IEC Type Industrial Control Relays; TeSys D-Line, K-Line, and SK-Line SK-Line Ordering Information SK-Line Ordering Information – Miniature size saves space – Mounts on 35mm DIN3 track or can be mounted directly to a panel – Up to 4 poles
Contact Configuration Control Circuit Supply
Consumption
Type of Termination
CAZSK11G7 AC
4.2 VA
DC
Weight lb (kg)
N/O
N/C
1
1
CA2SK11 ▲
0.24 (0.109)
2
0
CA2SK20 ▲
0.24 (0.109)
1
1
CA3SK11 ▲
0.24 (0.109)
2
0
CA3SK20 ▲
0.24 (0.109)
Catalog Number
Weight lb (kg)
Screw clamp
2.2 W
Catalog Number
Screw clamp
Contact Adder Decks Used to expand the CA2SK20 two pole relays to a four pole relay.
Contact Configuration
Type of Termination LA1SK11
Screw clamp
N/O
N/C
2
0
LA1SK20
0.05 (0.022)
1
1
LA1SK11
0.05 (0.022)
0
2
LA1SK02
0.05 (0.022)
Transient suppressor module LA4SKE1U
Dampens the voltage spike that may occur when the relay coil is de-energized. The spike may adversely affect solid state equipment near the relay. The transient suppressor module snaps into a cavity located in the side of the relay. These modules can be used with CA2SK and CA3SK relays.
Control Circuit Voltage
Catalog Number
Weight lb (kg)
24-48 V 50/60 Hz 24-48 Vdc
LA4SKE1E
0.02 (0.010)
110-250 V 50/60 Hz 110-250 Vdc
LA4SKE1U
0.02 (0.010)
Coil Voltage Codes Voltage
12
24
36
48
110
120
220
230
240
380
400
480
50/60 Hz (CA2SK relays)
—
B7
—
E7
F7
G7
M7
P7
U7
Q7
V7
T7
DC
JD
—
CD
ED
SD
—
—
—
—
—
—
—
(CA3SK relays)
▲ Add proper voltage code to the end of the catalog number.
04/01
© 2001 Schneider Electric All Rights Reserved
19
IEC Type Industrial Control Relays; TeSys D-Line, K-Line, and SK-Line SK-Line Ordering Information
Environment Type
CA2
Conforming to Standards
IEC337-1, 947-1, 947-5, NF C 63-140, VDE0660, BS4794
Approvals
UL Listed File E164353 CCN NKCR, CSA File LR12721 Class 3211 03, SEMKO, SEV, DEMKO, CE
Operating Temperature Range
CA3
°F (°C)
-4 to 131 (-20 to 55)
Stranded wire
AWG (mm2)
Two #20 (0.75) to #16 (1.5)
Solid wire
AWG (mm2)
Two #18 (1) to #14 (2.5)
CA2
CA3
Conforming to UL508 Conforming to VDE 0110 Group C
V V
600 660
600 660
V
24 to 600
12 to 220
Wire Range
Control circuit characteristics Type Rated Insulation Voltage Rated Coil Voltage Uc Permissible Voltage Variation
+10/-20% Uc
Average Consumption Operating Time Mechanical Life
Inrush
15.5 VA
2.2 W
Sealed
4.2 VA
2.2 W
Pick-up
ms
8 to 16
10 to 18
Drop-out
ms
6 to 8
4 to 6
10
10
In millions of operations
Contact Ratings AC
DC Inductive 35% PF
Volts
Resistive 75% PF Amps
VA
Make, Break & Cont. Amps
Continuous Amps
VA
Continuous Amps
Volts
Amps
Make
120
60
7200
6
720
10
10
24
3
240
30
7200
3
720
10
10
60
2
15
7200
1.5
720
10
10
110
0.8
12
7200
1.2
720
10
10
240
0.2
UL Rating
A600
480 600
Break
Approximate dimensions
Contact Configurations Contact adder decks
33 NO
41 NC
31 NC
41 NC
34
42
32
42
21 NC 22
2 N/C
43 NO
13 NO 14
1 N/O and 1 N/O
44
23 NO 22
20
2 N/O
33 NO
13 NO
1 N/O and 1 N/C
14
2 N/O
34
Relays
© 2001 Schneider Electric All Rights Reserved
04/01