Transcript
Product Sheet | Detecon
Industrial detectors Fire detectors for industrial risks
UniVario FMX5000 IR 3-channel infrared Àame detector with three-way optics test for complete function monitoring. Very high responsivity and ¿ltering of interfrence such as sunlight and hot surfaces through intelligent evaluation algorithms UniVario FMX5000 UV Flame detector with spectral sensitivity in the ultraviolet range. High response sensitivity with monitoring area up to 676 m2. Interference such as cosmic radiation and thunderstorms (lightning) is ¿ltered out intelligent evaluation algorithms with integrated self-testing for monitoring the functionality (optical test). UniVario WMX5000 Heat detector with a robust stainless steel heat sensor. A microcontroller monitors the functionality and analyses data. The detector can be freely con¿gured for any application. For this, response temperatures, response classes and indices can be adjusted. Can be expanded by adding an LCD display. UniVario WMX5000 FS Heat detector for heavy-duty daily use with a robust stainless steel heat sensor rod or Àexible hose which protrudes from the enclosure. Thermoelectric sensors for response temperatures up to 850 °C (1562 °F). A microcontroller monitors the functionality and analyses data. Prominent response temperatures and all response classes can be freely con¿gured, along with rate-of-rise and static (¿xed temperature) response behaviour. Can be expanded by adding an LCD display.
UniVario A family of industrial ¿re detectors based on a uniform platform. Highly variable, with a modular system for maximum adaptability.
P31.312.000en / 02.14
Conventional detectors are available and can be changed to analog addressable detectors by adding the communication module KMX5000 AP / KMX5000 AP Ex. To achieve the best possible protection in each individual scenario, ¿re detectors of different designs and response sensitivity are used according to the requirements of each protected site. They work indoors and outdoors; in the direct vicinity of the protected site like UniVario WMX5000, or from further a¿eld like UniVario FMX5000 UV; in clean room environments as well as in extremely dirty process conditions. Equipped internally with the very latest advanced technology, they also feature a robust and attractive enclosure design. This new generation of high-tech ¿re detectors is substantially prefabricated, is easy and quick to install and can be easily integrated into existing solutions, making them an affordable alternative to conventional systems. One major advantage of the new range is their ability to forward detector data to databases for the purposes of analysis, maintenance or statistics compilation. Variations of UniVario detectors for conventional lines or analogue addressable systems are available, well graded for different hazard areas. The UniVario detector series with state of the art technology has big advantages due to lower installation costs in analogue addressable systems and increased safety due to permanent data transfer between control panel and detectors.
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 1
Product Sheet | Detecon
Industrial detectors Fire detectors for industrial risks Overview accessories UniVario
Bracket
Console
Base
Base 3M16
Base LCD
Base+Isolator
Relay module
Comms module Service device
F
FMX5000 IR
FMX5000 IR HR
Base HR
Bracket HR
F
FMX5000 UV
FMX5000 UVs
F
W
WMX5000
WMX5000 FS
WMX5000 FS Flex
WMX5000 single hole
W
W
F
P31.312.000en / 02.14
WMX5000 VA
W
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 2
Product Sheet | Detecon
Industrial detectors Fire detectors for industrial risks Overview accessories UniVario
Ex barrier
Bracket
Console
Base
Base Ex
Comms Comms Service module module Ex device
3GD F
FMX5000 IR 3GD
*1
2G1D F
FMX5000 IR Ex 3GD
FMX5000 UV 3GD
F
*1
P31.312.000en / 02.14
*1) The service device should only be used outside of the explosion hazardous zone
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 3
Product Sheet | Detecon
Industrial detectors Fire detectors for industrial risks Overview accessories UniVario
Ex barrier
Bracket
Console
Base
Base Ex
Comms Comms Service module module Ex device
3GD W
WMX5000 3GD
*1
2G1D W
WMX5000 Ex 3GD
W
WMX5000 FS 3GD
*1
2G1D W
WMX5000 FS Ex 3GD
W
WMX5000 FS Flex 3GD
*1
2G1D W
WMX5000 FS Flex Ex 3GD
WMX5000 single hole 3GD
W
*1
2G1D
WMX5000 single hole Ex
W
P31.312.000en / 02.14
*1) The service device should only be used outside of the explosion hazardous zone
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 4
Product Sheet | Detecon
Industrial detectors UniVario IR flame detector FMX5000 IR
Order no.: 907481 Triple IR Àame detector for the detection of typical ¿res. Including 3 channel optic test monitoring all functional characteristics of detector. Designed for use in rough industrial environments. Equipped for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
•
Highly reliable against false alarms, e.g. from hot surfaces or sunlight.
•
A microcontroller monitors the functionality and analyses the recorded data. Faults can be indicated on the detector or on a separate line.
Parallel indicator LMX5000 Weather protection MX5000 complete KMX5000 AP communication module Silicone-free design
•
Service interface, history memory.
•
Connection of remote indicator possible.
•
3-channel optic test.
908499 910134 905883
Not included in delivery Base UniVario MX5000 Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
904701 904757 675235
Connection / mounting Technical specifications Detection method Sensitivity class Viewing angle
1 90°
Operating voltage
7.6 V - 30 V DC
Quiescent current
2.3 mA
Alarm current Alarm indication Fault indication current Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to P31.312.330 - 1en / 02.13
3 IR Sensors
Weight Dimensions
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking G 209141
0786-CPD-20784
approx. 15 mA 1 LED red approx. 15 mA 1 LED yellow -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 10 820 g (1.8 lbs) 100 x 50 mm (dia. x H) 3.9 x 2 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 5
Product Sheet | Detecon
Industrial detectors UniVario IR flame detector FMX5000 IR HR
Art.-Nr.: 909404 Triple IR Àame detector for the detection of typical ¿res. Including 3 channel optic test monitoring all functional characteristics of detector. Variante HR (high ressistance) designed for use in highly rough industrial environments such as chemical industry. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
•
Highly reliable against false alarms, e.g. from hot surfaces or sunlight
•
A microcontroller monitors the functionality and analyses the recorded data. Faults can be indicated on the detector or on a separate line
Parallel indicator LMX5000 Weather protection MX5000 complete KMX5000 AP communication module Silicone-free design
•
Service interface, history memory
•
Connection of remote indicator possible
•
3-channel optic test
Sensitivity class Viewing angle Operating voltage Quiescent current Alarm current Alarm indication Fault indication current Fault indication Operating temperature IP rating (EN 60529)
P31.312.330 - 2en / 02.13
Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
Not included in delivery Base UniVario MX5000 HR Bracket MX5000 Mounting device bracked MX5000 HR Terminating resistor 1.8 K / 0.5 W
909406 904757 909359 675235
Connection / mounting
Technical specifications Detection method
908499 910134 905883
3 IR Sensors 1 90° 7.6 V - 30 V DC 2.3 mA
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)
Approvals / marking G 209141
0786-CPD-20784
approx. 15 mA 1 LED red approx. 15 mA 1 LED yellow -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 10 820 g (1.8 lbs) 100 x 50 mm (dia. x H) 3.9 x 2 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 6
Product Sheet | Detecon
Industrial detectors UniVario UV flame detector FMX5000 UV
Order no.: 904702 UV Àame detector for the detection of typical ¿res. Including UV optic test monitoring all functional characteristics of detector. Designed for use in rough industrial environments. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
•
Parallel indicator Weather protection MX5000 complete KMX5000 AP communication module Silicone-free design
•
• •
Highly reliable against false alarms, e.g. from lightning Àashes or strong sunlight. A microcontroller monitors the functionality and analyses the recorded data. Faults can be indicated on the detector or on a separate line. Service interface, history memory. Connection of remote indicator possible.
Technical specifications Detection method Sensitivity class Viewing angle
UV sensor 1 90°
Operating voltage
7.6 V - 30 V DC
Quiescent current
approx. 0.25 mA
Alarm current Alarm indication Fault indication current Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight
Not included in delivery Base UniVario MX5000 Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking
1 red LED approx. 15 mA
904701 904757 675235
Connection / mounting
G 206132
0786-CPD-20286
1 yellow LED -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 10 820 g (1.8 lbs) 100 x 50 mm (dia. x H) 3.9 x 2 inch (dia. x H)
P31.312.310en / 02.13
Dimensions
approx. 15 mA
908499 910134 905883
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 7
Product Sheet | Detecon
Industrial detectors UniVario UV flame detector FMX5000 UVs
Order no.: 907375 UV Àame detector for the detection of typical ¿res. Designed for use in rough industrial environments. Designed for operation as a conventional detector. Expansion for a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
•
Parallel indicator Weather protection MX5000 complete KMX5000 AP communication module Silicone-free design
•
• •
Highly reliable against false alarms, e.g. from lightning Àashes or strong sunlight. A microcontroller monitors the functionality and analyses the recorded data. Faults can be indicated on the detector or on a separate line. Service interface, history memory. Connection of external signal indication possible.
Technical specifications Detection method Sensitivity class Viewing angle
UV sensor 1 90°
Operating voltage
7.6 V - 30 V DC
Quiescent current
approx. 0.25 mA
Alarm current Alarm indication Fault indication current Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight
1 red LED approx. 15 mA
Not included in delivery Base UniVario MX5000 Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
904701 904757 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking G 206132
0786-CPD-20286
1 yellow LED -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% No condensation EN 54 Part 10 820 g (1.8 lbs) 100 x 50 mm (dia. x H) 3.9 x 2 inch (dia. x H)
P31.312.310en / 02.13
Dimensions
approx. 15 mA
908499 910134 905883
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 8
Product Sheet | Detecon
Industrial detectors UniVario Heat detectors, standard WMX5000
Order no.: 905441 The WMX5000 heat detectors are designed to detect open ¿res with rapid rise of temperature, e.g.: – Flammable liquids and gases – Highly Àammable plastics. They are designed speci¿cally for operation in polluted industrial environments, both indoors and outdoors. In addition to static temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
•
Robust stainless steel heat sensor, resistant against impact and vibration.
•
Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector.
Detector remote indicator Weather protection MX5000 complete KMX5000 AP communication module Silicone-free design
•
Service interface, history memory.
•
Connection of remote indicator possible.
Detection method
NTC sensor
Response classes
Operating voltage
A1, A2, B, C, indices S, R 0 °C to +90 °C (+32 °F to +194 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.15 mA
Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current indication Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to
P31.312.110 - 1en / 02.14
Weight Dimensions
Not included in delivery Base UniVario MX5000 Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
Technical specifications
approx. 15 mA
904701 904757 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking
1 red LED 1 green LED, Àashing
801297 910134 905883
G 207090
0786-CPD-20280
approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 g (1.2 lbs) 130 x 84 mm (dia. x H) 5.1 x 3.3 inch (dia. x H)
WMX5000 CN
Order no.: 909375
Version China
Approvals / marking
Technical data see Order no 905441
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 9
Product Sheet | Detecon
Industrial detectors UniVario Heat detectors, standard UniVario WMX5000 single hole
Order no.: 905847 The single hole mounted WMX5000 heat detectors are speci¿cally designed for use in dryer and ventilation ducts for the detection of ¿res with rapid rise in temperature, e.g.: – Flammable liquids and gases – Highly Àammable plastics. In addition to ¿xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
•
Robust stainless steel heat sensor, resistant to impact and vibration.
•
Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector.
Parallel indicator Weather protection MX5000 complete KMX5000 AP communication module Silicone-free design
•
Service interface, history memory.
•
Connection of remote indicator possible.
