No.59-1501-0
INSTALLATION INSTRUCTIONS High Mount Outdoor Detector
N219
HX -40/40AM
CONTENTS (1) INSTALLATION HINTS (2) PARTS IDENTIFICATION (3) KNOCKOUTS (4) DETECTION AREA SETTING (5) INSTALLATION (6) BRACKET INSTALLATION AND ADJUSTMENT (7) WIRING (8) FUNCTION SETTING (9) OPERATION TEST (10) LED FUNCTIONS (11) SPECIFICATIONS
By utilising the OPTEX’s unique pyro-element, HX series achieves high reliable detection performance against false and missed alarms. HX series provides stable and accurate detection in outdoor severe environmental conditions. •HX-40 •HX-40AM
1
: standard model with two PIRs : HX-40 with IR anti-masking feature
INSTALLATION HINTS Warning
Never repair or modify product
Parallel
Warning
Caution
Do not pour water over the product
Mount securely
2.5 - 3.0 m (8.3 - 10 ft.)
Tilt
Mount the detector so that a majority of traffic flow is across the detection pattern.
-1-
1 2 2 3 3 4 6 7 9 10 11
2
PARTS IDENTIFICATION Bracket base
Base Screw (3×10 mm)
Terminals
Main unit
Hood PIR sensor (Don not touch) Anti-masking infrared LED (HX-40AM only)
Bracket Shaft cover
Screw (4×20 mm) Lock screw (M4×35 mm) 䎃
Lens Cover 䎃
䎃
䎃
䎃
䎃
LED indicator Lock screw
䎃
3
Area masking seal
KNOCKOUTS 3-B Bracket
3-A Main unit
Wiring Hole
(Off-the-shelf) magnet switch installation position For hood fastening
Wiring Hole
Wiring knockout
Wiring sponge pad
Don’t touch
For bracket up-down lock screw
For wall fastening/bracket fastening (installation pitch 83.5 mm (3.3 inch))
-2-
For wall fastening
For switch box fastening
Adjustment screw
Up-down lock screw For main unit fastening
4
DETECTION AREA SETTING 4-A Detection Area Side view of detection area (Installation height 3.0 m (1 ft.) )
Top view of detection area
12 m (40 ft.)
10°
20°
30°
40°
3.0 m (10 ft.)
8m (26.7ft.)
90°
(Installation height 2.5 m) 0
2.5 m (8.3 ft.)
12 m (40 ft.)
8m (26.7ft.)
12 m (40 ft.)
4-B Detection Length Adjustment To limit the detection distance, apply the appropriate masking seal. Note that there are three different types of seal.
5
1
2
1 3 2
INSTALLATION 1
Pass the wire through the base knockout.
Out In
Wiring sponge pad
-3-
2
Fasten the base to the wall.
3.0 m (10 ft.)
1
4.0 m (13.3 ft.)
5.5 m (18.3 ft.) 3.0 m (10 ft.)
3.0 m (10 ft.)
9.0 m (30 ft.)
6
BRACKET INSTALLATION AND ADJUSTMENT Using the bracket makes it possible to adjust the unit through 180° degree. In cases where the ground is uneven and therefore not parallel with the base of the unit, it is possible to adjust the unit vertically by +/- 20 degree (see section 6-B)
Caution>> Do not change the detection distance with bracket. Use the masking seal to adjust the detection distance. 90°
90°
20° 20°
6-A Bracket installation 1
Push the shaft cover clip outwards to remove the cover.
3
Fasten the bracket to the wall. Change the bracket direction according to whether the Main unit is to face left or right.
4
Pass the wire through the base knockout and install the base on the bracket.
Shaft cover Push
2
Loosen the adjustment screw, tilt the bracket about 45° and pass through the wire. In
In Wiring sponge pad
Adjustment screw
Out Out
-4-
5
Tighten the adjustment screw.
8
Using 6-B as reference, adjust the updown orientation, then tighten the lock screw.
9
Fit the shaft cover into place.
Adjustment screw
6
Wire to the terminal and install the Main unit and lens on the base.
7
On the Main unit, make the settings and check operation.
Caution>> Once the operation checks are complete, fit the shaft cover into place. When the Main unit is fastened to the bracket, you can not remove the shaft cover.
6-B Detection distance check and up-down angle adjustment In cases where he ground is not parallel with the base of the unit the correct detection distance will not be obtained. In such cases, a walk test will be required. To ensure that the required area of detection is achieved.
The LED lights when you come closer within 9 m (30 ft.). Adjust the angle upward. Carry out the walk test again.
3.0 m (10 ft.)
12 m (40 ft.)
Complete walk test from outside the walking area to inside. Check that at a distance of 12 to 13m (40 to 43ft.) from the Main unit, the sensor detects the person and the LED lights.
The LED lights at 12 m (40 ft.). There is no need to adjust the up-down angle.
