Preview only show first 10 pages with watermark. For full document please download

I56-2644-000 M400rfe-as Conv Radio System.pmd

   EMBED


Share

Transcript

M400RFE-AS CONVENTIONAL RADIO FIRE DETECTION SYSTEM INSTALLATION INSTRUCTIONS GENERAL RADIO COMMUNICATION TECHNICAL DATA Each radio component contains a transmission processor with bi-directional data communications and automatic frequency changing (frequency hopping) and facilitates a connection in which the security of the transmission is comparable to that of hard-wired apparatus. All fire system installations must conform to the relevant local standards, for example BS5839 part 1. Frequency range: 434MHz and 868MHz bands Max. Transmitted power: 10mW Number of channels: 20 in 434MHz band and 4 in 868MHz Channel width: 75kHz Channel separation: 434MHz band - 75kHz; 868MHz band - 150kHz Average data rate: 16,384kHz ± 200ppm Receiver sensitivity: -100dBm Detector address: 4-byte non-recurring code M400RFE-AS RADIO INTERFACE TECHNICAL DATA • Power supply either 240VAC 50Hz or 10.8-30VDC plus facility for 1.2AH/12V battery back-up if required. • Current consumption from 150mA quiescent • Up to 32 radio detectors can be auto configured and arranged in 2 detection zones • Each of the zones has its own fire and fault relays • Fire and fault of each zone will be transmitted to analogue panels using one or more modules • Activated radio detector may also be reset via the detection loop using output modules (dependant on panel functionality. • One LED indicator per detector signals alarm or fault. Further LEDs then indicate the status of that detector, including Alarm, Tamper (Device removed from socket), Chamber Fault, Detector Dirty, Battery Status and Communications failure. • Additional LEDs indicate the status of the M400RFE-AS radio interface 2100RFT-AS RADIO SMOKE DETECTOR TECHNICAL DATA • Photoelectric radio smoke detector conforming to EN54-7 combined with a fixed temperature (58o C) thermal sensor. • Conforms to CEA 4021 - capable of detecting both smoke and heat. • Fault conditions are recognised and signalled to the control panel • Removal of a detector from its base results in the transmission of a tamper fault signal • Little affected by wind speed or air pressure • Low current operation • Integral red alarm LED • Bayonet type connection gives simple installation. • Removable cover for simple cleaning of the detector chamber • Local test switch • Electronics free base • Powered by 2 x 3V lithium batteries type CR-123. M400DKM-AS & MCPRFE-AS RADIO CALL POINT TECHNICAL DATA • Radio call points conforming to EN54-11 • Low current operation - in-built battery warning • Integral red alarm LED • MCPRFE-AS powered by a 2 x 3V lithium pack type BATV-23 battery. • M400DKM-AS powered by a 2 x 3.6V lithium pack type CR-4148 or LS14500 battery • M400DKM-AS has tamper-proof cover that locks with a key and sends fault notification if opened, MCPRFE-AS requires special tool for access/reset and cannot be removed without setting off an alarm. D400-40-00 1 Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy DESCRIPTION OF SOFTWARE OPERATION OF THE RADIO SYSTEM has changed channel, or a data error has occurred, further communication attempts will be made. If these also fail, then the radio detector starts to try to communicate on the remaining channels. This attempt will be completed in 180 seconds. If the radio detector is still unable to communicate the status message with the M400RFE-AS, for example if the M400RFE-AS has lost power, then the communication attempt is terminated. The detector will then retry communications every 180 seconds. M400RFE-AS INTERFACE MODULE On start-up, the installed software version is indicated by means of a code signal on the green LED on the processor board. All alarm and fault signals received by the interface are latched, and remain on until the M400RFE-AS is reset by the control panel. All faults must be cleared before resetting the M400RFE-AS. Once a fault has been cleared, the new status is transmitted from the detector to the M400RFE-AS; however the fault LED will remain illuminated until reset by the control panel. Once the M400RFE-AS has returned to normal operation, communications should be automatically