accordance with the current issue of the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with. * An approved class of person listed on the gas register.