Detection method
NTC sensor
Response classes
Operating voltage
A1, A2, B, C, D indices S, R 0 °C to +105 °C (+32 °F to +221 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.15 mA
Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current indication Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to
P31.312.110 - 3en / 02.14
Weight Dimensions
Not included in delivery Base UniVario MX5000 Single hole mounting ¿xture Single hole mounting tool Terminating resistor 1.8 K / 0.5 W
Technical specifications
approx. 15 mA 1 red LED 1 green LED, Àashing
908499 910134 905883
904701 800034 800388 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking G 207090
0786-CPD-20280
approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5 580 g (1.3 lbs) 130 x 133 mm (dia. x H) 5.1 x 5.2 inch (dia. x H)
WMX5000 single hole CN
Order no.: 909376
Version China
Approvals / marking
Technical data see Order no 905847
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 10
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS WMX5000 FS 400°C (752 °F)
Order no.: 905505 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to ¿xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
• •
Parallel indicator KMX5000 AP communication module Silicone-free design
• •
Robust stainless steel heat rod sensor Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector. Service interface, history memory. Connection of remote indicator possible.
Technical specifications Detection method
Operating voltage
PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +400 °C (+32 °F to +752 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.25 mA
Response classes Response temperatures
Alarm current consumption
approx. 15 mA
Alarm indication
1 red LED
Normal operation indication Current consumption Fault indication Fault indication
1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67
Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight
P31.312.130en / 02.14
Dimensions
908499 905883
Not included in delivery Base UniVario MX5000 Single hole mounting ¿xture Single hole mounting tool Terminating resistor 1.8 K / 0.5 W
904701 800034 800388 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the sensor rod must be speci¿ed in millimetres at the time of placing the order. Alternatively, ¿xed standard rod lengths are available to choose from.
Approvals / marking G 207091
0786-CPD-20281
Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 to 1600 g (1.2 to 3.5 lbs) 130 x 150 to 1500 mm (dia. x H) 5.1 x 5.9 x 59.1 inch (dia. x H)
WMX5000 FS 400 °C (752 °F) CN
Order no.: 909378
Version China
Approvals / marking
Otherwise like Order no 905505
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 11
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS
WMX5000 FS 400 °C 200 mm (752 °F 7.9 inch)
Order no.: 906401
Version with ¿xed rod length of 200 mm (7.9 inch)
Otherwise like Order no.: 905505
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 680 g (1.5 lbs) 130 x 260 mm (dia. x H) 5.1 x 10.2 inch (dia. x H)
WMX5000 FS 400 °C 400 mm (752 °F 15.8 inch)
Order no.: 906402
Version with ¿xed rod length of 400 mm (15.8 inch)
Otherwise like Order no.: 905505
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 840 g (1.9 lbs) 130 x 460 mm (dia. x H) 5.1 x 18.1 inch (dia. x H)
WMX5000 FS 400 °C 600 mm (752 °F 23.6 inch)
Order no.: 906403
Version with ¿xed rod length of 600 mm (33.6 inch)
Otherwise like Order no.: 905505
Technical specifications Response temperatures Weight
P31.312.130en / 02.14
Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 1000 g (2.2 lbs) 130 x 660 mm (dia. x H) 5.1 x 26 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 12
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS WMX5000 FS 850°C (1562 °F)
Order no.: 906454 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to ¿xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
• •
Parallel indicator KMX5000 AP communication module
• •
Robust stainless steel heat rod sensor Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector. Service interface, history memory. Connection of remote indicator possible.
Technical specifications Detection method
Operating voltage
PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +840 °C (+32 °F to +1544 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.35 mA
Response classes Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current consumption Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight
P31.312.130en / 02.14
Dimensions
approx. 15 mA 1 red LED 1 green LED, Àashing
908499 905883
Silicone-free design
Not included in delivery Base UniVario MX5000 Single hole mounting ¿xture Single hole mounting tool Terminating resistor 1.8 K / 0.5 W
904701 800034 800388 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the sensor rod must be speci¿ed in millimetres at the time of placing the order.
approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 to 1600 g (1.2 to 3.5 lbs) 130 x 150 to 1500 mm (dia. x H) 5.1 x 5.9 x 59.1 inch (dia. x H)
Approvals / marking
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 13
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS Flex WMX5000 FS Flex 400°C (752 °F)
Order no.: 906176 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to ¿xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
• •
Parallel indicator KMX5000 AP communication module
• •
Robust Àexible stainless steel heat sensor Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector. Service interface, history memory. Connection of remote indicator possible.
Technical specifications Detection method
Operating voltage
PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +400 °C (+32 °F to +752 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.25 mA
Response classes Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current consumption Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight
1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5
Silicone-free design
Not included in delivery Base UniVario MX5000 Holder WMX FS, from 250 °C (482 °F) to 600 °C (1112 °F) Terminating resistor 1.8 K / 0.5 W
904701 894679 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the Àexible sensor rod must be speci¿ed in metres at the time of placing the order. The sensor rod holder is designed for application temperatures of up to 250 °C (482 °F). In case of higher application temperatures, the holder WMX FS from 250 °C (482 °F) to 600°C (1112 °F) Order no. 804679 is to be used.
Approvals / marking G 207091
0786-CPD-20281
520 to 1600 g (1.2 to 3.5 lbs) 130 x 2000 to 9000 mm (dia. x H) 5.1 x 78.7 x 354.3 inch (dia. x H)
P31.312.150en / 01.14
Dimensions
approx. 15 mA
908499 905883
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 14
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS Flex
WMX5000 FS Flex 400 °C 2 m (752 °F 79 inch)
Order no.: 906404
Version with Àexible hose of 2 m length (79 inch)
Otherwise like Order no.: 906176
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 680 g (1.5 lbs) 130 x up to 2000 mm (dia. x H) 5.1 x up to 78.73 inch (dia. x H)
WMX5000 FS Flex 400 °C 6 m (752 °F 236 inch)
Order no.: 906405
Version with Àexible hose of 6 m length (236 inch)
Otherwise like Order no.: 906176
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 840 g (1.9 lbs) 130 x up to 6000 mm (dia. x H) 5.1 x up to 236.2 inch (dia. x H)
WMX5000 FS Flex 400 °C 9 m (752 °F 354 inch)
Order no.: 906406
Version with Àexible hose of 9 m length (354 inch)
Otherwise like Order no.: 906176
Technical specifications Response temperatures Weight
P31.312.150en / 01.14
Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 1000 g (2.2 lbs) 130 x up to 9000 mm (dia. x H) 5.1 x up to 354.3 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 15
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS Flex WMX5000 FS Flex 850°C (1562 °F)
Order no.: 906455 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to ¿xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
• •
Parallel indicator KMX5000 AP communication module Silicone-free design
• •
Robust Àexible stainless steel heat sensor. Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector. Service interface, history memory. Connection of remote indicator possible.
Operating voltage
PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +840 °C (+32 °F to +1544 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.35 mA
Response classes Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current consumption Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight
P31.312.150en / 01.14
Dimensions
Not included in delivery Base UniVario MX5000 Terminating resistor 1.8 K / 0.5 W
904701 675235
Connection / mounting
Technical specifications Detection method
908499 905883
approx. 15 mA 1 red LED
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the Àexible sensor rod must be speci¿ed in metres at the time of placing the order.
Approvals / marking
1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 to 1600 g (1.2 to 3.5 lbs) 130 x 2000 to 9000 mm (dia. x H) 5.1 x 78.7 x 354.3 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 16
Product Sheet | Detecon
Industrial detectors UniVario IR flame detector, Ex UniVario FMX5000 IR 3GD
Order no.: 909481 Triple IR Àame detector for the detection of typcal ¿res. Including 3 channel optic test monitoring all functionalties of detector. ATEX-approved for category 3, Gas and Dust, suitable for use in Ex zones 2 and 22. The detector must not connected with a safety barrier and a blue ¿re alarm cable. Designed for use in rough industrial environments. Equipped for operation as a conventional detector. Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.
Product features
Optional accessories
•
Highly reliable against false alarms, e.g. from hot surfaces or sunlight.
•
A microcontroller monitors the functionality and analyses the recorded data. Faults can be indicated on the detector or on a separate line.
Parallel indicator LMX5000 KMX5000 AP communication module Weather protection MX5000 complete Silicone-free design
•
Service interface, history memory.
•
Connection of remote indicator possible.
•
3-channel optic test.
•
For use in Ex zones 2 and 22, ATEX category 3 Gas/ Dust
Sensitivity class Viewing angle
1 90°
Quiescent current
2.3 mA
Fault indication current Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to P31.312.340 - 1en / 01.14
3 IR Sensors
7.6 V - 30 V DC
Alarm indication
Weight Dimensions
904701 904757 675235
Connection / mounting
Operating voltage
Alarm current
Not included in delivery Base UniVario MX5000 Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
Technical specifications Detection method
908499 905883 910134
approx. 15 mA 1 LED red
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 3G Ex nAc IIC T4 x II 3D Ex tc IIIC T110°C IP65
approx. 15 mA 1 LED yellow -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 10
Type examination certi¿cate: BVS 11 ATEX E135 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ia IIC T6/T4 Gb 0Ex ia IIC T6/T4 Ga Ex ia IIIC T95°C Da G 209141
0786-CPD-20784
820 g (1.8 lbs) 100 x 50 mm (dia. x H) 3.9 x 2 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 17
Product Sheet | Detecon
Industrial detectors UniVario IR flame detector, Ex FMX5000 IR Ex
Order no.: 911674 Triple IR Àame detector for the detection of typical ¿res. Including 3 channel optic test monitoring all functionalties of detector. ATEX and IECEx approved for category 2 Gas and 1, 2 Dust, suitable for use in Ex zones 1, 20 and 21. The detectors must be connected via a safety barrier. Designed for use in tough industrial environments. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex. communication module.
Product features
Optional accessories
•
Highly reliable against false alarms, e.g. from hot surfaces or sunlight.
•
A microcontroller monitors the functionality and analyses the recorded data. Faults can be indicated on the detector or on a separate line.
Safety barrier IS conventional 9 V Safety barrier IS addressable 24 V KMX5000 AP Ex communication module Weather protection MX5000 complete Silicone-free design
•
Service interface, history memory.
Not included in delivery
•
Connection of remote indicator possible.
•
3-channel optic test.
•
For use in Ex zones 1, 20 and 21, ATEX category 2 Gas/1, 2 Dust.
Base UniVario MX5000 Ex Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
Sensitivity class Viewing angle Operating voltage Quiescent current Alarm current Alarm indication Fault indication current Fault indication
P31.312.340 - 1en / 01.14
3 IR Sensors 1
7.6 V - 30 V DC 4.5 mA
1 LED red approx. 15 mA
Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to
Diecast aluminium 0 to 95% no condensation EN 54 Part 10
Dimensions
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 2G Ex ia IIC T6/T4 Gb x II 1D Ex ia IIIC T95°C Da
approx. 15 mA
IP rating (EN 60529)
Weight
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
90°
1 LED yellow -25 °C to +80 °C (-13 °F to +176 °F) IP 67
Operating temperature
912082 904757 675235
Connection / mounting
Technical specifications Detection method
904991 901324 912086 910134
Type examination certi¿cate: BVS 12 ATEX E088 IECEx conformity: IECEx BVS 12.0056 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ia IIC T6/T4 Gb 0Ex ia IIC T6/T4 Ga Ex ia IIIC T95°C Da G 209141
0786-CPD-20784
860 g (1.9 lbs) 100 x 50 mm (dia. x H) 3.9 x 2 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 18
Product Sheet | Detecon
Industrial detectors UniVario UV flame detector Ex FMX5000 UV 3GD
Order no.: 907267 UV Àame detector for detection of typical ¿res. Designed for use in harsh industrial environments. Fitted for use as a conventional detector. The WMX5000 UV 3GD UV Àame detectors are Atex approved for Category 3 gas and dust and are intended for use in Ex Zones 2 and 22. Expansion to a detector with Loop AP protocol via the KMX5000 AP communications module. The Àame detector features a built-in optical channel function test.
