Transcript
50HJQ008,012 Single-Package Rooftop Heat Pump Units
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-19 Step 1— Provide Unit Support . . . . . . . . . . . . . . . . 1 • ROOF CURB • SLAB MOUNT Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . 1 Step 3 — Install Condensate Drain Line and External Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . 3 • POSITIONING Step 5 — Make Electrical Connections . . . . . . . . 7 • FIELD POWER SUPPLY • FIELD CONTROL WIRING • DEFROST BOARD • HEAT ANTICIPATOR SETTINGS Step 6 — Adjust Factory-Installed Options . . . . . 9 • DISCONNECT SWITCH • OPTIONAL VARISLIDE™ ECONOMIZER • OPTIONAL PARABLADE ECONOMIZER Step 7 — Adjust Indoor-Fan Speed . . . . . . . . . . . 13 PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20,21 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22,23 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 24-26 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
INSTALLATION
Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight.
Step 1 — Provide Unit Support ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb. If electric or control power is to be routed through the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb. IMPORTANT: The gasketing of the unit to the roof curb is critical for watertightness. Install gasket supplied with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance. Curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required. SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. NOTE: Horizontal units may be installed on a roof curb if required.
Step 2 — Field Fabricate Ductwork — On vertical discharge units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. For horizontal applications, field-supplied flanges should be attached to horizontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On horizontal discharge units, a minimum clearance of 1 in. is required for the first 12 in. of ductwork. Cabinet return-air static should not exceed −0.35 in. wg with Varislide economizer, −0.20 in. wg with PARABLADE economizer, or −0.45 in. wg without economizer.
Unit is shipped in the vertical configuration. To convert to horizontal configuration, remove side duct opening covers. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No. 565-066 Printed in U.S.A. Form 50HJQ-2SI Pg 1 6-95 Replaces: New Tab 5a 5a
CONNECTION SIZES UNIT SIZE
(B(
(C(
(D( ALT DRAIN HOLE
50HJQ008,012
28-87⁄169 [827]
18-1015⁄169 [583]
13⁄49 [45]
POWER CONNECTION
CONTROL CONNECTION
⁄ 9 NPT
34
11⁄49 NPT
⁄ 9 NPT
12
⁄ 9 NPT
12
UNIT SIZE
(A(
50HJQ008,012
18-29 [356] 28-09 [610]
CONNECTOR ACCESSORY PACKAGE CRBTMPWR00A100 (THRU-THE-BOTTOM) CRBTMPWR00A200 (THRU-THE-BOTTOM) ROOF CURB ACCESSORY CRRFCURB003A00 CRRFCURB004A00
NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: galvanized steel. 5. Attach ductwork to curb (flanges of duct rest on curb). 6. Service clearance 4 ft on each side. 7.
Fig. 1 — Roof Curb Details 2
Direction of airflow.
MAXIMUM ALLOWABLE DIFFERENCE (in.) A-B 0.5
B-C 1.0
A-C 1.0 NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
Fig. 2 — Unit Leveling Tolerance
Fig. 4 — External Trap Condensate Drain
Step 3 — Install Condensate Drain Line and External Trap — Condensate drain connections are located at the bottom and end of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used in vertical or horizontal applications. When using the standard end drain connection, make sure the plug in the alternate bottom connection is tight before installing the unit. To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug from the bottom connection to the end connection. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place. All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against freezeup. See Fig. 4. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection.
Step 4 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information. Operating weight is shown in Table 1 and Fig. 5. Lifting holes are provided in base rails as shown in Fig. 5 and 6. Refer to rigging instructions on unit. POSITIONING — Maintain clearance around and above unit to provide proper airflow and service access. See Fig. 6. Position unit on roof curb so that the following clearances are maintained: 1⁄4-in. clearance between roof curb and base rails on each side and in front of unit; 15⁄32-in. clearance between roof curb and rear of unit (see Fig. 1, section C-C). Do not install unit in an indoor location. Do not locate unit air inlet near exhaust vents or other sources of contaminated air. Although unit is weatherproof, guard against water from higher level runoff and overhangs. After unit is in position, remove polyethylene shipping wrapper and rigging skid.
Fig. 3 — Condensate Drain Location
3
NOTES: 1. Dimension in ( ) is in millimeters. 2. Hook rigging shackles through holes in base rail, as shown in detail 9A.9 Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit. 3. Unit weights do not include economizer. See Table 1 for economizer weights.