The LED lights at a point farther than 13 - 14 m (43 - 47 ft.). Adjust the angle downward. Carry out the walk test again.
Caution>> If the base of the unit is already parallel to the ground, • Do not change the detection distance by tilting the unit up or down. • Always use the Masking seals. • Walk test the unit to ensure that the disired detection distance is achieved.
-5-
TAMPER (NC)
AUX INPUT (NC)
TROUBLE SP OUTPUT T.O.(NC)
SP
POWER INPUT (+) (9.5 - 18VDC)
POWER INPUT (–) (9.5 - 18VDC)
ALARM OUTPUT (N.C.)
HX-40AM
ALARM OUTPUT (COM)
ALARM OUTPUT (N.O.)
SPARE (Non short)
TROUBLE OUTPUT (N.C.)
AUX INPUT (N.C.)
WIRING
TAMPER OUTPUT (N.C.) *1
7
NO COM NC – + ALARM POWER 9.5-18VDC
HX-40
TAMPER (NC)
AUX INPUT (NC)
SP
SP
NO COM NC – + ALARM POWER 9.5-18VDC
*1: TAMPER terminals to be connected to a 24 hour supervisory loop.
-6-
8
FUNCTION SETTING
Dip SW 1 LED ON/OFF SELECTOR 2 PULSE COUNT SELECTOR 3 EXTERNAL SENSOR INPUT SELECTOR 4 TROUBLE OUTPUT SELECTOR
(8-A) (8-B) (8-C) (8-D)
ANTI-MASKING SENSITIVITY SELECTOR (8-F)
PIR SENSITIVITY SELECTOR (8-E)
Do not touch
8-A LED ON/OFF
Dip switch
ON
HX-40 HX-40AM
FUNCTION
POSITION
OFF
1
ON (factory default) The LED lights when someone is detected. The LED does not light even if someone is OFF detected NOTE: For the walk test, move more than 1 m (0.3 ft.) away from the detector.
8-B PULSE COUNT
Dip switch
2
HX-40 HX-40AM
FUNCTION
POSITION
2 times (factory default) Suitable for standard applications. 2 times
3 times 3 times
Set this when used in a location with drastic temperature fluctuation or hostile environment.
8-C EXTERNAL SENSOR INPUT
AND
OR
Dip switch
3
HX-40 HX-40AM
By connecting a satellite unit (another warning sensor), you can expand the detection area and correct false alarms. As a satellite unit, you can use any general no-voltage contact output (NC) warning sensor, including the following. FUNCTION When both the Main unit and the satellite detect someone, the alarm is output. Set to this when not connecting a satellite unit. AND (factory default) Note: The alarm is not output unless both the Main unit and the satellite detect someone within 60 seconds. When either the Main unit or the satellite detects OR someone, the alarm is output. POSITION
-7-
8-D TROUBLE OUTPUT
OFF
ON
Dip switch
4
HX-40 HX-40AM
Trouble output is used for anti-masking signal. When an object is placed close to the lens surface, for a period of more than 180 seconds, the IR Anti-Masking circuit will activate and generate a trouble signal. OUTPUT TERMINAL
POSITION ON (factory default)
TROUBLE
OFF
TROUBLE and ALARM Use this when not wiring a dedicated trouble input terminal on the control panel.
LED Operation>> DETECTOR STATUS LED Indication LED operation Anti-Masking booting Red blinks 2 times and goes Red (Anti-Masking start up) off for 5 sec. This movement is repeated. Red blinks 3 times and goes Red Anti-Masking off for 3 sec. This movement is repeated.
8-E PIR SENSITIVITY
PIR SENSITIVITY SELECTOR
POSITION HIGH
HX-40 HX-40AM
FUNCTION Suitable for sites requiring greater sensitivity applications
MIDDLE (factory default) Suitable for standard applications LOW
Suitable for hostile and narrow area
HIGH MIDDLE LOW HX-40 ANTI-MASKING SENSITIVITY SELECTOR HX-40AM
8-F ANTI-MASKING POSITION HIGH STD OFF
HIGH
FUNCTION Suitable for site requires greater sensitivity applications.
STD (factory default) Suitable for standard applications. OFF
Suitable for site requires no anti-masking function.
-8-
9
OPERATION TEST 9-A Example of adjustment for false alarms If there is a road where people or vehicles can pass in front of the detection area, and can trigger false alarms, adjust the area as follows.
1
Delete the unneccesory detection area (a) using the appropriate masking seal(s) 1 2 or 3.
b
(Reduce the distance fromo 12m, 9m, 5.5m ,4m (40ft., 30ft., 18.3ft., 13.3ft.) as determined by the walk testing.
2
Actually move and check that the system does not detect movement on the road (a) but does detect when you enter the detection area (b).
