Transcript
HZB12-120 HZB12-120 Valve Regulated Lead Acid battery. 12 year design life for stand by power applications. 12 Volts 120 Ah
§
Special formation process
§
Analytical Grade electrolyte
§
Spill proof / leak proof
§
Valve regulated Max internal pressure 2.5 psi
§
Multi-position usage
§
ABS Case and cover - V0 on request
§
Low self discharge
§
FAA and IATA approved as non-hazardous
§
Built to comply with IEC 8962, DIN 43534, BS 6290 Pt4, Eurobat.
Specifications Nominal Voltage Nominal Capacity Design Life Operating Temperature Grid alloy Plates Separator Active material Case and cover Charge Voltage Electrolyte Venting Valve
RE
LE
AD
Terminal Torque setting Cables
TU RN
RUBBISH BIN
RECYCLE
Pb
12 Volts 120Ah (C20 @ 20 oC) 12 Years -20 °C to 50 °C Calcium / Tin lead alloy Flat Pasted Absorbant Glass Mat Very high purity lead ABS (VO on request) Float 2.25 - 2.30 VPC @25 °C Cycliing 2.35 @25 °C Max. 2.4 VPC Max ripple 0.05C (A) Sulphuric acid Analytical grade purity EPDM Rubber 1.5 to 2 psi (10.5 - 14 KPa) release pressure. Resealing at 1 psi (7 KPa) Insert 16mm Dia M6 thread. Epoxy sealed by extended mechanical paths The recommended torque value for all types is 5-7 Nm Connectors, cables, terminal covers on request.
Haze Battery Company keenly encourages environmental awareness; PLEASE follow guidelines for the recycling /disposal of lead.
Website: www.hazebattery.com E mail :
[email protected]
PRODUCT SHEET HZB12-120
Completely maintenance free, sealed construction eliminates the need for watering
Sealed Lead Acid 12 Volt Bloc
§
AGM Range
Innovative Features
12V AGM
3
A
R10
10
R3
Specifications
227 mm
8.94 inches
(Inc. terminals)
n/a mm
n/a inches
Length
408 mm
16.06 inches
Width
176 mm
Weight
37 Kg
6.93 inches
16
Dimensions
122
120 Ah
A-A
12V
Nominal Voltage Nominal Capacity Total Height
81.77 lbs A
Characteristics
20
112.2 Ah
5 hour rate
97.7 Ah
1 hour rate
77.6 Ah
15 min rate
52.2 Ah 3 mOhms
Internal Resistance
1250 S
Impedance 40 oC (104 oF) o
Self-Discharge 20 oC (68 oF)
102%
o
20 C (68 F)
100%
0 oC (32 oF)
85%
-15 oC (5 oF)
65%
Capacity after 1 months storage
98%
Capacity after 3 months storage
94%
Capacity after 6 months storage
86%
Short Circuit Current 20 oC (68 oF)
408
Capacity correct ion for Temperature Variations (C20)
25
Capacity 20-25 oC (68-77 oF) To 1.7 volts
176
122.5 Ah
10 hour rate
To Terminal 206
20 hour rate
Standard Optional
16mm Insert M6 t hread Cu/Lead Flag - J Type - Auto
Cyclic
2.35 - 2.40 VPC (20-25 C)
o
48.5
Charging (Constant Voltage)
o
2.27 - 2.30 VPC (15-25 C)
Float
Battery 227
Terminal
48.5
3300
Constant Power Discharge - Watts per Cell @ 20-25 °C End V per Cell
5M
10M 15M 20M 25M 30M 35M 40M 45M 60M 90M
2 hr
3 hr
4 hr
5 hr
6 hr
7 hr
8 hr 10 hr 12 hr 20 hr
1.85
473
386
327
284
250
223
201
183
169
136
99
77.5
54.1
41.4
34.6
29.6
26.2
23.4
19.5
16.7
11.0
1.80
546
424
353
301
262
233
209
190
175
141
101
78.9
54.8
42.0
35.2
30.2
26.6
23.8
19.8
17.0
11.2
1.75
589
443
366
310
269
239
213
194
178
143
103
79.9
55.5
42.4
35.6
30.6
26.9
24.1
20.0
17.2
11.4
1.70
615
459
374
314
272
242
217
196
180
145
104
80.5
55.9
42.9
35.8
31.0
27.2
24.4
20.2
17.4
11.6
1.67
629
466
378
317
274
243
218
197
181
145
104
80.9
56.1
42.9
-
-
-
-
-
-
-
1.65
642
474
381
319
275
244
219
199
182
146
105
81.2
56.2
43.0
-
-
-
-
-
-
-
1.60
673
486
389
325
279
247
222
201
184
147
105
81.6
56.5
43.2
-
-
-
-
-
-
-
Constant Amps Discharge - Amps @ 20-25 °C End V per Cell
5M
10M 15M 20M 25M 30M 35M 40M 45M 60M 90M
2 hr
3 hr
4 hr
5 hr
6 hr
7 hr
8 hr 10 hr 12 hr 20 hr
1.85
259
213
180
156
135
120
108
98.6
90.3
72.8
52.1
40.7
28.7
22.6
18.6
16.0
14.1
12.7
10.6
9.12
5.73
1.80
309
240
196
165
143
126
112
102
93.6
74.8
53.3
41.6
29.2
22.9
18.9
16.3
14.4
13.0
10.9
9.35
5.90
1.75
332
255
203
170
147
129
115
105
95.6
76.3
54.4
42.3
29.6
23.2
19.2
16.6
14.7
13.2
11.1
9.49
5.97
1.70
349
265
209
174
150
132
117
106
97.2
77.6
55.0
42.8
30.0
23.6
19.5
16.8
14.9
13.4
11.2
9.66
6.13
1.67
358
268
212
176
151
133
118
107
97.7
78.0
55.2
42.9
30.1
23.6
-
-
-
-
-
-
-
1.65
366
270
214
177
152
133
119
107
98.1
78.4
55.5
43.1
30.2
23.7
-
-
-
-
-
-
-
1.60
385
279
218
180
154
135
120
108
99.2
78.9
56.0
43.4
30.4
23.8
-
-
-
-
-
-
-
Ampere Hour @ 20-25 °C End V per Cell
2 hr
3 hr
4 hr
5 hr
6 hr
7 hr
8 hr 10 hr 12 hr 20 hr
1.85
78.2
81.4
86.2
89.6
93.1
96.2
98.5
1.80 1.75 1.70
83.2 84.7 85.6
87.5 88.9 90.1
90.9 92.2 93.6
94.6 96.1 97.7
97.7 100.7 103.8 99.4 102.6 106 101.0 104 107
1.67
85.9
90.3
93.8
-
-
-
1.65
86.2
90.6
94.1
-
-
1.60
86.8
91.2
94.7
-
-
101.5
106
109
109 111 112
112 114 116
118 119 123
-
-
-
-
-
-
-
-
-
-
-
-
-
-
R
UL Recognised Component MH28512
EMC Germany
tested
220311