Preview only show first 10 pages with watermark. For full document please download

Installation And Operating Manual For The Ultrabox 1125

   EMBED


Share

Transcript

© MHG Heating Ltd Installation and Operating Manual for the Ultrabox 1125 1 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd Section 1.0 1.1 2.0 2.1 3.0 4.0 4.1 5.0 6.0 6.1 6.2 6.3 6.4 6.5 6.6 7.0 7.1 8.0 8.1 9.0 9.1 10.0 10.1 10.2 10.3 11.0 11.1 11.2 12.0 13.0 14.0 15.0 16.0 Appliance TypeThere are three outputs within the Wallcon range Installation Regulations and Requirements Appliance Warranties Supplied Components Technical Data Dimensions Installation and Service Clearances Electrical Connections Hydraulic Design Single Unit (Option 1) Hydraulic Design Single Unit (Option 2) Hydraulic Design Single Unit (Option 3) Hydraulic Design Single Unit (Option 4) Hydraulic Design Single Unit (Option 5) Hydraulic Design Single Unit (Option 6) Hydraulic Design Single Unit (Option 7) Hydraulic Design Single Unit (Option 8) Fluing Options Balanced Flue Terminal Positions For Boilers Below and Above 70kW Net Input Filling The System Expansion Vessel, System Water Quality Care With The Use of Flux Boiler Controller Accessing Controller Parameters Weather Compensation Slope Controller Error Codes Commissioning The Appliance Combustion System Commissioning Routine Inspection and Servicing Routine Service Inspection Routine Cleaning &Maintenance (E:105 Indication) Troubleshooting Internal Wiring Spares Diagram Notes Page # 3 3 4 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19 19 20 21-48 49 50-52 53 53 53-54 55 55 56-57 58 59 60 2 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 1.0 Appliance Type There are 2 outputs within the largeUltrabox range. Please ensure you have the correct unit for the application and where required located correctly within the cascade prior to beginning the installation. 1.1 Installation Regulations and Requirements The installation of Ultrabox boilers must be in accordance with the relevant requirements of Gas Safety (Installation & Use) Regulations 1994, Health & Safety at Work Act, Building Regulations, IEE Regulations, Construction (Design & Management) Regulations 1994, Local Authority Bye-Laws, National, Fire Regulations and Insurance Company requirements. The following Codes of Practice are also applicable:BS 5440-1: 2000 Installation of flues and ventilation for gas appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family gases). Part 1: Specification for the installation of flues. BS 5440-2: 2000 Installation of flues and ventilation for gas appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family gases). Part 2: Specification for installation and maintenance of ventilation for gas appliances. BS 5449: 1990 Specification for forced circulation hot water central heating systems for domestic premises. BS 6644: 2011 Specification for gas fired hot water boilers of rated inputs between 70kW (net) and 1.8MW(net) (2nd and 3rd family gases). BS 6798: 1987 Specification for installation of gas fired hot water boilers of rated input not exceeding 60 kW. BS 6880: 1988 Code of Practice for low temperature hot water heating systems of output greater than 45kW.Parts 1, 2 & 3. BS 6891: 1988 Specification for installation of low pressure gas pipework of up to 28mm (R1) in domestic premises (2nd family gases) BS 7593: 1992 Code of Practice for treatment of water in domestic hot water central heating systems. BS 7671: 1992 Requirements for electrical installations.IEE Wiring Regulations.Sixteenth edition. CISBE Guide reference sections B7, B11 and B13. CP342 Part 2: 1974 Code of Practice for centralized hot water supply. GE/UP/2 Gas installation pipework, boosters and compressors on industrial and commercial premises. IGE/UP/4 Commissioning of gas fired plant on industrial and commercial premises IGE/UP/10 Installation of gas appliances in industrial and commercial premises. Part 1: Flued appliances. And any addition prevailing regulation and or code of practice not detailed above. 3 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 2.0 Appliance Warranties All MHG appliances enjoy a full 24 month warranty as detailed in our terms and conditions. The guarantee period shall begin on the day of commissioning, or at latest 3 months after delivery has been made. The customer shall only be able to claim against MHG under guarantee if the commissioning of the object of delivery has been carried out by MHG staff or the authorised supplier, If the customer has followed MHG's instructions relating to the treatment and maintenance of the object of delivery, and if no replacement parts of outside origin have been fitted. Parts subject to wear such as ignition electrodes, seals etc. are strictly excluded from the guarantee. In addition to the above warranties, the Primary Heat Exchangers, of stainless steel construction, carry a 60 month guarantee against manufacturing or material defect. 2.1 Supplied Components All Ultrabox are supplied with a HWS probe sensor and QAC 34 outside Air Sensor. (To activate direct on boiler weather compensation) 4 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 3.0 Technical Data 1000 Model Min. Type of Flue Installation Gas Category Fuel Type Gas Pressure (Min/Max) Natural Gas Nominal Heat Input Nominal Heat Output at (80-60°C) Nominal Heat Output at (50-30°C) Water Operating Pressure Maximum Operation Temperature Water Content Efficiency & Emissions Heat Efficiency Qmin(80-60°C) Heat Efficiency Qmax (80-60°C) Heat Efficiency Qmin(50-30°C) Heat Efficiency Qmax (50-30°C) Partial Load, Return 30°C (Direct Method) Flue gas Temperature (50-30°C) Flue gas Temperature (80-60°C) CO2 Emissions CO Emissions NOX Emissions NOX Class Combustion products mass flow rate Gas Consumption Boiler Connections Boiler Flow Connection Boiler Return connection Gas Supply Condensate Syphon Discharge Flue Gas Outlet Air Inlet Electrical Connections Power supply Electrical Power IP Class Boiler dimensions & weight Dimensions WxLxH Weight mbar kW kW kW Bar °C L 1125 Max. Min. B23,C43,C53,C83 G20 17/25 998.9 115.8 967.8 124.1 1061.3 124.4 6.0 0.8 115.8 124.1 124.3 0.8 Max. 1069.9 1037.3 1135.7 6.0 90 95 90 95 % % % % 97.26 96.89 107.19 106.25 97.47 96.96 107.19 106.15 % 107.35 107.4 °C °C % ppm ppm 31.22 61.32 9.1 6 g/sec 3 m /h 87 12.26 30.53 61.81 9.4 22 30.53 61.32 9.2 7 41 5 33.61 63.01 9.4 28 48 5 440 105.70 87 12.26 471 113.21 “ “ “ Ø Ø Ø DN100 DN100 DN65 25 250 200 DN100 DN100 DN65 25 250 200 V/Hz W IP 380 2650 X4D 380 2650 X4D mm kg 935x2030x1875 750 935x2030x1875 750 5 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 4.0 Dimensions Label Connections F System Flow – DN100 R G FO System Return – DN100 Gas Supply – DN65 Flue Outlet – Ø250mm Condensate Discharge – Ø25mm Con Model 10001125 Dimensions W:935mm, D:2030mm, H:1875mm 6 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 4.1 Installation and Service Clearances Clearances A Minimum of 1000mm B C D Minimum of 600mm Minimum of 700mm Minimum of 500mm 7 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 5.0 Electrical Connections Basic electrical connection for the Ultrabox range. The wiring connections of the Ultrabox boilers are located within a terminal box mounted to the rear of the boilers case. All wiring via terminal blocks provided. High voltage Wiring terminals Power in to Boiler Q2 Heating circuit pump Q3 Hot water charging pump *Additional wiring to be added at commissioning if required. 230 Volts - 50 Hertz Live, Neutral, Earth, (Max switching 0.5Amp) (Q2) Can be used as Multifunctional Output Live, Neutral, Earth, (Max switching 0.5Amp) (Q3) Can be used as a Multifunctional Output Additional outputs can be configured if required. Low Voltage Wiring Terminals Room Thermostat 0-10V enable * Outside Air Temperature Sensor Cascade Sensor Hot Water Enable Cascade Communication * Volt Free Enable, Not Polarity Sensitive, Room stat/BMS ( <24 Volts) (H5) Polarity sensitive, Max 10Volts, To be configured at Commissioning, (H3) QAC34 sensor provided for direct on boiler weather compensation. (B9) QAD36 strap on sensor, provided on request. Thermostat or Sensor, to be configured at commissioning, (B3) To be wired from Master boiler to all slave boilers in parallel, polarity sensitive. *Additional wiring to be added at commissioning if Additional outputs can be configured if required. required. * Screened cable must be used for this connection. 8 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6.0 Hydraulic Design Single Unit (Option 1) Electrical Connections Single Unit (Option 1) High Voltage Mains power External Boiler Pump Heating Circuit Pump Input/Output Input Output Output Low Voltage Input/Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump Max 0.5Amp Q2 Central Heating Pump Max 0.5Amp Type 230Volts-50Hz 230Volts-50Hz 230Volts-50Hz Terminal Description/Label Outside temperature Sensor. QAC34 sensor Outside Air Sensor Input provided **Room Thermostat Input Room thermostat, Volt free Enable **0-10Volt Enable Input 0-10Volt Enable H3 Multifunctional to be configured during MHG Pressure Manager Input commissioning **Only one enable to be used per installation. Volt Free or 0-10. Type <24 Volts 0-10Volts <24 Volts 9 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6.1 Hydraulic Design Single Unit (Option 2) Electrical Connections Single Unit (Option 2) High Voltage Mains power External Boiler Pump Heating Circuit Pump DHW Pump Input/Output Input Output Output Output Low Voltage Input/Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump Max 0.5Amp Q2 Central Heating Pump Max 0.5Amp Q3DHW Storage Pump Max 0.5Amp Type 230Volts-50Hz 230Volts-50Hz 230Volts-50Hz 230Volts-50Hz Terminal Description/Label Outside temperature Sensor. QAC34 sensor Outside Air Sensor Input provided **Room Thermostat Input Room thermostat, Volt free Enable **0-10Volt Enable Input 0-10Volt Enable H3 DHW Demand Input Volt free thermostat or sensor Multifunctional to be configured during MHG Pressure Manager Input commissioning **Only one enable to be used per installation. Volt Free or 0-10. Type <24 Volts 0-10Volts <24Volts <24 Volts 10 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6.2 Hydraulic Design Single Unit (Option 3) Electrical Connections Single Unit (Option 3) High Voltage Mains power External Boiler Pump Input/Output Input Output 3 Way Valve Open Output 3 Way Valve Close Output Heating Circuit Pump DHW Pump Output Output Low Voltage Input/Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump Max 0.5Amp Additional internal wiring