BACNET/N2 FUME HOOD CONTROLLER PRIMARY FEATURES / BENEFITS Closed loop control - measures and controls based on hood face velocity with or without sash height. Dedicated velocity flow sensor input, and a second input, provides for true readings with a high degree of reliability. Safety Halo™ edge lighting technology increases hood status viewing to 180°. Safety Halo intensity is fully programmable to dim for night hours or can be shut off completely Flexible Design - 6 analog and 4 digital inputs (along with 4 relay, 4 linear or PID analog outputs) allow for a variety of configuration options.
Configurable and programmable screen can be set to display most any hood parameter including sash height. OTHER FEATURES INCLUDE: • Multiple alarms for face velocity & sash • BACnet and Metasys N2 native • Closed-loop system w/sash control & sidewall sensor feedback • Zone Presence Sensor (ZPS) support • Automatic sash closer support • Multi-trigger emergency purge • Programmable audible and visual alarms • Intuitive touch screen interface • Non-volatile memory
Programmable audible and visual alarms increases warning and alarms status notifications at a glance. w w w . t r i a t e k . c o m
Action Icon Warning System
TRIATEK HMS-1655
TRIATEK HMS-1655 Specifications Alarm Range
0-200 fpm
Display Range
0-200 fpm (0-1.016 m/s)
Accuracy
±1% @ 60-140 fpm, ±2.5% outside this range Sidewall sensor (0-1.59 Pa)
Sash Position Sensor Control Capability
Vertical height (0-43 in) Sash position w/ sidewall sensing feedback for closed-loop
Calibration
2-pt (zero & target setpoint); field calibration feature
Low Air Flow Alarm Analog Inputs
Fully Programmable w/ Low Sash Mute 4 Universal (4-20mA, 0-5V, 0-10V), 2 Thermistor (NTC 10K Type 2 or 3)
Analog Outputs
4 Universal (4-20mA, 0-5V, 0-10V)
Digital Inputs
4 Active-High or Low
Relay Outputs
4 Relay Outputs, support for auto sash closer
Native Protocols
BACnet MS/TP, Metasys N2
Emergency Purge
Touch screen, digital input, via network front end
Sash High Indication
Sash position or sash switch
Power Requirement Display - Visual
Standby Mode
Isolated Universal 120/240 VAC to 24 VAC, 60/50 Hz Full Color 3.2" Touch Screen Display w/ intuitive menu system
Alarm Indication
4 Color, Audible alarm, "Action" icons
Alarm Silence
Normal Mode
Directly from touch screen, programmable silent period
Mounting
Surface Mount (no cutout required)
Operating Temp.
32-125 °F
Outside Dimensions
4.875" x 3.188" x 1"
Agency Listings
UL 61010-1, FCC Part 15
Password Protection
Up to 10 entries w/ 4 access levels
ETL LISTED ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL & LABORATORY USE CONFORMS TO ANSI/UL 61010-1
Triatek Venturi Valve
HMS 1600 Controller
Fast Acting Electronic Actuator
Warning Mode
Part Number Guide: HMS1655
HMS 1600 Air Flow Sensor
-
-
Sensor Type 1 = single smart sidewall sensor 2 = dual smart sidewall sensor A = single legacy sidewall sensor B = dual legacy sidewall sensor
Sash Sensor blank = no sash sensor S = sash position sensor included
HMS Display & Alarm Annunciator
Typical Fume Hood Equipped with TRIATEK Controls
*Accuracy is ± 5FPM when velocity drops below 60 FPM or exceeds 140 FPM