Transcript
IES INDOOR REPORT PHOTOMETRIC FILENAME : L051603306.IES DESCRIPTION INFORMATION (From Photometric File) IESNA:LM-63-2002 [TEST] L051603306 [TESTLAB] LIGHT LABORATORY, INC. [ISSUEDATE] 5/19/2016 [MANUFAC] Colt LED [LUMCAT] D24X6-GEN2-30W BiColor Fixture [LUMINAIRE] 24 Lamp LED Fixture - Daylight [BALLASTCAT] N/A [OTHER] INDICATING THE CANDELA VALUES ARE ABSOLUTE AND [MORE] SHOULD NOT BE FACTORED FOR DIFFERENT LAMP RATINGS. [REMARK] CANDELA VALUES AND ELECTRICAL DATA ARE PRORATED FROM [MORE] LIGHT LABORATORY REPORT L051603302 BY USING THE RATIO OF [MORE] TOTAL NUMBER OF LAMPS. RATIO=2.0(24 LAMPS / 12 LAMPS). [INPUT] 120VAC, 733.19W [TEST PROCEDURE] IESNA:LM-79-08 CHARACTERISTICS Lumens Per Lamp Total Lamp Lumens Luminaire Lumens Total Luminaire Efficiency Luminaire Efficacy Rating (LER) Total Luminaire Watts Ballast Factor CIE Type Spacing Criterion (0-180) Spacing Criterion (90-270) Spacing Criterion (Diagonal) Basic Luminous Shape Luminous Length (0-180) Luminous Width (90-270) Luminous Height
N.A. (absolute) N.A. (absolute) 49233 N.A. 67 733.19 1.00 Direct 1.22 1.30 1.40 Rectangular 3.75 ft 3.84 ft 0.00 ft
LUMINANCE DATA (cd/sq.m) Angle In Degrees
Average 0-Deg
Average 45-Deg
Average 90-Deg
45 55 65 75 85
10893 10226 9542 7756 3993
11683 11723 12394 12349 7763
12486 12957 13522 12396 7232
Photometric Toolbox Professional Edition - Copyright 2002-2012 by Lighting Analysts, Inc. Calculations based on published IES Methods and recommendations, values rounded for display purposes. Results derived from content of manufacturers photometric file.
Page 1
IES INDOOR REPORT PHOTOMETRIC FILENAME : L051603306.IES CANDELA TABULATION
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
0.0 16416 16308 16040 15600 15012 14280 13430 12482 11442 10314 9118 7854 6622 5400 4046 2688 1424 466 0
22.5 16416 16312 16054 15632 15064 14356 13532 12610 11604 10516 9376 8198 7074 5982 4808 3638 2338 902 0
45.0 16416 16328 16094 15710 15190 14542 13792 12954 12040 11062 10044 9004 8006 7014 5776 4280 2608 906 0
67.5 16416 16350 16136 15786 15320 14738 14070 13316 12492 11600 10668 9688 8698 7538 6010 4328 2560 868 0
90.0 16416 16362 16162 15820 15366 14816 14176 13466 12676 11822 10916 9952 8912 7652 6042 4296 2504 844 0
Photometric Toolbox Professional Edition - Copyright 2002-2012 by Lighting Analysts, Inc. Calculations based on published IES Methods and recommendations, values rounded for display purposes. Results derived from content of manufacturers photometric file.
Page 2
IES INDOOR REPORT PHOTOMETRIC FILENAME : L051603306.IES ZONAL LUMEN SUMMARY Zone
Lumens
%Lamp
%Fixt
0-20 0-30 0-40 0-60 0-80 0-90 10-90 20-40 20-50 40-70 60-80 70-80 80-90 90-110 90-120 90-130 90-150 90-180 110-180 0-180
5984.83 12690.78 20804.89 37361.96 48134.99 49232.58 47681.06 14820.06 23360.2 23201.48 10773.02 4128.61 1097.6 0.00 0.00 0.00 0.00 0.00 0.00 49232.58
N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A.
12.20 25.80 42.30 75.90 97.80 100.00 96.80 30.10 47.40 47.10 21.90 8.40 2.20 0.00 0.00 0.00 0.00 0.00 0.00 100.00
Total Luminaire Efficiency = N.A.% ZONAL LUMEN SUMMARY Zone
Lumens
0-10 10-20 20-30 30-40 40-50 50-60 60-70 70-80 80-90 90-100 100-110 110-120 120-130 130-140 140-150 150-160 160-170 170-180
1551.52 4433.31 6705.95 8114.11 8540.14 8016.94 6644.41 4128.61 1097.6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Photometric Toolbox Professional Edition - Copyright 2002-2012 by Lighting Analysts, Inc. Calculations based on published IES Methods and recommendations, values rounded for display purposes. Results derived from content of manufacturers photometric file.
Page 3
IES INDOOR REPORT PHOTOMETRIC FILENAME : L051603306.IES COEFFICIENTS OF UTILIZATION - ZONAL CAVITY METHOD Effective Floor Cavity Reflectance 0.20 RC RW
80 70 50 30 10
70 70 50 30 10
50 50 30 10
30 50 30 10
10 50 30 10
0 0
0 1 2 3 4 5 6 7 8 9 10
119 119 119 119 108 103 99 95 98 89 82 76 89 78 70 63 81 69 60 53 75 61 52 45 69 55 46 39 64 50 41 35 59 46 37 31 55 42 33 28 52 38 30 25
116 116 116 116 105 101 97 93 95 87 81 75 86 76 69 62 79 68 59 52 72 60 52 45 67 54 46 39 62 49 41 35 58 45 37 31 54 41 33 28 51 38 30 25
111 111 111 97 93 90 84 78 73 73 67 61 65 58 52 58 50 45 52 45 39 48 40 34 43 36 31 40 33 27 37 30 25
106 106 106 93 90 87 80 76 72 71 65 60 63 56 51 56 49 44 51 44 38 46 39 34 42 35 30 39 32 27 36 29 25
102 102 102 89 87 85 77 74 70 68 63 59 60 55 50 54 48 44 49 43 38 45 38 34 41 35 30 38 32 27 35 29 25
100 83 68 57 48 41 36 32 28 25 23
Photometric Toolbox Professional Edition - Copyright 2002-2012 by Lighting Analysts, Inc. Calculations based on published IES Methods and recommendations, values rounded for display purposes. Results derived from content of manufacturers photometric file.
Page 4
IES INDOOR REPORT PHOTOMETRIC FILENAME : L051603306.IES POLAR GRAPH
16416
12312
8208 3 4104
2 1
Maximum Candela = 16416 Located At Horizontal Angle = 0, Vertical Angle = 0 # 1 - Vertical Plane Through Horizontal Angles (0 - 180) (Through Max. Cd.) # 2 - Vertical Plane Through Horizontal Angles (90 - 270) # 3 - Horizontal Cone Through Vertical Angle (0) (Through Max. Cd.)
Photometric Toolbox Professional Edition - Copyright 2002-2012 by Lighting Analysts, Inc. Calculations based on published IES Methods and recommendations, values rounded for display purposes. Results derived from content of manufacturers photometric file.
Page 5