required at Commissioning Additional internal wiring required at Commissioning Q2 Central Heating Pump Max 0.5Amp Q3DHW Storage Pump Max 0.5Amp Type 230Volts-50Hz 230Volts-50Hz 230volts-50Hz 230volts-50Hz 230Volts-50Hz 230Volts-50Hz Terminal Description/Label Outside temperature Sensor. QAC34 sensor Outside Air Sensor Input provided **Room Thermostat Input Room thermostat, Volt free Enable **0-10Volt Enable Input 0-10Volt Enable H3 Additional internal wiring required at Mixed Circuit Sensor Input CommissioningQAD 36 sensor required DHW Demand Input Volt free thermostat or sensor Multifunctional to be configured during MHG Pressure Manager Input commissioning **Only one enable to be used per installation. Volt Free or 0-10. Type <24 Volts 0-10Volts <24 Volts <24Volts <24 Volts 11 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6.3 Hydraulic Design Single Unit (Option 4) Electrical Connections Cascade System (Option 5) Master Boiler High Voltage Mains power External Boiler Pump Heating Circuit1 Pump DHW Pump Input/Output Input Output Output Output Low Voltage Cascade Communication Input/Output Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump max 0.5Amp Q2 Central Heating Pump Max 0.5Amp Q3DHW Storage Pump Max 0.5Amp Terminal Description/Label Cascade Module. Screened Cable must be used Outside temperature Sensor. QAC34 sensor Outside Air Sensor Input provided **Room Thermostat HC1 Input Room thermostat, Volt free Enable **0-10Volt Enable HC1 Input 0-10Volt Enable H3 DHW Demand Input Volt free thermostat or sensor Multifunctional to be configured during MHG Pressure Manager Input commissioning **Only one enable to be used per installation. Volt Free or 0-10. Type 230Volts-50Hz 230Volts-50Hz 230Volts-50Hz 230Volts-50Hz Type Coms <24 Volts 0-10Volts <24Volts <24 Volts Slave Boiler High Voltage Mains power External Boiler Pump Input/Output Input Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump max 0.5Amp Type 230Volts-50Hz 230Volts-50Hz Low Voltage Cascade Communication Input/Output Input Terminal Description/Label Cascade Module. Screened Cable must be used Type Coms 12 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6.4 Hydraulic Design Single Unit (Option 5) Electrical Connections Cascade System (Option 5) Master Boiler High Voltage Input/Output Terminal Description/Label Mains power Input Brown=Live, Blue=Neutral, Yellow/Green=Earth External Boiler Pump Output Q1 Boiler Circulation Pump max 0.5Amp Heating Circuit1 Pump Output Q2 Central Heating Pump Max 0.5Amp DHW Pump Output Q3DHW Storage Pump Max 0.5Amp Low Voltage Cascade Communication Input/Output Output Type 230Volts-50Hz 230Volts-50Hz 230Volts-50Hz 230Volts-50Hz Terminal Description/Label Cascade Module. Screened Cable must be used Outside temperature Sensor. QAC34 sensor Outside Air Sensor Input provided **Room Thermostat HC1 Input Room thermostat, Volt free Enable **0-10Volt Enable HC1 Input 0-10Volt Enable H3 Additional internal wiring required at Mixed Circuit Sensor Input Commissioning QAD 36 sensor required DHW Demand Input Volt free thermostat or sensor Multifunctional to be configured during MHG Pressure Manager Input commissioning **Only one enable to be used per installation. Volt Free or 0-10. Type Coms <24 Volts 0-10Volts <24 Volts <24Volts <24 Volts Slave Boiler High Voltage Mains power External Boiler Pump Input/Output Input Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump max 0.5Amp Type 230Volts-50Hz 230Volts-50Hz Low Voltage Cascade Communication Input/Output Input Terminal Description/Label Cascade Module. Screened Cable must be used Type Coms 13 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6.5 Hydraulic Design Single Unit (Option 6) Electrical Connections BMS System (Option 6) High Voltage Mains power External Boiler Pump Low Voltage **Room Thermostat HC1 **0-10Volt Enable HC1 Input/Output Input Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump max 0.5Amp Type 230Volts-50Hz 230Volts-50Hz Input/Output Terminal Description/Label Input Room thermostat, Volt free Enable Input 0-10Volt Enable H3 **Only one enable to be used per installation. Volt Free or 0-10. Type <24 Volts 0-10Volts 14 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6.6 Hydraulic Design Single Unit (Option 7) Electrical Connections BMS System (Option 7) Master and Slave boilers require the following wiring High Voltage Mains power External Boiler Pump Low Voltage **Room Thermostat HC1 **0-10Volt Enable HC1 Input/Output Input Output Terminal Description/Label Brown=Live, Blue=Neutral, Yellow/Green=Earth Q1 Boiler Circulation Pump max 0.5Amp Input/Output Terminal Description/Label Input Room thermostat, Volt free Enable Input 0-10Volt Enable H3 **Only one enable to be used per installation. Volt Free or 0-10. Type 230Volts-50Hz 230Volts-50Hz Type <24 Volts 0-10Volts 15 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 7.0 Fluing Options Flue Type B23 C43 C53 C83 Description Open Flued Installation with products of combustion flued through a wall or roof to outside. Combustion air taken from the room via adequate ventilation. A Balanced Flue System/ Room sealed installation. Independent air ducted in and products out via a duct. A Balanced Flue System/ Room sealed installation. Independent air ducted in and products flued out to separate zones. A Balanced Flue System/ Room sealed installation. Air ducted from outside and the products flued out via a shared stack. 16 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 7.1 Balanced Flue Terminal Positions For Boilers Below and Above 70kW Net Input (All measurements are in mm and are minimum clearances) Terminal Location A Directly below an opening into the building BS5440 Boilers with a rated Input <70kW Net IGE-UP-10 Boilers Input >70kW <333kW Net Fan Draught Balanced Flue X IGE-UP-10 Boilers Input >70kW <333kW Net Fan Draught& Open Flued V 300 2500 2500 B C D E F G H I J K L M N P P+ Q R S T T+ Below gutter soil pipes etc. 75 200 200 Below Eaves 200 200 200 Below balconies or car port roof 200* Not Recommended** Not Recommended** From vertical drain or soil pipe etc. 150 150 150 If <2500 use P/T below# From internal or external corners 300 If <2500 use Plume Ext Above ground or balcony level 300 If <3000 use Plume Ext If <3000 use Plume Ext From a surface facing the terminal 600 23.126 x (kW) + 618.84 23.126 x (kW) + 618.84 From a terminal facing the terminal# 1200 19.32 x (kW) + 647.59 19.32 x (kW) + 647.59# From opening in a carport into a dwelling 1200* Not Recommended** Not Recommended** Vertically from a terminal on the same wall# 1500 2500 2500# Horizontally from a terminal on the same wall 300 7.232 x (kW) + 93.708 9.5156 x (kW) + 833.91 Above an opening into the building 300 7.232 x (kW) + 93.708 9.5156 x (kW) + 833.91 Horizontally to an opening into the building 300* 7.232 x (kW) + 93.708 9.5156 x (kW) + 833.91 Above a flat roof (Obstacle> 2500) From Roof Level 300 4.5675 x (kW) -19.723 4.5675 x (kW) -19.723 Above a flat roof (Obstacle<2500) From Obstacle Level 300 4.5675 x (kW) -19.723 4.5675 x (kW) -19.723 If <2500 use Plume Ext# From an adjacent wall (edge of terminal) 300 If <2500 use Plume Ext To an opening into the building 1000 7.232 x (kW) + 93.708 9.5156 x (kW) + 833.91 9.5156 x (kW) + 833.91# From any other flue terminal# 300 7.232 x (kW) + 93.708 0 Above a >20 Pitched Roof (BOT) 300 4.5675 x (kW) -19.723 4.5675 x (kW) -19.723 Above a >200 Pitched Roof (BOT) (Valley) 300 4.5675 x (kW) -19.723 4.5675 x (kW) -19.723 kW=Net Heat Input. * Positions not recommended. ** Risk assessment required (App 9). (BOT = Base of Terminal). # Contact MHG Groups of appliances of 150kW gross input (136kW net input) and above must comply with the Clean Air Act with respect to the chimney discharge height. The terminal/s shall be guarded if it is less than 2000mm above the ground or in any position where it may cause injury to persons resulting from touching a hot surface. Absolute guidance must be sought from the respective regulation. 17 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 8.0 Filling The System The Initial filling of a sealed heating system, and subsequent refilling, must be by a method that has been approved by the Water Regulation Advisory Scheme (WRAS) for that type of heating system. i.e Non Domestic (Other than In-House) Fluid Category 4 (C-4) For Category 4 systems, the approved method of filling must comprise of the following components in the arrangement shown;  Control Valve.  Strainer.  Verifiable Backflow Device with Reduced Pressure Zone (RPZ Valve)  Incorporating a ‘Type BA’ Air Gap.  Tundish.  Control Valve. Further more, in accordance with BS 6644: 2011 system with an input greater than 70kW (nett), an automatic water replenishment unit shall be installed to automatically replenish any lost or evaporated water. Please refer to BS 6644: 2011 for allowable water replenishment methods for use with sealed/pressurized heating systems. For information on a comprehensive range of pressurization units that comply with current British Standards and WRAS Regulations, please contact MHG Heating Ltd Sales. 18 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 8.1 Expansion Vessel In accordance with BS 6644: 2011, WRAS Regulations, and Local Authority Water Regulations, as applicable, the installer shall install a suitably sized, and approved, Expansion Vessel to ensure that the water capacity of the system has ample expansion capacity. The location of the expansion vessel shall only be isolatable from the system via a Lockable Type Service Valve, which shall be locked in the OPEN position, to prevent accidental isolation. Furthermore, a drain facility should be provided adjacent to the expansion vessel to aide the routine maintenance, overhaul, of the vessels Air Pressure setting. For information on a comprehensive range of expansion vessels that comply with current British Standards and WRAS Regulations, please contact MHG Heating Ltd Sales. 