Transcript
HTB Series
High Temperature Battery HTB-1000
Main Applications ■
High temperature environment (35°C)
■
Off-grid & bad-grid environment
■
Renewable energy (wind & solar) site
■
Hybrid telecom site
Benefits ■
Reduce operational cost (less cooling consumption)
■
Excellent deep cycling performance
■
Reduce CO2 emission
■
Secure operation under high temprature up to 55°C
Technical Features Dimensions 211
■
Operating temperature range -20°C to +65°C
■
Best performance for continuous operation up to 35°C
■
Extend service life under high temperature
■
Excellent over discharge recovery capability
■
Long life design for cyclic or float application
357
358 372
Technical Parameters
Attain certificate ISO9001 ISO14001 ISO18001 UL CE
Normal Voltage
2V
Capacity
1000 Ah @10hr to 1.80V per cell @ 25˚C(77˚F) 1030 Ah @10hr to 1.80V per cell @ 35˚C(95˚F)
Weight
71.4kg (157.4 lbs)
Dimensions
Length: 357 mm (14.06 in) Width: 211 mm (8.31 in) Height: 358 mm (14.09 in) Total height: 372 mm (14.65 in)
Internal Resistance (full charged)
0.19mΩ
Short- circuit current
11000A
Self Discharge @ 35˚C(95˚F)
Less than 7 % after 90 days storage
Operating Temperature Range
Discharge: -40˚C ~ 65˚C(-40˚F ~ 149˚F) Charge: -20˚C ~ 45˚C(-4˚F ~ 113˚F) Storage: -20˚C ~ 40˚C(4˚F ~ 104˚F)
Recommended Operating Temperature
15˚C ~ 35˚C(59˚F ~ 95˚F)
Recommended Charging Current
150A
Charging Voltage @35˚C(95˚F)
Float: 2.23 V/cell Equalize: 2.30 V/cell
Terminal
M8
Container Materials
High Temp ABS/High Temp ABS V0 (Optional)
Capacity Affected by Temperature(C10)
106 % @ 40˚C 85 % @ 0˚C 60 % @ -20˚C
Design life @35°C
15 years V2.0 20160910EN
HTB Series
High Temperature Battery HTB-1000 Constant Current Discharge Characteristics Unit: A (35ºC, 95ºF) 15min
30min
1h
3h
5h
8h
10h
12h
20h
24h
1.70V
1560.0
906.8
590.9
268.5
188.5
130.0
107.0
91.9
57.9
49.57
1.75V
1326.0
842.4
563.6
260.7
181.4
128.0
107.0
90.5
57.5
48.96
1.80V
1086.2
789.8
526.5
252.8
177.3
125.0
105.0
88.4
56.5
1.83V
F.V/Time
72h
120h
25.00
17.20
10.92
24.60
16.94
10.76
48.14
24.20
16.56
10.60
48h
1049.1
752.7
493.4
243.0
173.0
124.0
104.0
87.2
55.1
47.12
23.60
16.20
10.40
1.85V
955.5
704.0
475.8
239.1
171.2
120.0
101.0
86.6
54.5
46.31
23.40
16.12
10.22
1.90V
813.2
604.5
421.2
223.4
164.7
109.0
92.0
84.0
53.3
45.29
22.80
15.56
9.88
Constant Power Discharge Characteristics Unit: W (35ºC, 95ºF) F.V/Time
15min
30min
1h
3h
5h
8h
10h
12h
20h
24h
48h
72h
120h
1.70V
2190
1737
1182
557
366
283
235
193
121.6
104.08
52.49
36.11
22.93
1.75V
2108
1679
1135
533
355
276
233
190
120.3
102.38
51.44
35.42
22.50
1.80V
2009
1619
1110
515
345
270
228
187
118.1
100.59
50.56
34.60
22.15
1.83V
1917
1527
1071
504
337
263
224
184
115.1
98.36
49.26
33.81
21.71
1.85V
1829
1439
1008
488
333
255
216
180
113.4
96.34
48.68
33.54
21.26
1589
1215
323
239
204
167
109.9
93.29
46.97
32.05
20.35
1.90V
870
453
Performance curve
Upo(V)
Current ( I10A )
Discharge Characteristic Curve
2.2 2.1
2.0
1.9 20HR
1.8 1HR
0.5HR
2HR
5HR 8HR 10HR
Discharge capacity (%C10)
140
0.1
0.5
1
2.35
1.50
2.25
1.20
2.15
0.90
2.05
0.60
1.95
0.30
1.85
Capacity (%)
Charge Voltage
100
Battery Capacity
75 50
50% DOD 100% DOD
25 0
Charge Current
2
5
10
0
20
Discharge time(h)
Capacity at Different Temperature
4
8
12
16
20 24 Time( h )
Capacity(%) Curve of Self-discharge at Different Temperature 100
120
10HR 8HR
100
4HR
80
10°C
80
20°C
60
40°C
2HR
60
30°C
40
40
20
20 0
Constant Voltage Charge Characteristics@ 35℃
1.80
1.7
0.01
Voltage
( V)
-20
-10
0
10
20
30
40
50
0
Temperature℃ Declaration: This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact CHINASHOTO for the latest information.
3
6
9
12
15
18 21 24 Storage Time (months)
Welcome to Visit: www.chinashoto.com