Product features
Optional accessories
•
High degree of immunity against false alarms, such as storm lightning or strong sunlight.
•
Function monitoring and evaluation of measured values by microcontroller, faults can be displayed on the detector or a separate line.
Parallel indicator LMX5000 KMX5000 AP communication module Weather protection MX5000 complete Silicone-free design
•
Service interface, history memory.
•
Connection of external display possible.
•
Use in Ex Zones 2 and 22 Atex Categorie 3 gas/dust.
Not included in delivery Base UniVario MX5000 Bracket MX5000 Terminating resistor 1,8 K / 0,5 W
Technical specifications Detection method Sensitivity class Viewing angle
1 90°
Quiscent current
approx. 0.25 mA approx. 15 mA
Alarm indication
1 LED red
Fault indication current
ca. 15 mA
Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight P31.312.320 - 1en / 01.14
UV-Sensor
7.6 V - 30 V DC
Fault indication
Dimensions
904701 904757 675235
Connection / mounting
Operating voltage
Alarm current
908499 905883 910134
1 LED yellow -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 10 820 g (1.8 lbs) 100 x 50 mm (DxH) 3.9 x 2 inch (dia. x H)
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 3G Ex nAc IIC T4 x II 3D Ex tc IIIC T110°C IP65 EC type approval certi¿cate: BVS 11 ATEX E137 Ex conformity Russia in acc. with TP TC 012/2011: 2Ex nAc IIC T4 Ex tc IIIC T110°C IP65 applied fo
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
applied fo
Chapter 6 - 19
Product Sheet | Detecon
Industrial detectors UniVario Heat detectors, Ex standard WMX5000 3GD
Order no.: 907268 The WMX5000 3GD heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They are designed to detect open ¿res with rapid rise of temperature, e.g.: – Flammable liquids and gases – Highly Àammable plastics. They are designed speci¿cally for operation in dirty industrial environments, both indoors and outdoors. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection.
Product features
Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP communication module.
• •
Optional accessories
• • •
Robust stainless steel heat sensor. Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Setting via DIP switches on the detector or SMX5000 service device. Service interface, history memory. Connection of remote indicator possible. For use in Ex zones 2 and 22, ATEX category 3 Gas/ Dust.
Technical specifications NTC sensor
Response classes
Operating voltage
A1, A2, B, C, indices S, R 0 °C to +90 °C (+32 °F to +194 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.15 mA
Alarm current consumption Alarm indication Normal operation indication Current indication Fault indication Fault indication Operating temperature IP rating (EN 60529)
P31.312.120 - 1en / 01.14
Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
908499 905883
Not included in delivery Base UniVario MX5000 Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
904701 904757 675235
Connection / mounting
Detection method
Response temperatures
Parallel indicator KMX5000 AP communication module Silicone-free design
approx. 15 mA 1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking Ex conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°C Type examination certi¿cate: BVS 07 ATEX E 156 Ex conformity Russia in acc. with TP TC 012/2011: 2Ex nAc IIC T4 Ex tc IIIC T110°C IP65 G 207090
0786-CPD-20280
Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 g (1.2 lbs) 130 x 84 mm (dia. x H) 5.1 x 3.3 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 20
Product Sheet | Detecon
Industrial detectors UniVario Heat detectors, Ex standard WMX5000 Ex
Order no.: 912117 The WMX5000 3 Ex heat detectors are ATEX and IECEx approved for category 2 gas and 1,2 dust, and are suitable for use in Ex zones 1, 20 and 21. They are designed to detect open ¿res with rapid rise of temperature, e.g.: – Flammable liquids and gases – Highly Àammable plastics. They are designed speci¿cally for operation in dirty industrial environments, both indoors and outdoors. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection.
Product features
Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex communication module.
• •
Optional accessories
• • •
Robust stainless steel heat sensor. Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Setting via DIP switches on the detector or SMX5000 service device. Service interface, history memory. Connection of remote indicator possible. For use in Ex zones 1, 20 and 21, ATEX category 2 Gas/1, 2Dust.
Technical specifications Detection method
NTC sensor
Response classes
Operating voltage
A1, A2, B, C, indices S, R 0 °C to +90 °C (+32 °F to +194 °F) 7.6 V - 30 V DC
Quiescent current
approx. 2.8 mA
Alarm current consumption
approx. 15 mA
Response temperatures
Alarm indication Normal operation indication Current indication Fault indication Fault indication Operating temperature IP rating (EN 60529)
P31.312.120 - 1en / 01.14
Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -25 °C to +80 °C (-13 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5
Safety barrier IS conventional 9 V Safety barrier IS addressable 24 V KMX5000 AP Ex communication module Weather protection MX5000 complete Silicone-free design
904991 901324 912086 910134
Not included in delivery Base UniVario MX5000 Ex Bracket MX5000 Terminating resistor 1.8 K / 0.5 W
912082 904757 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 2G Ex ia IIC T6/T4 Gb x II 1D Ex ia IIIC T95°C Da Type examination certi¿cate: BVS 12 ATEX E121 IECEx conformity: IECEx BVS 12.0074 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ia IIC T6/T4 Gb 0Ex ia IIC T6/T4 Ga Ex ia IIIC T95°C Da G 207090
0786-CPD-20280
520 g (1.2 lbs) 130 x 84 mm (dia. x H) 5.1 x 3.3 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 21
Product Sheet | Detecon
Industrial detectors UniVario Heat detectors, Ex standard WMX5000 3GD single hole
Order no.: 907269 The single hole mounted WMX5000 3GD heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They are speci¿cally suited for use in dryer and ventilation ducts for the detection of ¿res with rapid rise in temperature, e.g.: – Flammable liquids and gases – Highly Àammable plastics. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP communication module.
Product features • •
• • •
Robust stainless steel heat sensor, resistant against impact and vibration. Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector or SMX5000 service device. Service interface, history memory. Connection of remote indicator possible. For use in Ex zones 2 and 22, ATEX category 3, Gas/ Dust.
Technical specifications Detection method
NTC sensor
Response classes
Operating voltage
A1, A2, B, C, D, indices S, R 0 °C to +105 °C (+32 °F to +221 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.15 mA
Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current indication Fault indication Fault indication Operating temperature IP rating (EN 60529)
P31.312.120 - 2en / 01.14
Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
approx. 15 mA 1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67
Optional accessories Parallel indicator Weather protection MX5000 complete KMX5000 AP communication module Silicone-free design
908499 910134 905883
Not included in delivery Base UniVario MX5000 Single hole mounting ¿xture Single hole mounting tool Terminating resistor 1.8 K / 0.5 W
904701 800034 800388 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Line cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking Ex conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°C Type examination certi¿cate: BVS 07 ATEX E 156 Ex conformity Russia in acc. with TP TC 012/2011: 2Ex nAc IIC T4 Ex tc IIIC T110°C IP65 G 297090
0786-CPD-20280
Diecast aluminium 0 to 95% no condensation EN 54 Part 5 580 g (1.3 lbs) 130 x 133 mm (dia. x H) 5.1 x 5.2 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 22
Product Sheet | Detecon
Industrial detectors UniVario Heat detectors, Ex standard WMX5000 Ex single hole
Order no.: 912118 The single hole mounted WMX5000 Ex heat detectors are ATEX-approved for category 2, gas and 1, 2 dust, and are suitable for use in Ex zones 1, 20 and 21. They are speci¿cally suited for use in dryer and ventilation ducts for the detection of ¿res with rapid rise in temperature, e.g.: – Flammable liquids and gases – Highly Àammable plastics. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex communication module.
Product features • •
• • •
Robust stainless steel heat sensor, resistant against impact and vibration. Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector or SMX5000 service device. Service interface, history memory. Connection of remote indicator possible. For use in Ex zones 1, 20 and 21, ATEX category 2, Gas/ 1, 2 Dust.
Technical specifications NTC sensor
Response classes
Operating voltage
A1, A2, B, C, D, indices S, R 0 °C to +105 °C (+32 °F to +221 °F) 7.6 V - 28 V DC
Quiescent current
approx. 3.0 mA
Alarm current consumption
approx. 15 mA
Alarm indication Normal operation indication Current indication Fault indication Fault indication Operating temperature
P31.312.120 - 2en / 01.14
IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
Safety barrier IS conventional 9 V Safety barrier IS addressable 24 V KMX5000 AP Ex communication module Silicone-free design
904991 901324 912086
Not included in delivery Base UniVario MX5000 Ex Single hole mounting ¿xture Single hole mounting tool Terminating resistor 1.8 K / 0.5 W
912082 800034 800388 675235
Connection / mounting
Detection method
Response temperatures
Optional accessories
Connection cable standard detector 2-lead Additional fault line connection 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Line cross-section max. 2.5 mm2 (0.004 square inch)
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 2G Ex ia IIC T6/T4 Gb x II 1D Ex ia IIIC T95°C Da
1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -25 °C to +80 °C (-13 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5
Type examination certi¿cate: BVS 12 ATEX E121 IECEx conformity: IECEx BVS 12.0074 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ia IIC T6/T4 Gb 0Ex ia IIC T6/T4 Ga Ex ia IIIC T95°C Da G 207090
0786-CPD-20280
580 g (1.3 lbs) 130 x 133 mm (dia. x H) 5.1 x 5.2 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 23
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS, Ex WMX5000 FS 3GD 400°C (752 °F)
Order no.: 907270 The WMX5000 FS 3GD high temperature heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP communication module.
Product features • •
• • •
Robust stainless steel heat rod sensor. Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector or SMX5000 service device. Service interface, history memory. Connection of remote indicator possible. For use in Ex zones 2 and 22, Atex category 3, Gas/Dust.
Technical specifications Detection method
Operating voltage Quiescent current
approx. 0.25 mA
Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current consumption Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to
P31.312.140en / 01.14
Weight Dimensions
Parallel indicator KMX5000 AP communication module Silicone-free design
908499 905883
Not included in delivery Base UniVario MX5000 Single hole mounting ¿xture Single hole mounting tool Terminating resistor 1.8 K / 0.5 W
904701 800034 800388 675235
Connection / mounting PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +400 °C (+32 °F to +752 °F) 7.6 V - 30 V DC
Response classes
Optional accessories
approx. 15 mA 1 red LED 1 green LED, Àashing
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the sensor rod must be speci¿ed in millimetres at the time of placing the order. Alternatively, ¿xed standard rod lengths are available to choose from. The detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.
approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 to 1600 g (1.2 to 3.5 lbs) 130 x 150 to 1500 mm (dia. x H) 5.1 x 5.9 to 59.1 inch (dia. x H)
Approvals / marking Ex conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°C Type examination certi¿cate: BVS 07 ATEX E 157 Ex conformity Russia in acc. with TP TC 012/2011: 2Ex nAc IIC T4 Ex tc IIIC T110°C IP65 G 207091
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
0786-CPD-20281
Chapter 6 - 24
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS, Ex
WMX5000 FS 3GD 400 °C 200 mm (752 °F 7.9 inch)
Order no.: 907281
With ¿xed rod length of 200 mm (7.9 inch).
Otherwise like Order no.: 907270
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 680 g (1.5 lbs) 130 x 260 mm (dia. x H) 5.1 x 10.2 inch (dia. x H)
WMX5000 FS 3GD 400 °C 400 mm (752 °F 15.8 inch)
Order no.: 907282
With ¿xed rod length of 400 mm (15.8 inch).
Otherwise like Order no.: 907270
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 840 g (1.9 lbs) 130 x 460 mm (dia. x H) 5.1 x 18.1 inch (dia. x H)
WMX5000 FS 3GD 400 °C 600 mm (752 °F 23.6 inch)
Order no.: 907283
With ¿xed rod length of 600 mm (23.6 inch).