9.0 System Water Quality Water Treatment, System Cleaning (BS 7592: 2006) The entire primary system MUST be thoroughly cleaned and flushed to remove debris, flux residues, etc. before opening the boiler isolation valves & flooding the boiler. Particular care must be taken where the Ultrabox boiler is being retro-fitted into an old/existing system, as system silt or magnetite can be very damaging to the new boiler. Following cleaning and flushing the system MUST be dosed with a good quality water treatment to prevent corrosion and the formation of scale. FAILURE TO OBSERVE THESE REQUIREMENTS WILL RENDER THE WARRANTEE ON THE APPLIANCE VOID. Cleaning, flushing and water treatment must be carried out in accordance with the requirements of BS 7593:1992, prior to commissioning the boiler. Repeated draining and refilling of the system, without replenishment of water treatment, must be avoided, as this is very damaging to the boiler. The boiler must not operate without the system water being correctly and adequately treated, and maintained, with an appropriate level of corrosion inhibitor. For specific guidance on water treatment, direct contact is advisable with:- Fernox 2 Genesis Business Park Albert Drive Sheerwater Woking Surrey GU21 5RW P:0330 100 7750 F: 0330 100 7751 E: [email protected] W: www.fernox.com 9.1 Care With The Use of Solder Flux The Ultrabox range has heat exchangers fabricated from Stainless Steel. It is most important that the compatibility of any flux is checked with the supplier before use, and that any flux manufactures recommendations are strictly followed with regards to use in conjunction with Stainless Steel. If you are applying any of the Ultrabox Range to a system where the water quality cannot be cleansed or treated please consider installing a system separation plate heat exchanger to ensure absolute separation of the system water and the boiler water. Please refer to our website for further details on our matched brazed and gasketed plate heat exchanger range. 19 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 10.0 Boiler Controller Label 1 2 3 4 5 6 7 8 9 10 Symbol Description Heating Mode Select Button Show Information Manual (Hand) Emission Test Mode Accept Setting (Select) Navigation and Setting (Rotary) Escape Button Reset Button Service Connector for BSB data BUS Hot Water Mode Select Description Automatic Mode Continuous Operation (Day Mode) Reduced Operation (Night Mode) Frost Protection Mode Ongoing Process - Wait Battery Requires Changing Holiday Mode Active Heating Circuit 1/2/3 Active Maintenance / Special Operation Error Alarm Activated Burner in Operation (Burner Stage) INFO Level Activated PROG Level Activated ECO Function Activated (Heating Temporarily Switched Off) 20 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 10.1 Accessing Controller Parameters To access the controller parameter menu, from the standard home screen, press the OK button once then press and hold the INFO button for 5 seconds until the lower section of the screen changes. Use the wheel to highlight the ENGINEER setting. Press the OK button. Access to all setting below is now possible using the rotary button. Notation Description Rotary Button Used to move through menus/lists of options. Parameter # OK Button Escape Button Used to escape back one level through menus Description Time And Date 1 Hours/Minutes 2 Day/Month 3 Year Operator Section 20 Language 22 26 27 Info Operation Programming Lock 28 Direct Adjustment 29 Units 44 Operation HC2 46 Operation HC3/P 70 Software Time Program Heating Circuit 1 500 Used to confirm a selection Day/Days st 501 1 Phase On st 502 1 Phase Off nd 503 2 Phase On nd 504 2 Phase Off rd 505 3 Phase On rd 506 3 Phase Off 516 Default Values Time Program Heating Circuit 2 520 Day/Days 521 1 Phase On st Range 00:00-24:00 01.01-31.12 2004-2099 English / Deutsch / Französisch / Italienisch /Niederländisch / Spanisch / Portugiesisch / Dänisch / Schwedisch / Finnisch Temporarily, Permanent On, Off On, Off Storage with Confirmation, Automatic Storage °C, bar / Fahrenheit, PSI Jointly with HC1, Independent Jointly with HC1, Independently ---Mo-Su, Mo-Fr,SaSu,Mo,Tu,We,Th,Fr,Sa,Su 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 No, Yes Mo-Su, Mo-Fr,SaSu,Mo,Tu,We,Th,Fr,Sa,Su 00:00-24:00 Default ---------- Advised Change Button Unit hh:mm dd:mm yyyy English Temporarily Off Off Storage With Confirmation °C, bar Jointly with HC1 Jointly with HC1 06.7 Mo-Su 06:00 22:00 24:00 24:00 24:00 24:00 No hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm Mo-Su 06:00 hh:mm 21 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd st 522 1 Phase Off nd 523 2 Phase On nd 524 2 Phase Off rd 525 3 Phase On rd 526 3 Phase Off 536 Default Values Time Program3/ Heating Circuit 3 540 Day/Days st 541 1 Phase On st 542 1 Phase Off nd 543 2 Phase On nd 544 2 Phase Off rd 545 3 Phase On rd 546 3 Phase Off 556 Default Values Time Program 4/DHW 560 Day/Days st 561 1 Phase On st 562 1 Phase Off nd 563 2 Phase On nd 564 2 Phase Off rd 565 3 Phase On rd 566 3 Phase Off 576 Default Values Time Program 5 600 Day/Days st 601 1 Phase On st 602 1 Phase Off nd 603 2 Phase On nd 604 2 Phase Off rd 605 3 Phase On rd 606 3 Phase Off 616 Default Values Holiday Heating Circuit 1 641 Preselection 642 Start 643 End 648 Operating Level Holiday Heating Circuit 2 651 Preselection 652 Start 653 End 658 Operating Level Holiday Heating Circuit 3 661 Preselection 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 No, Yes Mo-Su, Mo-Fr,SaSu,Mo,Tu,We,Th,Fr,Sa,Su 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 No, Yes Mo-Su, Mo-Fr,SaSu,Mo,Tu,We,Th,Fr,Sa,Su 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 No, Yes Mo-Su, Mo-Fr,SaSu,Mo,Tu,We,Th,Fr,Sa,Su 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 00:00-24:00 No, Yes Period1, Period2, Period3, Period4, Period5, Period6, Period7, Period8 01.01-31.12 01.01-31.12 Frost, Reduced Period1, Period2, Period3, Period4, Period5, Period6, Period7, Period8 01.01-31.12 01.01-31.12 Frost, Reduced Period1, Period2, Period3, Period4, Period5, Period6, Period7, Period8 22:00 24:00 24:00 24:00 24:00 No hh:mm hh:mm hh:mm hh:mm hh:mm Mo-Su 06:00 22:00 24:00 24:00 24:00 24:00 No hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm Mo-Su 06:00 22:00 24:00 24:00 24:00 24:00 No hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm Mo-Su 06:00 22:00 24:00 24:00 24:00 24:00 No hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm Period1 --.---.-Frost Protection dd:mm dd:mm Period1 --.---.-Frost Protection dd:mm dd:mm Period1 22 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 662 Start 663 End 668 Operating Level Heating Circuit 1 700 Operating Mode HC1 710 712 714 716 720 721 726 730 732 733 740 741 742 744 746 750 760 761 770 Comfort Setpoint Reduced Setpoint Frost Protection Setpoint Comfort Setpoint Max Heating Curve Slope Heating Curve Displacement Heating Curve Adaption Summer/Winter heating limit 24-Hour heating limit Ext’n 24-Hour heating limit Flow temp setpoint min Flow temp setpoint max Flow temp setpoint room stat Swi-on ratio room stat Delay Heat request Room Influence Room temp limitation Heating limit room controller Boost heating 780 Quick setback 790 791 794 800 801 809 812 820 830 832 833 834 835 836 Optimum start control max Optimum stop control max Heat up gradient Reduced setp. increase start Reduced setp. increase end Continuous pump operation Frost protection flow temp. Overtempprot. pump circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator running time Mixing valve Xp Mixing valve Tn 850 Floor curing Function 851 855 856 861 870 872 Floor curing setp. manually Floor curing setp. current Floor curing day current Excess heat draw With buffer With prim contr./system pump 01.01-31.12 01.01-31.12 Frost, Reduced Protection, Automatic, Reduced, Comfort P712-P716 P714-P710 4-P712 P710 - 35 0.10 - 4.00 -4.5 - 4.5 Off - On ---/8 – 30 ---/-10 – 10 Yes – No 8 – P741 P740 – 95 ---/P740 - ---/P741 ---/1 – 99 0 – 600 ---/1 – 100 ---/0.5 – 4 ---/0 – 100 ---/0 – 20 Off, Down to Reduced Setpoint, Down to Frost Protection Setpoint 0 - 360 0 – 360 0 – 600 ---/P801 – 10 -30 – P800 No – Yes Off – On Off – On 0 – 50 Two Position – Three Position 0 – 20 30 – 873 1 – 100 10 – 873 Off, Function heating, Curing heating, Function + Curing heating, Curing + functional heating, Manually 0 – 95 0 – 95 0 – 32 Off, Heating mode, Always No, Yes No, Yes --.---.-Frost Protection dd:mm dd:mm Automatic 20.0 16.0 10.0 35.0 1.50 0.0 Off 18 -3 Yes 8 85 ----0 --1 --5 3.20 °C °C °C °C °C °C °C °C °C °C % S % °C % °C To Reduced Setpoint - 0 0 60 ---15 No On On 5 Three-position 2 120 32 120 Min. Min. Min/k °C °C Off - 25 °C °C Always Yes Yes °C °C S °C S - 23 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 880 Pump speed reduction 881 882 883 885 886 888 889 890 898 Starting speed Pump speed min Pump speed max Pump speed min OEM Pump speed max OEM Curve readj. at 50% speed Filter time const. speed ctrl. Flow setp. readj. speed ctrl. Operating level changeover 900 Optgmode changeover According HC operating level, According characteristic curve, Temp. differential nominal 0 – 100 P885 – P883 P882 – P886 0 – P882 P883 – 100 0 – 100 0 – 20 No, Yes Frost protection, Reduced, Comfort None, Protection, Reduced, Comfort, Automatic According characteristic curve 100 50 100 50 100 33 5 No Reduced % % % % % % Min. Protection Min. Automatic - 20.0 16.0 10.0 35.0 1.50 0.0 Off 18 -3 Yes 8 85 ----0 --1 --5 °C °C °C °C °C °C °C Heating Circuit 2 1000 Operating Mode HC2 101 1012 1014 1016 1020 1021 1026 1030 1032 1033 1040 1041 1042 1044 1046 1050 1060 1061 1070 Comfort Setpoint Reduced Setpoint Frost Protection Setpoint Comfort Setpoint Max Heating Curve Slope Heating Curve Displacement Heating Curve Adaption Summer/Winter heating limit 24-Hour heating limit Ext’n 24-Hour heating limit Flow temp setpoint min Flow temp setpoint max Flow temp setpoint room stat Swi-on ratio room stat Delay Heat request Room Influence Room temp limitation Heating limit room controller Boost heating 1080 Quick setback 1090 1091 1094 1100 1101 1109 1112 1120 1130 1132 1133 1134 1135 Optimum start control max Optimum stop control max Heat up gradient Reduced setp. increase start Reduced setp. increase end Continuous pump operation Frost protection flow temp. Overtempprot. pump circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator running time Mixing valve Xp Protection, Automatic, Reduced, Comfort P1012 – P1016 P1014 – P1010 4 – P1012 P1010 - 35 0.10 - 4.00 -4.5 - 4.5 Off - On ---/8 – 30 ---/-10 – 10 Yes – No 8 – P1041 P1040 – 95 ---/P1040 - ---/P1041 ---/1 – 99 0 – 600 ---/1 – 100 ---/0.5 – 4 ---/0 – 100 ---/0 – 20 Off, Down to Reduced Setpoint, Down to Frost Protection Setpoint 0 – 360 0 – 360 0 – 600 ---/P1101 – 10 -30 – P1100 No – Yes Off – On Off – On 0 – 50 Two Position – Three Position 0 – 20 30 – 873 1 – 100 3.20 °C °C °C % S % °C % °C To Reduced Setpoint - 0 0 60 ---15 No On On 5 Three-position 2 120 32 Min. Min. Min/k °C °C °C °C S °C 24 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 1136 Mixing valve Tn 1150 Floor curing Function 1151 1155 1156 1161 1170 1172 Floor curing setp. manually