This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully. NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION Type 1 SPD, Type 2 SPD for hardwired parallel installations on 120/240 VAC High Leg, 3 phase Delta circuits.
INSTRUCTIONS: Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Remove front cover from the panel. 3. Remove 1/2" knockout on side of panel box. 4. Make sure the leads are as short as possible with the ground wire being the shortest of all. 5. Unscrew nut from unit. 6. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit. 7. Connect the Ground wire (Green) to the Ground buss making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 8. Connect the Neutral wire (White) to the Neutral buss. 9. Connect the 240V High Leg wire (RED) to the line side or load side of the High Leg breaker. 10. Connect the 120V Phase wires (Black) to the line side or load side of the 120V Phase leg breakers. 11. Securely mount the enclosure using the mounting holes located under the cover. 12. After all connections have been made and no hazards exist, replace cover and restore power. 13.This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for .15 NIPPLE SIDE replacing the device. 4 PLCS .26
Expected System Voltages 120V Single Ø 240V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 347/600V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
L - L HiL-G,N NA NA NA NA 240 NA 240 240 208 NA 480 NA 600 NA NA 240 NA 480 NA 600
L-G L-N 120 120 240 240 120 120 120 120 120 120 277 277 347 347 240Max NA 480Max NA 600Max NA
N-G 0 0 0 0 0 0 0 0 0 0
3.05 4.21 (D50)
.65
Drawn By: J.Ramirez/R.Mitchell 10-28-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43 2.25 (D50)
Doc # INT-100126-001 Part No. 191546 Rev. 4
INSTALL INSTRUCTIONS D50-347/6003Y
DITEK Corporation
This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
INSTALLATION
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Type 1 SPD, Type 2 SPD for hardwired parallel installations on 347/600 VAC 3 phase Wye circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Remove front cover from the panel. 3. Remove 1/2" knockout on side of panel box. 4. Make sure the leads are as short as possible with the ground wire being the shortest of all. 5. Unscrew nut from unit. 6. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit. 7. Connect the Ground wire (Green) to the Ground buss making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 8. Connect the Neutral wire (White) to the Neutral buss of the panel. 9. Connect the Phase wires (Black) to the line side or load side of the Phase A, Phase B and Phase C, 3 pole breaker. 10. Securely mount the enclosure using the mounting holes located under the cover. 11. After all connections have been made and no hazards exist, replace cover and restore power. 12. This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for replacing the device. .15 NIPPLE 4 PLCS
SIDE
.26
Expected System Voltages 120V Single Ø 240V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 347/600V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
Drawn By: J.Ramirez 1-21-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
L - L HiL-G,N NA NA NA NA 240 NA 240 240 208 NA 480 NA 600 NA NA 240 NA 480 NA 600
L-G L-N 120 120 240 240 120 120 120 120 120 120 277 277 347 347 240Max NA 480Max NA 600Max NA
N-G 0 0 0 0 0 0 0 0 0 0
3.05 4.21 (D50)
.65
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43 2.25 (D50)
Doc # INT-100135-001 Part No. 191567 Rev. 2
INSTALL INSTRUCTIONS
D50-120/2401, D50-120/240HD, D100-120/2401 DITEK Corporation
This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
INSTALLATION
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Type 1 SPD, Type 2 SPD for hardwired parallel installations on 120/240 VAC split phase circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Remove front cover from the panel. 3. Remove 1/2" knockout on side of panel box. 4. Unscrew nut from unit. 5. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit. 6. Connect the Ground wire (Green) to the Ground buss of the panel, making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 7. Connect the Neutral wire (White) to the Neutral buss of the panel. 8. Connect the Phase wires (Black) to the line side or load side of the 2 pole circuit breaker. 9. Securely mount the enclosure using the mounting holes located under the cover. 10. After all connections have been made and no hazards exist, replace cover and restore power. 11. This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for replacing the device. .15 4 PLCS
NIPPLE SIDE .26
Expected System Voltages 120V Single Ø 240V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 347/600V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
