QuickSpecs
HP Basic Power Distribution Units (bPDU)
Overview
HP Basic Power Distribution Units (bPDU) HP Basic PDUs are designed for simple installation, reliability and cost effective power distribution. They come in a variety of form factors and outlet configurations to meet the needs of today's high-density data center rack environments. Choose a low profile single piece design PDU for ease of access to rear devices for maintenance consideration and provides multiple mounting options. These are designed for HP racks but will also work in a large variety of third party racks as well. They can be installed on either side of the rack with outlets facing the back of the rack for easy access and improved clearance. Also for higher power density they can be installed side by side on both sides of the rack with the outlets facing in towards the center of the rack. With effective power distribution supporting from 12 to 42 outlet receptacles and power levels ranging from 1.9 kVA through 22kVA, HP has the Basic single or 3-phase PDU for any application. HP PDUs with a unique modular architecture are designed specifically for data center customers who want to maximize power distribution and space efficiencies in the rack. These PDUs consist of two building blocks - the Control Unit (core) and optional Extension Bar(s) (sticks). The Control Unit is 1U/0U, and the optional Extension Bars mount directly to the frame of the rack in multiple locations. Available models range from 24A to 48A current ratings, with output connections ranging from four to six C-IEC C20 outlets.
Basic PDU, 1U/0U Models (H5M54A shown)
Basic PDU, Half Height Models (H5M55A shown)
Basic PDU, Mid Height Models (H5M62A/H5M70A shown)
Basic PDU, Full Height Models (H5M67A/H5M73A shown)
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 1
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Overview
Basic PDU, 480V Half Height model (H3X07A shown)
Basic PDU, 480V Full Height model (H3X08A shown)
Basic PDU, Zero-U/1U installed in the rack
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 2
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Models HP Basic PDU Models
HP 1.9kVA 120 Volt L5-20 Input (12xNEMA 5-20R) NA/JP Basic PDU HP 2.8kVA 120 Volt L5-30 Input (18xNEMA 5-20R) NA/JP Basic PDU HP 3.6kVA 200-240 Volt Detachable C20 Input ( 12xC13) WW Basic PDU HP 3.6kVA 200-240 Volt Detachable C20 Input (18xC13) WW Basic PDU HP 4.9kVA 208 Volt L6-30 Input (20xC13) NA/JP Basic PDU HP 4.9kVA 208 Volt L6-30 Input (24xC13/6xC19) NA/JP Basic PDU HP 8.3kVA 208 Volt CS8265C Input (30xC13/6xC19) NA/JP Basic PDU HP 8.6kVA 208 Volt L15-30 3-Phase Input (18xC13) NA/JP Basic PDU HP 8.6kVA 208 Volt L15-30 3-Phase Input (24xC13/6xC19) NA/JP Basic PDU HP 5.7kVA 208 Volt L21-20 3-Phase Input (24xC13/3xNEMA 5-20R) NA/JP Basic PDU HP 8.6kVA 208 Volt L21-30 3-Phase Input (24xC13/3xC19/3xNEMA 5-20R) NA/JP Basic PDU HP 7.3kVA 230 Volt IEC309 32A Input (20xC13) INTL Basic PDU HP 7.3kVA 230 Volt IEC309 32A Input (24xC13/6xC19) INTL Basic PDU HP 11kVA 400 Volt IEC309 16A 3-Phase Input (30xC13/6xC19) INTL Basic PDU HP 11kVA 230 Volt IEC309 63A Input (30xC13/6xC19) INTL Basic PDU HP 11kVA 400 Volt IEC309 16A 3-Phase Input (36xC13/6xC19) INTL Basic PDU HP 11kVA 400 Volt IEC309 30A 3-Phase Input (36xC13/6xC19) NA Basic PDU HP Hardwired 200-240 Volt Input (30xC13/6xC19) WW Basic PDU HP 13.2kVA 480 Volt IEC309 30A 3-Phase Input (15 Outlet) NA Basic PDU HP 19.9kVA 480 Volt IEC309 30A 3-Phase Input (30 Outlet) NA Basic PDU HP 8.3kVA 40A High Voltage NA/JP Core Modular Power Distribution Unit HP 4.9kVA 24A High Voltage NA/JP Core Modular Power Distribution Unit HP 8.6kVA 24A Three Phase NA/JP Modular Power Distribution Unit HP 14.4kVA 40A Three Phase NA/JP Modular Power Distribution Unit HP 17.3kVA 48A Three Phase NA/JP Modular Power Distribution Unit HP 9.2kVA 40A High Voltage INTL Core Modular Power Distribution Unit HP 7.3kVA 32A High Voltage INTL Core Modular Power Distribution Unit HP 11kVA 16A Three Phase INTL Modular Power Distribution Unit HP 22kVA 32A Three Phase INTL Core Modular Power Distribution Unit HP 3.6kVA 16A High Voltage INTL Power Distribution Unit HP 4.9kVA 24A High Voltage NA/JP Power Distribution Unit HP 8.3kVA 40A High Voltage NA/JP Power Distribution Unit HP 8.3kVA 40A High Voltage INTL Power Distribution Unit HP 7.3kVA 32A High Voltage INTL Power Distribution Unit HP 9.2kVA 40A High Voltage INTL Power Distribution Unit