Floor curing setp. current Floor curing day current Excess heat draw With buffer With prim contr./system pump 1180 Pump speed reduction 1181 1182 1183 1185 1186 1188 1189 1190 1198 Starting speed Pump speed min Pump speed max Pump speed min OEM Pump speed max OEM Curve readj. at 50% speed Filter time const. speed ctrl. Flow setp. readj. speed ctrl. Operating level changeover 1200 Optgmode changeover 10 – 873 Off, Function heating, Curing heating, Function + Curing heating, Curing + functional heating, Manually 0 – 95 0 – 95 0 – 32 Off, Heating mode, Always No, Yes No, Yes According HC operating level, According characteristic curve, Temp. differential nominal 0 – 100 P1185 – P1183 P1182 – P1186 0 – P1182 P1183 – 100 0 – 100 0 – 20 No, Yes Frost protection, Reduced, Comfort None, Protection, Reduced, Comfort, Automatic 120 S Off - 25 °C °C °C Always Yes Yes - According characteristic curve 100 50 100 50 100 33 5 No Reduced % % % % % % Min. Protection Heating Circuit 3 1300 Operating Mode HC3 1310 1312 1314 1316 1320 1321 1326 1330 1332 1333 1340 1341 1342 1344 1346 1350 1360 1361 1370 Comfort Setpoint Reduced Setpoint Frost Protection Setpoint Comfort Setpoint Max Heating Curve Slope Heating Curve Displacement Heating Curve Adaption Summer/Winter heating limit 24-Hour heating limit Ext’n 24-Hour heating limit Flow temp setpoint min Flow temp setpoint max Flow temp setpoint room stat Swi-on ratio room stat Delay Heat request Room Influence Room temp limitation Heating limit room controller Boost heating 1380 Quick setback 1390 1391 1394 Optimum start control max Optimum stop control max Heat up gradient Protection, Automatic, Reduced, Comfort P1312 – P1316 P1314 – P1310 4 – P1312 P1310 - 35 0.10 - 4.00 -4.5 - 4.5 Off - On ---/8 – 30 ---/-10 – 10 Yes – No 8 – P1341 P1340 – 95 ---/P1340 - ---/P1341 ---/1 – 99 0 – 600 ---/1 – 100 ---/0.5 – 4 ---/0 – 100 ---/0 – 20 Off, Down to Reduced Setpoint, Down to Frost Protection Setpoint 0 – 360 0 – 360 0 – 600 Automatic - 20.0 16.0 10.0 35.0 1.50 0.0 Off 18 -3 Yes 8 85 ----0 --1 --5 °C °C °C °C °C °C °C 3.20 °C °C °C % S % °C % °C To Reduced Setpoint - 0 0 60 Min. Min. Min/k 25 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 1400 4101 1409 1412 1420 1430 1432 1433 1434 1435 1436 Reduced setp. increase start Reduced setp. increase end Continuous pump operation Frost protection flow temp. Overtempprot. pump circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator running time Mixing valve Xp Mixing valve Tn 1450 Floor curing Function 1451 1455 1456 1461 1470 1472 Floor curing setp. manually Floor curing setp. current Floor curing day current Excess heat draw With buffer With prim contr./system pump 1480 Pump speed reduction 1481 1482 1483 1485 1486 1488 1489 1490 1498 Starting speed Pump speed min Pump speed max Pump speed min OEM Pump speed max OEM Curve readj. at 50% speed Filter time const. speed ctrl. Flow setp. readj. speed ctrl. Operating level changeover 1500 Optgmode changeover DHW 1600 1610 1612 1614 DHW Operating Mode Nominal setpoint Reduced setpoint Nominal setpoint max 1620 Release 1630 Charging priority 1640 1641 Legionella function Legionella func. periodically 1642 Legionella func. weekday 1644 1645 1646 1647 Legionella funct. Time Legionella funct. Setpoint Legionella funct. Duration Legionella funct. circ pump ---/P1401 – 10 -30 – P1400 No – Yes Off – On Off – On 0 – 50 Two Position – Three Position 0 – 20 30 – 873 1 – 100 10 – 873 Off, Function heating, Curing heating, Function + Curing heating, Curing + functional heating, Manually 0 – 95 0 – 95 0 – 32 Off, Heating mode, Always No, Yes No, Yes According HC operating level, According characteristic curve, Temp. differential nominal 0 – 100 P1485 – P1483 P1482 – P1486 0 – P1482 P1483 – 100 0 – 100 0 – 20 No, Yes Frost protection, Reduced, Comfort None, Protection, Reduced, Comfort, Automatic ---15 No On On 5 Three-position 2 120 32 120 °C °C Off - 25 °C °C Off, On, Eco P1612 – P1614 8 – P1610 P1610 – 80 24h/day, Heating program with forward shift, time switch program 4 Absolute, shifting, none, shifting, absolute Off, periodically, fixed weekday 1–7 Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday ----/00:00 – 23.50 55 – 95 ---/10 – 360 Off – On On 55 40 65 Heating programs with shift °C °C S °C S Always Yes Yes - According characteristic curve 100 50 100 50 100 33 5 Yes Reduced % % % % % % Min. Protection 60 °C °C °C - Shifting, - Fixed weekday 3 Days Monday ---65 30 On hh:mm °C Min. 26 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 1660 Circulating pump release 1661 Circulating pump cycling 1663 Circulating setpoint 1680 Optg. Mode changeover Consumer Circuit 1 1859 Flow temp. setp. cons. request 1874 DHW charging priority 1875 Excess heat draw 1878 With Buffer 1880 With prim. Contr./system pump Consumer Circuit 2 1909 Flow temp. setp. cons. request 1924 DHW charging priority 1925 Excess heat draw 1928 With Buffer 1930 With prim. Contr./system pump Swimming pool Circuit 1959 Flow temp. setp. cons. request 1947 DHW charging priority 1945 Excess heat draw 1948 With Buffer 1980 With prim. Contr./system pump Swimming pool 2055 Setpoint solar heating 2056 Setpoint source heating 2065 Charging priority solar 2070 Swimming pool temp max 2080 With solar integration Primary contr./system pump 2110 Flow temp. setpoint min 2111 Flow temp. setpoint max 2121 Syst. Pump on heat gen. lock 2130 Mixing valve boost 2132 Actuator type 2133 Switching differential 2-pos. 2134 Actuator running time 2135 Mixing valve Xp 2136 Mixing valve Tn 2150 Primary contr./system pump Boiler 2203 2208 2210 2211 2212 2213 2214 2217 Release below outside temp. Full charging buffer Setpoint min Setpoint min OEM Setpoint max Setpoint max OEM Setpoint manual control Setpoint frost protection Time switch program 3, DHW release, Time switch program 4, time switch program 5 Off, On 8 – 80 None, Off, On DHW release - On 45 Off °C 8 – 120 Yes, No Off, On No, Yes No, Yes 70 Yes On Yes Yes °C 8 – 120 Yes, No Off, On No, Yes No, Yes 70 Yes On Yes Yes °C 8 – 120 Yes, No Off, On No, Yes No, Yes 70 Yes On Yes Yes °C 8 – 80 8 – 80 Priority 1, Priority 2, Priority 3 P2055 – 95 No, Yes 26 22 Priority 3 32 Yes °C °C 8 – P2111 P2110 – 95 Off, On 0 – 50 Two position, Three position 0 – 20 30 – 873 1 – 100 10 – 873 Up stream of buffer, Downstream from buffer 8 80 Off 10 Three position 2 120 32 120 Downstream from buffer °C °C ---/-50 – 50 Off, On P2211 – P2214 8 – P2210 P2214 – P2213 P2212 – 120 P2210 – P2212 ---/-20 – 20 0 Off 10 40 90 85 70 8 °C °C °C °C S °C S - °C °C °C °C °C °C 27 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 1 – 200 4 – 873 0 – 30 1 – 200 4 – 873 0 – 30 0 – 20 0 – 20 0 – 80 0 – 240 0 – 20 Off, On Off, On 0 – 240 P2270 – 95 8 – P2270 Off, On Off, On Off, On Heating mode only, Heating and DHW mode Off, On ----/0 – 80 ----/0 – 80 None, Demand, Boiler setpoint, Temp differential Nominal, Burner output 52 80 0 34 80 8 0 3 15 5 1 Off Off 0 8 8 On Off Off Starting speed ----/0 – 100 100 2322 Pump speed min P2327 – P2323 80 2323 Pump speed max P2322 – P2328 100 2324 2325 2326 Speed Xp Speed Tn Speed Tv 1 – 200 10 – 873 0 – 30 32 120 10 2327 Pump speed min OEM 0 – P2322 40 2328 Pump speed max OEM P2323 – 100 100 2329 2330 2331 2334 2335 2441 2442 2443 2444 2445 2446 Pump setpoint reduction Output nominal Output basic stage Output at pump speed min Output at pump speed max Fan speed heating max Fan speed full charging max Fan sp. start value inst. DHW Fan speed DHW max Fan shutdown heating mode Fan shutdown delay 10 25 5 0 100 6900 6900 0 --Off 3 2450 Controller delay 2452 Controller delay speed 0 – 20 0 – 2000 0 – 2000 0 – 100 0 – 100 P9525 – P9530 P9525 – P9530 0 – P9530 ----/P9525 – P9530 Off, On 0 -0200 Off, Heating mode only, DHW mode only, Heating and DHW mode P9525 – P9530 2233 2234 2235 2236 2237 2238 2241 2243 2245 2250 2253 2260 2263 2264 2270 2271 2272 2300 2301 P-band Xp HCs Int action time Tn HCs Der action time Tv HCs P-band Xp DHW Int action time Tn DHW Der action time Tv DHW Burner running time min Burner off time min SD burner off time Pump overrun time Pump over. time after DHW Prot. boiler startup consumers Setpoint min boiler Switch Off Prot. boiler startup anticipation Return setpoint min Return setpoint min OEM Return influence consumers Frost protection boiler plant Boiler pump on heat gen. lock 2305 Impact heat generation lock 2310 2316 2317 Limit thermostat function Temp. differential max Temp. differential nominal 2320 Pump modulation 2321 °C S S °C S S Min. Min. °C Min. Min. S °C °C Heating mode only On ---16 °C °C Temp Differential Nominal °C S S °C kW kW % % -1 Min. -1 Min. -1 Min. -1 Min. S Off 2400 -1 Min. 28 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 2453 Controller delay duration 2454 Switching diff on HCs 2455 Switching diff off min HCs 2456 Switching diff off max HCs 2457 Settling time HCs 2460 Switching diff on DHW 2461 Switching off min DHW 2462 Switching off max DHW 2463 Settling time DHW 2464 Dyn SD on setpoint 2465 Min setpoint change dyn SD 2466 Dyn SD with HC/DHW change 2467 Dyn SD when burner on 2470 Delay heat req special op. 2473 Flue gas temp output red 2474 Flue gas temp switch-off limit 2476 Flue gas superv. Shutdown 2477 Flue gas superv. st. prev. time 2478 Flue gas temp output limit 2479 Fl’gsuperv. time con rel mod 2480 Static press superv. sh’down 2490 Dyn press superv. sh’down 2491 Dynsuperv. press diff min 2492 Dynsuperv. press diff max 2494 Dynsuperv. press increase 2495 Dyn press superv time 2630 Auto deaeration procedure Cascade 0 – 255 0 – 20 0 – 20 0 – 20 0 – 240 0 – 20 0 – 20 0 – 20 0 – 240 Off, On 0 – 80 Off, On Off, On 0 – 600 0 – 200 0 – 200 Start pre-ventilation, Lockout position 10 – 218 0 – 200 0 – 50 Start preventilation, Lockout position Start preventilation, Lockout position 0–5 0–5 No, Yes 0 – 10 Off, On 10 4 4 4 10 0 5 5 10 Off 20 Off On 0 95 100 Lockout position 10 80 0 Lockout position Lockout position 0 5 Yes 0.2 Off 3510 Lead Strategy 3511 3512 Output ban min Output ban max [Late on, Early off], [Late on, late off], [Early on, late off] 0 – P3512 P3511 – 100 3530 Release integral source seq. 0 – 500 50 3531 Reset integral source seq. 0 – 500 20 3532 3533 3534 3540 Restart lock Switch on delay Forced time basic stage Auto source seq. ch’over 300 5 60 500 3541 Auto source seq. exclusion 3544 Leading source 3560 3561 3562 Return setpoint min Return setpoint min OEM Return influence consumers 0 – 1800 0 – 120 0 – 1200 ----/10 – 990 None, First producer, last producer, first and last producer Producer 1, Producer 2, Producer 3, Producer 4, Producer 