re-established with all detectors within 180 seconds. Once a communication has been acknowledged, the detector will return to its normal mode of operation, communicating each 90 seconds. If a system fault occurs on the M400RFE-AS, both Fault-relays will be simultaneously operated. System fault will be indicated using the 3 M400RFE-AS status LEDS. During Normal operation, the AC LED (mains supply connected or power supplied via the ext. PSU connector) is switched on (Green) and the LEDs, Battery (battery fault) and Tx/Rx Fail (all frequencies are disturbed), are off. All detectors should have received a confirmation message within 180 seconds, and the system will return to normal operation On entering a Fire Alarm Condition, the radio detector immediately starts to transmit its 'alarm' status to the M400RFEAS. On a radio smoke detector, the LED starts blinking red, whilst on a call point the LED is continuously on. The device attempts to communicate with the M400RFE-AS every 10 seconds. If the alarm signal from the radio device is not acknowledged by the M400RFE-AS within 10 seconds, then the device will try to reestablish communications as described above for M400RFE-AS failure. The battery supervision can be switched off if selector DIP4 on the daughter board (processor PCB) is switched off. This change must only be made when power to the M400RFE-AS is removed. 2100RFT-AS RADIO SMOKE DETECTOR (and M400DKM-AS and MCPRFE-AS RADIO CALL POINTS) On initial start up, or after a change to the system, a Learn procedure must be carried out as described in Learn Mode. In the learn mode, the red LED on the 2100RFT-AS blinks to indicate that it is sending information to the M400RE-AS. Once this information has been received, the M400RFE-AS will send a signal to terminate the learn mode. On receipt of this signal the 2100RFT-AS led will turn off (both call points operate in the same way, where the 2100RFT-AS is mentioned in this section, the same is true for the call points as well). If a Fault Condition occurs (tamper activation or detector replaced), the radio detector sends the new condition to the M400RFE-AS immediately. Battery Condition of the detectors and call points is monitored to ensure correct operation of the radio devices. If the battery voltage of the radio device falls below 5.1V, a battery alarm message is transmitted to the M400RFE-AS. This signal gives approximately 60 days warning of battery failure. The device will fail if the battery voltage falls below 4.8V. The battery warning is reset when the voltage at the end of a transmission sequence is above 5.2V. This ensures hysteresis, which prevents oscillation between battery alert and battery OK. For a change in battery fault status, the voltage must be below 5.1V (to enter fault) or above 5.2V (to exit fault) for 10 communications. In the Normal Condition, the radio detector sends a status communication to the M400RFE-AS every 90 seconds indicating the current status of the detector. Should this status communication not be received by the M400RFE-AS (Interface Fault), for example if the M400RFE-AS OVERVIEW OF THE M400RFE-AS PCB Plug-in Daughter Board (processor PCB) Dip Switch Reset Switch 5 4 3 2 1 6 7 8 9 RS232 Port Detector LEDs Indicates detector selected in Learn, Display or Delete Modes, or the detector in Alarm or Fault in Normal mode. Detector LEDs are all red Device Number > M400RFE-AS Control Switches Selection of interface Mode Detector Select Accept and Decline Operation View, Learn and Delete buttons have red LEDs to indicate mode active M400RFE-AS Status LEDs Indicate status of interface module. 