Description
Main Base – IC200CHS111
The Relay-Style Interposing I/O Terminals (IC200CHS111 and IC200CHS112) each provide dry contacts capable of switching high current outputs (up to 8A). The relays on these interposing terminals are intended to be controlled with standard 24VDC 0.5A VersaMax output modules (IC200MDL740 and IC200MDL750). Each relay is replaceable, individually fused, and includes status indication.
The Interposing Relay Base has a connector (J1) for attaching a cable from the Connector-Style I/O Carrier (IC200CHS003) and 50 box-style terminals for field I/O wiring and power connections. The Interposing Relay Base also has an expansion connector (J2) that can be used to attach to an Interposing Relay Expansion Base (IC200CHS112).
Preinstallation Check J2
126mm (4.95in)
Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system.
A16
A15
A14
A13
J1
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
Main and Expansion Base Two different versions of the Relay-Style Interposing I/O Terminals are available, the main and expansion bases. The Main Base, IC200CHS111, is for use with the 16 point VersaMax module (IC200MDL740) or points 1-16 of the 32 point VersaMax module (IC200MDL750). The Expansion Base, IC200CHS112, is for use with points 17-32 of the 32 point VersaMax module (IC200MDL750).
A16
A15
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
252mm (9.95in)
Expansion Base – IC200CHS112 The Interposing Relay Expansion Base has a connector (J2) for attaching a ribbon cable to the expansion connector of the Main Base (IC200CHS111) and 50 box-style terminals for field I/O wiring and power connections. The Expansion base includes a ribbon cable for connecting the expansion base to the main base.
VersaMax 32-Point 24VDC Output Module IC200MDL750 mounted on Connector Carrier IC200CHS003
IC200CBL105, 110, or 120
126mm (4.95in)
J2
Ribbon Cable (included with IC200CHS112) Relay-Style Interposing I/O Expansion Base IC200CHS112
B16
B16
B15
B15
B14
B14
B13
B13
B12
B12
B11
B11
B10
B10
B9
B9
B8
B8
252mm (9.95in)
Relay-Style Interposing I/O Main Base IC200CHS111
1
B7
B7
B6
B6
B5
B5
B4
B4
B3
B3
B2
B2
B1
B1
Relay-Style Interposing I/O Terminals April 2002
GFK-2143
Field Wiring
Relay Specifications
Power for operation of the relay coils must be provided by an external 24VDC power supply. This power must be provided to both the main base and the expansion base. Connection of this external power supply is made at the terminals A17 & A18 (B17 & B18 for the expansion base). This power connection is for the relay coils only. User loads must be powered by an external source.
The field-replaceable, form-C relay used in IC200CHS111 and IC200CHS112 is manufactured by Omron Electronics (part number G2R-14). The relay has the following specifications: Number of Poles
1 Pole
Each relay, status LED and fuse is labeled to indicate the specific point on the VersaMax output module they are associated with. Components labeled A1-A16 correspond to points Q1-Q16. Components labeled B1-B16 correspond to points Q17-Q32. Each point is associated with 3 terminal connections, labeled NO (Normally Open), C (Common), and NC (Normally Closed). User loads may be connected between C and NO, C and NC, or both.
Load
Resistive Load (cosΦ = 1)
Inductive Load (cosΦ = 0.4, L/R = 7ms)
Rated Load
8A at 250VAC
6A at 250VAC
8A at 30VDC
4A at 30VDC
Contact Ratings
Rated Carry Current
24VDC -
+
A18 A17
J2
A16
A15
A14
A13
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
Max Switching Voltage
380VAC, 125VDC
Max Switching Current
8A
Max Switching Power
2,000VA, 240W
Min Permissible Load
100mA at 5VDC
1,500VA, 120W
Characteristics
J1
A12
8A
A1
Contact Resistance
30 mΩ max
Operate (set) Time
15 ms max
Release (reset) Time
AC: 10 ms max; DC: 5ms max
Max Operating Frequency
Mechanical:
18,000 operations/hr
Electrical:
1,800 operations/hr (under rated load)
Insulation Resistance
1,000 MΩ min (at 500VDC)
Dielectric Strength
5,000 VAC, 50/60 Hz for 1 min between coil and contact 1,000 VAC, 50/60 Hz for 1 min between contacts of the same polarity
A16
A15
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
Vibration Resistance
A1
Shock Resistance A1
Destruction:
10 to 55Hz, 1.5mm double amplitude
Malfunction:
10 to 55Hz, 1.5mm double amplitude
Destruction:
1,000 m/s2
Malfunction:
200 m/s2 when energized; 100 m/s2 when not energized
Mechanical:
20,000,000 operations min (at 18,000 ops/hour)
Electrical
100,000 operations min (at 1,800 ops/hr under rated load)
NO C NC
Life Expectancy V
Q1
Ambient Temperature
Terminal Wiring
Ambient Humidity
Each terminal accommodates:
2
One solid (0.2 to 4.0mm cross section) or stranded (0.2 to 2 2.5mm cross section), AWG #12 to AWG #24.
When inserting two wires in the same position, the wires must be the same size and type (solid or stranded), as specified below:
Rigid or flexible wires: 0.2 to 1.5mm cross section.
Stranded wires with twin ferrule, with plastic sleeve
2
Stranded wires with ferrules, no plastic sleeve: 0.25 to 0.75mm cross section
2
Recommended torque for the terminal screws is 0.5 to 0.6 Nm.
2
Operating:
-40˚C to 70˚C (with no icing)
Storage:
-40˚C to 70˚C (with no icing)
Operating:
35% to 85%
Storage:
35% to 85%
Relay-Style Interposing I/O Terminals April 2002
GFK-2143
Life Expectancy
Life expectancy (10 operations)
AC inductive load - AC resistive (cosφ =0.4) load
10 8
5000
3
Switching current (Amps)
Switching Current
4
DC inductive load (L/R = 7ms) 1
DC resistive load 0.5
250VAC / 30VDC resistive load
1000 500
250VAC inductive load (cosφ =0.4)
100
30VDC inductive load (L/R = 7ms) 50
0.1 0
5
10
20 30 50
100
0
300 500
3
2
4
6
8
10