Preview only show first 10 pages with watermark. For full document please download

Installation Instructions

   EMBED


Share

Transcript

Installation Instructions Twinning Kit for HSI Single-and 2-Speed Upflow Condensing and Non-Condensing Gas Furnaces KGATW0501HSI NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. TABLE OF CONTENTS Safety Considerations ....................................................................................................................................................................................................2 Introduction ....................................................................................................................................................................................................................2 Description and Usage...................................................................................................................................................................................................2 Electrostatic Discharge (ESD) Precautions...................................................................................................................................................................3 SECTION I: MODELS 58PAV, 58WAV, 383KAV, 395CAV, 480BAV, GB1AAV, AND PG8UAA UPFLOW SINGLE-SPEED NONCONDENSING HSI FURNACES................................................................................................................................................................................3 Install Furnaces.........................................................................................................................................................................................................3 Connect Electrical Components—Heating ..............................................................................................................................................................4 Connect Electrical Components-Cooling.................................................................................................................................................................8 Venting......................................................................................................................................................................................................................8 Gas Supply Piping....................................................................................................................................................................................................8 Electrical Supply Connections .................................................................................................................................................................................8 Start-Up and Adjustment........................................................................................................................................................................................10 Sequence of Operation ...........................................................................................................................................................................................10 SECTION II: MODELS 58TUA, 58UXT, 330AAV, AND 330JAV UPFLOW 2–SPEED NON-CONDENSING HSI FURNACES.................11 Install Furnaces.......................................................................................................................................................................................................11 Connect Electrical Components—Heating ............................................................................................................................................................11 Connect Electrical Components—Cooling ............................................................................................................................................................15 Venting....................................................................................................................................................................................................................16 Gas Supply Piping..................................................................................................................................................................................................16 Electrical Supply Connections ...............................................................................................................................................................................16 Start-Up and Adjustment........................................................................................................................................................................................17 Sequence of Operation ...........................................................................................................................................................................................18 SECTION III: MODELS 58MCA, 58MXA, 340MAV, 350MAV, 490AAV, AND PG9MAA UPFLOW SINGLE-SPEED CONDENSING HSI FURNACES.................................................................................................................................................................................................................18 Install Furnaces.......................................................................................................................................................................................................18 Connect Electrical Components—Heating ............................................................................................................................................................22 Connect Electrical Components—Cooling ............................................................................................................................................................26 Venting....................................................................................................................................................................................................................26 Gas Supply Piping..................................................................................................................................................................................................26 Condensate Drain Connections (Furnaces After Serial No. 2894A00001)..........................................................................................................26 Electrical Supply Connections ...............................................................................................................................................................................26 Start-Up and Adjustment........................................................................................................................................................................................28 Sequence of Operation ...........................................................................................................................................................................................28 → SECTION IV: MODELS 58MTA AND 352MAV UPFLOW 2-SPEED CONDENSING HSI FURNACES........................................................28 Install Furnaces.......................................................................................................................................................................................................28 Connect Electrical Components—Heating ............................................................................................................................................................33 Connect Electrical Components—Cooling ............................................................................................................................................................34 Venting....................................................................................................................................................................................................................34 Gas Supply Piping..................................................................................................................................................................................................34 Condensate Drain Connections ..............................................................................................................................................................................34 Electrical Supply Connections ...............................................................................................................................................................................34 Start-Up and Adjustment........................................................................................................................................................................................35 Sequence of Operation ...........................................................................................................................................................................................35 ......................................................................................................................................................................................................................................36 ......................................................................................................................................................................................................................................36 ......................................................................................................................................................................................................................................36 Form: AG-GATW-11 Cancels: AG-GATW-10 Printed in U.S.A. 6-01 Catalog No. 63GA-TW4 ......................................................................................................................................................................................................................................36 SAFETY CONSIDERATIONS Installing and servicing of heating equipment can be hazardous due to gas and electrical components. Only trained personnel should install or service heating equipment. Untrained personnel can perform basic maintenance such as cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available. . When you see this symbol on the furnace and in instructions or manuals, be Recognize safety information. This is the safety-alert symbol alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. INTRODUCTION IMPORTANT: Only the furnace sizes listed in Tables 2, 3, 4, and 5 can be twinned. Both furnaces must have the same product number, including heating and cooling sizes, to achieve correct operation. → This furnace twinning kit P/N KGATW0501HSI permits connection of 2 upflow, single-speed, non-condensing furnaces (See Fig. 1 and 2); 2 upflow, 2-speed, non-condensing furnaces (See Fig. 1 and 12); 2 upflow, single-speed, condensing furnaces (See Fig. 17 and 18) or 2 upflow, 2-speed, condensing furnaces (See Fig. 18 and 30) to operate as a single unit on the same duct work. The kit is applicable only to upflow furnaces listed in Tables 2, 3, 4, and 5. A single non-condensing furnace shall NOT be twinned with a single condensing furnace or with a non-condensing furnace with a different number of speeds. Variable-speed furnaces shall not be twinned. DESCRIPTION AND USAGE → This twinning kit is designed for use in 2 upflow, single-speed, non-condensing, hot surface ignition (HSI) furnaces as shown in Table 2; 2 upflow, 2-speed, non-condensing, HSI furnaces as shown in Table 3; 2 upflow, single-speed, condensing HSI furnaces as shown in Table 4; 2 upflow, 2-speed, condensing HSI furnaces as shown in Table 5. Refer to the appropriate section for your furnaces. SECTION I: Models 58PAV, 58WAV, 383KAV, 395CAV, 480BAV, GB1AAV, and PG8UAA Upflow Single-Speed Non-Condensing HSI Furnaces • Single-Stage Heat with Single-Stage Gas-Heat Thermostat • Two-Stage Heat with 2-Stage Gas-Heat Thermostat SECTION II: Models 58TUA, 58UXT, 330AAV, and 330JAV Upflow 2-Speed Non-Condensing HSI Furnaces • Two-Stage Heat with Single-Stage Gas-Heat Thermostat • Two-Stage Heat with 2-Stage Gas-Heat Thermostat SECTION III: Models 58MCA, 58MSA, 58MXA, 340MAV, 345MAV, 350MAV, 490AAV, and PG9MAA Upflow Single-Speed Condensing HSI Furnaces • Single-Stage Heat with Single-Stage Gas-Heat Thermostat → SECTION IV: Models 58MTA and 352MAV Upflow 2-Speed Condensing HSI Furnaces • Two-Stage Heat with Single-Stage Gas-Heat Thermostat • Two-Stage Heat with 2-Stage Gas-Heat Thermostat The furnaces must be installed to ensure sufficient return air. A combination of 1 full side and bottom inlet plenum or bottom only inlet plenum shall be used for return air to each furnace. The preferred method is to have all return air brought into the bottom of the furnaces through a common bottom plenum. The bottom return-air plenum shall be at least as high as the width of the furnace bottom return-air opening. When there are height limitations, the bottom return-air plenum height can be reduced to 8 in. minimum if 1 entire side return-air opening of each furnace is used in conjunction with the bottom return opening. Rear inlet plenums shall not be used. (See Fig. 2, 12, 17, or 30.) WARNING: Do not remove the center return-air partitions between the furnaces. Failure to follow this warning could result in improper auxiliary limit operation, fire, personal injury, or death. Staged heating operation is permitted only with this twinning kit. With the 2-speed, non-condensing furnaces, low-gas heat in both furnaces is used for first-stage heat, and high-gas heat in both furnaces is used for second-stage heat. With the single-speed, non-condensing, and condensing furnaces, the left-hand furnace is used for first-stage heat, and both furnaces are used for second-stage heat. This kit ensures both furnace blowers operate simultaneously so air flows through the duct work rather than recirculating in a loop between the furnaces. NOTE: As a result of staged heating with single-speed furnaces, the air temperature distribution in the supply plenum may be uneven when only 1 furnace is heating. NOTE: Refer to the Installation, Start-Up, and Operating Instructions supplied with each furnace for information on venting, clearances, start-up, maintenance, and other information not covered in this publication. —2— See Table 1 for kit contents. Table 1—Kit Contents DESCRIPTION Foam Strip Relay and Harness Assembly (TKR) Wiring Label Schematic Diagram (Single-Speed NonCondensing) Wiring Label Connection Diagram (Single-Speed NonCondensing) Wiring Label Schematic Diagram (2-Speed Non-Condensing) Wiring Label Connection Diagram (2-Speed NonCondensing) Wiring Label Schematic Diagram (Single-Speed Condensing) Wiring Label Connection Diagram (Single-Speed Condensing) Wiring Label-Schematic Diagram (2-Speed Condensing) Wiring Label-Connection Diagram (2-Speed Condensing) Auxiliary Limit Switch Harness-Master Furnace (ALS-M) Auxiliary Door Switch/Limit Switch Harness Slave Furnace (ALS-S/ILK-1) No. 6 X 3/4-in. LG Sheet Metal Screw 1/4-in. Quick-Connect Wire Terminal Wire Tie Snap Bushing Strain Relief Bushing Installation Instructions PART NO. 313596-201 320770-301 QUANTITY 4 1 322867-101 1 322866-101 1 322032-401 1 322031-401 1 322865-101 1 322864-101 1 326684-201 326685-201 320773-701 1 1 1 320777-701 1 AL76AZ128 HY60AM065 HY76TB125 HY93NH070 HW60ZW250 AG-GATW-11 7 1 2 2 2 1 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS CAUTION: Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential. 1. Disconnect all power to the furnace. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND. 2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged. 3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.). 4. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires. 5. Use this procedure for installed and uninstalled (ungrounded) furnaces. 6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects. 7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage. SECTION I: MODELS 58PAV, 58WAV, 383KAV, 395CAV, 480BAV, GB1AAV, AND PG8UAA UPFLOW SINGLE-SPEED NON-CONDENSING HSI FURNACES NOTE: The furnace installed on the left-hand (LH) side will be referred to as the LH furnace, and the furnace installed on the right-hand (RH) side as the RH furnace throughout these instructions. PROCEDURE 1—INSTALL FURNACES Refer to Fig. 1 and 2 for appearance and dimensional drawing of twinned furnaces and their connection locations. 1. Select 2 identical heating and airflow furnaces. (See Table 2.) 2. Remove bottom closure panels from both furnaces. (See Fig. 3.) a. Remove 2 screws from bottom front panel. b. Rotate front panel downward to remove. c. Remove bottom closure panel and discard. d. Reinstall bottom front panel. 3. If return air is to enter 1 side of each furnace, cut open 1 entire return-air opening in appropriate side of each furnace. (See Fig. 2.) —3— JUNCTION BOX JUNCTION BOX AUXILIARY BLOWER DOOR SWITCH BLOWER DOOR SWITCH BLOWER DOOR SWITCH TKR RELAY 10″ TWIN/ TEST CONNECTION AUXILIARY LIMIT SWITCHES A95227 Fig. 1—Twinning Kit Installed on Non-Condensing Furnaces 4. Apply 2 factory-supplied foam strips to mating side of each furnace. Locate strips equal distance from top and bottom as shown in Fig. 4. 5. Remove gas hole closure from RH furnace only and power hole closure from LH furnace only as indicated in Fig. 2. 6. Remove 7/8-in. diameter accessory hole closures from mating sides of furnaces. (See Fig. 4.) 7. Position furnaces against each other on return-air plenum. Adjust and shim each furnace to align 7/8-in. diameter holes in both furnaces. 8. Drill two 1/8-in. holes, approximately 1 in. below discharge flange, from inside top of discharge opening and through both furnaces. (See Fig. 5.) 9. Drive 1 factory-supplied No. 6 X 3/4-in. LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces. 10. Insert 1 snap bushing through each adjoining accessory hole of each furnace. 11. Remove 7/8-in. diameter knockout from blower shelf of LH furnace near front right corner. 12. Insert 1 strain relief bushing through blower shelf hole. 13. Connect return- and supply-air ducts to furnaces. Seal duct connections to prevent air leakage. 14. Move 115-v junction box JB in LH furnace from right-hand side to left-hand side. For models produced before January 1995, blower door switch ILK in LH furnace must also be moved from right-hand side to left-hand side. WARNING: DO NOT use the back of the furnace for return-air duct connections as limit cycling will occur. A failure to follow this warning can cause a fire, personal injury, or death. PROCEDURE 2—CONNECT ELECTRICAL COMPONENTS—HEATING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. See electrostatic discharge precaution on page 2. 1. Remove control doors and blower access doors from both furnaces. 2. Install twinning kit relay (TKR) and harness assembly. The twinning kit can be used for single-stage or 2-stage heating operation. —4— AIRFLOW AI MASTER OR LH FURNACE 28 A 13⁄16″ 1⁄2″ F D 2 1⁄16″ 1″ 7⁄8- IN. DIA HOLE POWER ENTRY 7⁄8-IN. DIA HOLE CLOSURE ACCESSORY FLUE COLLARS D 7⁄8-IN. DIA CLOSURE ENTRY 1 1⁄2-IN. D CLOSUR R.H. GA 5 3⁄8″ 12 5⁄16″ 13⁄16″ 5 13⁄16″ 2 11⁄16″ 1 3⁄4-IN. DIA HOLE GAS ENTRY 39 7⁄8″ HOLE THERMOSTAT WIRE ENTRY 7⁄8-IN. DIA CLOSURE 1⁄2-IN. DIA CLOSURE WIRE ENT 2 3⁄8″ 2 3⁄8″ 1⁄2-IN.DIA SIDE INLET 14 1⁄2″ 1 3⁄4″ 11⁄16″ 23 1⁄4″ 24 5⁄16″ BOTTOM INLET 3″ 11⁄16″ E E INLET INLET 11⁄16″ A93532 Fig. 2—Dimensional Drawing for Twinned Single-Speed Non-Condensing Furnaces Table 2—58PAV, 58WAV, 383KAV, 395CAV, 480BAV, GB1AAV, and PG8UAA Single-Speed Non-Condensing Furnace Dimensions (In.) INPUT HEATING SIZE (BTUH) 88,000 110,000 110,000 132,000 132,000 154,000 NOMINAL COOLING SIZE (BTUH) 48,000 48,000 60,000 48,000 60,000 60,000 A D E F 42-5/16 42-5/16 49-5/16 42-5/16 49-5/16 49-5/16 19-3/8 19-3/8 22-7/8 19-3/8 22-7/8 22-7/8 19-1/2 19-1/2 23 19-1/2 23 23 40-11/16 40-11/16 47-11/16 40-11/16 47-11/16 47-11/16 This kit applies to the above furnaces with the date codes of 1594 and later. Single-Stage Heat with Single-Stage Gas-Heat Thermostat (Field Supplied) NOTE: This application allows both furnaces to operate as 1 furnace in gas heat mode as determined by single-stage thermostat operation. Both furnaces operate in heating mode simultaneously. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. a. Secure relay of TKR assembly to LH furnace control mounting bracket using 2 factory-supplied No. 6 X 3/4-in. LG screws. See Fig. 6 for location of holes to be drilled. NOTE: See Fig. 7. b. Connect TKR white wire labeled W from TKR to LH furnace control thermostat connection W. c. Connect TKR black wire labeled C from TKR to LH furnace control thermostat connection COM 24V. d. Connect TKR yellow wire labeled TEST/TWIN (loose wire end near TKR relay) to LH furnace control TEST/TWIN terminal. e. Route remaining 4 loose TKR wires through: (1.) Strain relief bushing previously installed in 7/8-in. hole in right-hand side of blower shelf. (2.) Gas control compartment of LH furnace. (3.) Snap bushings previously installed between furnaces. (See Fig. 4.) f. Connect TKR red wire labeled R-SLAVE from TKR to RH furnace control thermostat connection R. g. Connect TKR white wire labeled W-SLAVE from TKR to RH furnace control thermostat connection W. h. Connect TKR black wire labeled C-SLAVE from TKR to RH furnace control thermostat connection Com 24V. —5— O 1″ 5 3⁄8″ 5 SLAVE OR 2 1⁄16″ 13⁄16″ BOTTOM CLOSURE PANEL FRONT FILLER PANEL A93047 Fig. 3—Removing Bottom Closure Panel 11 3⁄16″ REMOVE 7⁄8-IN. DIA ACCESSORY HOLE CLOSURE FOAM STRIPS RH FURNACE Fig. 5—Attaching Furnaces Together Fig. 4—Location of Foam Strips A91166 A93533 i. Connect TKR yellow wire labeled TEST SLAVE from LH furnace control TEST terminal to RH furnace control TEST terminal. Two-Stage Heat with 2-Stage Gas-Heat Thermostat (Field Supplied) NOTE: ALL thermostat connections are to be made to LH furnace control ONLY. (See Fig. 7.) NOTE: This application allows only the LH furnace to operate for first-stage heat mode or both furnaces to operate for second-stage heat mode as determined by a 2-stage thermostat. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. To operate furnaces in 2-stage heating mode when a 2-stage thermostat controls the staging, install TKR as described above then modify TKR wiring as follows: a. Disconnect TKR white wire labeled W from the LH furnace control thermostat connection W. b. Cut off terminal of TKR white wire labeled W and strip 1/4 in. c. Connect 2-stage thermostat W2 connection to TKR white wire labeled W. CAUTION: Supply-air temperature will be uneven left-to-right when only master system is operating. NOTE: ALL other 2-stage thermostat connections are to be made to LH furnace control ONLY. (See Fig. 8.) 3. Install LH furnace auxiliary limit switch harness ALS-M. NOTE: LH furnace ALS-M assembly DOES NOT include door switch. a. Drill 1/8-in. hole in blower housing 10 in. below blower shelf. (See Fig. 1.) b. Position ALS-M so reset button faces front of furnace. c. Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. d. Disconnect red transformer wire from LH furnace control SEC-1 connection. e. Cut off the 3/16-in. quick-connect terminal from red transformer wire. —6— TKR RELAY CONTROL MOUNTING BRACKET 1⁄4″ 1 1⁄2″ 1 3 2 4 W2 ON OFF COM 24 V 1 2 3 4 W/W1 Y/Y2 R G HUM 1 LED TWIN TEST MASTER SLAVE 1 2 1 5 4 8 7 3 6 9 10 11 12 SEC-1 PR1 2 5 8 3 6 9 L2 PR2 COM EAC-2 PARK EAC-1 7 FU1 3 4 L1 HI-COOL HI-GAS -HEAT LO-GAS -HEAT 1 SEC-2 CONTROL A93535 Fig. 6—Twinning Kit Relay Mounted on Control Mounting Bracket for LH Furnace (Two-Stage Control Shown) f. Strip the red wire 1/8 in. and secure the factory-supplied 1/4-in. quick-connect terminal. g. Connect red transformer wire connector to ALS-M wire connector PL7 labeled TRANS ASSY. h. Connect ALS-M wire connector labeled DOOR SWITCH or SEC 1 to LH furnace control SEC-1 terminal. i. Route 2-wire ALS-M connector PL6 through: (1.) Strain relief bushing previously installed in 7/8-in. hole in right-hand side of blower shelf. (2.) Gas control compartment of LH furnace. (3.) Snap bushings previously installed between furnaces into gas control compartment of RH furnace. 4. Install RH furnace auxiliary door switch and auxiliary limit switch harness ALS-S/ILK-1. NOTE: RH furnace auxiliary limit switch harness assembly ALS-S/ILK-1 has door switch included. a. Drill 1/8-in. hole in blower housing 10 in. below blower shelf. (See Fig. 1.) b. Position ALS-S with terminals facing front of furnace. c. Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. d. Relocate RH furnace junction box JB from left side to right side as shown in Fig. 1 if JB is not at right-hand side of RH furnace. For models produced before January 1995, blower door switch ILK must also be moved when JB changes location. e. Position auxiliary door switch ILK-1 on left-hand side of RH furnace. f. Secure auxiliary door switch ILK-1 using factory-supplied No. 6 X 3/4-in. LG screw. g. Route 2-wire harness connector PL6 of ALS-S/ILK-1 assembly up through snap bushing in 7/8-in. hole in left side of blower shelf and into gas control compartment. h. Connect RH ALS-S connector PL6 to LH ALS-M connector PL6 that was routed through furnace casings. 5. Select identical blower motor speed taps at control center motor connectors in both furnaces. CAUTION: Failure to select identical blower speed taps in both furnaces can result in overheating of furnace components and possible loss of furnace operation and damage to the furnaces. 6. Dress wires to ensure they do not contact sharp or moving parts nor interfere with blower operation, removal of filters, or operation of switches. 7. Make all thermostat connections to LH furnace only. —7— SINGLE-STAGE INDOOR THERMOSTAT NOTES: 1. TRANSFORMER = 115 VAC PRIMARY/24 VAC SECONDARY/40 VA. 2. RELAYS = 24 VAC COILS/PILOT DUTY/NORMALLY OPEN. W R G C Y LEFT HAND FURNACE (MASTER) Y COIL C G R W TWIN TEST RELAY 1 RIGHT HAND FURNACE (SLAVE) Y C G R W TWIN TEST YEL BLK BLK RED 4 WHT (FIELD SUPPLIED) NOTE 2 2 WHT TKR 24 VAC TRANS (FIELD SUPPLIED) 115 VAC NOTE 1 C Y OUTDOOR UNIT NO. 1 C Y OUTDOOR UNIT NO. 2 A97116 Fig. 7—Twinning 2 Single-Speed Outdoor Units with 2 Single-Speed Furnaces with a Single-Stage Thermostat PROCEDURE 3—CONNECT ELECTRICAL COMPONENTS-COOLING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. When installing twinned outdoor units with twinned gas furnaces, it is necessary to use a field-supplied 24-vac pilot-duty relay and a field-supplied 24/115-vac transformer as shown in Fig. 7 or 8 to prevent overloading furnace 24/115-vac transformer. PROCEDURE 4—VENTING Refer to Installation, Start-Up, and Operating Instructions supplied with each furnace for venting information. CAUTION: When common-venting twinned, Category I (negative-pressure venting), non-condensing furnaces, excessive condensate may occur as a result of oversized vent systems. Dedicated vents and/or proper vent sizing per the furnace Installation, Start-Up, and Operating Instructions will reduce the potential for condensation. PROCEDURE 5—GAS SUPPLY PIPING NOTE: All gas connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supplyand return-air ducts. Furnaces are recommended to be provided with a single shutoff valve. However, individual shutoff valves may be required by local codes or jurisdictions. Refer to Installation, Start-Up, and Operating Instructions provided with each furnace for additional gas supply information. PROCEDURE 6—ELECTRICAL SUPPLY CONNECTIONS NOTE: All electrical power connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supply- and return-air ducts. —8— TWO-STAGE INDOOR THERMOSTAT W2 W/W1 NOTES: 1. FOR TWO-STAGE COOLING, USE RELAY 1 AND 2 (FIELD SUPPLIED) AS SHOWN. 2. TRANSFORMER = 115 VAC PRIMARY/24 VAC SECONDARY/40 VA. 3. RELAYS = 24 VAC COILS/PILOT DUTY/NORMALLY OPEN. 4. FOR A DUAL-CIRCUITED SINGLE EVAPORATOR COIL THAT COVERS BOTH FURNACE AIR OUTLETS, INTERCHANGE THE THERMOSTAT CONNECTIONS AT Y1 AND Y/Y2 FOR STAGED BLOWER OPERATION. R G C Y1 Y/Y2 NOTE 1 LEFT HAND FURNACE (MASTER) COIL COIL RELAY 2 RELAY 1 Y C G R W TWIN TEST NOTE 1 RIGHT HAND FURNACE (SLAVE) Y C G R W TWIN TEST YEL BLK BLK (FIELD SUPPLIED) NOTE 3 RED 4 TKR WHT 2 WHT 24 VAC TRANS (FIELD SUPPLIED) C 115 VAC NOTE 2 Y OUTDOOR UNIT NO. 2 C Y OUTDOOR UNIT NO. 1 A97117 Fig. 8—Twinning 2 Single-Speed Outdoor Units with 2 Single-Speed Furnaces with a 2-Stage Thermostat 1. Each furnace shall be connected to its own 115-vac power supply. The twinning kit installation interconnects the furnaces, allowing them to operate as a single furnace. The L1 (black) connection to each furnace must be connected to circuit breakers connected to the same service panel 115-vac phase leg. On single-phase (residential) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 1 space to be connected to the same leg of the 1-phase power supply. On 3-phase (commercial) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 2 spaces to be connected to the same leg of the 3-phase power supply. The proper 115-vac phasing of furnace connections permits 24-vac transformer phasing as described below. 2. Phasing of the connected 24-vac transformer secondary circuits can be determined with the LED status of both furnaces. See furnace Installation, Start-Up, and Operating Instructions and status code labels on blower doors. The furnaces’ transformers’ black leads should be connected to PR1 connectors and white leads to PR2 connectors on controls. If 1 or both LEDs are rapidly flashing, disconnect lead at TEST/TWIN terminal of LH furnace and observe LED at each furnace. IF: a. Both LEDs are on continuously: System phasing is okay. b. One or both LEDs are rapidly flashing: (1.) Line voltage polarity is reversed —9— BLOWER OFF DELAY SWITCH OR JUMPER WIRE G 24-VAC THERMOSTAT LEAD TERMINALS R Y TEST/TWIN W Com 24V HUM SEC-1 LED OPERATION & DIAGNOSTIC LIGHT 24-VAC TRANSFORMER SEC-2 3-AMP FUSE SPARE 1 COOL HEAT BLOWER SPEED SELECTION TERMINALS SPARE 2 115-VAC (L1) POWER SUPPLY 115-VAC (L2) NEUTRAL CONNECTION A95228 Fig. 9—Single-Stage Furnace Control (2.) Reverse SEC-1 and SEC-2 in furnace with rapid flashing LED. c. One LED is off, 1 LED is on continuously: (1.) The 24-vac circuit is inoperative on furnace with LED light off. (2.) Check transformers, auxiliary limits, and door switches in both furnaces and correct problem. 3. Reconnect lead at TWIN/TEST terminal of LH furnace and observe LED at each furnace. The LEDs will glow steady for proper phasing. PROCEDURE 7—START-UP AND ADJUSTMENT Refer to Installation, Start-Up, and Operating Instructions supplied with furnaces for detailed information. 1. Shut off all power and gas to both furnaces. 2. Position blower off delay switches on controls in BOTH furnaces to SAME desired gas heat blower off delay. (See Fig. 9.) See furnace Installation, Start-Up, and Operating Instructions for further details. If 1 furnace control has blower off delay switches and the other has a fixed jumper wire which sets blower off delay at 135 sec, the control with selectable switches MUST be set for 135 sec off delay. 3. Attach twinning connection diagram label over existing wiring label on inside of LH furnace blower door. 4. Attach twinning schematic diagram label over existing wiring label on inside of RH furnace blower door. 5. Turn on power and gas to both furnaces. 6. Reinstall blower access doors on both furnaces. 7. Operate furnaces through 2 cycles in each mode to confirm correct operation by operating only thermostat. a. Single-stage gas heating thermostat R-to-W for gas heat. First stage of a 2-stage thermostat causes LH furnace to operate in gas-heat mode. b. First and second stage of 2-stage heating thermostat R-to-W/W1-and-W2 causes both furnaces to operate in gas-heat mode. c. Thermostat R-to-G for continuous fan or low-cooling blower. d. Cooling thermostat R-to-G-and-Y for single-speed cooling blower. 8. Reinstall control doors on both furnaces. 9. Instruct user in operation of furnace and thermostat. PROCEDURE 8—SEQUENCE OF OPERATION See Fig. 10 and 11 for single-speed non-condensing furnace twinning connection and schematic wiring diagrams while reviewing the sequence of operation. —10— Twinning operation is controlled by LH furnace. The TWIN/TEST and COM 24 connection wires ensure the 2 furnaces coordinate their blower operation. When either furnace requires blower operation, both furnaces operate their blowers at the same speed. Both furnaces operate simultaneously in the same mode: heat, cool, or continuous fan. Exceptions can occur if a safety switch on either furnace is activated (such as pressure switch, flame roll-out switch, main limit switch, draft safeguard switch, twinning kit auxiliary limit switch, or flame-proving sensor). In such a case, the other furnace continues to operate unless open switch is the flame roll-out, main limit, or twinning kit auxiliary limit switch, in which case both furnaces respond. Before performing component test, disconnect TKR yellow wire labeled TEST from LH furnace control TEST/TWIN terminal. After removing yellow wire, component test can be initiated on each furnace individually as stated in Installation, Start-Up, and Operating Instructions. Single-Stage Heat with Single-Stage Gas-Heat Thermostat See Section I, Procedure 2 for furnace and kit components used. 1. Single-stage thermostat causes both furnaces to operate in heating mode. 2. Operation in ALL modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on sequence of operation. Two-Stage Heat with 2-Stage Gas-Heat Thermostat See Section I, Procedure 2 for furnace and kit components used. 1. The 2-stage thermostat causes the furnaces to operate in first-stage heat (LH furnace operates in heat while RH furnace blower operates but RH furnace is not heating) or causes the furnaces to operate in second-stage heat (both furnaces operate in heat), depending on whether 1 or 2 thermostat stages are calling for heat. 2. Operation in ALL modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on sequence of operation. SECTION II: MODELS 58TUA, 58UXT, 330AAV, AND 330JAV UPFLOW 2–SPEED NON-CONDENSING HSI FURNACES PROCEDURE 1—INSTALL FURNACES NOTE: Multipoise units must be installed in UPFLOW configuration. Refer to Fig. 1 and 12 for appearance and dimensional drawing of twinned furnaces and their connection locations. 1. Select 2 identical heating and airflow furnaces. (See Table 3.) 2. Remove bottom closure panels from both furnaces. (See Fig. 3.) a. Remove 2 screws from bottom front panel. b. Rotate front panel downward to remove. c. Remove bottom closure panel and discard. d. Reinstall bottom front panel. 3. If return air is to enter 1 side of each furnace, cut open 1 entire return-air opening in appropriate side of each furnace. (See Fig. 12.) 4. Apply 2 factory-supplied foam strips to mating side of each furnace. Locate strips equal distance from top and bottom as shown in Fig. 4. 5. Remove gas and power hole closures from RH furnace only as indicated in Fig. 12. 6. Remove 7/8-in. diameter accessory hole closures from mating sides of furnaces. (See Fig. 4.) 7. Position furnaces against each other on return-air plenum. Adjust and shim each furnace to align 7/8-in. diameter holes in both furnaces. 8. Drill two 1/8-in. holes, approximately 1 in. below discharge flange, from inside top of discharge opening and through both furnaces. (See Fig. 5.) 9. Drive 1 factory-supplied No. 6 X 3/4-in. LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces. 10. Insert 1 snap bushing through each adjoining accessory hole of each furnace. 11. Remove 7/8-in. diameter knockout from blower shelf of LH furnace near front right corner. 12. Insert 1 strain relief bushing through blower shelf hole. 13. Connect return- and supply-air ducts to furnaces. Seal duct connections to prevent air leakage. 14. Move 115-v junction box JB in LH furnace from right-hand side to left-hand side. For models produced before January 1995, blower door switch ILK in LH furnace must also be moved from right-hand side to left-hand side. WARNING: DO NOT use the back of the furnace for return-air duct connections as limit cycling will occur. A failure to follow this warning can cause a fire, personal injury, or death. PROCEDURE 2—CONNECT ELECTRICAL COMPONENTS—HEATING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. See electrostatic discharge precaution on page 2. 1. Remove control and blower access doors from both furnaces. —11— WHT BLK DSS 4 PRS NOTE #15 LGPS NOTE #15 TEST/TWIN ORN ORN 90 SEC 180 SEC PL1 225 SEC BLU NOTE #5 COOL SPARE-1 PL3 PR2 1 2 3 SEC-1 EAC-2 RED BRN OL HSIR YEL (MED-HI) START NOTE #7 IDR TRAN L2 BRN WHT PL3 PL2 BLWM RED (LO) 120 VAC L1 1 2 PR1 2 PL5 WHT IDM WHT BLK 1 PR2 C OM EAC-2 IDM BLK GRN ILK WHT 2 BLK HSI BLK FU2 HSI GRN LEGEND GV GVR HI/LO HSI HSIR HUM IDM IDR ILK ILK-1 JB LED LGPS LS OL HEAT SPARE-2 EAC-1 WHT BLK BLK FUSED DISCONNECT SWITCH (WHEN REQ’D) NOTE #4 BLK BLK BLK BLK WHT JB WHT BLK ALS-M ALS-S BLWR BLWM CAP DSS EAC-1 EAC-2 FL FRS FSE FU1 FU2 COOL SPARE-1 WHT WHT 1 1 2 3 24 VAC-3A FUSE WHT (COM) BLK PL5 BLOWER SPEED SELECT BLWR BLU (MED-LO) C OM SEC-2 HI/LO RELAY FU1 GRN HEAT SPARE-2 EAC-1 3 2 1 6 5 4 9 8 7 WHT 225 SEC SLAVE OR RH FURNACE BLK L2 NOTE #3 RE GVR WHT BLOWER SPEED SELECT L PL1 180 SEC 2-C NOTE #8 1 1 PL6 ORN ORN ILK-1 ALS-S BLU ORN 2 2 BLU NOTE #8 RED PL7 ALS-M WHT (COM) BLK (HI) LED 135 SEC GV FRS1 (WHEN USED) BLK YEL TEST/TWIN BLU SEC-2 24 VAC-3A FU1 FUSE 1 2 FSE G R Y W OM 24V HUM 90 SEC 3-P FL RED HI/LO RELAY PL2 1-M BLOWER OFF DELAY SELECTION CHART 3 BLK GRN SEC-1 BLWR 120 VAC L1 PR1 WHT BLU CAP IDR LS 1.0 AMP HSIR 3 2 1 6 5 4 9 8 7 GVR MASTER OR LH FURNACE FRS2 RED NOTE #12 (NOT ON ALL MODELS) BLK 1 BLOWER SW1 OFF DELAY SW2 C PCB TKR 135 SEC NOTE #8 2 WHT YEL (WHEN USED) LED WHT RED YEL RED NOTE #12 (NOT ON ALL MODELS) BLOWER OFF DELAY SELECTION CHART WHT PCB G R Y W C OM 24V HUM 1.0 AMP NOTES #9 AND #14 BLOWER SW1 OFF DELAY SW2 MASTER AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) PCB SLAVE AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) BLOWER MOTOR RELAY, SPST-(N.O.) PL1 BLOWER MOTOR, 3- OR 4-SPEED, PERMANENT-SPLIT-CAPACITOR PL2 CAPACITOR DRAFT SAFEGUARD SWITCH, AUTO-RESET, SPST-(N.C.) PL3 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) PL5 ELECTRONIC AIR CLEANER CONNECTION (COMMON) PL6 FUSIBLE LINK FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) PL7 FLAME-PROVING SENSOR ELECTRODE PRS FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FUSE OR CIRCUIT-BREAKER CURRENT-INTERRUPT DEVICE TEST / TWIN (FIELD INSTALLED & SUPPLIED) TKR GAS VALVE-REDUNDANT OPERATORS GAS VALVE RELAY, DPST-(N.O.) TRAN BLOWER MOTOR SPEED CHANGE RELAY, SPDT HOT SURFACE IGNITER (115 VAC) HOT SURFACE IGNITER RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) INDUCED DRAFT MOTOR, SHADED-POLE INDUCER MOTOR RELAY, SPST-(N.O.) BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES LOW GAS-PRESSURE SWITCH, SPST (N.O.) LIMIT SWITCH, AUTO RESET, SPST(N.C.) AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SWITCH, SPST-(N.C.) PRINTED CIRCUIT BOARD 9-CIRCUIT CONNECTOR 2-CIRCUIT CONNECTOR 3-CIRCUIT IDM CONNECTOR 2-CIRCUIT HSI CONNECTOR 2-CIRCUIT TWINNING KIT CONNECTOR JUNCTION UNMARKED TERMINAL PCB CONTROL TERMINAL FACTORY WIRING (115VAC) FACTORY WIRING (24VAC) 1-CIRCUIT TWINNING KIT IN-LINE SPLICE PRESSURE SWITCH, SPST-(N.O.) FIELD WIRING (115VAC) COMPONENT TEST & TWIN TERMINAL FIELD ACCESSORY WIRING (24VAC) TWINNING KIT RELAY, SPST-(N.O.) TRANSFORMER-115VAC / 24VAC —12— FIELD WIRING TERMINAL, NOTE #14 FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE WIRES PASSING THROUGH HOLES IN 322866-101 REV. B CASINGS FROM LH TO RH FURNACE. NOTES: 1. If any of the for 105°C o 2. Inducer (ID auto-reset 3. Blower mo installation 4. Use only co furnace. 5. This wire m prove flame 6. Replace on 7. Yellow lead 8. Passes thr slave furna 9. Make therm 10. Make no th 11. Blower-on 2 seconds. 12. Blower-off (135 secon 90 seconds 13. Ignition-loc trials-for-ig 14. Some mod 15. Factory Co SCHEMATIC DIAGRAM (NATURAL GAS & PROPANE) TO 115VAC FIELD DISCONNECT MASTER OR LH FURNACE TO 115VAC FIELD DISCONNECT NOTE #4 L2 L1 EQUIPMENT GROUND ILK EQUIPMENT GROUND ILK BLWM LO SPARE-1 MED LO HEAT MED HI NOTE #7 HI/LO SPARE-2 OL HI COOL L1 MAKE THERMOSTAT CONNECTIONS TO ONLY THE LH FURNACE BLWR COM HSIR L2 START L1 MAKE NO THERMOSTAT CONNECTIONS TO RH FURNACE BRN CAP GRN NOTE #3 2 PL5 COM PASSES THROUGH HOLES IN CASINGS IDR PR1 PR2 115VAC 1 2 PL2 PL5 HS 2 IDR PR2 115VAC PR1 3 TRAN 1 1 IDM ALS-M PL7 COM EAC-2 HSI 2 PL3 1 3 TRAN PL3 RED 24VAC ORN 24VAC 2 YEL TEST/TWIN FU FRS1 SEC-2 LS W WHT BLK 3 NOTE #13 (WHEN USED) PRS PL1 DSS 4 BLWR IDR HI/LO GVR RED WHT 4 CPU GVR-1 Y G 2 W 8 HSIR BLWR HI/LO IDR 3 GV GVR-1 CPU NOTE #5 Y 5 6 NOT USED 24V 9 NOT USED 6 COM 24V BLK NOTE #12 9 PL6 ORN ALS-S ORN NOT ILK-1 BLU NOTE #8 2 LEGEND MASTER AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) SLAVE AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) BLOWER MOTOR RELAY, SPST-(N.O.) BLOWER MOTOR, 3- OR 4-SPEED, PERMANENT-SPLIT-CAPACITOR CAPACITOR MICROPROCESSOR AND CIRCUITRY DRAFT SAFEGUARD SWITCH, AUTO-RESET, SPST-(N.C.) ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FUSIBLE LINK FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FLAME-PROVING SENSOR ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED ORN NOT BLU 1 BLU ALS-M ALS-S BLWR BLWM CAP CPU DSS EAC-1 EAC-2 FL FRS FSE FU 2 8 G 5 COM PL1 GVR FSE BL K NO 4 WHT 2-C 1-M LS 1 NOTE #13 3 3-P 2 RED BLK TKR 7 R LGPS WHT GVR-2 HUM FL (WHEN USED) R FRS1 SEC-2 SEC-1 NOTE #12 1 NOT U NOTE #6 FRS2 7 HUM 1 FU TEST/TWIN GVR-2 HSIR 2 YEL NOT USED NOTE #6 SEC-1 OL HI EAC-1 HSIR PL2 RED HI/LO SPARE-2 COOL BLWR EAC-2 1 LO MED LO MED HI NOTE #7 SPARE-1 HEAT BRN COM EAC-1 1 BLU SLAV NOTE #4 L2 L1 GV GVR HI/LO HSI HSIR HUM IDM IDR ILK ILK-1 GAS VALVE-REDUNDANT OPERATORS GAS VALVE RELAY, DPST-(N.O.) -1 = VALVE -2 = HUMIDIFIER BLOWER MOTOR SPEED CHANGE RELAY, SPDT HOT SURFACE IGNITER (115 VAC) HOT SURFACE IGNITER RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) INDUCED DRAFT MOTOR, SHADED-POLE INDUCER MOTOR RELAY, SPST-(N.O.) BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) —13— LED LGPS LS OL PCB PL1 PL2 PL3 PL5 PL6 LIGHT-EMITTING DIODE LOW GAS-PRESSURE S LIMIT SWITCH, AUTO RE AUTO-RESET INTERNAL TEMP. SW., SPST (N.C.) PRINTED CIRCUIT BOAR 9-CIRCUIT CONNECTOR 2-CIRCUIT CONNECTOR 3-CIRCUIT IDM CONNEC 2-CIRCUIT HSI CONNEC 2-CIRCUIT TWINNING KI AIRFLOW AIRFL MASTER OR LH FURNACE 28 A 13⁄16″ 1⁄2″ F D 2 1⁄16″ 1″ 7⁄8- IN. DIA HOLE POWER ENTRY 7⁄8-IN. DIA HOLE CLOSURE ACCESSORY FLUE COLLARS D 7⁄8-IN. DIA HO CLOSURE, PO ENTRY 1 1⁄2-IN. DIA CLOSURE R.H. GAS E 5 3⁄8″ 12 5⁄16″ 13⁄16″ 5 13⁄16″ 2 11⁄16″ 1 3⁄4-IN. DIA HOLE GAS ENTRY 39 7⁄8″ HOLE THERMOSTAT WIRE ENTRY 7⁄8-IN. DIA HO CLOSURE, AC 1⁄2-IN. DIA HO CLOSURE, TH WIRE ENTRY 2 3⁄8″ 2 3⁄8″ 1⁄2-IN.DIA SIDE INLET 14 1⁄2″ 1 3⁄4″ 11⁄16″ 23 1⁄4″ 24 5⁄16″ BOTTOM INLET 3″ 11⁄16″ E E INLET INLET 11⁄16″ A93532 Fig. 12—Dimensional Drawing for Twinned 2–Speed Non-Condensing Furnaces Table 3—58TUA, 330AAV, and 330JAV 2-Speed Non-Condensing Furnace Dimensions (In.) INPUT HEATING SIZE (BTUH) 80,000 100,000 100,000 120,000 120,000 130,000 NOMINAL COOLING SIZE (BTUH) 48,000 48,000 60,000 48,000 60,000 60,000 A D E F 42-5/16 42-5/16 49-5/16 42-5/16 49-5/16 49-5/16 19-3/8 19-3/8 22-7/8 19-3/8 22-7/8 22-7/8 19-1/2 19-1/2 23 19-1/2 23 23 40-11/16 40-11/16 47-11/16 40-11/16 47-11/16 47-11/16 2. Determine desired furnace control operation and see appropriate section for use and application of twinning kit relay and harness assembly (TKR). Two-Stage Heat with Single-Stage Gas-Heat Thermostat (Field-Supplied) NOTE: This application allows both furnaces to operate in either high- or low-gas-heat as determined by adaptive mode of both furnace controls. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. a. Remove black and yellow wires from wire-tied TKR harness assembly for later use. b. Discard relay, red wire, and both white wires from TKR harness assembly. c. Use field-supplied electrical tape to insulate black wire’s 1/4-in. quick-connect terminal labeled 3. d. Connect black wire terminal labeled C to LH furnace control thermostat connection COM 24. e. Connect yellow wire terminal labeled TEST to LH furnace control TWIN/TEST terminal. f. Route black and yellow wire loose ends through snap bushings previously installed between furnaces. (See Fig. 4.) g. Connect black wire terminal labeled C-SLAVE to RH furnace control thermostat connection COM 24. h. Connect yellow wire terminal labeled TEST SLAVE to RH furnace control TWIN/TEST terminal. i. Connect yellow wire terminal labeled TEST SLAVE to RH furnace control TWIN/TEST terminal. Two-Stage Heat with 2-Stage Gas-Heat Thermostat (Field Supplied) NOTE: This attachment allows both furnaces to operate in either high- or low-gas heat as determined by thermostat’s 2-stage operation. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. a. Secure relay of TKR assembly to LH furnace control mounting bracket using 2 factory-supplied No. 6 X 3/4-in. LG screws. See Fig. 6 for location of holes to be drilled. —14— OUT 1″ 5 3⁄8″ 5 SLAVE OR R 2 1⁄16″ 19 13⁄16″ b. Connect TKR white wire labeled W from TKR to LH furnace control thermostat connection W/W1. c. Connect TKR black wire labeled C from TKR to LH furnace control thermostat connection COM 24. d. Connect TKR yellow wire labeled TEST (loose wire end near TKR) to LH furnace control TWIN/TEST terminal. e. Route remaining 4 loose TKR wires through: (1.) Strain relief bushing previously installed in 7/8-in. hole in right side of blower shelf. (2.) Gas control compartment of LH furnace. (3.) Snap bushings previously installed between furnaces. (See Fig. 4.) f. Connect TKR red wire labeled R-SLAVE from TKR to RH furnace control thermostat connection R. g. Connect TKR white wire labeled W-SLAVE from TKR to RH furnace control thermostat connection W/W1. h. Connect TKR black wire labeled C-SLAVE from TKR to RH furnace control thermostat connection COM 24V. i. Connect TKR yellow wire labeled TEST SLAVE from LH furnace control TWIN/TEST terminal to RH furnace control TWIN/TEST terminal. j. Proceed to item 3 to complete electrical connections. 3. Install LH furnace auxiliary limit switch harness ALS-M. NOTE: LH furnace ALS-M assembly DOES NOT include door switch. a. Drill 1/8-in. hole in blower housing 10 in. below blower shelf. (See Fig. 1.) b. Position ALS-M so reset button faces front of furnace. c. Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. d. Disconnect red transformer wire from LH furnace control SEC-1 connection. e. Cut off the 3/16-in. quick-connect terminal from red transformer wire. f. Strip red wire 1/8 in. and secure factory-supplied 1/4-in. quick-connect terminal. g. Connect red transformer wire connector to ALS-M wire connector labeled TRANS ASSY. h. Connect ALS-M wire connector labeled DOOR SWITCH or SEC 1 to LH furnace control SEC-1 terminal. i. Route 2-wire ALS-M connector PL8 through: (1.) Strain relief bushing previously installed in 7/8-in. hole in right side of blower shelf. (2.) Gas control compartment of LH furnace. (3.) Snap bushings previously installed between furnaces into gas control compartment of RH furnace. 4. Install RH furnace auxiliary door switch and auxiliary limit switch harness ALS-S/ILK-1. NOTE: RH furnace auxiliary limit switch harness assembly ALS-S/ILK-1 has door switch included. a. Drill 1/8-in. hole in blower housing 10 in. below blower shelf. (See Fig. 1.) b. Position ALS-S so terminals face front of furnace. c. Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. d. Relocate RH furnace junction box JB from left side to right side as shown in Fig. 1 if JB is not at right-hand side of RH furnace. For models produced before January 1995, blower door switch ILK must also be moved when JB changes location. e. Position auxiliary door switch ILK-1 on left side of RH furnace. f. Secure auxiliary door switch ILK-1 using factory-supplied No. 6 X 3/4-in. LG screw. g. Route 2-wire harness connector PL8 of ALS-S/ILK-1 assembly up through snap bushing in 7/8-in. hole in left side of blower shelf and into gas control compartment. h. Connect RH ALS-S connector PL8 to LH ALS-M connector PL8 that was routed through furnace casings. 5. Select identical blower speed taps at blower motor connectors in both furnaces. CAUTION: Failure to select identical blower speed taps in both furnaces can result in overheating of furnace components and possible loss of furnace operation and damage to the furnaces. 6. Dress wires to ensure they do not contact sharp or moving parts nor interfere with blower operation, removal of filters, or operation of switches. 7. Make all thermostat connections to LH furnace only. PROCEDURE 3—CONNECT ELECTRICAL COMPONENTS—COOLING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. When installing single- and 2-stage twinned outdoor units with twinned gas furnaces, it is necessary to use a field-supplied 24-vac pilot relay and a field-supplied 24/115-vac transformer as shown in Fig. 13 to prevent overloading furnace 24/115-vac transformer. —15— INDOOR THERMOSTAT W2 NOTES:1. TWO-SPEED FURNACES CAN BE USED WITH SINGLE-SPEED OUTDOOR UNITS. 2. TRANSFORMER = 115 VAC PRIMARY/24 VAC SECONDARY/40 VA. 3. RELAYS = 24 VAC COILS/PILOT DUTY/NORMALLY OPEN. 4. FOR 2-STAGE COOLING, USE RELAY 1 AND 2 (FIELD-SUPPLIED) AS SHOWN. 5. USE THIS WIRE ONLY FOR SINGLE-STAGE HEAT THERMOSTAT OPERATION IN ADAPTIVE HEATING MODE: HIGH-HEAT-ONLY SWITCH SW-1 IS OFF, AND LOW-HEAT-ONLY SWITCH SW-2 IS ON IN BOTH FURNACES. 6. USE THIS WIRE/TKR ONLY FOR 2-STAGE HEAT THERMOSTAT OPERATION IN NON-ADAPTIVE HEATING MODE: HIGH-HEAT-ONLY SWITCH SW-1 IS OFF, AND LOW-HEAT-ONLY SWITCH SW-2 IS OFF IN BOTH FURNACES. 7. TWINNING JUMPERS TJ SHALL BE SET IN THE APPROPRIATE POSITIONS (MASTER AND SLAVE) IN ACCORDANCE WITH THE START-UP AND ADJUSTMENT PROCEDURE. NOTE 6 W/W1 R G C Y/Y2 NOTE 4 Y1 Y/Y2 COIL COIL RELAY RELAY NOTE 4 LEFT HAND FURNACE (MASTER) Y/Y2 C G NOTE 4 (FIELD SUPPLIED) NOTE 3 W/W1 BLK C NOTE 5 C W2 TWIN TEST Y/Y2 TEST C G R C-SLAVE W/W1 R-SLAVE 24 VAC C Y1 TWIN TEST YEL TEST-SLAVE NOTES 5 & 6 1 4 3 2 TKR NOTE 6 RED NOTE 6 WHT NOTE 6 USE ONLY TWINNING KIT PARTS NOTE 4 BLK NOTE 6 W2 W-SLAVE BLK W NOTE 6 WHT TRANS (FIELD SUPPLIED) NOTE 2 115 VAC R RIGHT HAND FURNACE (SLAVE) NOTE 4 Y1 C Y/Y2 Y1 Y/Y2 OUTDOOR UNIT NO. 2 OUTDOOR UNIT NO. 1 A98225 Fig. 13—Twinning 2 Outdoor Units with Two 2-Speed Furnaces with 1 Thermostat PROCEDURE 4—VENTING Refer to the Installation, Start-Up, and Operating Instructions supplied with each furnace for venting information. CAUTION: When common-venting twinned, Category I (negative pressure venting), non-condensing furnaces, excessive condensate may occur as a result of oversized vent systems. Dedicated vents and/or proper vent sizing per the furnace Installation, Start-Up, and Operating Instructions will reduce the potential for condensation. PROCEDURE 5—GAS SUPPLY PIPING NOTE: All gas connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supplyand return-air ducts. Furnaces are recommended to be provided with a single shutoff valve. However, individual shutoff valves may be required by local codes or jurisdictions. Refer to Installation, Start-Up, and Operating Instructions provided with each furnace for additional gas supply information. PROCEDURE 6—ELECTRICAL SUPPLY CONNECTIONS NOTE: All electrical power connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supply- and return-air ducts. 1. Each furnace shall be connected to its own 115-vac power supply. The twinning kit installation interconnects the furnaces, allowing them to operate as a single furnace. The L1 (black) connection to each furnace must be connected to circuit breakers connected to the same service panel 115-vac phase leg. On single-phase (residential) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 1 space to be connected to the same leg of the 1-phase power supply. —16— 5 3 6 9 2 8 4 7 1 SET-UP SWITCHES SW4 SW3 SW2 SW1 ON OFF PR2 PR1 L1 L2 COM HI-COOL EAC-2 HI-GAS -HEAT LO-GAS -HEAT 9 12 6 10 11 3 5 8 2 7 TWIN/TEST CONNECTOR 4 MASTER SLAVE 1 1 1 THERMOSTAT CONNECTIONS EAC-1 PARK SEC-1 FU1 3 MASTER SEC-2 TWINNING JUMPER TJ LED SLAVE A93534 Fig. 14—Two-Stage Furnace Control On 3-phase (commercial) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 2 spaces to be connected to the same leg of the 3-phase power supply. The proper 115-vac phasing of furnace connections permits 24-vac transformer phasing as described below. 2. Phasing of the connected 24-vac transformer secondary circuits can be determined with the LED status of both furnaces. See furnace Installation, Start-Up and Operating Instructions and status code labels on blower doors. The furnaces’ transformers’ black leads should be connected to PR1 connectors and white leads to PR2 connectors on controls. If 1 or both LEDs are rapidly flashing, disconnect lead at TEST/TWIN terminal of LH furnace and observe LED at each furnace. IF: a. Both LEDs are on continuously: System phasing is okay. b. One or both LEDs are rapidly flashing: (1.) Line voltage polarity is reversed. (2.) Reverse SEC-1 and SEC-2 in furnace with rapid flashing LED. c. One LED is off, 1 LED is on continuously: (1.) The 24-vac circuit is inoperative on furnace with LED light off. (2.) Check transformers, auxiliary limits, and door switches in both furnaces and correct problem. 3. Reconnect lead at TWIN/TEST terminal of LH furnace and observe LED at each furnace. The LEDs will glow steady for proper phasing. PROCEDURE 7—START-UP AND ADJUSTMENT Refer to Installation, Start-Up, and Operating Instructions supplied with furnace for detailed information. 1. Shut off all power and gas to both furnaces. 2. Position TWINNING JUMPERS TJ on furnace controls. (See Fig. 14.) a. The LH furnace control TWINNING JUMPER TJ MUST remain in the MASTER position. b. The RH furnace control TWINNING JUMPER TJ MUST be moved to the SLAVE position. 3. Determine desired furnace control operation and position set-up switches on furnace control. (See Fig. 14.) Two-Stage Heat with Single-Stage Gas-Heat Thermostat a. Position SW1 switch on controls in BOTH furnaces to OFF. b. Position SW2 switch on controls in BOTH furnaces to OFF. c. Position SW3 and SW4 switches on control in BOTH furnaces to desired gas-heat blower off delay. (See furnace Installation, Start-Up, and Operating Instructions for further details.) Two-Stage Heat with 2-Stage Gas-Heat Thermostat a. Position SW1 switch on controls in BOTH furnaces to OFF. b. Position SW2 switch on controls in BOTH furnaces to ON. c. Position SW3 and SW4 switches on controls in BOTH furnaces to desired gas-heat blower off delay. (See furnace Installation, Start-Up, and Operating Instructions for further details.) 4. Attach twinning connection diagram label over existing wiring label on inside of LH furnace blower door. —17— 5. Attach twinning schematic diagram label over existing wiring label on inside of RH furnace blower door. 6. Turn on power and gas to both furnaces. 7. Reinstall blower access doors on both furnaces. 8. Determine furnace model. Using appropriate section below, operate furnaces through 2 cycles in each mode to confirm correct operation by operating only the thermostat. a. Single- or 2-stage gas heating thermostat R-to-W/W1 for low-gas heat. Single-stage thermostat with adaptive heating mode causes furnace to operate in low-gas-heat mode for up to 16 minutes, and then furnace automatically switches to high-gas heat. First stage of a 2-stage thermostat without adaptive heating mode causes furnace to operate in low-gas-heat mode indefinitely. b. First- and second-stage of 2-stage heating thermostat R-to-W/W1-and-W2 for high-gas-heat. c. Thermostat R-to-G for continuous fan or 2-speed cooling low-cool blower. d. Cooling thermostat R-to-G-and-Y/Y2 for single-speed cooling blower or for 2-speed cooling high-cool blower. 9. Reinstall control doors on both furnaces.Reinstall control doors on both furnaces. 10. Instruct user in operation of furnaces and thermostat. PROCEDURE 8—SEQUENCE OF OPERATION See Fig. 15 and 16 for 2-speed non-condensing furnace twinning connection and schematic wiring diagrams while reviewing sequence of operation. Twinning operation is controlled by LH or MASTER furnace. The TWIN/TEST and COM 24V connection wires ensure the 2 furnaces coordinate their blower operation. When either furnace requires blower operation, both furnaces operate their blowers at the same speed (the highest speed required by either furnace). Both furnaces operate simultaneously in the same mode: low-gas heat, high-gas heat, low-cool, high-cool, or continuous fan. Exceptions can occur if a safety device on either furnace is activated (such as low-gas-heat or high-gas-heat pressure switch, flame roll-out switch, limit switch, draft safeguard switch, twinning kit auxiliary limit switch, or flame-proving sensor). In such a case, the other furnace continues to operate unless the safety device is the flame roll-out, limit, or twinning kit auxiliary limit switch, in which case both furnaces respond. Two-Stage Heat with Single-Stage Gas-Heat Thermostat See Section II, Procedure 2 for furnace and kit components used. NOTE: Set-up switches SW1 and SW2 in BOTH furnaces are in OFF position. 1. LH furnace control determines whether furnaces are both operating in low-gas heat or high-gas heat, depending on the control’s adaptive gas heating mode when the R-to-W/W1 circuit is closed in LH furnace. 2. Operation in all modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on sequence of operation. Two-Stage Heat with 2-Stage Gas-Heat Thermostat See Section II, Procedure 2 for furnace and kit components used. NOTE: Set-up switches SW1 in BOTH furnaces are in OFF position, and set-up switches SW2 in BOTH furnaces are in ON position. 1. The 2-stage thermostat (NOT furnace control’s adaptive gas heating mode) determines whether furnaces are both operating in low-gas heat or high-gas heat, depending on whether 1 or both thermostat stages (W/W1 or W/W1-and-W2) are calling for heat. 2. Operation in all modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on sequence of operation. SECTION III: MODELS 58MCA, 58MXA, 340MAV, 350MAV, 490AAV, AND PG9MAA UPFLOW SINGLE-SPEED CONDENSING HSI FURNACES PROCEDURE 1—INSTALL FURNACES NOTE: Multipoise units must be installed in UPFLOW configuration. Refer to Fig. 17 and 18 for appearance and dimensional drawing of twinned furnaces and their connection locations. 1. Select 2 identical heating and airflow furnaces. (See Table 4.) 2. Remove bottom closure panels from both furnaces. (See Fig. 3.) a. Remove 2 screws from front filler panel. b. Rotate front filler panel downward to remove. c. Remove bottom closure panel and discard. d. Reinstall front filler panel. 3. Apply 2 factory-supplied foam strips to mating side of each furnace. Locate strips equal distance from top and bottom as shown in Fig. 19. 4. Position furnaces against each other on return-air plenum. On furnaces AFTER Serial No. 2894A00001, adjust and shim each furnace to align unused condensate drain line holes in lower section of both furnaces holes which will be used for wire routing between furnaces. (See Fig. 19.) 5. Drill two 1/8-in. holes, approximately 1 in. below discharge air flange, from inside top of discharge opening and through both furnaces. (See Fig. 20.) 6. Drive 1 factory-supplied No. 6 X 3/4-in. LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces. —18— FURNACE CONNECTION DIAG BLK HPS BRN BRN ILK RED WHT GRY GRN BLK RED FACTORY SETTINGS 8 7 9 COM HI MED-HI MED-LO LO NOTE #4 EAC-2 PARK SEC1 1 BRN WHT BLK YEL BLU RED * PASSES THROUGH HOLES IN CASINGS TRAN RED BLWM BRN R W2 COM W/W1 Y/Y2 24V CAP BLK BLU FU1 BLOWER-OFF BLOWER-OF LOW-HEAT O HIGH-HEAT O WHT RED BLU WHT L1 COMMON SEC2 S YEL WHT SW 1 2 3 4 ON OFF BLK 1 2 MAKE THERMOSTAT CONNECTIONS TO ONLY THE LEFT HAND FURNACE. LED PL3 PR2 L2 HI-COOL HI-GAS HEAT 12 11 10 G HUM FU2 FURNACE CONTROL CPU P1 LO-GAS HEAT EAC-1 3 2 SW 1 2 3 4 ON OFF RED R W2 COM W/W1 Y/Y2 24V GRN BLK 3 BRN PR1 M WHT GRN BLK ORN TWIN TEST TJ 3 L2 WHT PL2 FACTORY SETTINGS WHT BLK 2 FUSED DISCONNECT SWITCH (WHEN REQ’D) NOTE #1 BLK RED FURNACE CONTROL CPU RED 1 WHT BLK 2 ORN YEL BLOWER-OFF DELAY BLOWER-OFF DELAY LOW-HEAT ONLY HIGH-HEAT ONLY WHT BLK GRY WHT L1 DSS * JB ORN FSE NOTE #7 (WHEN USED) YEL RED GRN 1 FRS1 (WHEN USED) C NOTE #6 GRN GRN IDM HSI FRS2 RED GV M BLU PL6 LS TKR HI P LGPS FRS1 (WHEN USED) RED RED GRY YEL ORN RED RED WHT NOTE #7 2 WHT BLK LPS 1 BLU FRS2 RED WHT LS 4 ORN BLK 3 RED MASTER OR LH FURNACE KEEP TWINNING JUMPER IN "MASTER" POSITION ON MASTER FURNACE. PL9 ALS-M RED ORN PL8 BLU 2 2 BLU G MAKE NO THERMO CONNECTIONS TO RIGHT HAND FURN ILK-1 ALS-S ORN ORN 1 1 ORN LEGEND JUNCTION ALS-M MASTER AUX. LIMIT SWITCH, OVERTEMP. - MANUAL RESET, SPST (N.C.) ILK BLOWER DOOR INTERLOCK SWITCH, SPST (N.O.) ALS-S SLAVE AUX. LIMIT SWITCH, OVERTEMP. - MANUAL RESET, SPST (N.C.) JB JUNCTION BOX BLWM BLOWER MOTOR, 4 SPEED, PERMANENT-SPLIT-CAPACITOR LED LIGHT-EMITTING DIODE FOR STATUS CODES LGPS LOW GAS-PRESSURE SWITCH, SPST (N.O.) LPS LOW-HEAT PRESSURE SWITCH, SPST (N.O.) LS LIMIT SWITCH, OVERTEMPERATURE-AUTO RESET, SPST (N.C.) PL1 12-CIRCUIT CONNECTOR FACTORY CONTROL WIRI PL2 9-CIRCUIT CONNECTOR FIELD POWER WIRING (11 TERMINAL CONTROL TERMINAL CAP CAPACITOR CPU MICROPROCESSOR AND CIRCUITRY DSS DRAFT SAFEGUARD SWITCH, SPST (N.C.) EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC, 1 AMP MAX.) EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON) PL3 3-CIRCUIT IDM CONNECTOR FRS1 FLAME ROLLOUT SWITCH OVERTEMP.-MANUAL RESET, SPST (N.C.) PL6 2-CIRCUIT HSI CONNECTOR FIELD ACCESSORY WIRIN FRS2 FLAME ROLLOUT SWITCH OVERTEMP.-MANUAL RESET, SPST (N.C.) PL8 2-CIRCUIT TWINNING CONNECTOR FIELD WIRING SCREW TE FSE FLAME-PROVING SENSOR ELECTRODE PL9 1-CIRCUIT TWINNING CONNECTOR FU1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FU2 FUSE, FIELD INSTALLED GV GAS VALVE, REDUNDANT LOW-HEAT OPERATORS, 2-STAGE HPS HIGH-HEAT PRESSURE SWITCH, SPST (N.O.) HPSR HIGH-HEAT PRESSURE SWITCH RELAY, SPST (N.C.) HSI HOT-SURFACE IGNITER (115 VAC) HUM 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) IDM INDUCED DRAFT MOTOR, 2-SPEED, SHADED-POLE ILK-1 SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST (N.O.) * SW1 * SW2 * SW3 & 4 TJ HIGH-HEAT-ONLY SWITCH, SPST (MANUAL) LOW-HEAT-ONLY SWITCH, SPST (MANUAL) BLOWER-OFF DELAY SETTING SWITCHES, SPST (MANUAL) TWINNING JUMPER, SPDT FOR MASTER OR SLAVE STATUS-(MANUAL-CHANGE-OVER) TKR TWINNING KIT RELAY, SPST (N.O.) TRAN TRANSFORMER-115VAC / 24VAC TWIN / TEST —19— 1-CIRCUIT TWINNING BUSS CONNECTOR, ALSO COMPONENT TEST FACTORY POWER WIRING FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE TO 115VAC FIELD DISCONNECT SWITCH MASTER OR LH FURNACE NOTE #1 ILK BHI/LOR LO LO-GAS HEAT HI-GAS HEAT BLWR MAKE THERMOSTAT CONNECTIONS TO ONLY THE LEFT HAND FURNACE BLW BLWM BRN COM NOTE #4 COMMON HSIR PL6 1 HSI LO 4 IDR PL3 7 HI 3 COM I TRAN SEC-2 RED FU N/A 5 6 N/A SEC-1 12 N/A 2 MGVR-2 R W/W1 MASTER SW1 FRS2 LS FRS1 (WHEN USED) HUM 3 TWINNING JUMPER TJ 6 DSS 5 (WHEN USED) LGPS YEL SLAVE LPS MGVR-1 M 10 G ALS-M C NOTE #6 P HI W2 GV COM SW4 SW3 SW2 BLK MASTER AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) SLAVE AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR, 4-SPEED, PERMANENT-SPLIT-CAPACITOR BLOWER MOTOR RELAY, SPST-(N.O.) CAPACITOR MICROPROCESSOR AND CIRCUITRY DRAFT SAFEGUARD SWITCH, SPST (N.C.) ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SWITCH OVERTEMP. -MANUAL RESET, SPST-(N.C.) FLAME ROLLOUT SWITCH OVERTEMP. -MANUAL RESET, SPST-(N.C.) FLAME-PROVING SENSOR ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED GAS VALVE-REDUNDANT LOW-HEAT OPERATORS, 2-STAGE HIGH-HEAT PRESSURE SWITCH, SPST-(N.O.) HIGH-HEAT PRESSURE SWITCH RELAY, SPST-(N.C.) HOT SURFACE IGINITER (115 VAC) HOT SURFACE IGNITER RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) G BLK FSE BLK 3 WHT 1 TKR RED 4 2 BLK WHT ORN BLU LEGEND ALS-M ALS-S BHI/LOR BHT/CLR BLWM BLWR CAP CPU DSS EAC-1 EAC-2 FRS1 FRS2 FSE FU GV HPS HPSR HSI HSIR HUM Y/Y2 PASSES THROUGH HOLES IN CASINGS 7 8 N\A 11 N/A IDM IDR IHI/LOR ILK ILK-1 JB LED LGPS LPS LS MGVR * * * INDUCED DRAFT MOTOR, 2-SPEED, SHADED-POLE INDUCER MOTOR RELAY, SPST-(N.O.) TJ INDUCER MOTOR SPEED CHANGE RELAY, SPDT BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) TKR JUNCTION BOX TRAN LIGHT-EMITTING DIODE FOR STATUS CODES LOW GAS PRESSURE SWITCH, SPST-(N.O.) TWIN / TEST LOW-HEAT PRESSURE SWITCH, SPST-(N.O.) LIMIT SWITCH, OVERTEMPERTURE-AUTO RESET, SPST(N.C.) MAIN GAS VALVE RELAY, DPST-(N.O.) -1 = VALVE -2 = HUMIDIFIER PL1 12-CIRCUIT CONNECTOR PL2 9-CIRCUIT CONNECTOR PL3 3-CIRCUIT IDM CONNECTOR PL6 2-CIRCUIT HSI CONNECTOR PL8 2-CIRCUIT TWINNING CONNECTOR PL9 1-CIRCUIT TWINNING CONNECTOR SW1 HIGH-HEAT-ONLY SWITCH, SPST-(MANUAL) SW2 LOW-HEAT-ONLY SWITCH, SPST-(MANUAL) SW3 & 4 BLOWER-OFF DELAY SETTING SWITCHES, SPST-(MANUAL) —20— MASTER SW1 HPS 1 Y/Y2 W/W1 WHT NOTE #7 NOTE #7 4 BLU TWIN TEST PL1 CPU W2 R RED 9 TWIN / TEST SLAVE NO 2 NOTE #5 HUM MOVE TWINNING JUMPER TO "SLAVE" POSITION ON SLAVE FURNACE. 1 HPSR PL9 ORN RED IDM PR2 115VAC 24VAC WHT 2 1 8 PR1 H 2 9 IHI / LOR YEL MAKE NO THERMOSTAT CONNECTIONS TO RIGHT HAND FURNACE PL2 3 KEEP TWINNING JUMPER IN "MASTER" POSITION ON MASTER FURNACE. L1 HI EAC-2 EAC-1 MED-LO MED-HI PARK HI-COOL ILK L2 BRN CAP BHT/CLR L1 TO 115VA FURNACE SCHEMATIC DIAGRAM EQUIPMENT GROUND 1 COM PL8 ORN BLU ORN 2 TWINNING JUMPER, SPDT FOR MASTER OR S STATUS-(MANUAL CHANGE-OVER) TWINNING KIT RELAY, SPST-(N.O.) TRANSFORMER-115VAC / 24VAC 1-CIRCUIT TWINNING BUSS CONNECTOR, ALS COMPONENT TEST JUNCTION TERMINAL CONTROL TERMINAL FACTORY POWER WIRING (115VAC) FACTORY CONTROL WIRING (24VAC) FIELD ACCESSORY WIRING (24VAC) CONDUCTOR ON PCB FIELD WIRING SCREW TERMINAL FIELD GROUND 26 15/16″ 26 1/4 TYP A 24 1/2″ 22 1/4″ AIRFLOW AIRFLOW 13/16″ 2-IN. COMBUSTIONAIR CONN F D OUTLET D OUTLET 13/16″ 7/8-IN. DIA POWER CONN 1 /2-IN. GAS CONN 2-IN. VENT CONN 33 1/4″ TYP 32 5/8″ TYP 13/16″ 30 TYP 29 5/8″ TYP 27 5/8″ 1/2-IN. DIA THERMOSTAT ENTRY 22 11/16″ 14 1/2″ 7 /8-IN. DIA ACCESSORY POWER ENTRY 30 1/2″ 27 1/2″ TYP CONDENSATE DRAIN TRAP LOCATION (USED FOR LH FURNACES BEFORE SERIAL NO. 2894A00001) 24 1/2″ 17 5/16″ 18 1/4″ 3/8″ SIDE INLET 11/4″ 1" 23 1/4″ SIDE INLET 9 TYP CONDENSATE DRAIN LOCATION (USED FOR LH FURNACES AFTER SERIAL NO. 2894A00001) 26 15/16″ TYP 11/16″ INLET INLET E E 11/16″ CONDENSATE DRAIN TRAP LOCATION (USED FOR RH FURNACES BEFORE SERIAL NO. 2894A00001) —21— CONDENSAT DRAIN LOCA (USED FOR R SERIAL NO. 2 Table 4—58MCA, 58MSA, 58MXA, 340MAV, 345MAV, 350MAV, 490AAV, and PG9MAA Single-Speed Condensing Furnace Dimensions (In.) INPUT HEATING SIZE (BTUH) 60,000 80,000 80,000 100,000 100,000 120,000 NOMINAL COOLING SIZE A D E F 48,000 48,000 60,000 48,000 60,000 60,000 35 35 42 42 42 49 15-7/8 15-7/8 19-3/8 19-3/8 19-3/8 22-7/8 16 16 19-1/2 19-1/2 19-1/2 23 33-3/8 33-3/8 40-3/8 40-3/8 40-3/8 47-3/8 POWER JUNCTION BOX RELOCATED HERE AUXILIARY LIMIT DOOR SWITCH (ILK-I) 8″ TYP SLAVE 24-V TRANSFORMER SLAVE BLOWER ACCESS PANEL DOOR SWITCH MASTER AUXILIARY LIMIT SWITCH (ALS-M) SLAVE AUXILIARY LIMIT SWITCH (ALS-S) TWINNING KIT RELAY (TKR) MASTER BLOWER ACCESS PANEL DOOR SWITCH UNUSED CONDENSATE DRAIN LINE HOLES WITH SNAP BUSHING INSTALLED MASTER 24-V TRANSFORMER → A94261 Fig. 18—Twinning Kit Installed on Single-Speed and 2-Speed Condensing Furnaces (AFTER Serial No. 2894A00001)—Single-Speed Shown 7. On furnaces AFTER Serial No. 2894A00001, insert 1 snap bushing through each adjoining unused condensate drain line hole of each furnace. (See Fig. 17 and 18.) 8. Connect return- and supply-air ducts to furnaces. Seal duct connections to prevent air leakage. 9. 115-V junction boxes JB must be located on right side of right-hand furnace and left side of left-hand furnace. Relocate as necessary. (See Fig. 18.) WARNING: DO NOT use the back of the furnace for return-air duct connections as limit cycling will occur. A failure to follow this warning can cause a fire, personal injury, or death. PROCEDURE 2—CONNECT ELECTRICAL COMPONENTS—HEATING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. See electrostatic discharge precaution on page 2. 1. Remove blower access doors from both furnaces. 2. Install twinning kit relay (TKR) and harness (furnaces AFTER Serial No. 2894A00001). The twinning kit can be used for single-stage or 2-stage heating operation. —22— 7⁄8-IN. DIA POWER CONNECTION HOLE (USED ON FURNACES BEFORE SERIAL NO. 2894A00001) FOAM STRIPS UNUSED CONDENSATE DRAIN HOLE (USED ON FURNACES AFTER SERIAL NO. 2894A00001) A93538 Fig. 19—Location of Foam Strips and Hole to be Used for Twinning Kit Wire Routing SCREW DISCHARGE OPENINGS TOGETHER A93539 Fig. 20—Attaching Furnaces Together Single-Stage Heat with Single-Stage Gas-Heat Thermostat (Field Supplied) NOTE: This application of TKR allows both furnaces to operate in heating mode simultaneously. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. a. Mount TKR assembly to underside of LH furnace control enclosure using 1 No. 6 sheet metal screw (field supplied). Screw hole is located to left of door switch near front edge of control. (See Fig. 21.) → NOTE: See Fig. 7. b. Route 3 loose wires (black, yellow, and white) from TKR assembly wire harness through T-STAT/HUM hole adjacent to door switch. (See Fig. 21.) NOTE: Cut wire tie near TKR to provide appropriate length of wires for connection. c. Connect TKR white wire labeled W from TKR to LH furnace control thermostat connection W. d. Connect TKR black wire labeled C from TKR to LH furnace control thermostat connection COM 24V. e. Connect TKR yellow wire labeled TEST to LH furnace control TEST/TWIN terminal. f. Refer to Fig. 17, 18, and 21 and route remaining 4 loose TKR wires through the following: (1.) Snap bushing previously installed between furnaces in unused condensate drain holes. (2.) RH furnace thermostat cable hole T-STAT/HUM in control box. g. Connect TKR red wire labeled R-SLAVE from TKR to RH furnace control thermostat connection R. h. Connect TKR white wire labeled W-SLAVE from TKR to RH furnace control thermostat connection W. i. Connect TKR black wire labeled C-SLAVE from TKR to RH furnace control thermostat connection COM 24V. j. Connect TKR yellow wire labeled TEST SLAVE from LH furnace control TEST/TWIN terminal to RH furnace control TEST/TWIN terminal. → NOTE: All field thermostat connections are to be made to LH furnace control ONLY. k. Proceed to item 3 “Install LH furnace auxiliary limit switch harness ALS-M” to complete electrical connections. Two-Stage Heat with 2-Stage Gas-Heat Thermostat (Field Supplied) —23— CONTROL CENTER TKR RELAY BLOWER ACCESS PANEL DOOR SWITCH TKR HARNESS WIRES ROUTED THROUGH THERMOSTAT CABLE HOLE TKR HARNESS WIRES TO RH FURNACE A94245 Fig. 21—Twinning Kit Relay Mounted on Control Mounting Bracket for LH Furnace (AFTER Serial No. 2894A00001) NOTE: This modification allows LH furnace only to operate in heating mode for first-stage heat or both furnaces to operate in heating mode for second-stage heat as determined by a 2-stage thermostat. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. To operate furnaces in 2-stage heating mode when a 2-stage thermostat controls the staging, install TKR as described above, then modify TKR wiring as follows: CAUTION: Supply-air temperature will be uneven left-to-right when only master system is operating. NOTE: See Fig. 8. a. Disconnect TKR white wire labeled W from LH furnace control thermostat connection W. b. Cut terminal off TKR white wire labeled W and strip 1/4 in. c. Connect 2-stage thermostat W2 connection to TKR white wire labeled W. → NOTE: ALL other 2-stage thermostat connections are to be made to LH furnace control center ONLY. d. Proceed to item 3 “Install LH furnace auxiliary limit switch harness ALSM” to complete electrical connections. 3. Install LH furnace auxiliary limit switch harness ALS-M. For Series A/100 and B/111 of Models 58MCA, 58MXA, 340MAV, 350MAV, and 490AAV furnaces, follow the procedure below: NOTE: LH furnace ALS-M assembly DOES NOT include door switch. a. Drill 1/8-in. hole in blower housing 8 in. below blower shelf as shown in Fig. 18. b. Position ALS-M so reset button faces front of furnace. c. Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. d. Disconnect red transformer wire from LH furnace door switch. e. Connect removed red transformer wire to ALS-M wire connector labeled TRANS ASSY. f. Connect ALS-M connector labeled DOOR SWITCH or SEC 1 to LH furnace door switch, where red wire was removed. g. Route 2-wire ALS-M connector from LH furnace to RH furnace (furnaces AFTER Serial No. 2894A00001). Refer to Fig. 18 and route wires through unused condensate drain line hole with snap bushing. For Series C/121 and D/131 of Models 58MCA, 58MXA, 340MAV, 350MAV, and 490AAV and Series A/101 and B/111 of Models 58MSA, 345MAV, and PG9MAA furnaces, follow the procedure below: —24— AUXILIARY LIMIT DOOR SWITCH AND BRACKET AS SUPPLIED NOTCHED CORNER BRACKET REVERSED AUXILIARY LIMIT DOOR SWITCH A93540 Fig. 22—Reversing Auxiliary Limit Door Switch Bracket NOTE: LH furnace ALS-M assembly DOES NOT include door switch. a. Drill 1/8-in. hole in blower housing 8 in. below blower shelf as shown in Fig. 18. b. Position ALS-M so reset button faces front of furnace. c. Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. d. Disconnect red transformer wire from SEC-1 connection. e. Cut off 3/16-in. quick-connect terminal from red transformer wire. f. Strip red wire 1/8 in. and secure factory-supplied 1/4-in. quick-connect terminal. g. Connect removed red transformer wire to ALS-M wire connector labeled TRANS ASSY. h. Connect ALS-M connector labeled DOOR SWITCH or SEC 1 to LH furnace control SEC-1 terminal. Cut wire tie and route wire through T-STAT/HUM hole in control box to control board. i. Route 2-wire ALS-M connector from LH furnace to RH furnace through unused condensate drain line hole with snap bushing. 4. Install RH furnace (SLAVE) auxiliary door switch and harness (ALS-S/ILK-1). NOTE: RH furnace ALS-S assembly HAS door switch included. a. Install auxiliary limit switch (ALS-S). (1.) Drill 1/8-in. hole in blower housing 8 in. below blower shelf as shown in Fig. 18. (2.) Position ALS-S so terminals face front of furnace. (3.) Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. b. Install auxiliary door switch (ILK-1). (1.) Remove wires from ALS-S door switch (ILK-1). (2.) Reverse bracket on ALS-S door switch (ILK-1). (See Fig. 22.) NOTE: It is easier to remove switch from bracket by pushing the switch away from flexible catch side and rotating the flexible side through the bracket first. Door switch will only fit in bracket 1 way. Pivot side of switch will be located toward notched opening of bracket. (3.) Reconnect wires to ALS-S door switch (ILK-1). (4.) Drill 7/32-in. hole in left side of RH furnace blower shelf for mounting door switch as shown in Fig. 18. (5.) Secure ALS-S door switch (ILK-1) using factory-supplied No. 6 X 3/4-in. LG screw. c. Connect RH furnace 2-wire ALS-S connector PL6 to LH furnace 2-wire ALS-M connector PL6 that was routed through furnace casings. 5. Select identical blower speed taps at blower motor connections on control center in both furnaces. CAUTION: Failure to select identical blower speed taps in both furnaces can result in overheating of furnace components and possible loss of furnace operation and damage to the furnace. 6. Dress wires to ensure they do not contact sharp edges or moving parts, nor interfere with blower operation, removal of filters, or operation of switches. 7. Make all thermostat connections to the LH furnace only. —25— A A96128 Fig. 23—Rooftop Termination (Dimension “A” is Touching or 2-in. Maximum Separation) PROCEDURE 3—CONNECT ELECTRICAL COMPONENTS—COOLING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. When installing twinned outdoor units with twinned gas furnaces, it is necessary to use a field-supplied 24-vac pilot-duty relay and a field-supplied 24/115-vac transformer as shown in Fig. 7 or 8 to prevent overloading furnace 24/115-vac transformer. PROCEDURE 4—VENTING Refer to Installation, Start-Up, and Operating Instructions supplied with each furnace for venting information. Each furnace must always be individually vented. Do not common-vent or breach-vent condensing furnaces. For direct-vent installations, refer to Fig. 23, 24, 25, 26, or 27 for proper termination. It is important that vent terminations be made as shown to avoid recirculation of flue gases. VENT VENT A COMBUSTION AIR A93056 Fig. 24—Concentric Vent and Combustion-Air Roof Termination (Dimension “A” is Touching or 2-in. Maximum Separation) PROCEDURE 5—GAS SUPPLY PIPING NOTE: All gas connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supplyand return-air ducts. Furnaces are recommended to be provided with a single shutoff valve. However, individual shutoff valves may be required by local codes or jurisdictions. Refer to Installation, Start-Up, and Operating Instructions provided with each furnace for additional gas supply information. PROCEDURE 6—CONDENSATE DRAIN CONNECTIONS (FURNACES AFTER SERIAL NO. 2894A00001) The condensate trap is factory installed in blower shelf and factory connected for UPFLOW applications. Install condensate trap extension drain such that field drain connection are on the left side for LH (MASTER) furnace and on right side for RH (SLAVE) furnace. (See Fig. 18.) See furnace Installation, Start-Up, and Operating Instructions for details on attaching field drain. PROCEDURE 7—ELECTRICAL SUPPLY CONNECTIONS NOTE: All electrical power connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supply- and return-air ducts. 1. Each furnace shall be connected to its own 115-vac power supply. The twinning kit installation interconnects the furnaces, allowing them to operate as a single furnace. The L1 (black) connection to each furnace must be connected to circuit breakers connected to the same service panel 115-vac phase leg. On single-phase (residential) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 1 space to be connected to the same leg of the —26— VENT COMBUSTION AIR COMBUSTION AIR A A96129 Fig. 26—Sidewall Termination of 12 in. or Less (Dimension “A” is Touching or 2-in. Maximum Separation) 1″ MAXIMUM (TYP) COMBUSTION AIR VENT A VENT A93057 Fig. 25—Concentric Vent and Combustion-Air Side Termination (Dimension “A” is Touching or 2-in. Maximum Separation) VENT COMBUSTION AIR COMBUSTION AIR A A96130 Fig. 27—Sidewall Termination of More Than 12 in. (Dimension “A” is Touching or 2-in. Maximum Separation) 1-phase power supply. —27— On 3-phase (commercial) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 2 spaces to be connected to the same leg of the 3-phase power supply. The proper 115-vac phasing of furnace connections permits 24-vac transformer phasing as described below. 2. Phasing of the connected 24-vac transformer secondary circuits can be determined with the LED status of both furnaces. See furnace Installation, Start-Up, and Operating Instructions and status code label on blower access panel or main furnace door. The furnaces’ transformers’ black leads should be connected to PR1 connectors and white leads to PR2 connectors on controls. If 1 or both LEDs are rapidly flashing, disconnect lead at TEST/TWIN terminal of LH furnace and observe LED at each furnace. IF: a. Both LEDs are on continuously: System phasing is okay. b. One or both LEDs are rapidly flashing: (1.) Line voltage polarity is reversed. (2.) Reverse SEC-1 and SEC-2 in furnace with rapid flashing LED. c. One LED is off, 1 LED is on continuously: (1.) The 24-vac circuit is inoperative on furnace with LED light off. (2.) Check transformers, auxiliary limits, and door switches in both furnaces and correct problem. 3. Reconnect lead at TWIN/TEST terminal of LH furnace and observe LED at each furnace. The LEDs will glow steady for proper phasing. PROCEDURE 8—START-UP AND ADJUSTMENT NOTE: Refer to Installation, Start-Up, and Operating Instructions supplied with furnace for detailed information. 1. Shut off all power and gas to both furnaces. 2. Position blower off delay switches on controls in BOTH furnaces to the SAME desired blower off delay in heating. See furnace Installation, Start-Up, and Operating Instruction for further details. If 1 furnace control has blower off delay switches and the other has a fixed jumper wire which sets blower off delay at 135 sec, the control with selectable switches MUST be set for 135 sec off delay. 3. Attach twinning connection diagram label over existing wiring label of LH furnace (located on inside of blower access panel or main furnace door). 4. Attach twinning schematic diagram label over existing wiring label of RH furnace (located on inside of blower access panel or main furnace door). 5. Turn on power and gas to furnaces. 6. Operate furnaces through 2 heating cycles to ensure proper operation. 7. Reinstall all furnace access doors. PROCEDURE 9—SEQUENCE OF OPERATION See Fig. 28 and 29 for condensing furnace twinning connection and schematic wiring diagrams while reviewing sequence of operation. Twinning operation is controlled by LH or MASTER furnace. The TEST/TWIN connection wire ensures the 2 furnaces coordinate their blower operation. When either furnace requires blower operation, both furnace blowers operate at same speed. Both furnaces operate simultaneously in the same mode: heat, cool, or continuous fan. Exceptions can occur if a safety switch on either furnace is opened by a problem (such as pressure switch, flame roll-out switch, main limit switch, twinning kit auxiliary limit switch, or flame-proving sensor). In such a case, the other furnace continues to operate unless open switch is the flame roll-out, main limit, or twinning kit auxiliary limit switch, in which case both furnaces respond. Before performing component test, disconnect TKR yellow wire labeled TEST from LH furnace control center TEST/TWIN terminal. After removing yellow wire, component test can be initiated on each furnace individually as stated in Installation, Start-Up, and Operating Instructions. Single-Stage Heat with Single-Stage Gas-Heat Thermostat See Section III, Procedure 2 for furnace and kit components used. 1. LH (MASTER) furnace control center determines if both furnaces are operating in heating mode. 2. Operation in ALL modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on the sequence of operation. Two-Stage Heat with 2-Stage Gas-Heat Thermostat See Section III, Procedure 2 for furnace and kit components used. 1. The 2-stage thermostat determines if furnaces are operating in first-stage heat (LH furnace operates in heat while RH furnace blower operates but RH furnace is not heating) or if furnaces are operating in second-stage heat (both furnaces operate in heat), depending on how many thermostat stages are calling for heat. 2. Operation in all modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on sequence of operation. → SECTION IV: MODELS 58MTA AND 352MAV UPFLOW 2-SPEED CONDENSING HSI FURNACES PROCEDURE 1—INSTALL FURNACES NOTE: Multipoise units must be installed in UPFLOW configuration. Refer to Fig. 30 and 18 for appearance and dimensional drawing of twinned furnaces and their connection locations. 1. Select 2 identical heating and airflow furnaces. (See Table 5.) —28— NOTES #9 & #15 TEST/TWIN LGPS (WHEN USED) NOTE #16 135 SEC 180 SEC PL1 225 SEC 3 2 1 GVR SEC-2 BLU NOTE #14 24 VAC-3A FUSE COOL SPARE-1 1.0 AMP PR2 1 2 3 EAC-2 OL YEL (MED-HI) START NOTE #7 HSIR IDR PL3 PL2 120 VAC L1 PR1 HSI BLK M AUX ILK IDM OL ALS-M ALS-S BLWR BLWM CAP EAC-1 EAC-2 FRS FSE FU1 FU2 GV GVR HI/LO HSI HSIR HUM IDM IDR ILK ILK-1 JB LED LGPS LS OL HEAT SPARE-2 EAC-1 EAC-2 C OM BLK BLK GRN MASTER AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) SLAVE AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) BLOWER MOTOR RELAY, SPST-(N.O.) BLOWER MOTOR,3- OR 4-SPEED, PERMANENT-SPLIT-CAPACITOR CAPACITOR ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FLAME-PROVING SENSOR ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FUSE OR CIRCUIT-BREAKER CURRENT-INTERRUPT DEVICE (FIELD INSTALLED & SUPPLIED) GAS VALVE-REDUNDANT OPERATORS GAS VALVE RELAY, DPST-(N.O.) BLOWER MOTOR SPEED CHANGE RELAY, SPDT HOT SURFACE IGNITER (115 VAC) HOT SURFACE IGNITER RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) INDUCED DRAFT MOTOR INDUCER MOTOR RELAY, SPST-(N.O.) BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES LOW GAS-PRESSURE SWITCH, SPST (N.O.) LIMIT SWITCH, AUTO RESET, SPST(N.C.) AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW., SPST (N.C.) PCB PL1 PL2 PL3 PL4 PL5 PL6 PL7 PRS TEST / TWIN TKR TRAN BLK CAP -2 BLK 1 2 3 PL4 PL5 1 NOTE #14 LEGEND WHT WHT FUSED DISCONNECT SWITCH (WHEN REQ’D) NOTE #4 WHT BLK BRN BRN WHT JB BLK CAP -2 1 2 3 PL4 GRN COOL SPARE-1 PR2 1 2 3 1 2 N 24 VAC-3A FUSE WHT (COM) BLK BLK BLK BLK WHT 2 BLOWER SPEED SELECT BLWR WHT 1 RE L2 BRN SEC-2 HI/LO RELAY BLK PL5 SEC-1 TRAN BLWM RED (LO) 6 5 4 9 8 7 FU1 BRN BLU (MED-LO) C OM WHT 1 2 SLAVE OR RH FURNACE NOTE #8 3 2 1 WHT GVR ORN ALS-S ORN GRN NOTE #3 PL3 PL2 BLK (HI) PL1 225 SEC NOTE #5 PL7 WHT (COM) RED ALS-M LED 180 SEC WHT BLOWER SPEED SELECT BLWR NOTE #8 1 1 ORN ILK-1 BLU 2 2 BLU PL6 ILK RED HEAT SPARE-2 L2 EAC-1 120 VAC L1 PR1 2 CAP -1 IDR GV FSE RED SEC-1 90 SEC FRS RED HI/LO RELAY BL YE TEST/TWIN 135 SEC GRN FU1 HSIR LS WHT 6 5 4 9 8 7 WHT BLOWER OFF DELAY SELECTION CHART 3 BLK 3 G R Y W SW1 C OM 24V HUM SW2 BLOWER OFF DELAY NOTE #12 (NOT ON ALL MODELS) BLK 1 BLU 1 RED RED NOTE #8 PCB WHT YEL LED 2 TKR ORN 90 SEC MASTER OR LH FURNACE 4 1.0 AMP NOTE #16 PRS WHT RED YEL RED BLK GRN WHT WHT BLOWER OFF DELAY SELECTION CHART G R Y W SW1 C OM 24V HUM BLU NOTE #12 (NOT ON ALL MODELS) WHT SW2 BLK PCB BLOWER OFF DELAY 2 GRN HSI AUX BLK FIELD GROUND UNMARKED TERMINAL EQUIPMENT GROUND PCB TERMINAL FACTORY WIRING (115VAC) FIELD SPLICE FACTORY WIRING (24VAC) FIELD WIRING (115VAC) FIELD ACCESSORY WIRING (24VAC) OL IDM NOTES: PRINTED CIRCUIT BOARD 9-CIRCUIT CONNECTOR 2-CIRCUIT CONNECTOR 3-CIRCUIT IDM CONNECTOR 3-CIRCUIT IDM EXTENSION CONNECTOR 2-CIRCUIT HSI CONNECTOR 2-CIRCUIT TWINNING KIT CONNECTOR 1-CIRCUIT TWINNING KIT IN-LINE SPLICE PRESSURE SWITCH, SPST-(N.O.) COMPONENT TEST & TWIN TERMINAL TWINNING KIT RELAY, SPST-(N.O.) TRANSFORMER-115VAC / 24VAC JUNCTION —29— M FU2 GRN FIELD WIRING TERMINAL BRN BRN WHT PLUG RECEPTACLE WIRES PASSING THROUGH HOLES IN CASINGS FROM LH TO RH FURNACE 1. If any of the origi the same type. 2. Inducer (IDM) an thermal overload 3. Blower motor spe instructions for de 4. Use only copper junction box (JB) 5. This wire must be prove flame. 6. Replace only with 7. Yellow lead (MED 8. Passes through h slave furnace blo 9. Make thermostat 10. Make no thermos 11. Blower-on delay, 2 seconds. 12. Blower-off delay, only on some mo 13. Ignition-lockout w trials-for-ignition. 14. Factory installed L1 or the SEC-1 15. Some models ma 16. Factory connecte TO 115VAC FIELD DISCONNECT NOTE #4 L1 EQUIPMENT GROUND ILK NOTE #12 L1 HI/LO SPARE-2 COOL BLWR ALS-M PR1 RED ORN NOTE #12 YEL TEST/TWIN 1 2 2 PL5 PR2 115VAC TRAN ILK HSI 1 1 3 3 PL3 GVR-2 WHT WHT BLK NOTE #14 BLWR IDR PL1 GVR 3-P RED WHT CPU GVR-1 Y G RED 2 SEC-1 8 7 1 LGPS ( W NOTE #14 4 HSIR BLWR HI/LO IDR PL1 GVR PRS N 3 GV 3-P GVR-1 CPU NOTE #5 2 1-M Y 8 G 5 5 6 6 COM 24V FRS SEC-2 GVR-2 FSE BL K C 2 R D RE BRN PL4 NOTE #6 FU 2-C 1-M 3 2 NOTE #14 3 TKR 1 3 PL3 PRS BLK 1 24VAC T WH HI/LO PR2 115VAC TRAN NOTE #13 HUM 4 HSIR PR1 LS (WHEN USED) HSI 2 M YEL LGPS PL5 IDR ILK 1 1 2 PL2 NOTE #12 7 W NOTE #3 1 CAP -2 FRS SEC-2 COM EAC-2 BRN 2 R 4 COM STAR OL HI EAC-1 TEST/TWIN HUM 2 AUX BRN PL4 2 SEC-1 HI/LO SPARE-2 COOL BLWR PASSES THROUGH HOLES IN CASINGS NOTE #6 NOTE #13 3 L1 IDM OL 24VAC RED FU MAKE NO THERMOSTAT CONNECTIONS TO RH FURNACE BLW LO MED LO MED HI NOTE #7 SPARE-1 HSIR M PL7 EQUIPMENT GROUND ILK NOTE #12 EAC-2 IDR RED 1 BRN CAP-1 GRN COM 1 SLAVE OR R HEAT START NOTE #3 PL2 BLU BRN EAC-1 HSIR L2 BLWM OL HI COM NEUTRAL L1 LO MED LO MED HI NOTE #7 SPARE-1 HEAT MAKE THERMOSTAT CONNECTIONS TO ONLY THE LH FURNACE TO 115VAC FIELD DISCONNECT SCHEMATIC DIAGRAM NOTE #4 (NATURAL GAS & PROPANE) MASTER OR LH FURNACE NEUTRAL COM 24V 9 BLK 9 PL6 ORN ALS-S ORN ORN BLU 1 BLU ILK-1 BLU NOTE # 8 2 LEGEND ALS-M ALS-S BLWM BLWR CAP CPU EAC-1 EAC-2 FRS FSE FU MASTER AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) SLAVE AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) BLOWER MOTOR, 3- OR 4-SPEED, PERMANENT SPLIT-CAPACITOR BLOWER MOTOR RELAY, SPST-(N.O.) CAPACITOR MICROPROCESSOR AND CIRCUITRY ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.) FLAME-PROVING SENSOR ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED GV GVR HI/LO HSI HSIR HUM IDM IDR ILK ILK-1 GAS VALVE-REDUNDANT OPERATORS GAS VALVE RELAY, DPST-(N.O.) -1 = VALVE -2 = HUMIDIFIER BLOWER MOTOR SPEED CHANGE RELAY, SPDT HOT SURFACE IGNITER (115 VAC) HOT SURFACE IGNITER RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) INDUCED DRAFT MOTOR INDUCER MOTOR RELAY, SPST-(N.O.) BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) —30— LED LGPS LS OL PCB PL1 PL2 PL3 PL4 PL5 PL6 LIGHT-EMITTING DIODE FOR STAT LOW GAS PRESSURE SWITCH, SPS LIMIT SWITCH, AUTO RESET, SPST AUTO-RESET INTERNAL MOTOR O PRINTED CIRCUIT BOARD 9-CIRCUIT CONNECTOR 2-CIRCUIT CONNECTOR 3-CIRCUIT IDM CONNECTOR 3-CIRCUIT IDM EXTENSION CONNE 2-CIRCUIT HSI CONNECTOR 2-CIRCUIT TWINNING KIT CONNEC 26 15/16″ 26 1/4 TYP A 24 1/2″ 22 1/4″ AIRFLOW AIRFLOW 13/16″ 2-IN. COMBUSTIONAIR CONN F D OUTLET D OUTLET 13/16″ 7/8-IN. 1/2-IN. DIA POWER CONN GAS CONN 2-IN. VENT CONN 32 1/2-IN. DIA THERMOSTAT ENTRY 22 11/16″ 14 1/2″ 11/4″ 1" 23 1/4″ SIDE INLET 30 13/16″ TYP 29 5/8″ TYP 5 27 /8″ 7/8-IN. DIA ACCESSORY POWER ENTRY 30 1/2″ 27 1/2″ TYP CONDENSATE DRAIN TRAP LOCATION (USED FOR LH FURNACES BEFORE SERIAL NO. 2894A00001) SIDE INLET 33 1/4″ TYP 5/8″TYP 24 1/2″ 17 5/16″ 18 1/4″ 9 3/8″ TYP CONDENSATE DRAIN LOCATION 11/16″ 26 15/16″ TYP INLET INLET E E 11/16″ CONDENSATE DRAIN LOCATIO —31— Table 5—58MTA and 352MAV 2-Speed Condensing Furnace Dimensions (In.) INPUT HEATING SIZE (BTUH) 80,000 100,000 100,000 120,000 NOMINAL COOLING SIZE A D E F 48,000 48,000 60,000 60,000 35 42 42 49 15-7/8 19-3/8 19-3/8 22-7/8 16 19-1/2 19-1/2 23 33-3/8 40-3/8 40-3/8 47-3/8 2. Remove bottom closure panels from both furnaces. (See Fig. 3.) a. Remove 2 screws from front filler panel. b. Rotate front filler panel downward to remove. c. Remove bottom closure panel and discard. d. Reinstall front filler panel. 3. Apply 2 factory-supplied foam strips to mating side of each furnace. Locate strips equal distance from top and bottom as shown in Fig. 19. 4. Position furnaces against each other on return-air plenum. Adjust and shim each furnace to align unused condensate drain line holes in lower section of both furnaces holes which will be used for wire routing between furnaces. (See Fig. 19.) 5. Drill two 1/8-in. holes, approximately 1 in. below discharge air flange, from inside top of discharge opening and through both furnaces. (See Fig. 20.) 6. Drive 1 factory-supplied No. 6 X 3/4-in. LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces. 7. Insert 1 snap bushing through each adjoining unused condensate drain line hole of each furnace. (See Fig. 30 and 18.) 8. Connect return- and supply-air ducts to furnaces. Seal duct connections to prevent air leakage. —32— 9. 115-V junction boxes JB must be located on right side of right-hand furnace and left side of left-hand furnace. Relocate as necessary. (See Fig. 18.) WARNING: DO NOT use the back of the furnace for return-air duct connections as limit cycling will occur. A failure to follow this warning can cause a fire, personal injury, or death. PROCEDURE 2—CONNECT ELECTRICAL COMPONENTS—HEATING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. See electrostatic discharge precaution on page 2. 1. Remove control and blower access doors from both furnaces. 2. Determine desired furnace control operation and see appropriate section for use and application of twinning kit relay and harness assembly (TKR). Two-Stage Heat with Single-Stage Gas-Heat Thermostat (Field-Supplied) NOTE: This application allows both furnaces to operate in either high- or low-gas-heat as determined by adaptive mode of both furnace controls. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. a. Remove black and yellow wires from wire-tied TKR harness assembly for later use. b. Discard relay, red wire, and both white wires from TKR harness assembly. c. Use field-supplied electrical tape to insulate black wire’s 1/4-in. quick-connect terminal labeled 3. d. Connect black wire terminal labeled C to LH furnace control thermostat connection COM 24. e. Connect yellow wire terminal labeled TEST to LH furnace control TWIN/TEST terminal. f. Route black and yellow wire loose ends through snap bushings previously installed between furnaces. g. Connect black wire terminal labeled C-SLAVE to RH furnace control thermostat connection COM 24. h. Connect yellow wire terminal labeled TEST SLAVE to RH furnace control TWIN/TEST terminal. i. Proceed to item 3 “Install LH furnace auxiliary limit switch harness ALS-M” to complete electrical connections. Two-Stage Heat with 2-Stage Gas-Heat Thermostat (Field Supplied) NOTE: This attachment allows both furnaces to operate in either high- or low-gas heat as determined by thermostat’s 2-stage operation. See furnace Installation, Start-Up, and Operating Instructions for further details on this heating mode. a. Mount TKR assembly to underside of LH furnace control center enclosure using 1 No. 6 sheet metal screw (field supplied). Screw hole is located to left of door switch near front edge of control. (See Fig. 21.) b. Route 3 loose wires (black, yellow, and white) from TKR assembly wire harness through T-STAT/HUM hole adjacent to door switch. (See Fig. 21.) c. Connect TKR white wire labeled W from TKR to LH furnace control thermostat connection W/W1. d. Connect TKR black wire labeled C from TKR to LH furnace control thermostat connection COM 24. e. Connect TKR yellow wire labeled TEST (loose wire end near TKR) to LH furnace control TWIN/TEST terminal. f. Refer to Fig. 17, 18, and 21 and route remaining 4 loose wires through the following: (1.) Snap bushing previously installed between furnaces in unused condensate drain holes. (2.) RH furnace T-STAT/HUM hole in control center box. g. Connect TKR red wire labeled R-SLAVE from TKR to RH furnace control thermostat connection R. h. Connect TKR white wire labeled W-SLAVE from TKR to RH furnace control thermostat connection W/W1. i. Connect TKR black wire labeled C-SLAVE from TKR to RH furnace control thermostat connection COM 24V. j. Connect TKR yellow wire labeled TEST SLAVE from LH furnace control TWIN/TEST terminal to RH furnace control TWIN/TEST terminal. k. Proceed to item 3 “Install LH furnace auxiliary limit switch harness ALS-M” to complete electrical connections. 3. Install LH furnace auxiliary limit switch harness ALS-M. NOTE: LH furnace ALS-M assembly DOES NOT include door switch. a. Drill 1/8-in. hole in blower housing 8 in. below blower shelf. (See Fig. 18.) b. Position ALS-M so reset button faces front of furnace. c. Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. d. Disconnect red transformer wire from LH furnace control SEC-1 connection. e. Cut off the 3/16-in. quick-connect terminal from red transformer wire. f. Strip red wire 1/8 in. and secure factory-supplied 1/4-in. quick-connect terminal. g. Connect red transformer wire connector to ALS-M wire connector labeled TRANS ASSY. —33— h. Connect ALS-M wire connector labeled DOOR SWITCH or SEC 1 to LH furnace control SEC-1 terminal. Cut wire tie and reoute wire through T-STAT/HUM hole in control box to control board. i. Route 2-wire ALS-M connector form LH furnace to RH furnace control through unused condensate drain line hole with snap bushing. 4. Install RH furnace auxiliary door switch and auxiliary limit switch harness ALS-S/ILK-1. NOTE: RH furnace auxiliary limit switch harness assembly ALS-S/ILK-1 has door switch included. a. Install auxiliary limit switch (ALS-S). (1.) Drill 1/8-in. hole in blower housing 8 in. below blower shelf as shown in Fig. 18. (2.) Position ALS-S so terminals face front of furnace. (3.) Secure bracket to blower housing using factory-supplied No. 6 X 3/4-in. LG screw. b. Install auxiliary door switch (ILK-1). (1.) Remove wires from ALS-S door switch (ILK-1). (2.) Reverse bracket on ALS-S door switch (ILK-1). (See Fig. 22.) NOTE: It is easier to remove switch from bracket by pushing the switch away from flexible catch side and rotating the flexible side through the bracket first. Door switch will only fit in bracket 1 way. Pivot side of switch will be located toward notched opening of bracket. (3.) Reconnect wires to ALS-S door switch (ILK-1). (4.) Drill 7/32-in. hole in left side of RH furnace blower shelf for mounting door switch as shown in Fig. 18. (5.) Secure ALS-S door switch (ILK-1) using factory-supplied No. 6 X 3/4-in. LG screw. c. Connect RH furnace 2-wire ALS-S connector PL6 to LH furnace 2-wire ALS-M connector PL6 that was routed through furnace casings. 5. Select identical blower speed taps at blower motor connectors in both furnaces. CAUTION: Failure to select identical blower speed taps in both furnaces can result in overheating of furnace components and possible loss of furnace operation and damage to the furnaces. 6. Dress wires to ensure they do not contact sharp or moving parts nor interfere with blower operation, removal of filters, or operation of switches. 7. Make all thermostat connections to LH furnace only. PROCEDURE 3—CONNECT ELECTRICAL COMPONENTS—COOLING WARNING: Make no connections between the R 24-vac connector in 1 furnace and the R 24-vac connector in other furnace. Failure to follow this warning can cause a fire, personal injury, or death. When installing twinned outdoor units with twinned gas furnaces, it is necessary to use a field-supplied 24-vac pilot-duty relay and a field-supplied 24/115-vac transformer as shown in Fig. 13 to prevent overloading furnace 24/115-vac transformer. PROCEDURE 4—VENTING Refer to Installation, Start-Up, and Operating Instructions supplied with each furnace for venting information. Each furnace must always be individually vented. Do not common-vent or breach-vent condensing furnaces. For direct-vent installations, refer to Fig. 23, 24, 25, 26, or 27 for proper termination. It is important that vent terminations be made as shown to avoid recirculation of flue gases. PROCEDURE 5—GAS SUPPLY PIPING NOTE: All gas connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supplyand return-air ducts. Furnaces are recommended to be provided with a single shutoff valve. However, individual shutoff valves may be required by local codes or jurisdictions. Refer to Installation, Start-Up, and Operating Instructions provided with each furnace for additional gas supply information. PROCEDURE 6—CONDENSATE DRAIN CONNECTIONS The condensate trap is factory installed in blower shelf and factory connected for UPFLOW applications. Install condensate trap extension drain such that field drain connection are on the left side for LH (MASTER) furnace and on right side for RH (SLAVE) furnace. (See Fig. 18.) See furnace Installation, Start-Up, and Operating Instructions for details on attaching field drain. PROCEDURE 7—ELECTRICAL SUPPLY CONNECTIONS NOTE: All electrical power connections must be made through exposed outer side of each furnace. Do not common connect any connection other than supply- and return-air ducts. 1. Each furnace shall be connected to its own 115-vac power supply. The twinning kit installation interconnects the furnaces, allowing them to operate as a single furnace. The L1 (black) connection to each furnace must be connected to circuit breakers connected to the same service panel 115-vac phase leg. On single-phase (residential) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 1 space to be connected to the same leg of the 1-phase power supply. On 3-phase (commercial) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 2 spaces to be connected to the same leg of the 3-phase power supply. The proper 115-vac phasing of furnace connections permits 24-vac transformer phasing as described below. —34— 2. Phasing of the connected 24-vac transformer secondary circuits can be determined with the LED status of both furnaces. See furnace Installation, Start-Up, and Operating Instructions and status code label on blower access door or main furnace door. The furnaces’ transformers’ black leads should be connected to PR1 connectors and white leads to PR2 connectors on controls. If 1 or both LEDs are rapidly flashing, disconnect lead at TEST/TWIN terminal of LH furnace and observe LED at each furnace. IF: a. Both LEDs are on continuously: System phasing is okay. b. One or both LEDs are rapidly flashing: (1.) Line voltage polarity is reversed. (2.) Reverse SEC-1 and SEC-2 in furnace with rapid flashing LED. c. One LED is off, 1 LED is on continuously: (1.) The 24-vac circuit is inoperative on furnace with LED light off. (2.) Check transformers, auxiliary limits, and door switches in both furnaces and correct problem. 3. Reconnect lead at TWIN/TEST terminal of LH furnace and observe LED at each furnace. The LEDs will glow steady for proper phasing. PROCEDURE 8—START-UP AND ADJUSTMENT Refer to Installation, Start-Up, and Operating Instructions supplied with furnace for detailed information. 1. Shut off all power and gas to both furnaces. 2. Position TWINNING JUMPERS TJ on furnace controls. (See Fig. 14.) a. The LH furnace control TWINNING JUMPER TJ MUST remain in the MASTER position. b. The RH furnace control TWINNING JUMPER TJ MUST be moved to the SLAVE position. 3. Determine desired furnace control operation and position set-up switches on furnace control. (See Fig. 14.) Two-Stage Heat with Single-Stage Gas-Heat Thermostat a. Position SW1 switch on controls in BOTH furnaces to OFF. b. Position SW2 switch on controls in BOTH furnaces to OFF. c. Position SW3 and SW4 switches on control in BOTH furnaces to desired gas-heat blower off delay. (See furnace Installation, Start-Up, and Operating Instructions for further details.) Two-Stage Heat with 2-Stage Gas-Heat Thermostat a. Position SW1 switch on controls in BOTH furnaces to OFF. b. Position SW2 switch on controls in BOTH furnaces to ON. c. Position SW3 and SW4 switches on controls in BOTH furnaces to desired gas-heat blower off delay. (See furnace Installation, Start-Up, and Operating Instructions for further details.) 4. Attach twinning connection diagram label over existing wiring label on inside of LH furnace blower door. 5. Attach twinning schematic diagram label over existing wiring label on inside of RH furnace blower door. 6. Turn on power and gas to both furnaces. 7. Reinstall blower access doors on both furnaces. 8. Using appropriate section below, operate furnaces through 2 cycles in each mode to confirm correct operation by operating only the thermostat. a. Single- or 2-stage gas heating thermostat R-to-W/W1 for low-gas heat. Single-stage thermostat with adaptive heating mode causes furnace to operate in low-gas-heat mode for up to 16 minutes, and then furnace automatically switches to high-gas heat. First stage of a 2-stage thermostat without adaptive heating mode causes furnace to operate in low-gas-heat mode indefinitely. b. First- and second-stage of 2-stage heating thermostat R-to-W/W1-and-W2 for high-gas-heat. c. Thermostat R-to-G for continuous fan or 2-speed cooling low-cool blower. d. Cooling thermostat R-to-G-and-Y/Y2 for single-speed cooling blower or for 2-speed cooling high-cool blower. 9. Reinstall control doors on both furnaces.Reinstall control doors on both furnaces. 10. Instruct user in operation of furnaces and thermostat. PROCEDURE 9—SEQUENCE OF OPERATION See Fig. 31 and 32 for 2-speed non-condensing furnace twinning connection and schematic wiring diagrams while reviewing sequence of operation. Twinning operation is controlled by LH or MASTER furnace. The TWIN/TEST and COM 24V connection wires ensure the 2 furnaces coordinate their blower operation. When either furnace requires blower operation, both furnaces operate their blowers at the same speed (the highest speed required by either furnace). Both furnaces operate simultaneously in the same mode: low-gas heat, high-gas heat, low-cool, high-cool, or continuous fan. Exceptions can occur if a safety device on either furnace is activated (such as low-gas-heat or high-gas-heat pressure switch, flame roll-out switch, limit switch, twinning kit auxiliary limit switch, or flame-proving sensor). In such a case, the other furnace continues to operate unless the safety device is the flame roll-out, limit, or twinning kit auxiliary limit switch, in which case both furnaces respond. —35— Two-Stage Heat with Single-Stage Gas-Heat Thermostat See Section IV, Procedure 2 for furnace and kit components used. NOTE: Set-up switches SW1 and SW2 in BOTH furnaces are in OFF position. 1. LH furnace control determines whether furnaces are both operating in low-gas heat or high-gas heat, depending on the control’s adaptive gas heating mode when the R-to-W/W1 circuit is closed in LH furnace. 2. Operation in all modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on sequence of operation. Two-Stage Heat with 2-Stage Gas-Heat Thermostat See Section IV, Procedure 2 for furnace and kit components used. NOTE: Set-up switches SW1 in BOTH furnaces are in OFF position, and set-up switches SW2 in BOTH furnaces are in ON position. 1. The 2-stage thermostat (NOT furnace control’s adaptive gas heating mode) determines whether furnaces are both operating in low-gas heat or high-gas heat, depending on whether 1 or both thermostat stages (W/W1 or W/W1-and-W2) are calling for heat. 2. Operation in all modes is the same for twinned furnaces as for an individual furnace. See furnace Installation, Start-Up, and Operating Instructions for more information on sequence of operation. —36— FURNACE CONNECTION DIAGRAM ORN W2 RED MED-LO BLU LO RED BLWM BLU BLU PL9 ALS-M ORN ORN BLU KEEP TWINNING JUMPER IN "MASTER" POSITION ON MASTER FURNACE. W/W1 R G H U COM Y/Y2 M 24V PL8 2 1 MASTER AUX. LIMIT SWITCH, OVERTEMP. - MANUAL RESET, SPST (N.C.) SLAVE AUX. LIMIT SWITCH, OVERTEMP. - MANUAL RESET, SPST (N.C.) BLOWER MOTOR, 4 or 5 SPEED, PERMANENT-SPLIT-CAPACITOR CAPACITOR -1 = BLWM -2 = IDM MICROPROCESSOR AND CIRCUITRY ELECTRONIC AIR CLEANER CONNECTION (115 VAC, 1 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SWITCH OVERTEMP.-MANUAL RESET, SPST (N.C.) FLAME-PROVING SENSOR ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED FUSE, FIELD INSTALLED GAS VALVE, REDUNDANT LOW-HEAT OPERATORS, 2-STAGE HIGH-HEAT PRESSURE SWITCH, SPST (N.O.) HOT-SURFACE IGNITER (115 VAC) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) INDUCED DRAFT MOTOR, 2-SPEED, SHADED-POLE SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST (N.O.) BLOWER DOOR INTERLOCK SWITCH, SPST (N.O.) JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES LOW GAS-PRESSURE SWITCH, SPST (N.O.) LPS LS * * * PL1 PL2 PL3 PL6 PL8 PL9 SW1 SW2 SW3 & 4 TJ TKR TRAN TWIN / TEST LOW-HEAT PRESSURE SWITCH, SPST (N.O.) LIMIT SWITCH, OVERTEMPERATURE-AUTO RESET, SPST (N.C.) 12-CIRCUIT CONNECTOR 9-CIRCUIT CONNECTOR 3-CIRCUIT IDM CONNECTOR 2-CIRCUIT HSI CONNECTOR 2-CIRCUIT TWINNING CONNECTOR 1-CIRCUIT TWINNING CONNECTOR HIGH-HEAT-ONLY SWITCH, SPST (MANUAL) LOW-HEAT-ONLY SWITCH, SPST (MANUAL) BLOWER-OFF DELAY SETTING SWITCHES, SPST (MANUAL) TWINNING JUMPER, SPDT FOR MASTER OR SLAVE STATUS-(MANUAL-CHANGE-OVER) TWINNING KIT RELAY, SPST (N.O.) TRANSFORMER-115VAC / 24VAC 1-CIRCUIT TWINNING BUSS CONNECTOR, ALSO COMPONENT TEST JUNCTION TERMINAL CONTROL TERMINAL —37— A01276 FSE GRY WHT BLU 9 8 7 3 2 GRN SEC1 SEC2 FU1 MOVE TWINNING JUMPER T MAKE NO THERMOSTAT CONNECTIONS TO RIGHT HAND FURNACE. ILK-1 ALS-S YEL To initiate the component test sequ Purge and Blower-Off Delay period terminal for about two seconds. Th inducer motor Low-Speed, blower Speed, and blower motor High-Co ON the entire length of the test). N LEGEND ALS-M ALS-S BLWM CAP CPU EAC-1 EAC-2 FRS FSE FU1 FU2 GV HPS HSI HUM IDM ILK-1 ILK JB LED LGPS WHT 1 TJ M LED S BLK ORN BLU MED FACTORY POWER WIRING (115VAC) FACTORY CONTROL WIRING (24VAC) FIELD POWER WIRING (115VAC) FIELD ACCESSORY WIRING (24VAC) FIELD WIRING SCREW TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE 326684-201 REV. A * HEAT SET-UP SWITCH SWITCH 2 1 NORM HI HT LO HT ON OFF ON Diagram for Twinned 2-Speed Condensing Furnace NOTE #13 FU1 BRN TWIN TEST BLOWER OFF DELAY SWITCH (SEC) 4 3 90 SEC 135 SEC 180 SEC 225 SEC ON OFF ON RED WHT TRAN YEL 12 11 10 MED-HI BLOWER-OFF DELAY BLOWER-OFF DELAY LOW-HEAT ONLY HIGH-HEAT ONLY PR2 L2 L1 COMMON HI-COOL HI-GAS HEAT EAC-2 LO-GAS HEAT EAC-1 P1 SPARE SPARE RED WHT BLK BLK ON OFF HI BRN COM WHT PASSES THROUGH HOLES IN CASINGS PR1 ORN RED 1 CAP-1 NOTE #4 BRN GRY WHT 12 3 4 BLK GRN 12 11 10 (WHEN USED) YEL * FACTORY SETTINGS WHT 3 2 9 8 7 1 YEL ORN RED PL2 SEC1 SEC2 BLK BLK WHT 4 RED MAKE THERMOSTAT CONNECTIONS TO ONLY THE LEFT HAND FURNACE. 3 2 BRN Fig. TWIN TEST TJ M W2 W/W1 R G H COM Y/Y2 U LED S M 24V BLU BLOWER-OFF DELAY BLOWER-OFF DELAY LOW-HEAT ONLY HIGH-HEAT ONLY RED 1 WHT BLK PR2 L2 L1 COMMON HI-COOL HI-GAS HEAT EAC-2 LO-GAS HEAT 31—Connection EAC-1 P1 SPARE SPARE PL6 1 2 P 2-STAGE FURNACE CONTROL PR1 ORN RED 3 2 ON OFF 123 4 * FACTORY SETTINGS HSI GRN PL2 2-STAGE FURNACE CONTROL CAP-2 BRN RED WHT 2 3 B LGPS NOTE #7 WHT FU2 L2 GND G GRY BLK BLK WHT NOTE #6 FUSED DISCONNECT SWITCH (WHEN REQ’D) JB NOTE #1 BLK L1 ILK GRN YEL FRS WHT 1 RED RED WHT RED BLK GRY OL GRN/YEL FSE BRN IDM PL3 LPS LS ORN ORN (WHEN USED) YEL PL6 1 2 2 WHT C GRN/YEL M GRN/YEL HSI 4 RED 1 TKR GV BLU CAP-2 BRN 3 WHT BLK HI BRN BRN LGPS NOTE #7 RED RED FRS ORN RED WHT LS HPS GRY LPS BLK ORN MASTER OR LH FURNACE EAC-2 HSIR EAC-1 PL2 IHI / LOR IDR 1 4 4 1 2 3 8 TRAN SEC-2 24VAC FU SEC-1 NOTE #5 HPSR RED ORN HSI 2 PL3 PL3 115VAC PR2 PR1 BRN BLWM 3 PL6 9 7 PL9 SET-UP * HEAT SWITCH SWITCH 1 2 NORM HI HT LO HT LO HI OL IDM COM 1 N/A 5 6 N/A 2 FRS 3 BLWR COMMON LS PL2 IHI / LOR IDR PR1 FU KEEP TWINNING JUMPER IN "MASTER" POSITION ON MASTER FURNACE. NOTE #5 YEL W2 M 1 10 Y/Y2 RED JUMPER TO "SLAVE" POSITION ON SLAVE FURNACE. HPS MGVR-1 C TWINNING JUMPER TJ FSE CPU MGVR-1 Y/Y2 G TKR COM RED 4 2 PL8 WHT ORN 1 BLU 2 LEGEND IDM IDR IHI/LOR ILK ILK-1 JB LED LGPS LPS LS MGVR * * * W2 BLK BLK BLK 3 WHT1 BLK MASTER AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) SLAVE AUX. LIMIT SW., OVERTEMP-MANUAL RESET, SPST-(N.C.) BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR SPEED CHANGE RELAY, SPDT BLOWER MOTOR, 4 or 5 SPEED, PERMANENT-SPLIT-CAPACITOR BLOWER MOTOR RELAY, SPST-(N.O.) CAPACITOR -1 = BLWM -2 = IDM MICROPROCESSOR AND CIRCUITRY ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FLAME ROLLOUT SWITCH OVERTEMP. -MANUAL RESET, SPST-(N.C.) FLAME-PROVING SENSOR ELECTRODE FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED GAS VALVE-REDUNDANT LOW-HEAT OPERATORS, 2-STAGE HIGH-HEAT PRESSURE SWITCH, SPST-(N.O.) HIGH-HEAT PRESSURE SWITCH RELAY, SPST-(N.C.) HOT SURFACE IGINITER (115 VAC) HOT SURFACE IGNITER RELAY, SPST-(N.O.) 24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.) MASTER GV NOTE#6 7 8 11 COM PL1 W/W1 PASSES THROUGH HOLES IN CASINGS ALS-M ALS-M ALS-S BHI/LOR BHT/CLR BLWM BLWR CAP CPU EAC-1 EAC-2 FRS FSE FU GV HPS HPSR HSI HSIR HUM WHT HI G BLU TWIN TEST SLAVE NOTE #7 (WHEN USED) LGPS 4 CPU MGVR-2 HUM RED 5 Fig. 32—Schematic Diagram for Twinned 2-Speed Condensing Furnace MOVE TWINNING MASTER TRAN SEC-2 24VAC YEL PL1 TJ W/W1 WHT LPS 6 TWINNING JUMPER 115VAC PR2 SEC-1 R 9 SLAVE EAC-2 HSIR EAC-1 R TWIN TEST SPARE SPARE HI-COOL COMPONENT TEST 12 N/A MGVR-2 LO-GAS HEAT HI-GAS HEAT L1 BLOWER OFF DELAY SWITCH (SEC) 3 4 90 SEC 135 SEC 180 SEC 225 SEC To initiate the component test sequence with no thermostat inputs and with all inducer Post-Purge and Blower-Off Delay periods completed, short the "TWIN/TEST" terminal to the "COM" terminal for about two seconds. The control will turn ON the inducer motor High-Speed, HSI inducer motor LowSpeed, blower motor Low-Gas-Heat Speed, blower motor High-Gas-Heat Speed, and blower motor High-Cool Speed for 7-15 seconds each (the inducer motor will be ON the entire length of the test). Neither the gas valve nor the humidifier will be turned ON. 2 HUM BHI/LOR BHT/CLR HPSR HI-COOL CAP-1 BLWR MED-LO NOTE #13 SPARE MED SPARE MED-HI HI COMMON COM NOTE #4 ILK MAKE NO THERMOSTAT CONNECTIONS TO RIGHT HAND FURNACE L2 ON OFF ON OFF BRN CAP-2 L1 MAKE THERMOSTAT CONNECTIONS TO ONLY THE LEFT HAND FURNACE LO LO-GAS HEAT HI-GAS HEAT ON OFF ON OFF BHI/LOR BHT/CLR TO 115VAC FIELD DISCONNECT SWITCH EQUIPMENT GROUND NO FURNACE SCHEMATIC DIAGRAM A01277 TO 115VAC FIELD DISCONNECT SWITCH EQUIPMENT GROUND NOTE #1 MASTER ILK OR LH FURNACE INDUCED DRAFT MOTOR, 2-SPEED, SHADED-POLE INDUCER MOTOR RELAY, SPST-(N.O.) INDUCER MOTOR SPEED CHANGE RELAY, SPDT BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) SLAVE AUX. BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIGHT-EMITTING DIODE FOR STATUS CODES LOW GAS PRESSURE SWITCH, SPST-(N.O.) LOW-HEAT PRESSURE SWITCH, SPST-(N.O.) LIMIT SWITCH, OVERTEMPERTURE-AUTO RESET, SPST(N.C.) MAIN GAS VALVE RELAY, DPST-(N.O.) -1 = VALVE -2 = HUMIDIFIER N/A NOT APPLICABLE PL1 12-CIRCUIT CONNECTOR PL2 9-CIRCUIT CONNECTOR PL3 3-CIRCUIT IDM CONNECTOR PL6 2-CIRCUIT HSI CONNECTOR PL8 2-CIRCUIT TWINNING CONNECTOR PL9 1-CIRCUIT TWINNING CONNECTOR SW1 HIGH-HEAT-ONLY SWITCH, SPST-(MANUAL) SW2 LOW-HEAT-ONLY SWITCH, SPST-(MANUAL) SW3 & 4 BLOWER-OFF DELAY SETTING SWITCHES, SPST-(MANUAL) —38— ALS-S ORN BLU ORN ILK-1 ORN BLU TJ TWINNING JUMPER, SPDT FOR MASTER OR SLAVE STATUS-(MANUAL CHANGE-OVER) TKR TWINNING KIT RELAY, SPST-(N.O.) TRAN TRANSFORMER-115VAC / 24VAC TWIN / TEST 1-CIRCUIT TWINNING BUSS CONNECTOR, ALSO COMPONENT TEST JUNCTION TERMINAL CONTROL TERMINAL FACTORY POWER WIRING (115VAC) FACTORY CONTROL WIRING (24VAC) FIELD ACCESSORY WIRING (24VAC) CONDUCTOR ON PCB EQUIPMENT GROUND FIELD WIRING SCREW TERMINAL FIELD SPLICE FIELD GROUND PLUG RECEPTACLE 326685-201 REV. A