5, Producer 6, Producer 7, Producer 8, Producer 9, Producer 10, Producer 11, Producer 12, Producer 13, Producer 14, Producer 15, Producer 16 P3561 – 95 8 – P3560 Off, On S °C °C °C Min. °C °C °C Min. °C S °C °C Min. °C S Bar Bar S Late on, Late off 40 90 % % °C*min . °C*min . S Min. S H None Producer 1 8 8 On °C °C 29 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 3590 Temp differential min Buffer Storage Tank 4720 Auto generation lock 4721 Auto heat gen lock SD 4722 Temp diff buffer/HC 4724 Min st tank temp heat mode 4750 Charging temp max 4751 Storage tank temp max 4755 Re-cooling temp 4756 Re-cooling DHW/HCs 4757 Re-cooling collector 4783 With solar integration 4790 Temp diff on return div 4791 Temp diff off return div ----/0 - 20 --- °C With B4 8 -5 ---80 90 60 Off Off None 10 5 °C °C °C °C °C °C 4795 Compar temp return div 4796 Optg. action return diversion 4800 4810 4811 Partial charging setpoint Full charging Full charging temp min None, With B4, With B4 and B42/B41 0 – 20 -20 – 20 ----/8 – 95 8 – P4751 P4750 – 95 8 – 95 Off, On Off, Summer, Always None, Yes P4791 – 40 0 – P4790 Buffer sensor B4, Buffer sensor B41, Buffer sensor B41 Return temp setback, Return temp rising ----/8 – 95 Off, Heating mode, Always 8 – 80 4813 Full charging sensor With B4, With B42/B41 DHW Storage Tank 5010 DHW charging 5011 DHW forward shift charge 5012 DHW forced charging 5020 Flow setpoint boost 5021 Transfer boost 5022 Type of charging 5024 5030 5040 5050 5051 5055 5060 Switching diff Charging time limitation Discharging protection Charging temp max Storage tank temp max Storage tank return cooling Storage tank return cooling producer/HC Storage tank return cooling Collector El imm heater optg mode 5061 El immersion heater release 5062 5070 5071 5085 5090 5092 Ei immersion heater control Automatic push Charging prio time push Excess heat draw With Buffer With prim contr/system pump 5056 5057 °C °C With B42 Return temp rising ---Off 8 With B42/B41With B42/B41 °C °C Once/day, Several times/day ---/00:30 – 04:00 Off, On 0 – 30 0 - 30 Recharging, full charging, full charging legio, full charging first time of day, full charging first time Legio 0 – 20 ----/10 – 600 Off, Always, Automatically 8 – P5051 P5050 – 95 8 – 95 Several times/day ---On 16 8 5 150 Automatically 80 90 80 °C Min. Off – On Off - Off, summer, always Off - Backup mode, summer only, always 24h/day, DHW release, time switch program 4 External thermostat, DHW sensor OFF, ON 0 – 120 Off – On No - Yes No, Yes Backup mode - DHW release - DHW sensor On 0 On No No - H °C °C Full charging °C °C °C Min. - 30 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 5093 With solar integration 5101 Pump speed min 5102 Pump speed max 5103 Speed Xp 5104 Speed Tn 5015 Speed Tv 5016 Pump speed min OEM 5107 Pump speed max OEM 5108 Starting speed charg pump 5109 St. speed intermcirc pump 5130 Transfer strategy 5131 Comparison temp transfer 5139 Intermcirc boost recharging 5140 Intermediate circuit boost 5141 Excess intern circuit temp max 5142 Flow setp. compensation delay 5143 Flow setp. compensation Xp 5144 Flow setp. compensation Tn 5145 Flow setp. compensation Tv 5146 Full charging with B36 5148 Min start temp diff Q33 5151 Excess intermcir temp delay Configuration 5700 Presetting 5710 Heating circuit 1 5711 Cooling circuit 1 5715 Heating circuit 2 5721 Heating circuit 3 5730 DHW sensor 5731 DHW controlling element 5732 5733 5734 5736 Pump off change div valve Delay pump off Basic position DHW div valve DHW separate circuit 5737 Optg action DHW div valve 5738 5774 5775 5840 Mid-position DHW div Valve Ctrl boiler pump/DHW valve Boiler pump with DHW Solar controlling element 5841 External solar charger 5870 Combi storage tank No, Yes P5106 – P5102 P5101 – P5107 1 – 100 10 – 873 0 – 60 0 – P5101 P5102 – 100 ----/0 – 100 ----/0 – 100 Off, Always, DHW release DHW sensor B3, DHW sensor B31 0 – 10 0 – 10 2 – 20 ----/0 – 60 1 – 100 10 – 873 0 – 60 No, Yes ----/-20 – 20 0 - 255 Yes 40 100 32 120 0 40 100 100 100 Always DHW sensor B3 2 2 2 30 24 120 0 Yes 0 30 Changed, Unchanged Off, On Off, 4-pipe system cooling Off, On Off, On DHE sensor B3, Thermostat, DHW outlet sensor B38 No charging request, charging pump, diverting valve 0 – 10s 0 – 10s Last request, Heating circuit, DHW Off, On Position on DHW, Position on heating circuit Off, On All requests, Request HC1/DHW only On, Off Charging pump, Diverting valve Jointly, DHW storage tank, Buffer storage tank No, Yes Changed On Off Off Off - DHW Sensor B3 - Diverting Valve - 0 0 DHW Off S S - Position on DHW - Off All requests On Charging Pump - Jointly - No - % % °C S S % % % % °C °C °C S °C S S Min. °C S - 31 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 5890 Relay output QX1 5891 5892 Relay output QX2 Relay output QX3 5894 Relay output QX4 5930 Sensor input BX1 5931 5932 Sensor input BX2 Sensor input BX3 None, Circulating pump Q4, El imm heater DHWK6, Collector pump Q5, Cons circuit pump VK1 Q15, Boiler pump Q1, Bypass pump Q12, Alarm nd output K10, 2 pump speed HC1 nd nd Q21, 2 pump speed HC2 Q22, 2 pump speed HC3 Q23, Heat circuit pump HC3 Q20, Cons circuit pump VK2 Q18, System pump Q14, Heat gen shutoff valve Y4, solid fuel boiler pump Q10, Time program 5 K13, Buffer return valve Y15, Solar pump extexch K9, Solar ctrl elem buffer K8, Solar ctrl elemswi pool K18, Swimming pool pump Q19, Cascade pump Q25, St tank transfer Q11, DHW mixing pump Q35, DHW intermcirc pump Q33, Heat request K27, Refrigeration request K28, Heat circuit pump HC1 Q2, Heat circuit pump HC2 Q6, DHW ctrl elem Q3, Instant heater ctrl elem Q34, Water nd filling K34, 2 boiler pump speed Q27, Status output K35, Status information K36, Flue gas damper K37, Fan shutdown K38, dT controller 1 K21, dT controller 2 K22 See Para 5890 See Para 5890 None, Heat gen shutoff valve Y4, Buffer return valve Y15, Solar ctrl elem buffer K8, Solar ctrl elemswi pool K18, DHW ctrl elem Q3, Instant heat ctrl elem Q34 None, DHW sensor B32, Collector sensor B6, DHW circulation sensor B39, Buffer sensor B4, Buffer sensor B41, Flue gas temp sensor B8, Segment flow sensor B10, Solid fuel boiler sensor B22, DHW charging sensor B36, Buffer sensor B42, Segment return sensor B73, Cascade return flow sensor B70, Pool sensor B13, Solar flow sensor B63, Solar return sensor B64, Primary exch sensor B26 See Para 5930 See Para 5930 Boiler Pump Q1 - None DHW ctrl elem Q3 - None - Flue gas temp sensor B8 - None None - 32 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 5950 Function of Input H1 5951 5953 5954 5955 5956 Contact Type H1 Voltage value 1 H1 Function value 1 H1 Voltage value 2 H1 Function value 2 H1 5960 Function input H3 5961 5963 5964 Contact type H3 Voltage value 1 H3 Function value 1 H3 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal Open 0 – 10 -1000 – 5000 0 – 10 -1000 – 5000 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open 0 – 10 -1000 – 5000 Boiler pressure switch - Normal Open 0 0 0 0 Volts Volts - None - Normal open 0 0 Volts 33 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 5965 5966 Voltage value 2 H3 Function value 2 H3 5970 Function input H4 5971 5973 5974 5975 5976 Contact type H4 Frequency value 1 H4 Function value 1 H4 Frequency value 2 H4 Function value 2 H4 5977 Function input H5 5978 Contact type H5 0 – 10 -1000 – 5000 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open 0 – 1000 -1000 - 5000 0 – 1000 -1000 - 5000 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open 0 0 Volts - None - Normal open 0 0 0 0 - Room Thermostat HC1 - Normal open 34 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6008 Function input H6 6009 Contact type H6 6011 Function input H7 6012 Contact type H7 6020 Function extension module 1 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open None, Multifunctional, Heating circuit 1, Heating circuit 2, Heating circuit 3, Return temp controller, Solar DHW, Primary contr/system pump - Normal open - Boiler flow switch - Normal open - Heating circuit 2 - 35 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6021 Function extension module 2 6022 Function extension module 3 6024 6026 6028 Funct. Input EX21 module 1 Funct. Input EX21 module 2 Funct. Input EX21 module 3 6030 Relay output QX21 module 1 6031 6032 6033 6034 6035 6036 6037 6038 Relay output QX22 module 1 Relay output QX23 module 1 Relay output QX21 module 2 Relay output QX22 module 2 Relay output QX23 module 2 Relay output QX21 module 3 Relay output QX22 module 3 Relay output QX23 module 3 None, Multifunctional, Heating circuit 1, Heating circuit 2, Heating circuit 3, Return temp controller, Solar DHW, Primary contr/system pump None, Multifunctional, Heating circuit 1, Heating circuit 2, Heating circuit 3, Return temp controller, Solar DHW, Primary contr/system pump None, Limit thermostat HC None, Limit thermostat HC None, Limit thermostat HC None, Circulating pump Q4, El imm heater DHW K6, Collector pump Q5, Cons circuit pump VK1 Q15, Boiler pump Q1, Bypass pump Q12, Alarm nd output K10, 2 pump speed HC1 nd nd Q21, 2 pump speed HC2 Q22, 2 pump speed HC3 Q23, Heat circuit pump HC3 Q20, Cons circuit pump VK2 Q18, System pump Q14, Heat gen shutoff valve Y4, Solid fuel boiler pump Q10, Time program 5 K13, Buffer return valve Y15, Solar pump extexch K9, Solar ctrl elem buffer K8, Solar ctrl elemswi pool K18, Swimming pool pump Q19, Cascade pump Q25, St tank transfer pump Q11, DHW mixing pump Q35, DHW intermcirc pump Q33, Heat request K27, Refrigeration request K28, Heat circuit pump HC1 Q2, Heat circuit pump HC2 Q6, DHW ctrl elem Q3, Instant heater ctrl elem Q34, Water nd filling K34, 2 boiler pump speed Q27, Status output K35, Status information K36, Fan shutdown K38, dT controller 1 K21, dT controller 2 K22 See Para 6030 See Para 6030 See Para 6030 See Para 6030 See Para 6030 See Para 6030 See Para 6030 See Para 6030 None - None - None None None - None None None None None None None None None 36 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6040 Sensor input BX21 module 1 6041 6042 6043 6044 6045 Sensor input BX22 module 1 Sensor input BX21 module 2 Sensor input BX22 module 2 Sensor input BX21 module 3 Sensor input BX22 module 3 6046 Function input H2 module 1 6047 6049 6050 6051 6052 Contact type H2 module 1 Voltage value 1 H2 module 1 Function value 1 H2 module 1 Voltage value 2 H2 module 1 Function value 2 H2 module 1 None, DHW sensor B31, Collectoe sensor B6, DHW circulation sensor B39, Buffer sensor B4, Buffer sensor B41, Flue gas temp sensor B8, Common flow sensor B10, Solid fuel boiler sensor B22, DHW charging sensor