1 x Green AC LED 2 x Yellow Fault LEDs Battery Warning Battery Low Low Temp Clean Device Comms Fail Delete Tamper YES Replace (Low) Replace A/D Learn Smoke Alarm Heat Alarm NO Tx / Rx Fail View AC < Battery Device Number Device 80mA 250V T 1A 250V T F2 2 Fire D. 1-16 Fault D. 1-16 C Fault D. 17- NC NC C Fire D. 17- NO NO C NC NO C NC NO GND GND AC Input Reset Ext PSU F1 AC Power Supply 240VAC 50Hz Power Supply Input Terminals Detector Status LEDs Indicates status of detector indicated by detector LEDs 2 x Red Alarm LEDs 8 x Yellow Fault LEDs M400RFE-AS Input and Output Terminals Alarm and Fault contacts. Reset input from panel. Optional Aux 12V 1.2Ah battery © System Sensor 2006 I56-2644-000 32 Detector LEDs • Device Number 1-32: Indicate device fault or alarm 8 Switches • View: Enter Display mode • Learn: Enter Learn mode 10 Detector status LEDs (Device) • Smoke Alarm: Fire from smoke detector • Delete: Enter Erase mode • < & >: Left and Right • Heat Alarm: Fire from heat detector • NO: Cancel • Tamper: Detector removed from socket • YES: Enter • Replace (low): Device chamber fault • Reset: Reset Transceiver • Replace (A/D): Detector fault (A/D Error) • Low Temp fault: Environment < 7°C ±3 5 Inputs • Clean Device: Smoke detector dirty • Ext. PSU Ext. Voltage + (galv. isolated) • Comms Fail: Detector lost after 180s • GND (2x) Ext. Voltage - (galv. isolated) • Battery Warning: Battery flat after 60 days • Reset I/P Reset detectors from alarm • Low Battery: • AC Mains input connection Not used 3 M400RFE-AS status LEDs • AC: Mains voltage applied 4 Outputs • Fire D.1-16: Alarm relay, Detectors 1 - 16 • Battery: Battery fault • Fault D.1-16: Fault relay, Detectors 1 - 16 • Tx/Rx Fail: All radio frequencies blocked • Fire D.17-32: Alarm relay, Detectors 17 - 32 • Fault D.17-32: Fault relay, Detectors 17 - 32 2 Fuses • F1, 80mA 250V T Mains supply protection • F2, 1A 250V T: M400RFE-AS RADIO ZONE INTERFACE MODULE OPERATING MODES • Repeat the above procedure to add further detectors. If all the available addresses are used, the learn mode cannot be entered and the M400RFE-AS remains in the NORMAL mode. Normal mode Erase mode The 32 radio detector LEDs (device number) are all off. When a radio detector generates an alarm or fault then the relevant device number LED is turned on. x10 NC C NO NC C NO NC C NO NC C GND 47kΩ 47kΩ 0 B 8 7 6 3 4 x1 9 1 2 9 0 5 4 1 C 8 2 7 6 3 5 0 1 A B 4 3 2 1 D400-40-00 M221E 5 Devices must be added to the system one at a time, batteries should therefore only be fitted to the devices at the time when the device is to be added to the system. It is important that only one new unlearnt device is transmitting during each learn cycle. A 6 • D.17-32 Fault 7 To accept the device and store the information in the M4000RFE-AS memory, press the YES button. To reject learning the device, press the NO button. The M400RFE-AS will return to the NORMAL mode. In order to learn another device, the learn mode process must be repeated. D.1-16 Fault 8 Fit the batteries into the device to be learnt. When the M400RFE-AS detects the signal, it indicates the received field strength on the 8 yellow status LEDs in the panel. A detector will be in the fault condition if the detector is not installed in its base, i.e. indicating a tamper fault. This is not a problem. • 12 11 10 9 Note: The device can optimize the transmission field strength. In order to avoid excessive and unnecessary power consumption from the battery, it is important to have the radio device generate this signal at the exact location it is going to be installed. To add a new detector: • Select a device number for the new device in the M400RFE-AS by using the arrow buttons on the PCB. D.1-16 Fire NO Ext. PSJ Learn mode Pressing the LEARN button, will put the M400RFE-AS panel into the learn mode. Free device numbers for new devices are allocated sequentially, but the arrow keys can be used to select an alternative number if required. GND By pressing the "VIEW" button, the display mode is entered. The device number LEDs illuminate to indicate which of the 32 numbers have learned a radio detector. The arrow buttons, ">" and "<" select radio detectors in sequence; the LED of the selected radio detector will blink and its status will be shown through the status LEDs. Press the "NO" button to return to Normal mode. Reset Input To select the erase mode, press the "DELETE" button. If no radio detectors have been learned, then this mode cannot be entered and the M400RFE-AS will remain in the normal mode. Select the detector to be removed from the M400RFE-AS memory using the arrow buttons. Press "YES" to erase the detector from the M400RFE-AS memory, or "NO" to exit the erase mode without deleting the detector. Display mode • External supply protection CONNECTION OF M400RFE-AS TO THE DETECTION LOOP The M400RFE-AS may be connected to an addressable detection loop using the System Sensor M221E Dual Input Single Output Module. The two supervised input channels monitor the radio interface fire and fault relays to signal alarm and fault conditions to the control panel in two zones, corresponding to detectors 1-16 and 17-32. End of line supervision is via a 47Kohm resistor. The output channel of the M221E is used to command a radio system reset from the control panel. The module address is set by rotary address switches. The address that the M221E is set to relates to the first input (LED A). 