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
H5M54A H5M55A H5M56A H5M57A H5M58A H5M59A H5M60A H5M61A H5M62A H5M63A H5M64A H5M68A H5M70A H5M72A H5M71A H5M73A H5M67A H5M75A H3X07A H3X08A 252663-D75 252663-D74 AF512A AF519A AF511A 252663-B34 252663-B33 AF513A AF518A 252663-B24 252663-D72 252663-D73 252663-B21 252663-B31 252663-B32
Page 3
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Standard Features Features List
Multiple models for flexible installation
One piece rack mount PDUs; PDUs with extension bars also available Industry standard button and keyhole mounting Easily accessible outlet receptacles and improved cable management Models range from 1.9kVA to 22kVA Ultra-thin design does not interfere with rear maintenance 1U/0U and vertical form factors with flexible mounting options Easy installation
The HP Basic PDUs is available in form factors for a variety of racks and environments. All HP Basic PDUs can be mounted to stay completely out of the critical rear maintenance path needed to service IT equipment in the rack. All vertical models use industry standard button and keyhole mounting for simple drop in installation in HP 11000 G2 and Intelligent Series racks and many third party racks. 4.9 kVA to 9.2kVA1Ø models Each Control Unit is a single-phase unit that branches out to 4 single-phase branch circuits. The Optional PDU extension bars can be plugged into the Control Unit, and can be mounted directly to the rack frame, spanning the entire length of the rack. 8.6 kVA to 22 kVA 3Ø models Each Control Unit is a three-phase input that branches out to 6 single-phase branch circuits. Optional extension bars can be added to provide C13 outlets. 1U/0U Basic PDUs Mounts in 1U of space in any EIA standard rack these PDUs can also mount in the side of an HP rack for 0U mounting. Available in either a low voltage model with twelve NEMA 5-20 receptacles or a high voltage model with twelve IEC C13 outlets. Vertical Basic PDUs A variety of sizes meet the needs of many environments Mounts vertically on either side in the rear of the rack using industry standard button and keyhole mounting. Standard mounting faces the outlet towards the rear of the rack. This configuration fully prevents interference in the maintenance zone between rear RETMA rails. Using the optional configuration of facing the outlets into the rack, multiple PDUs can be mounted on one side of the rack for higher power density.* NOTE: Facing the outlets into the rack will interfere with the lower few rack U spaces of the rear maintenance zone due to breakers on the PDUs.
Vertical PDU Form Factors
Half Height Basic PDU o Designed to fit in 22U and taller racks o Available in low voltage and three phase models with up to 20 outlets. o Up to 4 Half Height PDUs can be mounted in one side of a 42U or 47U rack using the optional inward facing configuration. Mid Height Basic PDUs o Designed to fit in 36U and taller racks o Available in high voltage and three phase models with a combination of C13 and C19 outlets for up to 36 outlets. o New Three Phase Dual Voltage models provide three NEMA 5-20 convenience outlets for low voltage equipment in a high voltage rack. Full Height Basic PDUs c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 4
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Standard Features
o Designed for 42U and taller racks. o Available in three phase only with 36 x C13 and 6x C19 for a total of 42 outlets. 480V Basic PDUs o 480V three phase 5 wire input provides 277V single phase output. o Unique outlets prevent connection of non-277V compatible equipment. o Available in a 15 outlet Half Height and a 30 outlet Full Height model.