B36, Buffer sensor B42, Common flow sensor B37, buffer return sensor B70, Swimming pool sensor B13, Solar flow sensor B63, Solar return sensor B64, Primary exch sensor B26 See Para 6040 See Para 6040 See Para 6040 See Para 6040 See Para 6040 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open 0 - 10 -1000 - 5000 0 - 10 -1000 - 5000 None None None None None None None Normal open 0 0 0 0 Volts Volts 37 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6054 Function input H2 module 2 6055 6057 6058 6059 6060 Contact type H2 module 2 Voltage value 1 H2 module 2 Function value 1 H2 module 2 Voltage value 2 H2 module 2 Function value 2 H2 module 2 6062 Function input H2 module 3 6063 6065 6066 Contact type H2 module 3 Voltage value 1 H2 module 3 Function value 1 H2 module 3 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open 0 - 10 -1000 - 5000 0 - 10 -1000 - 5000 None, Optg mode change HCs + DHW, Optgmode changeover DHW, Optgmode changeover HCs, Opt mode changeover HC1, Opt changeover HC2, Opt changeover HC3, Heat generation lock, Error/alarm message, Consumer request VK1, consumer request VK2, release swi pool source heat, Excess heat discharge, release swi pool solar, Operating level DHW, Operating level HC1, Operating level HC2, Operating level HC3, Room thermostat HC1, Room thermostat HC2, Room thermostat HC3, DHW flow switch, DHW thermostat, Pulse count, Checkb sign flue gas damper, Start prevention, Boiler flow switch, Boiler pressure switch, Consumer request VK1 10V, Consumer request VK2 10V, Pressure measurement 10V, Output request 10V Normal closed, Normal open 0 - 10 -1000 - 5000 None Normal open 0 0 0 0 Volts Volts None Normal open 0 0 Volts 38 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6067 6068 6072 Voltage value 2 H2 module 3 Function value 2 H2 module 3 Signal output UX 6078 Function output UX2 6085 Function output P1 6089 Function output UX3 6097 Sensor type collector 6098 Readjust collector sensor 6100 Readjust outside sensor 6101 Sensor type flue gas temp 6102 Readjust flue gas sensor 6110 Time constant building 6116 Time constant setp. compens. 6117 Central setp. compensation 6118 Setpoint drop delay 6120 Frost protection plant 6127 Pump/valve kick duration 6140 Water pressure max 6141 Water pressure min 6142 Water pressure critical min 6143 Water press. switching diff. 6150 Water pressure 2 max 6151 Water pressure 2 min 6152 Water pressure 2 critical min 6153 water press. 2 switching diff. 6180 Water pressure 3 max 6181 Water pressure 3 min 6182 Water pressure 3 critical min 6183 Water press. 3 switching diff. 6200 Save sensors 6204 Save parameters 6205 Reset to default parameters 6212 Check no. heat source 1 6213 Check no. heat source 2 6215 Check no. storage tank 6217 Check no. heating circuits 6220 Software version LPB System 6600 Device address 6601 Segment address 6604 Bus power supply function 6605 Bus power supply state 6610 Display system message 0 - 10 -1000 - 5000 0...10V, PWM None, Boiler pump Q1, DHW pump Q3, DHW intermcir pump Q33, Heat circuit pump HC1 Q2, Heat circuit pump HC2 Q6, Heat circuit pump HC3 Q20, Collector pump Q5, Solar pump extexch K9, Solar pump buffer K8, Solar pump swi pool K18, Instant heater pump Q34, Solid fuel boiler pump Q10, Bypass pump Q12 See Para 6078 See Para 6078 NTC, Pt 1000 -20 - 20 -3.0 - 3.0 NTC, Pt 1000, NTC 20k -20 - 20 0 - 50 0 - 14 ----/1 - 100 ----/1 - 200 Off, /on 0 - 51 ----/0.0 - 10.0 ----/0.0 - 10.0 ----/0.0 - 10.0 0.0 - 10.0 ----/0.0 - 10.0 ----/0.0 - 10.0 ----/0.0 - 10.0 0.0 - 10.0 ----/0.0 - 10.0 ----/0.0 - 10.0 ----/0.0 - 10.0 0.0 - 10.0 No, Yes No, Yes No, Yes 0 - 199999 0 - 199999 0 - 199999 0 - 199999 0 - 99 0 0 PWM 0 - 16 0 - 14 Off, Automatic Off, On No, Yes 1 0 Automatic On Yes Volts None Boiler pump Q1 None NTC 0 0 NTC 0 15 0 5 ---Off 30 3 0.8 0.5 0.3 3 0.8 0.5 0.3 3 0.8 0.5 0.3 No No No 12 0 0 101 03.5 °C °C °C H Min. °C °C S Bar Bar Bar Bar Bar Bar Bar Bar Bar Bar Bar Bar 39 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6611 6612 6620 6621 6623 6624 Sys message alarm Alarm delay Action changeover function Summer changeover Optgmode changeover Manual source lock 6625 DHW assignment 6630 6631 6632 Cascade master Ext source in Eco mode Note OT limit ext source 6640 Clock mode 6650 Fault 6700 Outside temp source 6705 6706 6710 6740 6741 6742 6743 6745 6800 6803 6805 6806 6810 6813 6815 6816 6820 6823 6825 6826 6830 6833 6835 6836 6840 6843 6845 6846 6850 6853 6855 Message Internal value of diagnostic code Current value of lockout phase Reset alarm Flow temp 1 alarm Flow temp 2 alarm Flow temp 3 alarm Boiler tamp alarm DHW charging alarm History 1 Error code 1 Internal diagnostic code 1 Burner control phase 1 History 2 Error code 2 Internal diagnostic code 2 Burner control phase 2 History 3 Error code 3 Internal diagnostic code 3 Burner control phase 3 History 4 Error code 4 Internal diagnostic code 4 Burner control phase 4 History 5 Error code 5 Internal diagnostic code 5 Burner control phase 5 History 6 Error code 6 Internal diagnostic code 6 No, Yes ----/2 – 60 Segment, System Local, Central Local, Central Local, Own segment Own controller, All controllers within own segment, All controllers within system Always, Automatically Off, On DHW, On No, Yes Autonomously, From BUS slave without remote setting, From BUS slave with remote setting, Controller is clock time master S0/G1 – S14/G16 No ---System Local Central Local Min. - All controllers within system - Automatically Off No - Autonomously - S0/G1 - No error, Error 1……. No Error - No, Yes ----/10 – 240 ----/10 – 240 ----/10 – 240 ----/10 – 240 ----/1 – 48 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 No ---------------No error No error No error No error No error No error - Min. Min. Min. Min. H 40 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6856 6860 6863 6865 6866 6870 6873 6875 6876 6880 6883 6885 6886 6890 6893 6895 6896 6900 6903 6905 6906 6910 6913 6915 6916 6920 6923 6925 6926 6930 6933 6935 6936 6940 6943 6945 6946 6950 6953 6955 6956 6960 6963 6965 6966 6970 6973 6975 6976 6980 6983 Burner control phase 6 History 7 Error code 7 Internal diagnostic code 7 Burner control phase 7 History 8 Error code 8 Internal diagnostic code 8 Burner control phase 8 History 9 Error code 9 Internal diagnostic code 9 Burner control phase 9 History 10 Error code 10 Internal diagnostic code 10 Burner control phase 10 History 11 Error code 11 Internal diagnostic code 11 Burner control phase 11 History 12 Error code 12 Internal diagnostic code 12 Burner control phase 12 History 13 Error code 13 Internal diagnostic code 13 Burner control phase 13 History 14 Error code 14 Internal diagnostic code 14 Burner control phase 14 History 15 Error code 15 Internal diagnostic code 15 Burner control phase 15 History 16 Error code 16 Internal diagnostic code 16 Burner control phase 16 History 17 Error code 17 Internal diagnostic code 17 Burner control phase 17 History 18 Error code 18 Internal diagnostic code 18 Burner control phase 18 History 19 Error code 19 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 0 – 255 0 – 65535 0 – 65535 No error No error No error No error No error No error No error No error No error No error No error No error No error 41 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 6985 Internal diagnostic code 19 6986 Burner control phase 19 6990 History 20 6993 Error code 20 6995 Internal diagnostic code 20 6996 Burner control phase 20 6999 Reset history Service / Special Operation 7040 Burner hours interval 7041 Burner hrs since maintenance 7042 Burner start interval 7043 Burner start sinc maintenance 0 – 255 7044 7045 No, Yes No error No - ----/10 – 10000 0 – 10000 ----/100 – 65500 0 – 65535 ---0 ---0 Maintenance interval ----/1 – 240 ---- Time since maintenance 0 – 240 0 H H Month s Month s 0 – 10000 0 Min No, Yes No - 7130 7131 7140 7143 7145 7146 Fan speed threshold for service Ionization current service message Chimney sweep function Chimney sweep burner output Manual operation Controller stop function Controller stop setpoint Deaeration function Off Max heating load Off Off 0 Off % - 7147 Type of ventilation None - 7165 7170 7250 7251 Forced heat draw DHW Telephone customer service PStick storage pos PStick description Off, On Low fire, High fire, Max heating load Off, On Off, On 0 – 100 Off, On None, heating circuit continuous, Heating circuit cycled, DHW continuous, DHW cycled Off, On 0–9 0 – 250 Off 0 0 - 7252 PStick command No operation - 7253 PStick progress 0 % 7254 PStick status 7050 7051 0 – 65535 0 – 65535 0 – 255 No operation, Reading from stick, Writing on stick 0 – 100 No stick, Stick ready, Writing on stick, Reading from stick, EMC test active, Writing error, Reading error, Incompatible data set, Wrong stick type, Stick format error, Check data set, Data set disabled, Reading disabled -1 No stick 42 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd Input / Output Test0 7700 Relay test 7713 7714 7716 7717 7717 * 7719 7724 7725 7725 * 7726 7730 7750 7760 7820 7821 7822 7823 7830 7831 7832 7833 7834 7835 7840 7841 7845 7846 7848 7849 7851 7852 7854 7855 7860 7862 7865 7872 Output test P1 PWM signal P1 Output test UX2 Output signal UX2 No test, Everything off, Relay output QX1, Relay output QX2, Relay output QX3, Relay output QX4, Relay output QX21 module 1, Relay output QX 22 module 1, Relay output QX23 module 1, Relay output QX21 module 2, Relay output QX22 module 2, Relay output QX23 module 2, Relay output QX21 module 3, Relay output QX22 module 3, Relay output QX23 module 3 ----/0 – 100 0 – 100 ----/0 – 100 ----/0 – 100 Voltage output UX2 No Test ---------- % % % ----/0 – 10 ---- V PWM output UX2 Output test UX3 Output signal UX3 ----/0 – 100 ----/0 – 100 ----/0 – 100 ---------- % % Voltage output UX3 ----/0 – 10 ---- V PWM output UX3 Outside temp B9 DHW temp B3/B38 Boiler temp B2 Sensor temp BX1 Sensor temp BX2 Sensor temp BX3 Sensor temp BX4 Sensor temp BX21 module 1 Sensor temp BX22 module 1 Sensor temp BX21 module 2 Sensor temp BX22 module 2 Sensor temp BX21 module 3 Sensor temp BX22 module 3 Voltage signal H1 Contact state H1 Voltage H2 module 1 Contact state H2 module 1 Voltage H2 module 2 Contact state H2 module 2 Voltage H2 module 3 Contact state H2 module 3 Voltage signal H3 Contact state H3 Contact state H4 Frequency H4 Contact state H5 Contact state H6 ----/0 – 100 -50 – 50 0 – 140 0 – 140 -28 – 350 -28 – 350 -28 – 350 -28 – 350 -28 – 350 -28 – 350 -28 – 350 -28 – 350 -28 – 350 -28 – 350 0 – 10 Open, Closed 0 – 10 Open, Closed 0 – 10 Open, Closed 0 – 10 Open, Closed 0 – 10 Open, Closed Open, Closed 0 – 