Otherwise like Order no.: 907270
Technical specifications Response temperatures Weight
P31.312.140en / 01.14
Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 1000 g (2.2 lbs) 130 x 660 mm (dia. x H) 5.1 x 26 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 25
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS, Ex WMX5000 FS Ex 400°C
Order no.: 912108 The WMX5000 FS Ex high temperature heat detectors are ATEX- and IEC approved for category 2 gas and 1, 2 dust, and are suitable for use in Ex zones 1, 20 and 21. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex communication module.
Product features • •
• • •
Robust stainless steel heat rod sensor. Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector or SMX5000 service device. Service interface, history memory. Connection of remote indicator possible. For use in Ex zones 1, 20 and 21, Atex category 3 Gas/ 1, 2 Dust.
Technical specifications Detection method
Operating voltage
PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +400 °C (+32 °F to +752 °F) 7.6 V - 30 V DC
Quiescent current
approx. 2.8 mA
Alarm current consumption
approx. 15 mA
Response classes Response temperatures
Alarm indication Normal operation indication Current consumption Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to P31.312.140en / 01.14
Weight Dimensions
1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -25 °C to +80 °C (-13 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 to 1600 g (1.2 to 3.5 lbs) 130 x 150 to 1500 mm (dia. x H) 5.1 x 5.9 to 59.1 inch (dia. x H)
Optional accessories Safety barrier IS conventional 9 V Safety barrier IS addressable 24 V KMX5000 AP Ex communication module Weather protection MX5000 complete Silicone-free design
904991 901324 912086 910134
Not included in delivery Base UniVario MX5000 Ex Single hole mounting ¿xture Single hole mounting tool Terminating resistor 1.8 K / 0.5 W
912082 800034 800388 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the sensor rod must be speci¿ed in millimetres at the time of placing the order. Alternatively, ¿xed standard rod lengths are available to choose from.
Approvals / marking Ex conformity in acc. with 94/9/EC:
x II 2G Ex ia IIC T6/T4 Gb x II 1D Ex ia IIIC T95°C Da Type examination certi¿cate: BVS 12 ATEX E120 IECEx conformity: IECEx BVS 12.0073 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ia IIC T6/T4 Gb 0Ex ia IIC T6/T4 Ga Ex ia IIIC T95°C Da G 207091
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
0786-CPD-20281
Chapter 6 - 26
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS, Ex
WMX5000 FS Ex 400 °C 200 mm (752 °F 7.9 inch)
Order no.: 912110
With ¿xed rod length of 200 mm (7.9 inch).
Otherwise like Order no.: 912108
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 680 g (1.5 lbs) 130 x 260 mm (dia. x H) 5.1 x 10.2 inch (dia. x H)
WMX5000 FS Ex 400 °C 400 mm (752 °F 15.8 inch)
Order no.: 912111
With ¿xed rod length of 400 mm (15.8 inch).
Otherwise like Order no.: 912108
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 840 g (1.9 lbs) 130 x 460 mm (dia. x H) 5.1 x 18.1 inch (dia. x H)
WMX5000 FS Ex 400 °C 600 mm (752 °F 23.6 inch)
Order no.: 912112
With ¿xed rod length of 600 mm (23.6 inch).
Otherwise like Order no.: 912108
Technical specifications Response temperatures Weight
P31.312.140en / 01.14
Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 1000 g (2.2 lbs) 130 x 660 mm (dia. x H) 5.1 x 26 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 27
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS Flex, Ex WMX5000 FS Flex 3GD 400°C (752 °F)
Order no.: 907284 The WMX5000 FS 3GD high temperature heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via the KMX5000 AP communications module.
Product features
Optional accessories
•
Robust Àexible stainless steel heat sensor.
•
Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector or SMX5000 service device.
Parallel indicator KMX5000 AP communication module Silicone-free design
•
Service interface, history memory.
•
Connection of remote indicator possible.
•
For use in Ex zones 2 and 22, Atex category 3, Gas/Dust.
908499 905883
Not included in delivery Base UniVario MX5000 Holder WMX FS, from 250 °C (482 °F) to 600 °C (1112 °F) Terminating resistor 1.8 K / 0.5 W
904701 894679 675235
Connection / mounting Technical specifications Detection method
Operating voltage
PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +400 °C (+32 °F to +752 °F) 7.6 V - 30 V DC
Quiescent current
approx. 0.25 mA
Response classes Response temperatures
Alarm current consumption Alarm indication Normal operation indication Current consumption Fault indication Fault indication Operating temperature IP rating (EN 60529)
P31.312.160en / 02.14
Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
approx. 15 mA 1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% no condensation EN 54 Part 5 520 to 1600 g (1.2 to7.5 lbs) 130 x 2000 to 9000 mm (dia. x H) 5.1 x 78.7 x 354.3 inch (dia. x H)
Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the Àexible sensor must be speci¿ed in metres at the time of placing the order. The sensor rod holder is designed for operation temperatures of up to 250 °C (482 °F). For higher operation temperatures, the WMX FS holder from 250 °C (482 °F) to 600 °C (1112 °F) Order no. 894679 is to be used. The detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.
Approvals / marking Ex conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°C Type examination certi¿cate: BVS 07 ATEX E 157 Ex conformity Russia in acc. with TP TC 012/2011: 2Ex nAc IIC T4 Ex tc IIIC T110°C IP65 G 207091
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
0786-CPD-20281
Chapter 6 - 28
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS Flex, Ex
WMX5000 FS Flex 3GD 400 °C 2 m (752 °F 79 inch)
Order no.: 907285
Version with Àexible hose of 2 m length (79 inch).
Otherwise like Order no.: 907284
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 680 g (1.5 lbs) 130 x up to 2000 mm (dia. x H) 5.1 x up to 78.73 inch (dia. x H)
WMX5000 FS Flex 3GD 400 °C 6 m (752 °F 236 inch)
Order no.: 907286
Version with Àexible hose of 6 m length (236 inch).
Otherwise like Order no.: 907284
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 840 g (1.9 lbs) 130 x up to 6000 mm (dia. x H) 5.1 x up to 236.2 inch (dia. x H)
WMX5000 FS Flex 3GD 400 °C 9 m (752 °F 354 inch)
Order no.: 907287
Version with Àexible hose of 9 m length (354 inch).
Otherwise like Order no.: 907284
Technical specifications Response temperatures Weight
P31.312.160en / 02.14
Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 1000 g (2.2 lbs) 130 x up to 9000 mm (dia. x H) 5.1 x up to 354.3 inch (dia. x H)
WMX5000 FS Flex 3GD 400 °C (752 °F) CN
Order no.: 909387 Approvals / marking
Version China Otherwise like Order no.: 907284
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 29
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS Flex, Ex WMX5000 FS Flex Ex 400°C
Order no.: 912113 The WMX5000 FS Ex high temperature heat detectors are ATEX and IEC approved for category 2 gas and 1, 2 dust, and are suitable for use in Ex zones 1, 20 and 21. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early ¿re detection. Designed for operation as a conventional detector. Expansion to a detector with Loop AP protocol via the KMX5000 AP Ex communications module.
Optional accessories
Product features Robust Àexible stainless steel heat sensor.
•
Freely con¿gurable response temperatures and classes in accordance with EN54-5, along with rate-of-rise and static responses. Con¿guration via DIP switches on the detector or SMX5000 service device.
•
Service interface, history memory.
Not included in delivery
•
For use in Ex zones 1, 20 and 21, Atex category 2, Gas/1,2 Dust.
Base UniVario MX5000 Ex Holder WMX FS, from 250 °C (482 °F) to 600 °C (1112 °F) Terminating resistor 1.8 K / 0.5 W
Technical specifications Detection method
Operating voltage
PT1000 sensor A1, A2, B, C, D, E, F, G, indices S, R 0 °C to +400 °C (+32 °F to +752 °F) 7.6 V - 28 V DC
Quiescent current
approx. 2.8 mA
Alarm current consumption
approx. 15 mA
Response classes Response temperatures
Alarm indication Normal operation indication Current consumption Fault indication Fault indication Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Speci¿cation according to Weight P31.312.160en / 02.14
Safety barrier IS conventional 9 V Safety barrier IS addressable 24 V KMX5000 AP Ex communication module Weather protection MX5000 complete Silicone-free design
•
Dimensions
1 red LED 1 green LED, Àashing approx. 15 mA 1 yellow LED (2nd line) -25 °C to +80 °C (-13 °F to +176 °F) IP 67 Diecast aluminium 0 to 95% No condensation EN 54 Part 5 520 to 1600 g (1.2 to7.5 lbs) 130 x 2000 to 9000 mm (dia. x H) 5.1 x 78.7 x 354.3 inch (dia. x H)
904991 901324 912086 910134
912082 894679 675235
Connection / mounting Connection cable standard detector 2-lead Additional fault line connection 2-lead External indication 2-lead Recommended cable JY (St) Y 2x2x0.8 mm (0.03 inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch)
Note The desired length of the Àexible sensor must be speci¿ed in metres at the time of placing the order. The sensor rod holder is designed for operation temperatures of up to 250 °C (482 °F). For higher operation temperatures, the WMX FS holder from 250 °C (482 °F) to 600 °C (1112 °F) Order no. 894679 is to be used.
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 2G Ex ia IIC T6/T4 Gb x II 1D Ex ia IIIC T95°C Da Type examination certi¿cate: BVS 12 ATEX E120 IECEx conformity: IECEx BVS 12.0073 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ia IIC T6/T4 Gb 0Ex ia IIC T6/T4 Ga Ex ia IIIC T95°C Da G 207091
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
0786-CPD-20281
Chapter 6 - 30
Product Sheet | Detecon
Industrial detectors UniVario High temperature heat detector FS Flex, Ex
WMX5000 FS Flex 3GD 400 °C 2 m (752 °F 79 inch)
Order no.: 912114
Version with Àexible hose of 2 m length (79 inch).
Otherwise like Order no.: 912113
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 680 g (1.5 lbs) 130 x up to 2000 mm (dia. x H) 5.1 x up to 78.73 inch (dia. x H)
WMX5000 FS Flex 3GD 400 °C 6 m (752 °F 236 inch)
Order no.: 912115
Version with Àexible hose of 6 m length (236 inch).
Otherwise like Order no.: 912113
Technical specifications Response temperatures Weight Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 840 g (1.9 lbs) 130 x up to 6000 mm (dia. x H) 5.1 x up to 236.2 inch (dia. x H)
WMX5000 FS Flex 400 °C 9 m (752 °F 354 inch)
Order no.: 912116
Version with Àexible hose of 9 m length (354 inch).
Otherwise like Order no.: 912113
Technical specifications Response temperatures Weight
P31.312.160en / 02.14
Dimensions
0 °C to +400 °C (+32 °F to +752 °F) 1000 g (2.2 lbs) 130 x up to 9000 mm (dia. x H) 5.1 x up to 354.3 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 31
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories KMX5000 AP communication module
Order no.: 905883 Communication module for the operation of UniVario detectors on ¿re alarm panels with Loop AP protocol. By simply plugging the module into the detector, a conventional detector is turned into an analogue addressable detector. The detector address is set via a DIP switch. Power supply and communications are connected via the ring bus; no additional power supply is required. The KMX5000 AP communication module is designed for integration into UniVario series detectors and must not be used in hazard areas.
Product features
Included in delivery
•
Communication module for constant signalling of operating condition, alarms and faults via Loop AP protocol.
1 KMX5000 AP communication module Pan-head screw and Spacer
•
Ring bus connection, no additional power supply.
Connection / mounting
•
Integration in UniVario series detectors.