Caution>> The detection area might increase when there is a big temperature difference between the moving object and the background. For example, when the detection distance is set to 12 m (40 ft.), sometimes vehicles 13 m (43 ft.) away may be detected. In this case, set the detection distance to 9 m (3 ft.). This shortens the alarm area but it can reduce false alarms due to vehicles.
Caution>> A heat source beyond the detection area may cause the detector to cause a false alarm by reflecting off the ground. Examples of reflective ground is water (puddle), wet road, smooth surface concrete and asphalt road. The heat source is strong and / or reflection rate is high, detectors detection distance will be longer than required and may detect unwanted objects beyond. According to the ground condition of the installation site, select the detection range position.
-9-
Approx. 9 m (30 ft.) Position B
Ap
pr o
x. 13
m
(4
3
ft. )
a
9-B Area Masking To limit the detection range, apply the area masking seal to the section you want to hide on the lens inside. Configure the area in such a way as to avoid having anything cut across the area. Pasting on example for masking No. 5 and No. 6
1 2 1 2 3 4 5 6 7 8 9
3 Area masking seal 4 0
5
56
6 7 8 9
10 LED FUNCTIONS Red OFF
Light
Blink
HX-40 DETECTOR STATUS
LED Indication
Alarm
Red light
Warm-up period
Red blinks
DETECTOR STATUS
LED Indication
Alarm
Red light
LED operation
HX-40AM
Warm-up period Anti-Masking booting (Anti-Masking start up) Trouble output Anti-Masking
Red blinks Red blinks 2 times and goes off for 5 sec. This movement is repeated. Red blinks 3 times and goes off for 3 sec. This movement is repeated.
-10-
LED operation
11
SPECIFICATIONS Model
HX-40
Detection method PIR Coverange Distance limit
HX-40 AM Passive infrared
12 m (40 ft.) 85° wide / 94 zones 4 m, 5.5 m, 9 m, 12 m (13 ft, 18 ft, 30 ft, 40 ft.)
Detectable speed
0.3 – 1.5 m/s (1 – 5 ft/s)
Sensitivity
2.0°C (3.6°F) at 0.6 m/s 9.5 – 18VDC
Power input Current draw
35 mA (max) at 12VDC
Approx. 60 sec(LED blinks)
Warm-up period
Form C 28VDC 0.2A max
Alarm output
N.C. 28V DC, 0.1A max
Tamper output Trouble output
N.C. 28V DC, 0.1A max
–
N.C. 28V DC, 0.1A max
Aux input LED indicator
40 mA (max) at 12VDC
2.0 ± 1 sec
Alarm period
Red:Warm-up, Alarm
Red:Warm-up, Alarm, Trouble
No alarm 10 V/m
RF Interference Operating temperature
-20 – +60°C (-4 – +140°F)
Environment humidity
95% max IP55
Weatherproof
Wall (Outdoor, Indoor)
Mounting
2.5 - 3.0 m (8.3 - 10 ft.)
Mounting height
Vertical: ± 20° Horizon: ± 95°
Bracket adjust angle
600 g (21.2 oz)
Weight Accessories
Bracket, Hood, Area masking seal, Screw kit (3×10-2, 4×20-4)
* Specifications and design are subject to change without prior notice.
-11-
DIMENSIONS Using bracket and hood
Without bracket and hood
148(5.8) 266(10.5)
92(3.6)
205(8.1)
197.5(7.8)
99(3.9)
Unit:mm (inch)
Unit:mm (inch)
WARRANTY 5 year replacement warranty The HX-40 series is designed to detect movement of an intruder and activate an alarm control panel. Being only a part of a complete system, we cannot accept complete responsibility for any damages or other consequences resulting from an intrusion. Due to our policy of continuous improvement Optex reserves the right to change specification without prior notice. The Warranty period is from the date of purchase.
OPTEX CO., LTD. (JAPAN) (ISO 9001 Certified by LRQA) (ISO 14001 Certified by JET) 5-8-12 Ogoto Otsu Shiga 520-0101 JAPAN TEL:+81-77-579-8670 FAX:+81-77-579-8190 URL:http://www.optex.co.jp/e/
OPTEX INCORPORATED (USA) OPTEX SECURITY SAS (FRANCE)
OPTEX KOREA CO., LTD. (KOREA)
TEL:+1-909-993-5770 Tech:(800)966-7839 URL:http://www.optexamerica.com
TEL:+82-2-719-5971 URL:http://www.optexkorea.com
OPTEX (EUROPE) LTD. (UK) TEL:+44-1628-631000 URL:http://www.optex-europe.com
TEL:+33-437-55-50-50 URL:http://www.optex-security.com
OPTEX SECURITY Sp.z o.o. (POLAND) OPTEX (DONGGUAN) CO., LTD. SHENZHEN OFFICE (CHINA) TEL:+48-22-598-06-55 URL:http://www.optex.com.pl
-12-
TEL:+86-755-33302950 URL:http://www.optexchina.com