50HJQ 008 012
MAX WEIGHT A B C Lb Kg in. mm in. mm in. mm 870 395 77.42 1966.5 41.5 1054 42.12 1070 1000 454 77.42 1966.5 41.5 1054 42.12 1070
All panels must be in place when rigging.
Fig. 5 — Rigging Details
4
Table 1 — Physical Data BASE UNIT 50HJQ NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit With Varislide™ Economizer With PARABLADE Economizer Roof Curb COMPRESSOR Quantity Oil (oz) (each compressor) REFRIGERANT TYPE Operating Charge (lb-oz) Circuit 1 Circuit 2 OUTDOOR FAN Qty...Diameter (in.) Nominal Cfm Motor Hp...Rpm Watts Input (Total) OUTDOOR COIL Rows...Fins/in. Total Face Area (sq ft) INDOOR FAN Qty...Size (in.) Nominal Cfm Maximum Continuous Bhp Motor Frame Fan Rpm Range Motor Bearing Type Maximum Fan Rpm Motor Pulley Pitch Diameter A/B (in.) Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Belt — Qty...Type...Length (in.) Pulley Center Line Distance (in.) Speed Change per Full Turn of Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns From Closed Position Factory Setting — Full Turns Open Factory Speed Setting (rpm) Fan Shaft Diameter at Pulley (in.) INDOOR COIL Rows...Fins/in. Total Face Area (sq ft) HIGH-PRESSURE SWITCH (psig) Cutout Reset (Auto.) LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line) (psig) Cutout Reset (Auto.) FREEZE-PROTECTION THERMOSTAT Opens (F) Closes (F) OUTDOOR-AIR INLET SCREENS Qty...Size (in.) RETURN-AIR FILTERS Qty...Size (in.)
008 71⁄2
012 10
870 914 932 143
1000 1044 1062 143 Scroll
2 57
2 57 R-22
5-3 5-8
9-11 9-11
Propeller Type 2...22 2...22 6500 6500 1⁄4...1100 1⁄4...1100 650 650 High Efficiency Enhanced Copper Tubes, Lanced Aluminum Fin, Acutrol™ Feed Device 2...17 2...17 20.5 25.1 Centrifugal Type, Belt Drive 1...15 x 15 1...15 x 15 3000 4000 2.90 4.20 56 56 840-1085 860-1080 Ball Ball 2100 2100 3.4/4.4 4.0/5.0 7 ⁄8 7 ⁄8 7.0 8.0 1...A...51 1...A...51 16.75-19.25 15.85/17.50 50 45 5
5
5 5 840 860 1 1 High Efficiency Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol Feed Device 3...15 4...15 8.9 11.1 450 6 5 428 320 763 22 6 7 30 6 5 45 6 5 Cleanable 1...20 x 25 x 1 1...16 x 25 x 1 Throwaway 4...16 x 20 x 2
LEGEND Bhp — Brake Horsepower
5
4...20 x 20 x 2
UNIT 50HJQ008 50HJQ012
STD UNIT WEIGHT Lb 870 1000
Kg 395 454
CORNER WEIGHT (A) Lb 195 231
Kg 90 105
CORNER WEIGHT (B) Lb 183 214
Kg 83 97
CORNER WEIGHT (C) Lb 237 269
Kg 108 122
CORNER WEIGHT (D) Lb 252 286
‘‘H’’
Kg 114 130
Ft-in. 28- 07⁄89 28-107⁄89
NOTES: 1. Dimensions in [
3.
Ft-in. 38-55⁄169 48-15⁄169
‘‘K’’ mm 1050 1253
Ft-in. 28-911⁄169 38-03⁄89
mm 856 924
CONNECTION SIZES 13⁄89 Dia. [35] Field Power Supply Hole 21⁄29 Dia. [64] Power Supply Knockout 13⁄49 Dia. [44] Charging Port Hole 7⁄89 Dia. [22] Field Control Wiring Hole 3⁄49—14 NPT Condensate Drain 29 Dia. [51] Power Supply Knockout
A B C D E F
2.
‘‘J’’ mm 632 885
] are in millimeters.
Center of gravity. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only. 5. Minimum clearance (local codes or jurisdiction may prevail): a. Bottom to combustible surfaces (when not using curb) 0 in. on horizontal discharge units with electric heat 1 in. clearance to ductwork for 1 foot. b. Outdoor coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater clearance is optional. c. Overhead, 60 in. to assure proper outdoor fan operation. d. Between units, control box side, 42 in. per NEC (National Electrical Code). e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC. f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per NEC. g. Horizontal supply and return end, 0 inches. 6. With the exception of the clearance for the outdoor coil and combustible surfaces as stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance. 7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering material. 8. The vertical center of gravity is 18-71⁄29 for 008, 28-09 for 012 up from the bottom of the base rail.