Drawn By: J.Ramirez 1-21-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
L - L HiL-G,N NA NA NA NA 240 NA 240 240 208 NA 480 NA 600 NA NA 240 NA 480 NA 600
L-G L-N 120 120 240 240 120 120 120 120 120 120 277 277 347 347 240Max NA 480Max NA 600Max NA
N-G 0 0 0 0 0 0 0 0 0 0
3.05 4.21 (D50)
.65
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43 2.25 (D50)
Doc # INT-100121-001 Part No. 191545 Rev. 3
INSTALL INSTRUCTIONS D50-4803D, D100-4803D
DITEK Corporation
This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
INSTALLATION
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Type 1 SPD, Type 2 SPD for hardwired parallel installations on 480 VAC 3 phase Delta circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Remove front cover from the panel. 3. Remove 1/2" knockout on side of panel box. 4. Make sure the leads are as short as possible with the ground wire being the shortest of all. 5. Unscrew nut from unit. 6. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit. 7. Connect the Ground wire (Green) to the Ground Buss making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 8. Connect the Phase wires (Black) to the line side or load side of the Phase A, Phase B and Phase C, 3 pole breaker. 9. Securely mount the enclosure using the mounting holes located under the cover. 10. After all connections have been made and no hazards exist, replace cover and restore power. 11. This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for replacing the device. .15 NIPPLE
120V Single Ø 240V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 347/600V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
Drawn By: J.Ramirez 1-21-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
4 PLCS
SIDE
.26
Expected System Voltages L - L HiL-G,N NA NA NA NA 240 NA 240 240 208 NA 480 NA 600 NA NA 240 NA 480 NA 600
L-G L-N 120 120 240 240 120 120 120 120 120 120 277 277 347 347 240Max NA 480Max NA 600Max NA
N-G 0 0 0 0 0 0 0 0 0 0
3.05 4.21 (D50)
.65
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43 2.25 (D50)
Doc # INT-100124-001 Part No. 191550 Rev. 3
INSTALL INSTRUCTIONS D50-2403D, D100-2403D
DITEK Corporation
This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
INSTALLATION
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Type 1 SPD, Type 2 SPD for hardwired parallel installations on 240 VAC 3 phase Delta circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Remove front cover from the panel. 3. Remove 1/2" knockout on side of panel box 4. Make sure the leads are as short as possible with the ground wire being the shortest of all. 5. Unscrew nut from unit. 6. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit. 7. Connect the Ground wire (Green) to the ground buss making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 8. Connect the Phase wires (Black) to the line side or load side of the Phase A, Phase B and Phase C, 3 pole breaker. 9. Securely mount the enclosure using the mounting holes located under the cover. 10. After all connections have been made and no hazards exist, replace cover and restore power. 11. This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for replacing the device. .15 NIPPLE 4 PLCS
SIDE
.26
Expected System Voltages 120V Single Ø 240V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 347/600V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
Drawn By: J.Ramirez 1-21-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
L - L HiL-G,N NA NA NA NA 240 NA 240 240 208 NA 480 NA 600 NA NA 240 NA 480 NA 600
L-G L-N 120 120 240 240 120 120 120 120 120 120 277 277 347 347 240Max NA 480Max NA 600Max NA
N-G 0 0 0 0 0 0 0 0 0 0
3.05 4.21 (D50)
.65
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43 2.25 (D50)
Doc # INT-100123-001 Part No. 191549 Rev. 3
INSTALL INSTRUCTIONS
D50-220/3803Y, D50-230/4003Y, D50-240/4153Y, D50-277/4803Y, D100-277/4803Y DITEK Corporation
This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
INSTALLATION
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Type 1 SPD, Type 2 SPD for hardwired parallel installations on 277/480 VAC three phase circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Remove front cover from the panel. 3. Remove 1/2" knockout on side of panel box. 4. Make sure the leads are as short as possible with the ground wire being the shortest of all. 5. Unscrew nut from unit. 6. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit. 7. Connect the Ground wire (Green) to the ground buss making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 8. Connect the Neutral wire (White) to the Neutral buss of the panel. 9. Connect the Phase wires (Black) to the line side or load side of the Phase A, Phase B and Phase C, 3 pole breaker. 10. Securely mount the enclosure using the mounting holes located under the cover. 11. After all connections have been made and no hazards exist, replace cover and restore power. 12. This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for .15 NIPPLE replacing the device. SIDE 4 PLCS