NOTE: When mounted in the standard rear facing configuration only 1 Mid or Full Height Basic PDU can be mounted per side of the rack. Up to 2 Half Height Basic PDUs can be mounted per side in the standard rear facing configuration in a 42U or taller rack. NOTE: HP 480V Basic PDUs can only be mounted in the standard rear facing configuration. Easy Installation and compatibility
Installation is quick and easy. Whether you choose to mount the Modular PDU in zero-U or 1U, all required mounting brackets, accessories, and installation instructions are shipped with the product. Standard button and keyhole mounting provides simple drop in installation in HP 11000 G2 and Intelligent Series Rack and many third party racks.
Warranty Upgrade Options
HP Basic PDUs are backed by a limited 3-year warranty. HP Basic PDUs automatically assume the Care Pack coverage level of any covered ProLiant server in the same rack.
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 5
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Service and Support HP Care Pack Services
Care Pack services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical. A full range of HP Care Pack hardware and software services are available including:
Installation and start up Education courses Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24 hours, 7 days call window with options including 4-hour response or 6-hour Call To Repair Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials and VMWare-based IT solutions helping to deliver high level of application availability. Response times range from 30 minutes for critical problems to 2 hours. System Management, Performance Services and Mission Critical Support Solution
NOTE: For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at: http://www.hp.com/hps/carepack NOTE: For more complete information on HP Services offerings, customers and resellers, please visit us at: http://www.hp.com/hps NOTE: Additional information regarding worldwide limited warranty and technical support is available at: http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 6
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Related Options
Related Options HP Two C-13 PDU Extension Bars HP Two Fixed Cord Extension Bars
HP Care Pack Services HP Power Cables
HP Two C13 PDU Extension Bar NOTE: Each extension bar has a C-19 input and 7 C-13 receptacles. HP Fixed Cord Extension Bars NOTE: Each extension bar has a C-19 input and 7 C-13 receptacles on 13 inch cords attached to the extension bars. The option is ideal for powering 1U servers and components. HP Install Rack and Rack Options Service HP Install Rack and Rack Options Service HP C13 - Nema 5-15P US/CA 110V 10Amp 1.83m Power Cord HP C19 - Nema L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord HP 240 VAC 4.5M Unterminated End NA Power Cord HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord NOTE: HP Basic PDU models H5M56A and H5M57A require an IEC 320-C19 to country specific plug inlet cord which is sold separately. NOTE: Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions: http://www.hp.com/go/powercordmatrix.
HP Jumper Cables
HP C13 - C14 WW 250V 10A Gray 0.7m Jumper Cord HP C13 - C14 WW 250V 10Amp 0.7m Jumper Cord HP C13 - C14 WW 250V 10Amp 1.4m Jumper Cord HP C13 - C14 WW 250V 10A Gray 1.37m Jumper Cord HP C13 - C14 WW 250V 10Amp 1.4m 15 pc Jumper Cord HP C13 - C14 WW 250V 10Amp 2.0m Jumper Cord HP C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord HP C13 - C14 WW 250V 10Amp 2.5m Jumper Cord HP C13 - C14 WW 250V 10Amp 3.0m Jumper Cord HP C13 - C14 WW 250V 10A Gray 3.0m Jumper Cord HP C20 - C13 WW 250V 15Amp 2.0m Jumper Cord HP C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord HP C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord HP 200-250V 10A C15 to C14 .76m Jumper Cable NOTE: Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions: http://www.hp.com/go/powercordmatrix.
