HYBRID UPS
E11A AC 230 V Model
Hybrid UPS Saves Energy and Achieves High Reliability
SANUPS E11A HYBRID UPS
Input
Output
AC 230 V
AC 230 V
single-phase 2-wire
single-phase 2-wire
19
NETWORK
MONITORING
inch rack
Mountable EIA
Output capacity
1 kVA
(0.7 kW)
2 kVA
(1.4 kW)
3 kVA
(2.1 kW)
The advancement of technology has increased the demand for quality power. In a perfect world, commercial power would always be stable and normal, however, we live in a world in which electricity from local utilities typically experiences anomalies such as spikes, surges, electrical noise, load fluctuations, and outages. To protect your investments in technology equipment from these problems, informed users rely on SANYO DENKI SANUPS E11A products to resolve these power issues and provide continuous, clean power to connected equipment. Not only does the SANYO DENKI SANUPS E11A create continuous and clean power, it is an intelligent device in which power is consumed only when power conditions are unfavorable, making the unit highly efficient. The SANYO DENKI SANUPS E11A Hybrid UPS provides highly efficient power protection to everything from heavy machinery and manufacturing devices to complex server systems and sensitive communication equipment (Voice and Data). With over 40 years of UPS experience, SANYO DENKI ensures the superior quality of the SANUPS E11A Hybrid UPS and provides the product equipped with extra long life batteries. The SANUPS E11A Hybrid UPS - a product truly in a class of its own.
1 Hybrid UPS-Energy conservation 2 Self battery check feature 3 UPS Management options
Mounted in a 19-inch rack ● Includes metal brackets for 19 inch rack installation. ● Rack support rail is optional.
2
Vertical Installation Includes vertical stand for upright support.
●
1 Hybrid UPS-Energy conservation ■ Conversion efficiency has reached 95%. This represents a 4% improvement over previous products (comparison performed at 1kVA / Economy mode.).
Conversion Efficiency
95%
Commercial Power Load Device
SANUPS E11A
■ The Hybrid type SANUPS E11A automatically selects the most efficient mode of operation for any given power condition. *The mode can be fixed manually. However, the ACTIVE FILTER mode cannot be fixed.
Under good power condition
ECONOMY mode
Hybrid Method
SANUPS E11A
ACTIVE FILTER mode Under unfavorable power factor Harmonic noise
Suppresses high frequencies generated by load and improves power factor.
DOUBLE CONVERSION mode Under unfavorable power condition Momentary blackout
Voltage fluctuation
Frequency fluctuation
Harmonic noise
3
2 Self battery check feature ■ The SANUPS E11A automatically performs regular battery tests for operation during a power outage, and maintains peak battery conditions for reliable operation during an actual power outage. *The frequency of the battery test is open to configuration. (Test frequency choices are 1, 3 and 6 months; the factory setting is 6 months.) *Sudden stoppage does not occur during battery operation test, no matter what the power supply mode. *A LAN interface card (optional) is necessary to transmit the battery test results to the user’s PC. Begin Testing
Battery Test
Normal Operation
Commercial Power
Rectifier
Load Device
Inverter
Periodic Check
Commercial Power
Rectifier
Battery
Inverter
Battery
Return to Normal Operations
* If a decline in the battery function is detected during test mode, normal operation will resume.
3 UPS Management options ■ To increase user control over equipment protection, our stand-alone windows compatible UPS Management Software “SANUPS SOFTWARE STANDALONE” is provided as a standard accessory. Use it to improve the utility of the UPS, through useful functions such as monitoring UPS performance over a network connection and configuring shutdown settings. PC SANUPS SOFTWARE STANDALONE
RS-232C
SANUPS E11A Compatible operating systems Windows NT4.0 Windows 2000 Windows XP Windows Server 2003 Windows Server 2008 Windows Vista Windows 7 Windows 8 Windows Server 2012
Network support options
■ LAN interface card
■ SANUPS SOFTWARE
Installing a LAN interface card in the option
The SANUPS SOFTWARE UPS Power
card slot at the back of the unit allows for
Management Software increases the
continuous monitoring and reporting of power
reliability and manageability of the entire
conditions, and quick response during power
system, including the network and the
failures. Power problems can also be reported
server. It provides UPS information to the
to the System Manager via e-mail.
system manager, and a variety of settings for handling power-related problems.