Plug-in module in UniVario series detectors
Technical specifications Connection
10 spring contacts (module/detector)
Operating voltage
17 V - 28 V DC
Operating current
approx. 0,3 mA
Communication protocol Addressing Operating temperature Relative humidity (IEC721-3-3)
Loop AP 8 position DIP switch -20 °C to +80 °C (-4 °F to +176 °F) 5 to 85% no condensation
Speci¿cation according to Weight Dimensions
EN 54 Part 18 15 g (0.03 lbs) 54 x 28 x 19.5 mm (LxWxH) 2.1 x 1.1 x 0.8 inch (LxWxH)
Approvals / marking 0786-CPD-20315
P31.312.810 - 1en / 01.14
G 207032
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 32
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories KMX5000 AP Ex communication module
Order no.: 912086 Communication module for the operation of UniVario detectors on ¿re alarm panels with Loop AP protocol. By simply plugging the module into the detector, a conventional detector is turned into an analogue addressable detector. The detector address is set via a DIP switch. Power supply and communications are connected via the ring bus; no additional power supply is required. The KMX5000 AP Ex communication module is designed for integration into UniVario series detectors and may be used in hazard areas.
Product features
Included in delivery
•
Communication module for constant signalling of operating condition, alarms and faults via Loop AP protocol.
1 KMX5000 AP Ex communication module Pan-head screw and Spacer
•
Ring bus connection, no additional power supply.
Connection / mounting
•
Integration in UniVario Ex series detectors.
Plug-in module in UniVario Ex series detectors
Technical specifications Connection
10 spring contacts (module/detector)
Operating voltage
14 V - 22 V DC
Operating current
approx. 0,3 mA
Communication protocol
Loop AP
Addressing
8 position DIP switch -20 °C to +80 °C (-4 °F to +176 °F) 5 to 85% no condensation
Operating temperature Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
EN 54 Part 18 15 g (0.03 lbs) 54 x 28 x 19.5 mm (LxWxH) 2.1 x 1.1 x 0.8 inch (LxWxH)
Approvals / marking Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ib IIC T5/T4 Gb applied for
P31.312.810 - 1en / 01.14
applied for
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 33
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories Base MX5000
Order no.: 904701 Retaining base for all UniVario industrial ¿re detectors. Contains cable entries, EMC and environmental seals, connecting terminals and space for the optional relay module KMX5000 RK. Enables replacement of a detector without any terminal work.
Not included in delivery End of line resistor 1.8 K / 0.5 W
675235
Spare parts Seal 127 x 2.9 / 1.6 mm Gland M 16 x 1.5 Ms Sealing cord 8 mm Vitron 0.036 m
Technical specifications Material
Aluminium
Relative humidity Conductor cross-section
max. 100 %
904752 901861 800605
Approvals / marking
max. 2.5 mm2 (0.004 square inch)
Colour
red -40 °C to +100 °C (-40 °F to +212 °F) 310 g (0.7 lbs)
Ambient temperature Weight
Base MX5000 SF
Order no.: 914235
Silicon free base.
Otherwise like Order no. 904701
Base MX5000 3M16
Order no.: 907011 Retaining base for all UniVario industrial ¿re detectors. Contains cable entries, EMC and environmental seals, connecting terminals and space for the optional relay module KMX5000 RK. The third cable gland allows the interface connection with detector remote indicators or similar devices.
Not included in delivery End of line resistor 1.8 K / 0.5 W
675235
Spare parts Seal 127 x 2.9 / 1.6 mm Gland M 16 x 1.5 Ms Sealing cord 8 mm Vitron 0.036 m
Technical specifications P31.312.810 - 1en / 01.14
Material
Aluminium
Relative humidity Conductor cross-section Colour Ambient temperature Weight
max. 100 % max. 2.5 mm (0.004 square inch) 2
Approvals / marking
red -40 °C to +100 °C (-40 °F to +212 °F) 350 g (0.8 lbs)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 34
904752 901861 800605
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories Base MX5000 LCD
Order no.: 906127 Base for displaying status and signal messages from industrial ¿re alarms of the UniVario series. The LCD display gives information about sensor temperature, alarms or other operating states, depending on the detector type. Includes cable entries, EMC and environmental seals and connecting terminals. Enables replacement of a detector without any terminal work. The LCD base must not be used in hazard areas.
Not included in delivery End of line resistor 1.8 K / 0.5 W
Spare parts
Technical specifications Operating voltage
By means of the detector
Operating current
0.3 mA
Material
Aluminium
Relative humidity Conductor cross-section
675235
max. 100 %
Seal 127 x 2.9 / 1.6 mm Gland M 16 x 1.5 Ms Sealing cord 8 mm Vitron 0.036 m
904752 901861 800605
Approvals / marking
max. 2.5 mm2 (0.004 square inch)
Colour
red -20 °C to +70 °C (-4 °F to +158 °F) 350 g (0.8 lbs)
Ambient temperature Weight
Base MX5000-I
Order no.: 912493 Detector base for installation of the UniVario industrial ¿re detectors in the LoopAP ringbus. Contains cable inlets, EMC and environmental sealing as well as terminals. Not suitable for use in explosion-prone areas. The installed dual isolator increases the operational safety of the LoopAP ringbus in the event of a short-circuit. The third cable screw connection is available for connecting detector mimic panels or similar devices.
Spare parts Seal 127 x 2.9 / 1.6 mm Gland M 16 x 1.5 Ms Ex Sealing cord 8 mm Vitron 0.036 m
Technical specifications Material
Aluminium
P31.312.810 - 1en / 01.14
Relative humidity Conductor cross-section Colour Ambient temperature Weight
max. 100 % max. 2.5 mm (0.004 square inch) 2
red -20 °C to +80 °C (-4 °F to +176 °F) 530 g (1.2 lbs)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 35
904752 904652 800605
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories Base MX5000 Ex
Order no.: 912082 Detector base for installation of the UniVario industrial ¿re detectors of the Ex series. Contains cable inlets, EMC and environmental sealing as well as terminals. In this way, detectors can be replaced without requiring connecting work.
Not included in delivery End of line resistor 1.8 K / 0.5 W
675235
Spare parts Seal 127 x 2.9 / 1.6 mm Gland M 16 x 1.5 Ms Ex Sealing cord 8 mm Vitron 0.036 m
Technical specifications Material
904752 904652 800605
Aluminium
Relative humidity Conductor cross-section
max. 100 % max. 2.5 mm2 (0.004 square inch)
Colour Ambient temperature Weight
red -40 °C to +100 °C (-40 °F to +212 °F) 530 g (1.2 lbs)
Bracket MX5000
Approvals / marking Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ib IIC T5/T4 Gb
Order no.: 904757 Mounting bracket for UniVario MX5000 base.
Included in delivery 1 bracket UniVario MX5000 2 x screws M8, hex socket size 5 mm (0.2 inch).
Not included in delivery Mounting screws for wall/ceiling-mounted installation.
Technical specifications Material Bracket retention
P31.312.810 - 1en / 01.14
Weight
Spare parts Stainless steel, 2 mm (0.08 inch) thick Plastic (POM), black
Screw M 8
904355
110 g (0.2 lbs)
Bracket MX5000 SF
Order no.: 914234
Silicon free bracket.
Otherwise like Order no. 904757
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 36
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories Isolator ISX 284 3GD
Order no.: 915864 Isolator XP and DIS for the separation of individual line sections in the event of short circuits in ring bus operation with approval for ATEX category 3 gas and dust. Are suitable for use in Ex zones 2 and 22.
Approvals / marking
Technical specifications Material
Aluminium
Fault indication inside IP rating (EN60529) Colour Ambient temperature Weight
x II 2G Ex d IIB T6 Gb x II 2D Ex tb IIIC T80°C Db
Yellow LED IP 66
EC type approval certi¿cate:
grey -20 °C to +60 °C (-4 °F to +140 °F) 1.2 kg (2.6 lbs) 90 mm (dia.) 3.5 inch (dia.)
P31.312.810 - 1en / 01.14
Dimensions
Ex conformity in acc. with 94/9/EG:
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 37
BVS 11 ATEX E114
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories Relay module KMX5000 RK
Order no.: 906361 Communication module for the operation of UniVario detectors, independent of any ¿re detection system. Dry contacts for alarm and fault signalling allow the detectors to be used as stand-alone units, in any ¿re and hazard detection system or in building management and control systems. The KMX5000 RK communication module is designed to be integrated into the UniVario detector base MX5000 and must not be used in hazard areas.
Product features
Included in delivery
• •
Relay module KMX5000 RK Jumper Installation material
Dry changeover contacts for alarm and fault signalling. Integration into MX5000 detector base.
Technical specifications Connection Operating voltage Quiescent current Current consumption with alarm relay active Current consumption with alarm relay and fault relay active Voltage load, contacts Current load, contacts Fault indication Operating temperature Relative humidity (IEC721-3-3)
6-conductor ribbon cable 24 V (14 V - 29 V) DC
Dimensions
Conductor cross-section
approx. 7 mA
min. 0.5 mm2 (0.0008 square inch) Max. 2.5 mm2 (0.004 square inch)
approx. 20 mA approx. 30 mA Max. 60 V DC, 25 V AC max. 1 A 1 yellow LED (2nd line) -20 °C to +80 °C (-4 °F to +176 °F) 5 to 85% no condensation
Speci¿cation according to Weight
Connection / mounting
EN 54 Part 18 50 g (0.1 lbs) 64 x 24 x 57 mm (LxWxH) 2.5 x 0.9 x 2.2 inch (LxWxH)
Approvals / marking 0786-CPD-20314
P31.312.810 - 1en / 01.14
G 208058
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 38
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories Console MX5000 Flame detector
Order no.: 904758 Console for the installation of UniVario Àame detectors outside of monitored areas, e.g. air ducts, machine tools, containers or silos. Easy access to the detector. Bayonet socket for reliable, vibration-proof hold. Antistatic material for use in hazard areas up to zones 1 and 21.
Included in delivery Technical specifications Material Dimensions Colour Ambient temperature Weight
PA6 99/0701 EC 138 x 15 mm (WxH) 6.6 x 0.6 inch (WxH) Black -20 °C to +100 °C (-4 °F to +212 °F) 145 g (0.3 lbs)
Console MX5000 Heat detector
Mount with Àat sealing and springs Screw M5 Self-tapping screw Blind rivets O-ring Installation drawing
906148 904341 765233 885078 904759 906970
Order no.: 906969 Console for the installation of UniVario heat detectors on e.g. air ducts, dryers or machine tools. Easy access to the detector. Bayonet socket for reliable, vibration-proof hold. Antistatic material for use in hazard areas up to zones 1 and 21.
Included in delivery
Technical specifications Material Dimensions Colour
P31.312.810 - 1en / 01.14
Ambient temperature Weight
PA6 99/07001 EC 138 x 16.2 mm (WxH) 5.4 x 0.6 inch (WxH) Black -20 °C to +100 °C (-4 °F to +212 °F) 145 g (0.3 lbs)
Console with Àat sealing and springs Screw M5 Self-tapping screw Blind rivets O-ring Installation drawing
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 39
906148 904341 765233 885078 904759 906970
Product Sheet | Detecon
Industrial detectors UniVario Detector accessories Weather protection MX5000 complete
Order no.: 910134 Additional equipment – weather protection for Àame detectors of the Uni Vario series for use in case of increased solar radiation or exposure to harsh weather conditions.
Connection / mounting Fasten the weather protection to the detector.
