HF12-420WP-X FEATURES
APPLICATION
Advanced pure lead technology The battery is designed for high rate usage Excellent consistency and reliability Longer float life Special design to avoid thermal runaway 4-fold terminal sealing to avoid leaking Strongest High Rated Discharge Performance Maintenance-free operation Low self-discharge rate
UPS Equipment (High rate) High power backup supply Emergency power supply Starting system Power tools Emergency lighting Electrical starting
SPECIFICATIONS Nominal Voltage Number of cell Nominal Capacity Approx. Weight Internal Resistance Max. Discharge Current Max. Charge Current
12 V 6 420W/cell @15 min rate F.V.(1.67V/cell) 31.5Kg(69.4 lbs) (Weight deviation: ± 3%) o 3.5m (Fully Charged,25 C ) 900 A (5 sec.) 30 A o o Charge -10 C~60 C o o Discharge -20 C~60 C o o Storage. -10 C~60 C o 25 ± 5 C ABS(UL94-HB)&Flammability resistance of(UL94-V0) can be available upon request. 3 % of capacity declined per month at 20 o C (average)
Operating Temperature Range Nominal Operating Temperature Range Container Material Self Discharge Charge Methods Constant Voltage Charge (25 o C) Cycle use Temperature compensation Standby use Temperature compensation
ISO9001:2008
2.40-2.45VPC -30mV/ oC 2.20-2.30VPC -20mV/ oC 341±1
173±1
SI Units
214.5±1 220±1
Dimensions English Units
341mm
13.4 inch
Width
173mm
6.81 inch
Height
215mm
8.46 inch
Total Height
220mm
8.66 inch
∅ 16
44
5
Length
266
M8
Constant Current Discharge( Amperes at 25 ℃ )
End Point Volts/cell
3 m in
5 m in
10m in
15 m in
20 m in
1 .60
634
1 .67
608
460
317
240
190
160
434
295
225
178
152
1 .70
571
411
280
210
167
140
1 .75
545
390
267
200
162
135
1 .80
509
365
250
191
156
127
30 m in
Constant Power Discharge( Watts per Cell at 25℃ )
End Point Volts/cell
3 min
5 m in
1 .60
1029
1 .67
968
1 .70
924
10m in
15 m in
20 m in
800
568
437
348
292
751
538
420
335
285
711
508
395
323
272
30 m in
1 .75
873
667
477
372
303
260
1 .80
823
627
454
349
290
251
(Note)The above characteristics data are average values obtained within three charge/discharge cycles not the mimimum values. All data shall be changed without prior notice, VISION reserves the right to explain and update the information contained hereinto.
Powered by
2015-7
Page 1 of 2
Shenzhen Center Power Tech. Co., Ltd
140
10.2 10.02 9.6
272W
120
0.25
100
0.20
420W 568W
800W
80
0.15
0
5
30
0.10
15
10 min
20
0.05
0
0
15.0
CHARGED VOLUME
14.0
CHARGE VOLTAGE
13.0
60 40
12.0 11.0
4
6
8
10
12
14
16
18
Self-discharge characteristic
10.4
7.8
5.2
2.6
15.0
10.0
7.5
5.0
2.5
14.4
9.6
7.2
4.8
2.4
Capacity(%)
100
15.6
90 80 70
13.8
9.2
6.9
4.6
2.3
60
13.2
8.8
6.6
4.4
2.2
50
-10
0
10
20
30
40
50
40
60
Ambient temperature( oC)
0
2
4
6
8 10 12 14 Storage time: months
16
18
Life characteristic of standby use
Temperature effects on float life 120
15
10
C apacit y(%)
Life(years)
100
5
80
60
40
20
0
10
20
110
(V/CELL)
(V/6V)
(V/4V)
2
Charging time (hours)
Relationship between charging voltage and temperature (V/8V)
CHARGING CURRENT
0
Discharge time
(V/12V)
Constant voltage charging o characteristic(0.25CA,25 C)
(%) (XCA) (V)
12.0 Battery voltage(V)
Current
Charged Volume
Discharge characteristic (25 oC)
Voltage
HF12-420WP-X
20
30
40
0
50
4
Temperature( oC)
6 Life(year)
8
THE INTERNATIONAL CERTIFICATION NETWORK
ISO9001:2008
MH25860
www.vision-batt.com
Shenzhen Center Power Tech. Co., Ltd. Center Power Industrial Park, Tongfu Industrial District Dapeng Town, 518120 Shenzhen, China Tel: (+86-755) 8431 8088 Fax: (+86-755) 8431 8038 E-mail:
[email protected] Copy Right Shenzhen Center Power Technology Co., Ltd (Edition:2015-7)
Page 2 of 2