Model : PRLANIF003-US PRLANIF005-US
■ Dry contact signal interface card When a Dry contact signal interface card is installed in the option card slot at the back of the unit, the external transmission signal can be output as a no-voltage contact signal to indicate the status of the UPS.
Model: PRCONIF001-US(Terminal block output) PRCONIF003-US(D-Sub connector output)
4
PMS40H00E (without cable) Windows Multiple OS* PMS41H00E (without cable) *For Windows, Unix and Linux
Load Device
Front Battery Power Low LED
Alarm LED Inverter Switch Battery Test Switch Clear Switch
Input LED
Output LED
Supply Mode LED
Load Level Display
Back (1kVA) Option Card Slot EPO, Systematic Control Contact Point
Output Plug / Connection (IEC60320-C13)
PC Interface (RS-232C)
Option Card Interface
Input Cable (1.8m) Input Plug / Connection External Battery Connection Port
Remote Interface
Power Switch (ON/OFF)
Interface & INPUT/OUTPUT Connection Chart Output (kVA)
CE
Model No.
PC (RS-232C)
Remote
EPO ※
Systematic control contact point
INPUT Plug/Connection
OUTPUT Plug/Connection
1
E11A102BDE12
IEC60320-C14 to CEE7 line cord option included.
IEC60320-C13×4
2
E11A202BDE12
IEC60320-C20 to CEE7 line cord option included.
IEC60320-C19×3
3
E11A302BDE12
※ EPO = Emergency Power Off
5
Specifications E11A
Item
Remarks
Economy mode*
Active filter mode*
Output power
1 kVA (0.7kW) / 2kVA (1.4 kW) / 3 kVA (2.1 kW)
System
Topology
Hybrid
Cooling
Forced Air
IEC Classification
VFD-SS-311
AC Input
Single-phase / 2 wire
AC Output
Number of phases / wires
VFI-SS-111
Nominal voltage
230V
Voltage range
±8% Max.
Frequency
50 Hz
Frequency range
± 1%, 3%, 5% Max.
Power factor
0.7
Number of phases / wires
Single-phase / 2 wire
User selectable +5% Max.
-20% to +15%
0.85 Min.
0.95 Min.
Auto selected mode 5% Max.
±8% Max. < 1% Input voltage distortion
Power factor
0.7 (lag)
Fluctuation tolerance: 0.7(lag) to 1.0
Nominal voltage
230V
User selectable
Voltage regulation
-10% to +8% (Auto selected mode -7% to 5%)
Nennfrequenz
50 Hz
Frequency range Voltage distortion Transient voltage regulation
-7% to 5%
±2% Max.
In terms of domain of load and input Same as input frequency
On Normal Operation ±1, 3, 5% Max.
±1% Max.
On Battery Operation ―
±0.5% Max.
User selectable
―
3% Max.
During rated operations
Non-linear load ―
7% Max.
During rated operations / 100% rectifier load
Input Voltage ― step
±5% Max.
Power failure: feedback or supply fluctuation
Linear load
100% step load ―
Overcurrent capacity Overcurrent protection Battery
Double Conversion mode
±5% Max.
0% : at the time of 100% sudden fluctuation
Greater than 200% (30 second interval)
105% (200ms)
Rated load power factor / at rated input
Greater than 800% (2 cycle)
―
Breaker Protection
Bypass Non-Hit Change (Auto Return)
Auto-return can be disabled
Type
Maintenance Free Sealed Lead-Acid Battery (small)
Backup time
5minutes
Ambient Temp. of 25°C , under rated load
1 kVA : 40 dB MAX. 2 kVA, 3 kVA : 45 dB MAX. Double conversion mode 1 kVA : 125W, 2 kVA : 270W, 3 kVA : 460W
At 1m (40in) from the front of unit , At Economy mode
Acoustic noise Nominal heat dissipation Environment Operating temperature Relative humidity Standard of safety EMC standard
0 to 40°C 20 to 90%
Non-condensing
CE: IEC62040-1:2008 Emission
EN62040-2 C2:2006, EN55022:2006 Class-A (FCC Part15 Sub partB Class-A, CISPR 22 Class A)
Immunitiy
EN62040-2:2006, EN55024:1998/A1:2001/A2:2003
*A momentary power interruption lasting less than 5 ms occurs when switching from Economy Mode or Active Filter Mode to battery power. The unit can also be fixed to the Double Conversion Mode for applications that require zero transfer time from utility power to battery power.