Technical specifications
Colour
Stainless steel, 0.5 mm (0.02 inch) thick 140 x 110 x 220 mm (BxHxL) 5.5 x 4.3 x 8.7 inch (BxHxL) internally black
Weight
300 g (0.67 lbs)
Material
P31.312.810 - 1en / 01.14
Dimensions
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 40
Product Sheet | Detecon
Industrial detectors UniVario Test equipment Service device SMX5000
Order no.: 906136 The service device is for the simpli¿ed con¿guration, diagnostics and function testing of the UniVario detectors, and for indicating events from the history memory. The SMX5000 can be used on UniVario detectors with software version V01 Exx or higher. An RS-232 interface can be used to transmit data from the history memory to the UniVario View software.
Product features
Included in delivery
• • •
1 service device SMX5000 1 connection cable, 30-pin 2 1.5 V batteries, type AA (LR6)
Display with 3 rows of 12 characters each. Simple operation with clear menu structure. Operation and fault indication.
Accessories
Technical specifications LCD display
Operating current (depends on the detector type)
Operation time (depends on the detector and battery types) Batteries required IP rating
3 rows of 12 characters each approx. 80 mA at 3 V (with background lighting) approx. 25 mA at 3 V (without background lighting) approx. 5 mA at 3 V (in detector mode) approx. 25 hrs (with background lighting) approx. 80 hrs (without background lighting) approx. 400 hrs (in detector mode) 2 x 1.5 V Mignon, type AA (LR6)
Battery 1.5 V Mignon, type AA (LR6) Connection cable, 30-pin
Not included in delivery UniVario View software
IP 20
Enclosure material Operating temperature Relative humidity (IEC721-3-3) Speci¿cation according to Weight Dimensions
ABS plastic, RAL 7038 grey 0 °C to +50 °C (-32 °F to +122 °F) 5 to 85% no condensation EN 55022/CISPR22 CL. B, EN 55024, EN 61000-6-3, EN 61000-4-2, EN 61000-4-3, 26 g (0.1 lbs) 165 x 92 x 30 mm (LxWxH) 6.5 x 3.6 x 1.2 inch (LxWxH)
P31.312.911en / 02.13
Approvals / marking
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 41
906751 906198
Product Sheet | Detecon
Industrial detectors IR flame detector FMX3511
Order no.: 801618 Double infrared Àame detector FMX3511 for the detection of open Àames. Optic test monitors the functionality of the detector. Designed for use in raugh industrial environments. Equipped for operation as a conventional detector.
Product features
Not included in delivery
•
Highly reliable against false alarms, e.g. from hot surfaces.
•
A microcontroller monitors the functionality. Faults can be indicated on the detector or on a separate line.
•
Connection of remote indicator possible.
Mounting device bracket with insulation Mounting device console 125x80Ø60 End of line-resistor 1.8 K / 0.5 W Sun screen Parallel indicator LMX5000 Plug for the pollution test
•
Single optic test.
801284 801280 675235 801277 908499 801079
Connection / mounting Connection cable standard detector 2-lead Recommended cable LiYCY 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, Brass nickel-plated, EMV
Technical specifications Detection method Sensitivity class Viewing angle
3
7.6 V - 15 V DC
Quiescent current
approx. 3 mA
Alarm indication
Fault indication
1 LED yellow
Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight Dimensions
0786-CPD-20312
1 LED red approx. 7 mA
Electrostatic shielding
G 296016
approx. 18 mA
Fault indication current
Number of detectors per line
Approvals / marking
60 °
Operating voltage
Alarm current
P31.312.330 - 3en / 02.13
2 IR Sensoren
max. 4 Required -25 °C to +80 °C (-13 °F to +176 °F) IP 65 Diecast aluminium, RAL5009-blue max. 100% at + 35 °C (+95 °F) 600 g (1.3 lbs) 127 x 125 x 70 mm (BxHxT) 5 x 4.9 x 2.8 inch (BxHxT)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 42
Product Sheet | Detecon
Industrial detectors IR flame detector
FMX3511 SF
Order no.: 801619
Silicone-free Àame detector
FMX3511 0.2 sec
Order no.: 902532
Flame detectors with fast response within range of milsecounds are used for object monitoring (e.g. tooling machine).
Technical specifications Criterion of detection
FMX3511 0.2 sec SF
Change of intensity
Order no.: 902767
P31.312.330 - 3en / 02.13
Silicone-free Àame detector
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 43
Product Sheet | Detecon
Industrial detectors IR flame detector FMX3511 BG
Order no.: 891319 Double infrared Àame detector FMX3511 for the detection of open Àames. Optic test monitors the functionality of the detector. Designed for use in raugh industrial environments. Equipped for operation as a conventional detector.
Product features
Not included in delivery
•
Highly reliable against false alarms, e.g. from hot surfaces.
•
A microcontroller monitors the functionality. Faults can be indicated on the detector or on a separate line.
End of line-resistor 1.8 K / 0.5 W Sun sreen Parallel indicator LMX5000 Plug for the pollution test
•
Connection of remote indicator possible.
•
Single optic test.
Connection /mounting Connection cable standard detector 2-lead Recommended cable LiYCY 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, brass nickel-plated, EMV
Technical specifications Detection method Sensitivity class Viewing angle Operating voltage Quiescent current Alarm current Alarm indication
3
Enclosure material Relative humidity (IEC721-3-3) Weight Dimensions
0786-CPD-20312
approx. 3 mA approx. 18 mA 1 LED red
1 LED yellow
IP rating (EN 60529)
G 296016
7.6 V - 15 V DC
Fault indication
Operating temperature
Approvals / marking
60 °
approx. 7 mA
Electrostatic shielding
P31.312.330 - 4en / 02.13
2 IR Sensoren
Fault indication current
Number of detectors per line
675235 801277 908499 801079
max. 4 Required -25 °C to +80 °C (-13 °F to +176 °F) IP 65 Diecast aluminium, RAL5009-blue max. 100% at + 35 °C (+95 °F) 750 g (1.7 lbs) 127 x 155 x 92 mm (BxHxT) 5 x 6.1 x 3.6 inch (BxHxT)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 44
Product Sheet | Detecon
Industrial detectors IR flame detector
FMX3511 BG SF
Order no.: 800029
Silicone-free Àame detector
FMX3511 BG 0.2 sec
Order no.: 902533
Flame detectors with fast response within range of miliseconds are used for object monitoring (e.g. tooling machine).
Technical specifications Criterion of detection
FMX3511 BG 0.2 sec SF
Change of intensity
Order no.: 902768
P31.312.330 - 4en / 02.13
Silicone-free Àame detector
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 45
Product Sheet | Detecon
Industrial detectors IR flame detector FMX3511 Console
Order no.: 801609 Double infrared Àame detector FMX3511 for the detection of open Àames. Optic test monitors the functionality of the detector. Version Brachet mounting. Designed for use in rough industrial environments. Equipped for operation as a conventional detector.
Product features
Not included in delivery
•
Highly reliable against false alarms, e.g. from hot surfaces.
•
A microcontroller monitors the functionality. Faults can be indicated on the detector or on a separate line.
•
Connection of remote indicator possible.
Mounting device bracket with insulation End of line-resistor 1.8 K / 0.5 W Sun sreen Parallel indicator LMX5000 Plug for the pollution test
•
Single optic test.
Connection / mounting Connection cable standard detector 2-lead Recommended cable LiYCY 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, brass nickel-plated, EMV
Technical specifications Detection method Sensitivity class Viewing angle
3 60 ° 7.6 V - 15 V DC
Quiescent current
approx. 3 mA
Alarm indication
Fault indication
1 LED yellow
Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight Dimensions
G 296016
0786-CPD-20312
1 LED red approx. 7 mA
Electrostatic shielding
Approvals / marking
approx. 18 mA
Fault indication current
Number of detectors per line
P31.312.330 - 5en / 02.13
2 IR Sensoren
Operating voltage
Alarm current
801284 675235 801277 908499 801079
max. 4 Required -25 °C to +80 °C (-13 °F to +176 °F) IP 65 Diecast aluminium, RAL5009-blue max. 100% at + 35 °C (+95 °F) 950 g (2.1 lbs) 127 x 150 x 75 mm (BxHxT) 5 x 5.9 x 3 inch (BxHxT)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 46
Product Sheet | Detecon
Industrial detectors IR flame detector
FMX3511 Console 0.2 sec
Order no.: 902534
Flame detectors with fast response within range of miliseconds are used for object monitoring (e.g. tooling machine).
Technical specifications Change of intensity
P31.312.330 - 5en / 02.13
Criterion of detection
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 47
Product Sheet | Detecon
Industrial detectors IR flame detector FMX3511 Console LSP
Order no.: 801610 Double infrared Àame detector FMX3511 for the detection of open Àames. Optic test monitors the functionality of the detector. Version Brachet mounting and air Àushing function. Designed for use in rough industrial environments. Equipped for operation as a conventional detector.
Product features
Not included in delivery
•
Highly reliable against false alarms, e.g. from hot surfaces.
•
A microcontroller monitors the functionality. Faults can be indicated on the detector or on a separate line.
•
Connection of remote indicator possible.
Mounting device bracket with insulation End of line-resistor 1.8 K / 0.5 W Sun sreen Parallel indicator LMX5000 Plug for the pollution test Compressed air supply
•
Single optic test.
801284 675235 801277 908499 801079
Connection / mounting Connection cable standard detector 2-lead Recommended cable LiYCY 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, brass nickel-plated, EMV
Technical specifications Detection method Sensitivity class Viewing angle
3
7.6 V - 15 V DC
Quiescent current
approx. 3 mA
Alarm indication
Fault indication
1 LED yellow
Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight Dimensions Compressed air supply on site
0786-CPD-20312
1 LED red approx. 7 mA
Electrostatic shielding
G 296016
approx. 18 mA
Fault indication current
Number of detectors per line
Approvals / marking
60 °
Operating voltage
Alarm current
P31.312.330 - 6en / 02.13
2 IR Sensoren
max. 4 Required -25 °C to +80 °C (-13 °F to +176 °F) IP 65 Diecast aluminium, RAL5009-blue max. 100% at +35 °C (+95 °F) 970 g (2.1 lbs) 141 x 150 x 75 mm (BxHxT) 5.6 x 5.9 x 3 inch (BxHxT) Pressure range 0.8 - 1.5 bar
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 48
Product Sheet | Detecon
Industrial detectors IR flame detector
FMX3511 Console LSP 0.2 sec
Order no.: 902535
Flame detectors with fast response within range of miliseconds are used for object monitoring (e.g. tooling machine).
Technical specifications Change of intensity
P31.312.330 - 6en / 02.13
Criterion of detection
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 49
Product Sheet | Detecon
Industrial detectors IR flame detector Ex FMX3501 Ex
Order no.: 903133 Infrared Àame detector FMX3501 Ex for the detection of open Àames. Optic test monitors the functionality of the detector. Designed for use in rough industrial environments. Equipped for operation as a conventional detector. Infrared Àame detector FMX3501 Ex are ATEX-approved for category 2 gas and 3 dust and are suitable for use in Ex zones 1 and 22. Intrinsically safe Àame detectors must be connected by correspondingly marked cables to explosion hazard barriers.
Product features
Not included in delivery
•
Highly reliable against false alarms, e.g. from hot surfaces.
•
A microcontroller monitors the functionality. Faults can be indicated on the detector or on a separate line.
•
Connection of remote indicator possible.
Mounting device bracket with insulation Safety barrier IS conventional 9 V End of line-resistor 1.8 K / 0.5 W Sun screen Plug for the pollution test
•
Single optic test.