2000 Open, Closed Open, Closed ---Open Open Open Open Open Open Open Open % °C °C °C °C °C °C °C °C °C °C °C °C °C V V V V V 43 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 7874 Contact state H7 7950 Input EX21 module 1 7951 Input EX21 module 2 7952 Input EX21 module 3 State 8000 State heating circuit 1 8001 State heating circuit 2 8002 State heating circuit 3 8003 State DHW 8005 State boiler 8007 State solar 8008 State solid fuel boiler 8009 State burner 8010 State buffer 8011 State swimming pool Diagnostic Cascade 8100 Priority/ state source 1 8102 Priority/ state source 2 8104 Priority/ state source 3 8106 Priority/ state source 4 8108 Priority/ state source 5 8110 Priority/ state source 6 8112 Priority/ state source 7 8114 Priority/ state source 8 8116 Priority/ state source 9 8118 Priority/ state source 10 8120 Priority/ state source 11 8122 Priority/ state source 12 8124 Priority/ state source 13 8126 Priority/ state source 14 8128 Priority/ state source 15 8130 Priority/ state source 16 8138 Cascade flow temp 8139 Cascade flow temp setp. 8140 Cascade return temp 8141 Cascade return temp setp. 8150 Source seqch’over current Diagnostic Heat Generation 8304 Boiler pump Q1 8308 Boiler pump speed Boiler temp, Control 8310 temperature 8311 Boiler/Control setpoint 8312 Boiler switching point Open, Closed 0V, 230 0V, 230 0V, 230 Open 0 0 0 SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. SLT cut out, Fault, Man ……. - Not available, Fault, Manual control active, Heat generation lock active, Chimney sweep funct active, Temporarily unavailable, utside temp limit active, No released, Released See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 See Para 8100 0 – 140 0 – 140 0 – 140 0 – 140 0 – 990 V V V °C °C °C °C H Off, On 0 – 100 Off - % 0 – 140 - °C 0 – 140 0 - 140 - °C °C 44 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 8313 Switching point DHW operation 8314 8315 8316 8318 8321 8323 8324 8325 8326 8327 8329 8330 8331 8338 8339 8378 8379 8380 8381 8382 8383 Boiler return temp Boiler return temp setpoint Flue gas temp Flue gas temp max Primary exchanger temp Fan speed Set point fan Current fan control Burner modulation Water pressure Ionization current st Hour run 1 stage st Start counter 1 stage Hours run burner Hours run DHW Total gas Heating Total gas DHW Total gas HC+DHW Gas energy heating Gas DHW Gas HC+DHW 8390 Current phase number 8499 8501 8502 8505 8506 8507 8508 8510 8511 8512 8513 8514 8515 8519 8520 8526 8527 8530 8531 8532 8560 Collector pump 1 Solar ctrl elem buffer Solar ctrl elemswi pool Speed collector pump 1 Speed solar pump extexch Speed solar pump buffer Speed solar swi pool Collector temp 1 Collector temp 1 max Collector temp 1 min dT collector 1/DHW dT collector 1/buffer dT collector 1/swimming pool Solar flow temp Solar return temp 24-hour yield solar energy Total yield solar energy Hours run solar yield Hours run collector overtemp Hours run collector pump Solid fuel boiler temp None, Boiler sensor B2, Return sensor B7, DHW charging sensor B36, DHW outlet sensor B38, DHW circulation sensor B39, Cascade sensor B10/B70 0 – 140 0 – 140 0 – 350 0 – 350 0 – 140 0 – 10000 0 – 10000 0 – 100 0 – 100 0 – 10 0 – 100 0 – 65535 0 – 199999 0 – 199999 0 – 199999 0 2147483647 0 2147483647 0 2147483647 0 2147483647 0 2147483647 0 2147483647 1 – 21 TNB, TLO, TNN, STY, STV, THL1, THL1A, TV, TBRE, TW1, TW2, TVZ, TSA1, TSA2 TI, MOD, THL2, THL21, TN, SAV, STOE Off, On Off, On Off, On 0 – 100 0 – 100 0 – 100 0 – 100 -28 – 350 -28 – 350 -28 – 350 -168 – 350 -168 – 350 -168 – 350 -28 – 350 -28 – 350 0 – 999.9 0 – 9999999.9 0 – 199999 0 – 199999 0 – 199999 0 – 140 °C 0 0 0 0 0 0 0 0 0 °C °C °C °C °C U/min U/min % % Bar µA H H H kWh kWh kWh kWh kWh kWh TNB Off Off Off 0 -28 350 - % % % % °C °C °C °C °C °C °C °C kWh kWh H H H °C 45 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 8570 Hours run solid fuel boiler Diagnostic Consumer 8700 Outside temp 8701 Outside temp min 8702 Outside temp max 8703 Outside temp attenuated 8704 Outside temp composite 8730 Heating circuit pump 1 8731 Heat circ. Mix valve 1 open 8732 Heat circ. Mix valve 1 close 8735 Speed heating circuit pump 1 8740 Room temp 1 8741 Room setpoint 1 8742 Room temp 1 model 8743 Flow temp 1 8744 Flow temp setpoint 1 8749 Room thermostat 1 8760 Heating circuit pump 2 8761 Heat circ. Mix valve 2 open 8762 Heat circ. Mix valve 2 close 8765 Speed heating circuit pump 2 8770 Room temp 2 8771 Room setpoint 2 8772 Room temp 2 model 8773 Flow temp 2 8774 Flow temp setpoint 2 8779 Room thermostat 2 8790 Heating circuit pump 3 8791 Heat circ. Mix valve 3 open 8792 Heat circ. Mix valve 3 close 8795 Speed heating circuit pump 3 8800 Room temp 3 8801 Room setpoint 3 8802 Room temp 3 model 8803 Flow temp 3 8804 Flow temp setpoint 3 8809 Room thermostat 3 8820 DHW pump 8825 Speed DHW pump 8826 Speed DHW interm. circ pump 8827 Speed inst. DHW Heater pump 8830 DHW temp 1 8831 DHW temp setpoint 8832 DHW temp 2 8835 DHW circulation temp 8836 DHW charging temp 8852 DHW consumption temp 8853 Instant DHW setpoint 8860 DHW flow 8875 Flow temp setp. VK1 8885 Flow temp setp. VK2 0 – 199999 - H -50.0 – 50.0 -50.0 – 50.0 -50.0 – 50.0 -50.0 – 50.0 -50.0 – 50.0 Off, On Off, On Off, On 0 – 100 0.0 – 50.0 4.0 – 35.0 0.0 – 50.0 0.0 – 140.0 0.0 – 140.0 No demand, Demand Off, On Off, On Off, On 0 – 100 0.0 – 50 4.0 – 35 0.0 – 50 0.0 – 140 0.0 – 140 No demand, Demand Off, On Off, On Off, On 0 – 100 0.0 – 50 4.0 – 35 0.0 – 50 0.0 – 140 0.0 – 140 No demand, Demand Off, On 0 - 100 0 – 100 0 – 100 0.0 – 140 8.0 – 80 0.0 – 140 0.0 – 140 0 – 140 0 - 140 0 – 140 0 – 30 5 – 130 5 – 130 Off Off Off 0 No Demand Off Off Off 0 No Demand Off Off Off 0 No Demand Off 0 0 0 - °C °C °C °C °C % °C °C °C °C °C % °C °C °C °C °C % °C °C °C °C °C 5 % % °C °C °C °C °C °C °C l/min °C °C 46 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd Flow temp setp. swimming pool 8900 Swimming pool temp 8901 Swimming pool setpoint 8930 Primary controller temp 8931 Primary controller setpoint 8950 Common flow temp 8951 Common flow temp setpoint 8952 Common return temp 8962 Common output setpoint 8980 Buffer temp 1 8981 Buffer setpoint 8982 Buffer temp 2 8983 Buffer temp 3 9005 Water pressure H1 9006 Water pressure H2 9009 Water pressure H3 9031 Relay output QX1 9032 Relay output QX2 9033 Relay output QX3 9034 Relay output QX4 9050 Relay output QX21 module 1 9051 Relay output QX22 module 1 9052 Relay output QX23 module 1 9053 Relay output QX21 module 2 9054 Relay output QX22 module 2 9055 Relay output QX23 module 2 9056 Relay output QX21 module 3 9057 Relay output QX22 module 3 9058 Relay output QX23 module 3 Burner Control 9500 Pre-purge time 9501 Pre-purge time min 9504 Required speed pre-purging 9505 Req. speed pre-purging min 9506 Speed tolerance pre-purging 9512 Required speed ignition 9513 Required speed ignition max 9514 Speed tolerance ignition 9517 Pre-ignition time 9518 Safety time 9519 Safety time with ignition 9524 Required speed LF 9525 Required speed LF min 9526 Required tolerance LF 9529 Required speed HF 9530 Required speed HF max 9531 Required tolerance HF 9534 Optg time with ignition load 9540 Post-purge time 9541 Post-purge time TL max 8895 5 – 130 - °C 0 – 140 8 – 80 0.0 – 140.0 0.0 – 140.0 0.0 – 140.0 0.0 – 140.0 0 – 140 0 – 100 0.0 – 140.0 0 – 140 0.0 – 140.0 0 – 140 0.0 – 10.0 0.0 – 10.0 0 – 10 Off, On Off, On Off, On Off, On Off, On Off, On Off, On Off, On Off, On Off, On Off, On Off, On Off, On 0 24 0 0 0 0 0 Off Off Off Off Off Off Off Off Off Off Off Off Off °C °C °C °C °C °C °C % °C °C °C °C Bar Bar Bar 0 – 51 0 – 51 200 – 10000 200 – 10000 50 – 1200 200 – 10000 200 – 10000 50 – 1200 0.4 – 1200 1.8 – 9.8 0.2 – 9.6 0 – 10000 0 – 10000 50 – 1200 0 – 10000 0 – 10000 50 – 1200 0.2 – 10 0 – 51 0 – 10 10 10 2400 2400 600 2700 2700 600 1 5 4.6 1250 1250 600 60000 60000 600 1 5 5 S S -1 Min -1 Min -1 Min -1 Min -1 Min -1 Min S S S -1 Min -1 Min -1 Min -1 Min -1 Min -1 Min S S Min 47 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 9542 9544 9545 9551 Post-purge time min Post-purge time 2 Post-purge in lockout pos Required speed stop max 9610 Capacity 9611 LP configuration 9612 GP configuration 9613 Home run mode 9614 9615 9616 9617 9618 9619 9626 9627 9630 9631 9632 9650 9651 9652 Post-purging level Forced pre-purging on error Max speed Hall sensor pulse/rev Ion. Curr. Level extran light Ion. Curr. Level flame exting Fan output/speed slope Fan output/speed Y-section Speed Kp Speed Tn Speed Tv Chimney drying Req. speed chimney drying Duration chimney drying 0 – 51 0.2 – 51 Off, On 0 – 2000 Up to 70kW, Up to 120kW, Above 120kW LP mode 1, LP mode 2, LP mode 3, LP mode 4, LP mode 5 GP not connected, GP connected Startup with home run, startup without home run Run, Pre-purge Off,On 0 – 10000 0–6 0 – 100 0 – 100 -1000 – 1000 -1500 – 1500 0 – 15.9375 0 – 600 0 – 1.75 Off, Temporarily, Permanently 0 – 10000 10 – 1440 5 0.2 Off 300 S S -1 Min Up to 70kW LP mode 1 GP not connected Startup with home run Run On 10000 2 0.61 0.78 0 0 1.125 8 0 Off 500 10 -1 Min µA µA S S -1 Min Min. 48 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 10.2 Weather Compensation Slope The correct positioning of the outside temperature sensor is fundamental for the correct operation of the climate control function of the boilers. The sensor must be installed on a North, North West facing wall and be away from flues, doors, windows and areas exposed to direct sunlight. The maximum length of cable allowed between the sensor and the controller is 50m 49 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 10.3 Controller Error Codes Code 10 20 26 28 30 32 38 40 46 47 50 52 54 57 60 65 68 70 71 72 78 81 82 83 84 85 91 98 99 100 102 103 105 109 110 111 117 118 119 121 122 125 126 127 128 129 130 132 Description Outside temperature, sensor error Boiler temperature 1, sensor error Common flow temperature, sensor error Flue gas temperature, sensor error Flow temperature 1, sensor error Flow temperature 2, sensor error Flow temperature, primary controller, sensor error Return temperature 1, sensor error Cascade return temperature, sensor error Common return temperature, sensor error DHW temperature 1 sensor error DHW temperature 2 sensor error Flow temperature DHW, sensor error DHW, circulation sensor error Room temperature 1, sensor error Room temperature 2, sensor error Room temperature 3, sensor error Storage tank temperature 1 (top), sensor error Storage tank temperature 2 (bottom), sensor error Storage tank temperature 3 (center), sensor error Water pressure, sensor error LPB short circuit or no bus