Dimensions Dimensions (mm) W
Width (W)
H
D
Paint color: Black (Munsell N1.5)
6
1 kVA 2 kVA 3 kVA
Depth (D) 408
440
565 750
Mass (kg)
Height (H) 17 86
29 39
Run-time chart Model No.
E11A102BDE12
E11A202BDE12
E11A302BDE12
Max. Output (VA)
1000
2000
3000
Max. Output (W)
700
1400
2100
VA
W
Run-time (Min)
100
70
87
150
240
200
140
48
87
150
300
210
30
61
87
400
280
20
48
71
500
350
15
37
54
600
420
12
30
48
700
490
9
25
40
800
560
7
20
34
900
630
6
18
31
1000
700
5
15
28
1200
840
12
20
1400
980
9
17
1500
1050
8
16
1600
1120
7
14
1800
1260
6
12
2000
1400
5
10
2200
1540
9
2400
1680
8
2600
1820
7
2800
1960
6
3000
2100
5
*The above run-time value assumes a load power factor = 0.7. *Figures should be used for reference only. Actual backup times depend on charging conditions, ambient temperature, years in use, etc.
Option Item
Model No.
Rack support rail
RM030-US
Used for mounting the UPS onto a 19 inch rack. Supports depth of 555mm to 913mm.
■ External battery Dimensions (mm) Width(W)
Model No. BCE11A102A01US
for 1kVA
BCE11A202A01US
for 2kVA
BCE11A302A01US
for 3kVA
Depth(D)
Height(H)
408 440
565
86
750
Mass(kg)
Run-time (Min.) 20
40
60
20
1 unit
2 unit
3 unit
34
1 unit
2 unit
3 unit
52
1 unit
2 unit
3 unit
■ Rack support rail (RM030-US) External demensions
External demensions
W
Effective dimensions (when fully retracted) B
A
B
C
86.6mm
555mm
913mm
D
A
Paint color: Black (Munsell N1.5)
Effective dimensions (when fully extended)
A
H
C
■ Battery module can be replaced by removing the front panel, while the power is turned on.
7
Eco Products Sanyo Denki’s ECO PRODUCTS are designed with the concept of lessening impact on the environment in the process from product development to waste.The product units and packaging materials are designed for reduced environmental impact.We have established our own assessment criteria on the environmental impacts applicable to all processes,ranging from design to manufacture.Those products that satisfy the criteria are accredited as ECO PRODUCTS.
Notes when investigating use of this product in your applications Before starting installation, assembling and use, read the “Operation Manual” carefully and use the product correctly in your applications. When you are going to use this product in the following application, the special considerations are required for operation, running, maintenance and control. Be sure to consult with our company as a part of your investigations. (a) Medical equipment and other equipment that are related directly to human life. (b) Train or elevator that can give injury to human body. (c) Socially and publicly important computer systems.
(d) And other equipment that are related to safety of human life and that can affect severe effects on maintenance of public functions. For the applications that undergo vibration such as vehicles, ships and transportation facilities, please consult with our company. Never modify this product or give additional processing to this product. For the installation andmaintenance work, please consult with our company or with specialized company.
http://www.sanyodenki.com 3-33-1, Minami-Otsuka, Toshima-ku, Tokyo, 170-8451, Japan P.A. Paris Nord Ⅱ, 48 Allée des Erables-VILLEPINTE, BP.57286, F-95958 ROISSY CDG Cedex, France
Phone: +81 3 5927 1020
http://www.sanyodenki.eu Phone: +33 1 48 63 26 61
The names of companies and/or their products specified in this catalog are the trade names, and/or trademarks and/or registered trademarks of such respective companies. *Specifications are subject to change without notice. CATALOG No.P0884B005’14.4