Connection / mounting Connection cable standard detector 2-lead recommended cable LiYCY 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, Brass nickel-plated, EMV
Technical specifications Detection method Sensitivity class Viewing angle
3 60 ° 7.6 V - 15 V DC
Quiescent current
approx. 3 mA
Alarm indication
approx. 18 mA 1 LED red
Fault indication current
approx. 7 mA
Fault indication
1 LED yellow
Number of detectors per line Electrostatic shielding Operating temperatur IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight P31.312.340 - 2en / 01.14
2 IR Sensoren
Operating voltage
Alarm current
Dimensions
801284 904991 675235 801277 801079
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 2G 3G Ex ib IIC T6/T4 Type examination certi¿cate: DMT 02 ATEX E224 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ib IIC T6/T4 Gb G 296016
0786-CPD-20312
max. 4 Required -25 °C to +80 °C (-4 °F to +176 °F) IP 65 Diecast aluminium, RAL5009-blue max. 100% at +35 °C (+95 °F) 600 g (1.3 lbs) 127 x 125 x 70 mm (BxHxT) 3.9 x 2 inch (dia. x H)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 50
Product Sheet | Detecon
Industrial detectors IR flame detector Ex
FMX3501 Ex SF
Order no.: 903134
Silicone-free Àame detector
FMX3501 Ex 0.2 sec
Order no.: 903135
Flame detectors with fast response within range of miliseconds are used for object monitoring (e.g. tooling machine).
Technical specifications Criterion of detection
Change of intensity
FMX3501 Ex 0.2 sec SF
Order no.: 903136
Silicone-free Àame detector
FMX3501 Ex T
Order no.: 903137
Flame detector with non-latching alarm
FMX3501 Ex T SF
Order no.: 903138
Silicone-free Àame detector
FMX3501 Ex T 0.2 sec
Order no.: 903139
Flame detectors with fast response within range of miliseconds are used for object monitoring (e.g. tooling machine).
P31.312.340 - 2en / 01.14
Technical specifications Criterion of detection
FMX3501 Ex T 0.2 sec SF
change of intensity
Order no.: 903140
Silicone-free Àame detector
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 51
Product Sheet | Detecon
Industrial detectors IR flame detector Ex FMX3501 Ex BG
Order no.: 800000 Infrared Àame detector FMX3501 Ex for the detection of open Àames. Optic test monitors the functionality of the detector. Designed for use in rough industrial environments. Equipped for operation as a conventional detector. Infrared Àame detector FMX3501 Ex are ATEX-approved for category 2 gas and 3 dust and are suitable for use in Ex zones 1 and 22. Intrinsically safe Àame detectors must be connected by correspondingly marked cables to explosion hazard barriers.
Product features
Not included in delivery
•
Highly reliable against false alarms, e.g. from hot surfaces.
•
A microcontroller monitors the functionality. Faults can be indicated on the detector or on a separate line.
Safety barrier IS conventional 9 V End of line-resistor 1.8 K / 0.5 W Sun screen Plug for the pollution test
•
Connection of remote indicator possible.
•
Single optic test.
Connection / mounting Connection cable standard detector 2-lead Recommended cable LiYCY 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, brass nickel-plated, EMV
Technical specifications Detection method Sensitivity class Viewing angle
3 60 ° 7.6 V - 15 V DC
Quiescent current
approx. 3 mA
Alarm inducation
1 LED red approx. 7 mA
Fault indication
1 LED yellow
Electrostatic shielding Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight Dimensions
Approvals / marking Ex Conformity in acc. with 94/9/EG:
x II 2G 3G Ex ib IIC T6/T4 Type examination certi¿cate: DMT 02 ATEX E224 Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ib IIC T6/T4 Gb
approx. 18 mA
Fault indication current
Number of detektors per line
P31.312.340 - 3en / 02.14
2 IR Sensoren
Operating voltage
Alarm current
904991 675235 801277 801079
G 296016
0786-CPD-20312
max. 4 Required -25 °C to +80 °C (-4 °F to +176 °F) IP 65 Diecast aluminium, RAL5009-blue max. 100% at +35 °C (+95 °F) 750 g (1.6 lbs) 127 x 155 x 92 mm (BxHxT) 5 x 6.1 x 3.6 inch (BxHxT))
FMX3501 Ex BG CN
Order no.: 907436
Version China
Approvals / marking
Otherwise like Order no 800000
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 52
Product Sheet | Detecon
Industrial detectors IR flame detector Ex
FMX3501 Ex SF BG
Order no.: 902769
Silicone-free Àame detector
Otherwise like Order no 800000
FMX3501 Ex 0.2 sec BG
Order no.: 902721
Flame detectors with fast response within range of miliseconds are used for object monitoring (e.g. tooling machine).
Otherwise like Order no 800000
Technical specifications Criterion of detection
Change of intensity
FMX3501 Ex 0.2 sec SF BG
Order no.: 902770
Silicone-free Àame detector
Otherwise like Order no 800000
FMX3501 Ex T BG
Order no.: 903141
Flame detector with non-latching alarm
Otherwise like Order no 800000
FMX3501 Ex T SF BG
Order no.: 903142
Silicone-free Àame detector
Otherwise like Order no 800000
FMX3501 Ex T 0.2 sec BG
Order no.: 903143
Flame detectors with fast response within range of miliseconds are used for object monitoring (e.g. tooling machine).
Otherwise like Order no 800000
P31.312.340 - 3en / 02.14
Technical specifications Criterion of detection
Change of intensity
FMX3501 Ex T 0.2 sec SF BG
Order no.: 903151
Silicone-free Àame detector
Otherwise like Order no 800000
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 53
Product Sheet | Detecon
Industrial detectors UV flame detector Ex UMX3001 Ex
Order.-no.: 903802 UV Àame detector for the detection of open Àames. Designed for use in rough industrial environments. Equipped for operation as a conventional detector. The UMX3001 Ex Àame detectors are ATEX-approved for category 2 gas and dust and are suitable for use in Ex zones 1 and 21. The UMX3001 Ex has a pressure resistant casing.
Product fetures
Not included in delivery
•
Wide ¿eld of view.
End of line-resistor 1.8 K / 0.5 W
•
Fast Àame response.
•
High water and dust protection (IP67).
Connection / mounting
Technical specifications Detections method Viewing angle Number of detectors per line
UV-Sensor 110 ° max. 4
Operating voltage
7.6 V - 13.2 V DC
Quiescent cuttent
approx. 1 mA
Alarm current Alarm indication Electrostatic shielding Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight
approx. 20 mA
Connection cable standard detector 2-lead Additional connection latching indication 1-lead Recommended cable LIYCY grey 5x0.5 mm2 (0.0008 square inch) Conductor cross-section max. 2.5 mm2 (0.004 square inch) Conducting cable diameter 5 mm to 9 mm (0.20 to 0.35 inch) Cable gland metal, EMV, Ex M16x1.5
Approvals / marking Ex conformity in acc. with 94/9/EG:
x II 2G Ex d e IIC T6 x II 2D Ex tD A21 IP67 T80°C
1 LED red requiered -20 °C to +70 °C (-4 °F to +158 °F) IP 67 Diecast aluminium, silver grey
Type examination certi¿cate:
BVS 04 ATEX E 168 X
max. 95% to +35 °C (95 °F) 3 kg (6.6 lbs) 88 x 190 mm (BxH) 3.5 x 7.5 inch (dia. x H)
P31.312.320 - 2en / 02.13
Dimensions
675235
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 54
Product Sheet | Detecon
Industrial detectors Detector accessories Mounting device console 80x75 Ø54 (3.1x2.9 Ø 2.1 inch)
Order no.: 902898 Mounting device to support gas emission detectors GMX1001CO I.
Included in delivery 1 Mounting device console 80x75 Ø54 complete 2 Countersunk screw DIN923-M5x10 St 5 Self-taping screw DIN7981 C4.2x16 5 Blind rivet 3.2x16 alu 1 O-ring 60x3 Viton 2 Hex screw DIN933-M8x20-A2 2 Spring washer DIN127 B8-1.4310
Technical specifications Material
Not included in delivery Plastic POM
Colour
black
Weight
160 g (0.4 lbs) 112 x 112 mm (LxB) (4.4 x 4.4 inch (LxB)
Adhesive LoctiteAVX 586, 50 ml
886226
Note Do not install the mounting device console in explosionhazard zone 1
P31.312.810 - 2en / 02.13
Dimensions
902896 835703 885080 885078 132587 772552 820707
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 55
Product Sheet | Detecon
Industrial detectors Detector accessories Mounting device console 125x80 Ø60 (4.9x3.1 Ø 2.3 inch)
Order no.: 801280 Mounting device to support Àame detector FMX3511.
Included in delivery 1 Mounting device console 125x80 Ø60 2 Countersunk screw DIN923-M5x10 St 5 Self-taping screw DIN7981 C4.2x16 5 Blind rivet 3.2x16 alu 1 O-ring 70x3 Viton 70°SH 2 Hex screw DIN933-M8x20-A2 2 Spring washer DIN127 B8-1.4310
Not included in delivery
Technical specifications Material
801069 835703 885080 885078 800774 772552 820707
Adhesive LoctiteAVX 586, 50 ml
886226
Plastic PETP
Colour
black
Weight
350 g (0.8 lbs) 120 x 150 mm (LxB) (4.7 x 5.9 inch (LxB)
Dimensions
Mounting device console 125x80 Ø60 (4.9x3.1 Ø 2.3 inch) LSP
Note Do not install the mounting device console in explosionhazard zone 1.
Order no.: 801281 Mounting device with air Àushing to support and preventive cleaning of the detector optics of Àame detectors FMX3511.
Included in delivery 1 Mounting device console 125x80 Ø60 LSP 2 Countersunk screw DIN923-M5x10 St 5 Self-taping screw DIN7981 C4.2x16 5 Blind rivet 3.2x16 alu 1 O-ring 60x3 Viton 70°SH 2 Hex screw DIN933-M8x20-A2 2 Spring washer DIN127 B8-1.4310
Not included in delivery
Technical specifications Medium
Compressed air
P31.312.810 - 2en / 02.13
Pressure range Connection thread Material
Adhesive LoctiteAVX 586, 50 ml 886226 Air Àushing has to be supplied with compressed air on site.
0.8 - 1.5 bar G1/8“, DIN ISO228 Plastic PEPT
Colour
black
Weight
370 g (0.8 lbs) 120 x 150 mm (LxB) (4.7 x 5.9 inch (LxB)
Dimensions
801298 835703 885080 885078 800774 772552 820707
Note Do not install the mounting device console in explosionhazard zone 1.
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 56
Product Sheet | Detecon
Industrial detectors Detector accessories Mounting device bracket with insulation
Order no.: 801284 Mounting device to support gas emission detectors, Àame detectors, spark detectors and spark test light detectors.
Included in delivery 1 Mounting device complete with 2 oval-head screw M8x12 for ¿xing the detector on the bracket.
Not included in delivery Clamping screw for wall/ceiling mounting.
Technical specifications Material bracket Material clamp Insulating Weight
Oval-head screw M8x12-1.4301 Hex. nut DIN934-M8-A2/A4 Spring washer DIN127 B8-1.4310
160 g (0.4 lbs) 81.5 x 86 x 31 mm (LxBxH) (3.2 x 3.4 x1.2 inch (LxBxH)
P31.312.810 - 2en / 02.13
Dimensions
Spare parts Stainless steel, 2 mm (0.08 inch) thick Stainless steel, 1.5 mm (0.06 inch) thick Plastic POM
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 57
800596 820781 820707
Product Sheet | Detecon
Industrial detectors Detector accessories Support disk mounting 90 °C (194 °F)
Order no.: 891848 Quick installation device to support detections with single-hole. The installation is allowed up to a wall thickness of 8 mm (0.3 inch).
Technical specifications Enclosure material: -mounting coupling -hex. nut -oval washer -tapered block Operating temperature
stainless steel brass stainless steel Polyamid PA12, black to +90 °C (+194 °F)
Weight
Support disk mounting 250 °C (482 °F)
120 g (0.3 lbs)
Order no.: 800034 Quick installation device to support detections with single-hole and ¿bre options.