power supply LPB address collision BSB wire cross-sectional/no communication BSB wire address collision BSB RF communication error Data overrun in EEPROM Extension module 1, error Extension module 2, error 2 clock time masters Clock time master without backup Communication error Maintenance message Supervision boiler temperature STB (SLT) lockout Temperature limiter safety shutdown Water pressure too high Water pressure too low Water pressure switch has cut out Flow temperature heating circuit 1 not reached Flow temperature heating circuit 2 not reached Maximum boiler temperature exceeded DHW charging temperature not reached DHW legionella temperature not reached Loss of flame during operation Wrong air supply Flue gas temperature limit exceeded Gas pressure switch safety shutdown 50 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 133 146 151 152 153 160 162 164 166 169 170 171 172 173 174 176 177 178 179 183 195 196 209 214 215 216 217 218 241 242 243 260 270 317 320 321 322 323 324 325 326 327 328 329 330 331 332 333 335 336 339 Safety time for establishment of flame exceeded Configuration error sensor/controlling elements LMS14… error, internally Parameterization error Unit manually locked Fan speed threshold not reached Air pressure switch does not close Flow/pressure switch, heating circuit error Air pressure switch error, does not open Sitherm Pro system error Error water pressure sensor, primary side Alarm contact 1 active Alarm contact 2 active Alarm contact 3 active Alarm contact 4 active Water pressure 2 too high Water pressure 2 too low Temperature limiter heating circuit 1 Temperature limiter heating circuit 2 Unit in parameterization mode Maximum duration of the refill per charging exceeded Maximum duration of the refill per week exceeded Fault heating circuit Monitoring of motor Fault fan air diverting valve Fault boiler Sensor error Pressure supervision Flow sensor for yield measurement, error Return sensor for yield measurement, error Swimming pool sensor, error 217 Flow temperature 3, sensor error 215 Temperature difference, heat exchanger too large 214 Mains frequency outside permissible range 217 DHW charging temperature, sensor error 217 DHW outlet temperature, sensor error 218 Water pressure 3 too high 218 Water pressure 3 too low 146 Input BX, same sensors 146 Input BX/extension module, same sensors 146 Input BX/mixing group, same sensors 146 Extension module, same function 146 Mixing group, same function 146 Extension module/mixing group, same function 146 Sensor input BX1 without function 146 Sensor input BX2 without function 146 Sensor input BX3 without function 146 Sensor input BX4 without function 146 Sensor input BX21 without function 146 Sensor input BX22 without function 146 Collector pump Q5 missing 51 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 340 341 349 350 351 352 353 371 372 373 374 375 376 377 378 382 384 385 386 387 388 426 427 429 430 431 432 433 146 Collector pump Q16 missing 146 Sensor B6 missing 146 Buffer storage tank return valve Y15 missing 146 Buffer storage tank address error 146 Primary controller/system pump, address error 146 Pressure-less header, address error 146 Sensor B10 missing 209 Flow temperature heating circuit 3 209 Temperature limiter heating circuit 3 103 Extension module 3 169 Sitherm Pro calculation 169 BV stepper motor 169 Drift test limit value 169 Drift test prevented 151 Internal repetition 129 Repetition speed 151 Extraneous light 151 Mains under-voltage 129 Fan speed tolerance 129 Air pressure tolerance 146 DHW sensor no function 151 Feedback flue gas damper 152 Configuration flue gas damper 218 Dynamic water pressure too high 218 Dynamic water pressure too low 217 Sensor primary heat exchanger 151 Function earth not connected 216 Temperature primary heat exchanger too high 52 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 11.0 Commissioning The Appliance 11.1 Pre-Commissioning Checks Prior to undertaking the commissioning of the unit please ensure that the system water has been cleansed and treated with a suitable inhibitor as detailed in Filling the system and system water quality. A tightness test must be carried out from the appliance to the first isolation valve (or further if connected to untested pipe work). 11.2 Combustion System Commissioning The combustion of the appliance must be commissioned by a suitably qualified engineer using a flue gas analyser. The following steps must be followed to ensure the correct and complete commissioning of the combustion system has taken place. 1: On completion of a tightness test the boiler must first be fired and tested in Maximum output. 2: To operate the boiler in maximum output the MODE selection butting is to be pressed and held for at least 3 seconds. 'Control functio stop' will appear on the display. 3: Press the INFORMATION button once, the screen will now display the modulation rate of the boiler as %. 4: Adjust the setting to 100% using the NAVIGATION button, then press OK to set. 5: Set the CO2 value by turning the throttle screw shown in the image below. Anticlockwise adjustment increases the CO2 reading Clockwise adjustment decreases the CO2 reading 6: Adjustments are to be done in small increments and the combustion allowed to stabalise before readjusting. 7: Once the correct CO2 valve has been set at Maximum output press the OK button, the 100% will flash. Use the NAVIGATION button to alter the value to read 0%. Press the OK button to set the boiler into Minimum output. 8: Set the CO2 value by adjusting the zero point screw shown below. Anticlockwise adjustment decreases the CO2 reading Clockwise adjustment increases the CO2 reading 9: Adjustments are to be done in small increments and the combustion allowed to stabalise before readjusting. 10: Once the correct CO2 valve has been set at Minimum output the controller is returned to normal operation by pressing and holding the MODE selection button for at least 3 seconds. 53 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd A flue gas analyser must be used to ensure that the correct combustion setting are achieved. This is undertaken by inserting the analyser’s probe in to plugged hole within the flue collector of the appliance or in the tapping in the flue immediately after the boiler outlet. The combustion setting required for all Ultrabox appliances are as detailed in the following tables. Model 1000 Min. Max. CO2 Emissions (G20) % 9.1 9.4 CO Emissions (G20) ppm 6 22 1125 Min. 9.2 7 Max. 9.4 28 54 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 12.0 Routine Inspection and Servicing Maintenance should be carried out in the appliance on at least an annual basis dependent on usage. during the servicing of the appliance any faults should be identified and remedied immediately to avoid further damage to the system. The boiler should be inspected only by a qualified service engineer. in addition, the maintenance and care of the boiler designated and explained on the following pages must be performed to ensure maximum boiler efficiency and reliability. Failure to service and maintain the boiler as detailed could lead to equipment premature failure. 13.0 Maintenance Procedure During maintenance the following points should be checked and/or part must be inspected and maintained. Before undertaking any work on the appliance notes and comments from the customer should be taken and investigated if any faults are reported. Servicing of heat exchanger; 1: Ensure electrical supply to boiler is isolated and made safe. Ensure that gas supply to boiler is isolated. 2: Allow time for the boiler to cool to a safe temperature to handle if it has been firing. 3: Remove the case from the boiler to allow access to the internal components. 4: Disconnect the internal gas pipe from the inlet pipe. 5: Disconnect the earth lead, HT cap and Lead from the ignition electrodes. Also removing rectification lead from probe 6: Disassemble the burner by removing the nuts around the burner door. Pull the burner forward and remove from the heat exchanger. Gently put to one side. 7: Once access has been gained to the combustion chamber and front section of the heat exchanger, inspect heat exchanger for any signs of overheating. 8: Using a NATURAL BRISTLE brush, and some MHG Heating boiler cleaning granules diluted in water, gently clean the heat exchanger ensuring all debris is removed and flushed through to the condensate drain. 9: Remove and clean out condensate syphon. Inspect condensate drain for any signs of leaks. If satisfied re assemble condensate syphon to boiler. 10: Inspect burner and burner door seals. If any signs of damage replace item. 11: Inspect ignition electrode and rectification probes. Replace on an annual basis or as required. Ensure gaskets are replaced along with probes to ensure a tight seal against burner door. 12: Inspect the fan and venturi assembly for any signs of damage or build-up of debris. Use compressed air or a brush to clean the venturi. Ensure the silicone tube between venturi and gas valve is clear and in good condition. If the fan blades have a build-up of debris a brush can be used to clean each blade in turn. Care must be taken to ensure the balance of the fan is not altered by the use of too much force. 13: Reinstall the burner, and burner door to heat exchanger ensuring all seals are intact. 14: Once the boiler is re assembled a gas tightness test must be carried out. 15: A Flue gas analysis must be completed on the completion of the tightness test. 55 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 14.0 Troubleshooting 56 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 57 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 15.0 Internal Wiring *Wiring loom and parameter adjustments required 58 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd 16.0 Spares Diagram Label Number 1 2 3 4 5 6 7 8 9 10 11 Item Description Combustion Fan Gas Valve Control Panel Heat Exchanger Ionization Electrode Ignition Electrode Ignition Transformer Limit Thermostat Pressure Sensor Flow Temperature Sensor Return Temperature Sensor Label Number 12 13 14 15 16 17 18 19 20 21 22 Item Description Automatic Air Vent Flue Gas Sensor Flue Gas Outlet Condensate Syphon Boiler Flow Connection Boiler Return Connection Gas Inlet Air Intake Venturi Condensate Syphon Level Switch Pressure Relief Valve 59 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417 © MHG Heating Ltd Notes 60 MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 01737 358000 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk 010417