HP Mounting Brackets
HP Vertical PDU 10K G2 Mounting Kit NOTE: Allows HP Basic PDU vertical models to be mounted in HP 10000 G2 series racks and in the HP V142 rack. This bracket is not needed for c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
AF500A 351655-B21
U2871A U2871E AF556A AF593A AF592A AF584A AF582A AF583A AF577A AF581A AF576A AF580A AF579A 359615-031 E7806A 295633-B22
A0K03A 142257-B28 142257-006 A0K04A 142257-007 A0K02A AF573A 142257-002 142257-003 A0K06A AF590A AF575A AF574A 295633-B22 E7807A
H6L32A
Page 7
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Related Options mounting in the HP 11000G2 or Intelligent Series racks HP 277 Volt options for H3X07A and H3X08A
HP LS-26 to LS-25 277 Volt 15Amp AC 0.76m Jumper Cord HP LS-26 to LS-25 277 Volt 15Amp AC 1.37M Jumper Cord HP 800VA - 277V Input / 230V Output NA Rack Mount Transformer NOTE: 720 watt, 2U transformer converts 277V to 230V for up to 4 devices. NOTE: Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions: http://www.hp.com/go/powercordmatrix.
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
TK801A TK802A H3X09A
Page 8
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Basic PDU Family Information
Model Selection Matrix HP Basic PDUs 1U/0U models Model
Part Number Input Circuit
1.9kVA PDU
H5M54A
100-127V 16A 20A
1920VA @120V
3.6kVA PDU
H5M56A
200-240V 16A 16-20A
3680VA @230V
Half Height vertical models Model Part Number Input Voltage
Current Maximum
Current Maximum
Load capacity
Load capacity
2.8kVA PDU
H5M55A
100-127V 24A 30A
2880VA @120V
3.6kVA PDU
H5M57A
200-240V 16A 16-20A
3680VA @230V
4.9kVA PDU
H5M58A
200-240V 24A 30A
4992VA @208V
7.3kVA PDU
H5M68A
200-240V 32A 32A
7360VA @230V
8.6kVA PDU
H5M61A
200-208V 41.5A 30A 3 Phase Delta
8646VA@208V 3 PHASE
Mid Height vertical models Model Part Number Input Voltage
Current Maximum
Load capacity
4.9kVA PDU
H5M59A
200-240V 24A 30A
4992VA @208V
7.3kVA PDU
H5M70A
200-240V 32A 32A
7360VA @230V
8.3kVA PDU
H5M60A
200-240V 40A 50A
8320VA @208V
11kVA PDU
H5M71A
200-240V 48A 63A
11040VA @230V
Hardwired PDU
H5M75A
200-240V 46A 50-63A
11040VA @230V
5.7kVA Dual Voltage PDU
H5M63A
200-208V 27.7A 20A 3 Phase
5764VA @208 3 PHASE
Input Connection Output circuit breakers 8ft(2.4m) cord 1 x 20A with attached NEMA L5-20P Detachable input 1 x 16A power cord with an IEC 320-C20 inlet*
Outlet Connections
Input Connection Output circuit breaker 8ft(2.4m) cord 2 x 20A with attached NEMA L5-30P Detachable input 2 x 16A power cord with an IEC 320-C20 inlet* 8ft(2.4m) cord 2 x 20A with attached NEMA L6-30P 8ft(2.4m) cord 2 x 16A with attached IEC 332P6 8ft(2.4m) cord 3 x 20A with attached NEMA L15-30
Outlet Connections
Input Connection Output circuit breaker 8ft(2.4m) cord 3 x 20A with attached NEMA L6-30P 8ft(2.4m) cord 3 x 16A with attached IEC 332P6 8ft(2.4m) cord 3 x 20A with attached CS8265C 8ft(2.4m) cord 3 x 16A with attached IEC 363P6 Terminal block for 3 x 20A hardwired installation 8ft(2.4m) cord 3 x 20A with attached NEMA L21-20P
Outlet Connections
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
12 x NEMA 5-20R 12 x IEC C13
18 x NEMA 5-20R 20 x IEC C13 20 x IEC C13 20 x IEC C13 18 x IEC C13
24 x IEC C13 6 x IEC C19 24 x IEC C13 6 x IEC C19 30 x IEC C13 6 x IEC C19 30 x IEC C13 6 x IEC C19 30 x IEC C13 6 x IEC C19 24 x IEC C13 3 x NEMA 5-20R Page 9