3 Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy The two successive addresses are automatically allocated to the second input (LED B) and the control module (LED C) respectively. When programming the modules during commissioning of the control panel, the following should be noted: 2100RFT-AS RADIO SMOKE DETECTOR OPERATION The 2 input modules must have short circuit detection switched off and fault delay set to 0 seconds. Should this status communication not be received by the M400RFE-AS (Interface Fault), for example if the M400RFE-AS has changed channel, or a data error has occurred, further communication attempts will be made. If these also fail, then the radio detector starts to try to communicate on the remaining channels. This attempt will be completed in 100 seconds. If the radio detector is still unable to communicate the status message with the M400RFE-AS, for example if the M400RFE-AS has lost power, then the communication attempt is terminated. The detector will then retry communications every 100 seconds. In the Normal Condition, the radio detector sends a status communication to the M400RFE-AS every 90 seconds indicating the current status of the detector. The input module must have short circuit and open circuit detection switched off. The entry in the control matrix for the control module must be for 5 seconds switching during a reset. 2100RFT-AS MOUNTING The 2100RFT-AS is removed from its base by rotating counterclockwise. The base is then fitted directly to the ceiling using 2 x M4 pan head screws (not supplied). If the mounting surface is uneven, care must be taken not to over tighten the screws and distort the ring. Once the M400RFE-AS has returned to normal operation, communications should be automatically re-established with all detectors within 100 seconds. Once a communication has been acknowledged, the detector will return to its normal mode of operation, communicating each 90 seconds. All detectors should have received a confirmation message within 100 seconds, and the system will return to normal operation The 2100RFT-AS is then replaced into the base by aligning the arrows on the ring with the lines on the detector cover, pressing home then rotating clockwise until the detector locks in place. On entering a Fire Alarm Condition, the radio detector immediately starts to transmit its 'alarm' status to the M400RFE-AS. On a radio smoke detector, the LED starts blinking red, whilst on a call point the LED is continuously on. The device attempts to communicate with the M400RFE-AS every 10 seconds. If the alarm signal from the radio device is not acknowledged by the M400RFE-AS within 10 seconds, then the device will try to re-establish communications as described above for M400RFE-AS failure. Note: Detector batteries must not be installed until the M500RFE-AS System Set-Up stage. 2100RFT MOUNTING CENTRES 140 mm T PA INT 10.2 cm If a Fault Condition occurs (tamper activation or detector replaced), the radio detector sends the new condition to the M400RFE-AS immediately. Battery condition of the detectors and call points is monitored to ensure correct operation of the radio devices. If the battery voltage of the radio device falls below 5.1V, a battery low message is transmitted to the M400RFE-AS. This signal gives approximately 60 days warning of battery failure. The device will fail if the battery voltage falls below 4.8V. 55 mm NO DO The battery warning is reset when the voltage at the end of a transmission sequence is above 5.2V. This ensures hysteresis, which prevents oscillation between battery alert and battery OK. For a change in battery fault status, the voltage must be below 5.1V (to enter fault) or above 5.2V (to exit fault) for 10 communications. 