Technical specifications Enclosure material: -tapered block 250 °C (482 °F) Operating temperature
Peck / Mod, black to +250 °C (+482 °F)
Otherwise like Order no. 891848.
Flushing air device
Order no.: 907822 Quick installation device to support detections with single-hole and air Àushing. .
Technical specifications Enclosure material:
V2A and PA 12 -10 °C to +60 °C (-14 °F to +140 °F) 0.2 to 10 bar
Operating temperature Operating pressure Weight
200 g (0.4 lbs) 55 x 48 mm (DxL) 2.2 x 1.9 inch (DxL)
Dimensions
Mounting tool mounting socket - F180
Order no.: 843474 Technical specifications
P31.312.810 - 2en / 02.13
Enclosure material
stainless spring band steel
Weight
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
90 g (0.2 lbs)
Chapter 6 - 58
Product Sheet | Detecon
Industrial detectors Flame detector accessories Sun screen FMX3511/FMX3501 Ex
Order no.: 801277 Protection against skewness parasitic radiation (e.g. sunlight for outside applications) for the Àame detector FMX3511 and FMX3501 Ex.
Connection / mounting Plug sun screen onto detector optic.
Note After mounting the sunscreen can not be removed.
Technical specifications
Colour
Stainless steel, 2.5 mm (0.09 inch) thick 62.5 x 53 mm (WxH) 2.5 x 2.1 inch (WxH) internally black
Weight
90 g (0.2 lbs)
Material Dimensions
Cleaning kit optic
Order no.: 916644 To clean the optic and reÀective surface by Àame detectors.
Included in delivery
P31.312.391en / 02.14
1 packaging unit (20 cleaning cloth and 10 cleaning sponge)
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 59
Product Sheet | Detecon
Industrial detectors Gas emission detector GMX1001CO I
Order no.: 900960 Multi sensor ¿re gas detector GMX1001CO I for the early detection of smoldering ¿res. Designed for use in rough industrial environments (e.g. silos, chip bunkers). The GMX1001CO I detects the burning characteristic substance carbon monoxide and temperature. False alarms are nearly impossible. Equipped for operation as a conventional detector.
Product features
Not included in delivery
•
A microcontroller monitors the functionality and values.
•
Multi sensor carbon monoxide and temperature.
•
Connection of remote indicator possible.
Mounting device bracket with insulation Mounting device console 80x75 Ø54 End of line-resistor 1.8 K / 0,5 W Test device smoke generator RG2000 Parallel indicator LMX5000
Technical specifications Detection method Alarm threshold: - Carbon monoxide - Temperature - Rate of rise measurement
CO (carbon monoxide) and temperature
Operating voltage
40 ppm > 60 °C (140 °F) dT > 3 °C/min. at T > 36 °C (96,8 °F) 7,6 V - 40 V DC
Quiescent current
approx. 0.15 mA
Alarm current Alarm indication Electrostatic shielding Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight
Connection / mounting Connection cable standard detector 2-lead Conductor cross-section max. 2.5 mm2 (0.004 square inch) Fire detection cable with static shield 606061 LIYCY grey 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, Brass nickel-plated, EMV
Spare parts Screwed mounting GMX1001COI complete Sensor GMX1002CO
1 LED red Required -20 °C to +50 °C (-4 °F to +122 °F) IP 65 Diecast aluminium, RAL5009-blue max. 15 to +90 % no condensation 480 g (1.1 lbs) 122 x 80 x 69 mm (BxHxT) 4.8 x 3.2 x 2.7 inch (BxHxT)
Note Simple one man calibration.
Approvals / marking G 204121
0786-CPD-20135
P31.312.610 - 1en / 02.13
Dimensions
approx. 18 mA
801284 902898 675235 902671 908499
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 60
902923 900968
Product Sheet | Detecon
Industrial detectors Gas emission detector
GMX1001CO 300ppm
Order no.: 909139
Special detector for application in areas with emissions of carbon monoxide increased due to operating conditions.
Approvals / marking
Technical specifications 300 ppm > 100 °C (212 °F) dT > 3 °C/min. at T > 80 °C (176 °F)
P31.312.610 - 1en / 02.13
Response monoxide: - Carbon monoxide - Temperature - Differential measurement
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 61
Product Sheet | Detecon
Industrial detectors Gas emission detector GMX1001CO I BG
Order no.: 902891 Multi sensor ¿re gas detector GMX1001CO I BG for the early detection of smoldering ¿res. Designed for use in rough industrial environments (e.g. silos, chip bunkers). The GMX1001CO I detects the burning characteristic substance carbon monoxide and temperature. False alarms are nearly impossible. Designed for operation as a conventional detector.
Product features
Not included in delivery
•
A microcontroller monitors the functionality and values.
•
Multi sensor carbon monoxide and temperature.
•
Connection of remote indicator possible.
Mounting device console 80x75 Ø54 End of line-resistor 1.8 K / 0.5 W Test device smoke generator RG2000 Parallel indicator LMX5000
Connection / mounting
Technical specifications Detection method Alarm threshold: - Carbon monoxide - Temperature - Rate of rise measurement
CO (carbon monoxide) and temperature
Operating voltage
40 ppm > 60 °C (140 °F) dT > 3 °C/min. at T > 36 °C (96,8 °F) 7.6 V - 40 V DC
Quiescent current
approx. 0.15 mA
Alarm current Alarm indication Electrostatic shielding Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight
Connection cable standard detector 2-lead Conductor cross-section max. 2.5 mm2 (0.004 square inch) Fire detection cable with static shield 606061 LIYCY grey, 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, Brass nickel-plated, EMV
Spare parts Screwed mounting GMX1001COI complete Sensor GMX1002CO
approx. 18 mA 1 LED red Required -20 °C to +50 °C (-4 °F to +122 °F) IP 65 Diecast aluminium, RAL5009-blue max. 15 to +90 % no condensation 600 g (1.3 lbs) 122 x 106 x 88 mm (BxHxT) 4.8 x 4.2 x 3.5 inch (BxHxT)
Note Simple one man calibration.
Approvals / marking G 204121
0786-CPD-20135
P31.312.610 - 2en / 02.13
Dimensions
902898 675235 902671 908499
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 62
902923 900968
Product Sheet | Detecon
Industrial detectors Gas emission detector
GMX1001CO 300ppm BG
Order no.: 909161
Special detector for application in areas with emissions of carbon monoxide increased due to operating conditions.
Approvals / marking
Technical specifications 300 ppm > 100 °C (212 °F) dT > 3 °C/min. at T > 80 °C (176 °F)
P31.312.610 - 2en / 02.13
Response values: - Carbon monoxide - Temperature - Differential measurement
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 63
Product Sheet | Detecon
Industrial detectors Gas emission detector GMX1001CO I Console
Order no.: 902893 Multi sensor ¿re gas detector GMX1001CO I Console for the early detection of smoldering ¿res. Designed for use in rough industrial environments (e.g. silos, chip bunkers). Version bracket mount. The GMX1001CO I detects the burning characteristic substance carbon monoxide and temperature. False alarms are nearly impossible. Designed for operation as a conventional detector.
Product features
Not included in delivery
•
A microcontroller monitors the functionality and values.
•
Multi sensor carbon monoxide and temperature.
•
Connection of remote indicator possible.
Mounting device bracket with insulation End of line-resistor 1.8 K / 0.5 W Test device smoke detector RG2000 Parallel indicator LMX5000
Connection / mounting
Technical specifications Detection method Alarm threshold: - Carbon monoxid - Temperature - Rate of rise measurement
CO (carbon monoxide) and temperature
Operating voltage
40 ppm > 60 °C (140 °F) dT > 3 °C/min. at T > 36 °C (96.8 °F) 7.6 V - 40 V DC
Quiescent current
approx. 0.15 mA
Alarm current Alarm indication Electrostatic shielding Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight
approx. 18 mA 1 LED red Required -20 °C to +50 °C (-4 °F to +122 °F) IP 65 Diecast aluminium, RAL5009-blue max. 15 at +90 % no condensation 600 g (1.3 lbs) 122 x 112 x 75 mm (BxHxT) 4.8 x 4.4 x 3 inch (BxHxT)
Connection cable standard detector 2-lead Conductor cross-section max. 2.5 mm2 (0.004 square inch) Fire detection cable with static shield 606061 LIYCY grey, 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, Brass nickel-plated, EMV
Spare parts Screwed mounting GMX1001COI complete Sensor GMX1002CO
Note Simple one man calibration.
Approvals / marking
P31.312.610 - 3en / 02.13
Dimensions
801284 675235 902671 908499
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 64
902923 900968
Product Sheet | Detecon
Industrial detectors Gas emission detector
GMX1001CO 300ppm Console
Order no.: 909162
Special detector for application in areas with emissons of carbon monoxide increased due to operating conditions.
Approvals / marking
Technical specifications 300 ppm > 100 °C (212 °F) dT > 3 °C/min. at T > 80 °C (96.8 °F)
P31.312.610 - 3en / 02.13
Response values: - Carbon monoxide - Temperature - Differential measurement
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 65
Product Sheet | Detecon
Industrial detectors Gas emission detector Ex GMX1001CO Ex Dust
Order no.: 905642 Multi sensor ¿re gas detector GMX1001CO Ex Dust for the early detection of smoldering ¿res. Designed for use in raugh industrial environments (e.g. silos, chip bunkers). The GMX1001CO I detects the burning characteristic substance carbon monoxide and temperature. False alarms are nearly impossible. Designed for operation as a conventional detector. The GMX1001CO Ex Dust gas detectors are ATEX-approved for category 1 and 2 dust and are suitable for use in Ex zone 20 and 21.
Product features
Not included in delivery
•
A microcontroller monitors the functionality and values.
•
Multi sensor carbon monoxide and temperature.
•
Connection of remote indicator possible.
Mounting device bracket with insulation Mounting device console 80x75Ø54 End of line-resistor 1.8 K / 0.5 W Test device smoke generator RG2000 Parallel indicator LMX5000
Technical specifications Detection method Alarm threshold: - Carbon monoxide - Temperature - Rate of rise measurement Number of detectors per line
CO (carbon monoxide) and temperature 40 ppm > 60 °C (140 °F) dT > 3 °C/min. at T > 36 °C (96.8 °F) max. 32
Operating voltage
7.6 V - 40 V DC
Quiescent current
approx. 0.15 mA
Alarm current Alarm indication Electrostatic shielding Operating temperature IP rating (EN 60529) Enclosure material Relative humidity (IEC721-3-3) Weight
1 LED red Required -20 °C to +50 °C (-4 °F to +122 °F) IP 65 Diecast aluminium, RAL5009-blue max. 15 at + 90 % no condensation 480 g (1.1 lbs) 122 x 80 x 69 mm (BxHxT) 4.8 x 3.2 x 2.7 inch (BxHxT)
Connection / mounting Connection cable standard detector 2-lead Conductor cross-section max. 2.5 mm2 (0.004 square inch) Fire detection cable with static shield 606061 LIYCY grey, 5x0.5 mm2 (0.0008 square inch) Cable gland M16x1.5, Brass nickel-plated, EMV, Ex
Spare parts Screwed GMX1001COI complete Sensor GMX1002CO
902923 900968
Hinweis Simple one man calibration
Approvals Ex conformity in acc. with 94/9/EG: x II 1/2D Ex tD A20/21 IP65 T136°C x II 1D Ex tD A20 IP65 T136°C Type examination certi¿cate: BVS 05 ATEX E179
Approvals / marking G 204121
0786-CPD-20135
P31.312.620 - 1en / 02.13
Dimensions
appro. 18 mA
801284 902898 675235 902671 908499
© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |
Chapter 6 - 66