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Basic PDU Family Information 8.6kVA Dual Voltage PDU
H5M64A
8.6kVA PDU
H5M62A
11kVA PDU
H5M72A
WYE 200-208V 41.5A 8646VA @208 3 30A PHASE 3 Phase WYE 200-208V 41.5A 8646VA @208 3 30A PHASE 3 Phase Delta 380-415V 16A per phase 11084VA 16A @ 400V 3 PHASE 3 Phase WYE
Full Height vertical models Model Part Input Number Voltage 11kVA PDU
H5M73A
480/277 Volt H5M67A models 13.2kVA PDU H3X07A 19.9kVA PDU H3X08A
Current Maximum
Load capacity
380-415V 16A per PHASE 11040VA 16A @ 400V 3Ø 3 phase WYE 380-415V 24A per PHASE 11040VA @400V 3Ø 30A 3 phase WYE 480V 30A 3 16A perPHASE 13301VA @480V 3Ø phase WYE
8ft(2.4m) cord with attached NEMA L21-30P
3 x 20A
20 x IEC C13 3 x IEC C19 3 x NEMA 5-20R
8ft(2.4m) cord with attached NEMA 15-30P
3 x 20A
24 x IEC C13 6 x IEC C19
8ft(2.4m) cord 3 x 16A with attached IEC 516P6
24 x IEC C13 6 x IEC C19
Input Connection Output circuit breaker 8ft(2.4m) cord 3 x 16A with attached IEC 516P6
Outlet Connections
8ft(2.4m) cord 3 x 20A with attached IEC 530P6
36 x IEC C13 6 x IEC C19
9.8ft(3M) cord with 3 x 20A attached IEC 530P7 480V 30A 3 24A per PHASE 19952VA @480V 3Ø 9.8ft(3M) cord with 6 x 20A phase WYE attached IEC 530P7
Modular models Model Part Number Input Circuit
Current Maximum
Load capacity
4.9 kVA PDU
252663-D74 24A 200- 24A 240V
4992 (@208V)
7.3 kVA PDU
252663-B33 32A 200240V
32A
7360 (@230V)
8.3 kVA PDU
252663-D75 40A 200240V
40A
8320 (@208V)
9.2 kVA PDU
252663-B34 40A 200240V
40A
9200 (@230V)
36 x IEC C13 6 x IEC C19
15 x LS-26 30 x LS-26
Input Connection Output circuit breakers
Outlet Connections
Input: 3.6m 4x15A attached cable with L6-30P Input: 3.6m 4x16A attached cable with IEC309-32A, Splashproof (IEC 332P6S)
4 IEC 320 C-19
Input: 3.6m 4x15A Attached Input cord, Non-NEMA Locking CS8265C, 50A Input: 3.6m 4x15A Attached Input cord, IEC 60309 63A, Splashproof (IEC 363P6S)
4 IEC 320 C-19
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
4 IEC 320 C-19
4 IEC 320 C-19
Page 10
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Basic PDU Family Information 8.6 kVA PDU
AF512A
41.52A 208v 3Ø Delta
41.52A
8600 (@208V)
11 kVA PDU
AF513A
16A 380415v 3Ø Wye
16A
11000 (@230v)
14.4 kVA
AF519A
69A 208v 3Ø Delta
69A
14393 (@208V)
17.3kVA PDU
AF511A
83.04A 208v 3Ø Delta
83.04A
17300 (@208V)
Input: 3.6m 6 X 20A Attached input cord, NEMA L1530P Input: 3.6m 6 X 16A Attached Input cord, IEC 60309 4 pole, 5 wire, 380415VAC, 16A, Splashproof (IEC 516P6S) Input: 3.6m 6 X 20A Attached input cord, CS8365C plug
6 IEC 320 C-19
6 IEC 320 C-19
6 IEC 320 C-19
Input 3.6m 6 X 20A 6 IEC 320 C-19 Attached Input cord IEC 60309 3 pole, 4 wire 200240VAC 60A Waterproof (IEC460P9W) 22 kVA PDU AF518A 32A phase 32A phase 22000 (@230V) Input: 3.6m 6 X 16A 6 IEC 320 C-19 380-415v Attached Input 3Ø Wye cord, IEC 60309 4 pole, 5 wire, 380415VAC, 32A, Waterproof (IEC 532P6W) *NOTE: HP Basic PDU models H5M56A and H5M57A require an IEC 320-C19 to country specific plug inlet cord which is sold separately. NOTE: Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions. http://www.hp.com/go/powercordmatrix. Disclaimer: HP makes no recommendations regarding power connector manufactures. Please consult a licensed professional to determine the best connector or receptacle for your specific needs.