.26
Expected System Voltages 120V Single Ø 240V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 347/600V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
Drawn By: J.Ramirez 1-21-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
L - L HiL-G,N NA NA NA NA 240 NA 240 240 208 NA 480 NA 600 NA NA 240 NA 480 NA 600
L-G L-N 120 120 240 240 120 120 120 120 120 120 277 277 347 347 240Max NA 480Max NA 600Max NA
N-G 0 0 0 0 0 0 0 0 0 0
3.05 4.21 (D50)
.65
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43 2.25 (D50)
Doc # INT-100122-001 Part No. 191548 Rev. 3
INSTALL INSTRUCTIONS
D50-120/2083Y, D50-127/2203Y, D100-120/2083Y DITEK Corporation
This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
INSTALLATION
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Type 1 SPD, Type 2 SPD for hardwired parallel installations on 120/208 VAC 3 phase Wye circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Remove front cover from the panel. 3. Remove 1/2" knockout on side of panel box. 4. Make sure the leads are as short as possible with the ground wire being the shortest of all. 5. Unscrew nut from unit. 6. Feed all wires and the nipple through knockout hole then through nut, tighten nut securing the unit. 7. Connect the Ground wire (Green) to the Ground buss making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 8. Connect the Neutral wire (White) to the Neutral buss of the panel. 9. Connect the Phase wires (Black) to the line side or load side of the Phase A, Phase B and Phase C, 3 pole breaker. 10. Securely mount the enclosure using the mounting holes located under the cover. 11. After all connections have been made and no hazards exist, replace cover and restore power. 12. This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for replacing .15 NIPPLE SIDE 4 PLCS the device.
120V Single Ø 240V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 347/600V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
Drawn By: J.Ramirez 1-21-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
.26
Expected System Voltages L - L HiL-G,N NA NA NA NA 240 NA 240 240 208 NA 480 NA 600 NA NA 240 NA 480 NA 600
L-G L-N 120 120 240 240 120 120 120 120 120 120 277 277 347 347 240Max NA 480Max NA 600Max NA
N-G 0 0 0 0 0 0 0 0 0 0
3.05 4.21 (D50)
.65
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43 2.25 (D50)
Doc # INT-100120-001 Part No. 191547 Rev. 3
INSTALL INSTRUCTIONS D100-6003D
DITEK Corporation
This Surge Protective Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read and follow the installation instructions carefully.
INSTALLATION
ONE DITEK CENTER 1720 Starkey Road Largo, FL 33771
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Type 1 SPD for hardwired parallel installations on 600 VAC Delta circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical Amperes. This SPD Contains no serviceable parts. 1. Turn off the power at the circuit breaker or main before beginning installation. 2. Make sure the leads are as short as possible with the ground wire being the shortest of all. 3. Unscrew nut from unit. 4. Feed all wires and the D100-6003D nipple through knockout hole then through nut, tighten nut securing the unit. 5. Connect the ground wire (Green) to earth ground making sure the ground wire is as short as possible. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum. This cannot be an assumed value and must be measured to assure proper grounding. 6. Connect the phase wires (Black) to the line side or load side of the Phase A, Phase B and Phase C 3 pole breaker. 7. After all connections have been made and no hazards exist, restore power. 8. This device features an internal protection that will disconnect the surge protective component but will maintain power to the load - now unprotected. If this situation is undesirable for the application, follow the manufacturer’s instructions for replacing the device. .15 4 PLCS
.26
NIPPLE SIDE
Expected System Voltages
120V Single Ø 120/240V Split Ø 120/240V Hi Leg Δ 120/208V 3 Ø Wye 277/480V 3 Ø Wye 240V 3 Ø Δ 480V 3 Ø Δ 600V 3 Ø Δ
Drawn By: J.Ramirez 1-21-10 Approved By: R. Mitchell 3-16-15 Revised By: K. Nguyen 3-16-15
L - L Hi L - G NA NA 240 NA 0 240 208 NA 480 NA 0 NA 0 NA 0 NA
L-G 120 120 120 120 277 240 480 600
L-N 120 120 120 120 277 NA NA NA
N-G 0 0 0 0 0 0 0 0
4.21
.65
DITEK Technical Support Available 24/7 1-888-472-6100 www.ditekcorp.com
3.43
Doc # INT-100125-001 Part No. 191551 Rev. 2