2100RFT-AS Battery Replacement Anti-Tamper Function The 2100RFT-AS has an anti tamper device that, when activated, prevents the removal of the detector from its base without the use of a tool. The 2100RFT-AS uses two 3V CR123A lithium batteries, having a normal life expectancy of eighteen months. To replace the batteries, remove the 2100RFT-AS from its base to allow access to the battery compartment. Ensure that the new batteries are installed with the correct polarity as indicated by the moulding mark next to the battery compartment (See 2100RFT-AS Assembly figure following). The detector will not need to be relearned and address information will be retained during the battery replacement. 2100RFT-AS Testing BREAK OFF SIDE TAB TO ACTIVATE ANTITAMPER FUNCTION. TO REMOVE DETECTOR ONCE ACTIVATED PRESS DOWN TAB WITH A SCREWDRIVER WHILST ROTATING DETECTOR ANTICLOCKWISE TO REMOVE Detectors must be tested after installation and following periodic maintenance. However, before testing, notify the proper authorities that the system is undergoing maintenance and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms. Test the detector as follows: Smoke method: CAUTION 1. Using generated smoke, or synthetic smoke aerosol from an approved manufacturer such as No Climb Products Ltd, subject the detector to controlled amounts of smoke in accordance with local codes of practice and manufacturer recommendations. Dust covers are fitted to the detectors to help protect units during shipment and when first installed. They are not intended to provide complete protection against contamination; therefore detectors should be removed before beginning construction, major re-decoration or other dust producing activity. Dust covers must be removed before the system can be made operational. 2. The red led on the detector should latch into alarm within 40 seconds, and the control panel should activate into alarm. 3. Press Reset on the M400RFE-AS to clear alarm. 4 © System Sensor 2006 I56-2644-000 Test Switch Method: 1. Using a small screwdriver or similar, depress the test switch located on the detector opposite the LED. 2100RFT-AS Assembly 2. Within a few seconds, the red led on the detector should start flashing; a fire alarm should be indicated at the control panel. 3. Press Reset on the M400RFE-AS to clear alarm. Detectors that fail these tests should be cleaned as described under 2100RFT-AS MAINTENANCE and re-tested. If the detectors still fail these tests they should be returned for repair. THERMISTORS I N T iNDICATOR LED PA After successful completion of all tests notify the proper authorities that the fire system is operational. T TEST SWITCH 2100RFT-AS Maintenance Before cleaning, notify the proper authorities that the system is undergoing maintenance and will be temporarily out of service. Disable the system to prevent unwanted alarms. NO DO DETECTOR COVER 1. Remove the detector to be cleaned from its base, and remove the batteries. 2. Gently release each of the four cover removal tabs that secure the cover in place by inserting a small screwdriver into the recess, and gently levering outwards, and remove the detector cover. INSECT SCREEN CHAMBER COVER 3. Vacuum the outside of the screen carefully without removing it. 4. Carefully remove the screen and chamber cover from the sensing chamber. 5. Use a vacuum cleaner and/or clean, compressed air to remove dust and debris from the sensing chamber and the inside of the screen. CHAMBER DETECTOR BASE RING 6. Re-install the chamber cover and screen, sliding the screen over the chamber and applying gentle pressure to secure it in place. COVER REMOVAL TABS 7. Reinstall the detector cover. Align the cover with the detector base guides and snap into place, ensuring that all the cover removal tabs are correctly engaged. 8. Replace the batteries in the detector, installing new batteries if required and replace it in its base. ALIGNMENT MARK TAMPER FAULT SIGNAL SWITCH 9. Restore power to the circuit and test the detector as described in TESTING above. After maintenance has been completed, notify the proper authorities that the fire system is operational. _ ALIGNMENT MARK + COVER REMOVAL TABS BATTERY COMPARTMENT D400-40-00 5 Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy