INSTALLATION INSTRUCTIONS drawing number 111924
This product must be installed in accordance with applicable national and local electrical and construction codes by a person familiar with the construction and operation of the product and the hazards involved. Failure to comply with the following installation instructions may result in death or serious injury.
! !
WARNING
!
SEPARATION OF FIELD INSTALLED POWER LIMITED CIRCUIT (DIMMING/CONTROL) WIRING FROM THE BRANCH CIRCUIT WIRING IN THE OUTLET BOX ARE TO BE MADE IN ACCORDANCE WITH LOCAL AND/OR NATIONAL ELECTRICAL INSTALLATION CODES.
WARNING
WARNING
!
DO NOT USE IF FIXTURE, PARTS OR CONNECTORS ARE DAMAGED.
DISCONNECT POWER BEFORE INSTALLING OR SERVICING TO AVOID ELECTRICAL SHOCK.
!
HORIZONTAL WHITE & STATIC COLORS, COLOR CHANGING & DYNAMIC WHITE
WARNING
CAUTION
DO NOT EXCEED FIXTURE SPECIFIED VOLTAGE.
UNAUTHORIZED FIELD REPAIRS WILL VOID WARRANTY.
ASYMMETRIC WALLWASH OPTIC OPTION WALL
RECOMMENDED SETBACK FROM WALL IS 1/10 OF THE WALL HEIGHT.
NOTICE ALWAYS POSITION FROSTED SIDE TOWARD THE WALL.
TOP VIEW
EXAMPLE: 2FT SETBACK FOR A 20FT WALL FRONT VIEW
RIGHT SIDE VIEW (Fixture pointing upwards)
STEP 1. SLIDE IN UMAS MOUNTING BRACKETS
STEP 2. TIGHTEN SET SCREWS
4X STEP 3. SCREW ONTO MOUNTING SURFACE 3 " 4 [19mm]
3 " 8 [10mm]
!
CAUTION
DO NOT LOOK INTO BEAM. LOOSEN SCREWS SLIGHTLY TO ADJUST LIGHT BEAM ORIENTATION AND RE-TIGHTEN TO SECURE
Ø 9"
32 [7mm]
!
21" 13" 2 4 [45mm] [64mm]
WARNING
USE 1/4” FASTENERS (4X BY OTHERS) THAT ARE APPROPRIATE FOR USE WITH YOUR MOUNTING SURFACE
2X OR
STEP 1. SLIDE IN WAMH MOUNTING BRACKETS
STEP 2. TIGHTEN SET SCREWS
4X STEP 3. SCREW ONTO MOUNTING SURFACE 1 " 16 [27mm] 1
9 " 32 [7mm]
!
CAUTION
DO NOT LOOK INTO BEAM.
3 1 4 " 2 2 " [45mm] [64mm] 1
!
WARNING
USE 1/4” FASTENERS (4X BY OTHERS) THAT ARE APPROPRIATE FOR USE WITH YOUR MOUNTING SURFACE
LOOSEN NUTS & BOLTS SLIGHTLY TO ADJUST LIGHT BEAM ORIENTATION AND RE-TIGHTEN TO SECURE
bin™, a proprietary binning method, guarantees color temperature consistency within a 3-step MacAdam ellipse. ™ Combine lumentranslator with Lumentalk-enabled luminaires housing Lumenpulse's proprietary lumenear control card to build your Lumentalk system.
p.1/2 2017.03.30 MS - R4
Lumenpulse, 1751 Richardson, Suite 1505, Montreal (Quebec) Canada H3K 1G6 1.877.937.3003 P. 514.937.3003 F. 514.937.6289
[email protected] www.lumenpulsegroup.com Copyright © Lumenpulse 2017 Confidential and proprietary Lumenpulse reserves the right to make changes to this product and related instructions at any time without prior notice and such changes shall be effective immediately. See http://www.lumenpulsegroup.com/support/downloads for current data and instructions.
lumenfacade™
INSTALLATION INSTRUCTIONS drawing number 111924
HORIZONTAL WHITE & STATIC COLORS, COLOR CHANGING & DYNAMIC WHITE
This product must be installed in accordance with applicable national and local electrical and construction codes by a person familiar with the construction and operation of the product and the hazards involved. Failure to comply with the following installation instructions may result in death or serious injury.
!
OR STEP 1. SLIDE IN UMP MOUNTING BRACKETS
STEP 2. TIGHTEN SET SCREWS
STEP 3. SCREW ONTO MOUNTING SURFACE 3 4" [19mm]
3 8" [10mm]
!
USE 1/4” FASTENERS (4X BY OTHERS) THAT ARE APPROPRIATE FOR USE WITH YOUR MOUNTING SURFACE
4X
*UMP BRACKETS CAN BE ADJUSTED HORIZONTALLY.
WARNING
STEP 4. CONNECT LEADER AND JUMPER CABLE
27" 8 [73mm]
9 32 " [7mm]
31" 2 [89mm]
STEP 5. PUT SEALING CAP ON UNUSED CONNECTOR
JUMPER
WARNING
!
INPUT CONNECTOR
PLACE SEALING CAP OVER PANEL MOUNT CONNECTOR. NO PART REMOVAL REQUIRED.
LEADER
CAUTION
1 SEALING END CAP PROVIDED WITH EACH LEADER CABLE
« clic k»
» « click
ONCE CABLE IS CONNECTED, TURN COLLAR 1/4 TURN CLOCKWISE TO SECURE INSTALLATION. (CLICK SOUND WILL OCCUR).
CAUTION
ENGAGE AND TURN COLLAR 1/4 TURN CLOCKWISE TO SECURE END CAP INSTALLATION. (CLICK SOUND WILL OCCUR).
WIRING DETAIL AT JUNCTION BOX (BY OTHERS) LUMENTALK (for 2, 3 or 4’ fixture lengths [0.6, 0.9 or 1.2m])
NON-DIMMING
0-10V DIMMING DALI DIMMING LUTRON® ECOSYSTEM® ENABLED DIMMING
*Lumentalk Data Bridge required for 1' [0.3m] fixture lengths see Lumentalk Data Bridge installation instructions for more details
From third party controller (dimmer, DALI controller, or Lutron® EcoSystem® controller)
To fixture Power input
To fixture Line Ground Neutral Wire-nuts (by others)
Junction box (by others)
Power input (control over power line via Lumentalk system)
To Lumentalk Data Bridge (for run lengths with 1' [0.3m] fixtures)
Junction box (by others)
Line Ground Neutral Wire-nuts (by others)
American Color Code
CE Color Code
USE
Green Black White Red/ Purple Orange
Yellow/Green Brown Blue Black Grey
Ground Live 100-277V Neutral 0-10V / Data + 0-10V / Data -
Data + Data Power input Junction box (by others)
To fixture Line Ground Neutral Wire-nuts (by others)
DMX/RDM
*see CBX installation instructions for more details
STEP 6. CONNECT LEADER CABLE TO J-BOX 1/2” NPT LIQUID TIGHT STRAIN RELIEF (BY OTHERS)
RT V
sil
DMX/Data Cable Specification DMX Cable from Controller to CBX and CBX to CBX shall adhere to ANSI E1.11 – 2008 (r2013) – Entertainment Technology – USITT DMX512-A, Asynchronous Serial Digital Data Transmission Standard for Controlling Lighting Equipment and Accessories. At minimum DMX Cable shall be 1-Pair (24 AWG, 7x32 Stranding)Twisted (minimum of 4.8 twists/foot), Shielded, minimum of 100 ohms Impedance, and <25 pF/ft. Capacitance. Combined Power & Data Cable Specification Fixture cabling from CBX to Fixtures shall be installed per NEC and Local Codes. All cables shall be SOOW style cables with minimum of 16 AWG annealed stranded bare copper per ASTM B-174 with a minimum temperature range of -40°C to +90°C. All conductor standing must be a minimum of 26/30 and capable of handling 13 amps. Cable must be water resistant, UL Listed and CSA certified for indoor and outdoor use. Must be Ozone-sunlight (UV) and weather resistant.
NOTICE
ico
ne
RECORD THE LOCATION OF EACH FIXTURE BY SERIAL NUMBER TO PREPARE FOR THE COMMISSIONING PROCESS (DMX/RDM).
TYPICAL UMAS INSTALLATION
TYPICAL ETE INSTALLATION
ETE INPUT CABLE
6 " MINIMUM COIL [152mm] DIMENSION ETE LEADER CABLE (ORDER SEPARATELY)
TYPICAL WAMH INSTALLATION
TOP VIEW
1" MINIMUM 4 [7mm] SPACING
TYPICAL UMP INSTALLATION
bin™, a proprietary binning method, guarantees color temperature consistency within a 3-step MacAdam ellipse. ™ Combine lumentranslator with Lumentalk-enabled luminaires housing Lumenpulse's proprietary lumenear control card to build your Lumentalk system.
p.2/2 2017.03.30 MS - R4
Lumenpulse, 1751 Richardson, Suite 1505, Montreal (Quebec) Canada H3K 1G6 1.877.937.3003 P. 514.937.3003 F. 514.937.6289
[email protected] www.lumenpulsegroup.com Copyright © Lumenpulse 2017 Confidential and proprietary Lumenpulse reserves the right to make changes to this product and related instructions at any time without prior notice and such changes shall be effective immediately. See http://www.lumenpulsegroup.com/support/downloads for current data and instructions.