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 11
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Technical Specifications All PDUs Operating Temperature Operating Relative Humidity (%) Operating Elevation Storage Temperature Storage Relative Humidity (%) Storage Elevation Input Plug Length (attached cord units) Conformance Standards
Mechanical Dimensions (WxHxD) - 1U/0U models Mechanical Dimensions (WxHxD) - Half Height models Mechanical Dimensions (WxHxD) - Mid Height models Mechanical Dimensions (WxHxD) - Full Height models Mechanical Dimensions (WxHxD) - 480V Half Height Model Mechanical Dimensions (WxHxD) - 480V Full Height Model 1Ø 4.9kVA to 9.2kVA Mechanical Dimensions (WxHxD) Unit Weight Shipping Dimensions (WxHxD) 3Ø 8.6 kVA to 22 kVA Mechanical Dimensions (WxHxD) Unit Weight Shipping Dimensions (WxHxD) Shipping Weight Kit Contents - All Basic PDUs
50° to 122° F (10° to 50° C) 10% to 90% 0 to 10,000 ft (0 to 3048 m) -4° to 140° F (-20° to 60° C) 5% to 95% 0 to 30,000 ft (0 to 9144 m) 96 inches (243.8 cm) or 142 inches (360.7 cm) UL, CUL - NA/JPN models CE, TUV, KC, EAC - INTL models UL, CUL, CE, TUV, KC, EAC - WW models UL, CUL, CE, NOM, D - 40A models UL, CUL, NOM - 24A models CE, D - 32A model 17.5 x 1.66 x 6 in (44.45 x 4.2x 15.3 cm) 1.9 x 29.02 x 3.75.0 in (48 x 73.7x 9.5 cm) 1.9 x 55.12 x 9.5in (48 x 140 x 9.5 cm) 1.9 x 61.07 x 3.75 in (48 x 155.1 x 9.5 cm) 1.98 x 32.4 x 3.15 in ( 5.03 x 82.3 x 8 cm) 1.98 x 62.9 x 3.15 in ( 5.03 x 159.7 x 8 cm)
17.46 x 1.66 x 6.00 in (44.34 x 4.21 x 15.24 cm) 18 lb (8.16 kg) 21.5 x 12.25 x 13.0 in (54.61 x 31.12 x 33.02 cm) 17.5 x 1.62 x 7.5 in (44.45 x 4.11 x 19.22 cm) 20 lb (9.07 kg) 21.5 x 12.25 x 15.0 in (54.61 x 31.12 x 38.1 cm) 22.2 lb (10.07 kg) All models ship with:
Environment-friendly Products and Approach
Mounting brackets/hardware Cord Retention bracket Tie wraps Shipping bracket( ? models only) Read me first card
End-of-life Management Hewlett-Packard offers end-of-life HP product return, trade-in, and and Recycling recycling programs in many geographic areas. For trade-in information, please go to: http://www.hp.com/go/green. To recycle your product, please c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 12
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Technical Specifications go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner. The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.
c04111250 – DA – 14557 North America — Version 9 — March 30, 2015
Page 13
QuickSpecs
HP Basic Power Distribution Units (bPDU)
Summary of Changes Date 30-Mar-2015 07-Mar-2014 01-Oct-2013 16-Aug-2013
Version History From Version 8 to 9 From Version 7 to 8 From Version 6 to 7 From Version 5 to 6
Action Changed Changed Changed Changed
Description of Change: Overview and Related Options were revised. Updates were made throughout, Corrected and error in the North America version. Changes made to the following Sections Overview Standard Features Related Options
11-Jun-2013 10-Jun-2013 10-Apr-2013
From Version 4 to 5 From Version 2 to 4 From Version 1 to 2
Changed Added Changed
PDU Family Information Correction made to the Changes file only. Added HP Mounting Brackets to Related Options section. Changes made to the Model Selection Matrix chart.
© Copyright 2015 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.