Fig. 6 — Base Unit Dimensions 6
When installing units, provide a disconnect per the NEC. All field wiring must comply with the NEC and local requirements. In Canada, electrical connections must be made in accordance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part One. Install field wiring as follows: 1. Install conduit through side panel openings. For units without electric heat, install conduit between disconnect and control box. 2. Install power lines to terminal connections as shown in Fig. 7. 3. For units with electric heat, refer to Accessory Installation Instructions.
Step 5 — Make Electrical Connections Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code) ANSI (American National Standards Institute) /NFPA (National Fire Protection Association) 70-1987 and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
During operation, voltage to compressor terminals must be within range indicated on unit nameplate (see Tables 2A and 2B). On 3-phase units, voltages between phases must be balanced within 2%, and the current within 10%. Use the formula shown in Tables 2A and 2B, Note 2 on page 8 to determine the percentage of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
FIELD POWER SUPPLY — All units except 208/230-v units are factory-wired for the voltage shown on the unit nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by disconnecting the black wire from the 230-v orange wire on the transformer and connecting it to the 200-v red wire from the transformer. The end of the orange wire must then be insulated. Refer to unit label diagram for additional information. Pigtails are provided for field wire connections. Use factorysupplied splices or UL (Underwriters’ Laboratories) approved copper/aluminum connector.
C COMP IFC NEC
— — — —
LEGEND Contactor Compressor Indoor Fan Contactor National Electrical Code Field Wiring Factory Wiring Splice Connection (Factory-Supplied)
Fig. 7 — Power Wiring Connections
7
Table 2A — Electrical Data (Units Without Electrical Convenience Outlet) UNIT
VOLTAGE RANGE Min Max
COMPRESSOR
OFM
IFM
RLA
LRA
FLA
FLA
208/230-3-60
187
254
12.4
88.0
1.4
7.5
460-3-60
414
508
6.4
44.0
0.7
3.4
208/230-3-60
187
254
19.3
123.0
1.4
10.6
460-3-60
414
508
10.0
62.0
0.7
4.8
NOMINAL VOLTAGE (V-Ph-Hz)
ELECTRIC HEAT* kW† — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 13.9 16.5 27.8 33.0 41.7 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0
50HJQ008 (71⁄2 Tons)
50HJQ012 (10 Tons)
FLA — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1
POWER SUPPLY MCA 38.2/ 38.2 65.3/ 69.5 79.8/ 86.3 102.7/112.8 121.5/134.5 148.6/165.7 19.2 40.1 44.0 61.0 68.8 82.0 56.8/ 56.8 84.0/ 88.1 98.5/105.0 140.1/153.1 167.2/184.3 187.3/177.1 28.7 53.3 70.5 78.3 91.5 88.8
MOCP 40/ 40** 70/ 70 80/ 90 110/125 125/150 150/175 20** 45** 45** 70 70 90 60/ 60** 90/ 90 100/110 150/175 175/200 200/200 30** 60** 80 80 100 100
MINIMUM UNIT DISCONNECT SIZE FLA LRA 40/ 40 242/242 65/ 69 264/267 79/ 85 275/281†† 100/109 294/302†† 117/129 309/319†† 142/159 330/344†† 20 121 39 138 43 141 59 155 66 161 78 171 60/ 60 337/337 85/ 89 358/362†† 98/104 370/375†† 136/148 403/414†† 161/177 425/439†† 180/198 441/457†† 30 170 53 189 69 203 76 209 88 220†† 99 230††
Table 2B — Electrical Data (Units With Electrical Convenience Outlet) UNIT
NOMINAL VOLTAGE (V-Ph-Hz)
VOLTAGE RANGE Min Max
COMPRESSOR
OFM
IFM
RLA
LRA
FLA
FLA
208/230-3-60
187
254
12.4
88.0
1.4
7.5
460-3-60
414
508
6.4
44.0
0.7
3.4
208/230-3-60
187
254
19.3
123.0
1.4
10.6
460-3-60
414
508
10.0
62.0
0.7
4.8
ELECTRIC HEAT* kW† — 7.8/10.4 12.0/16.0 18.6/24.8 24.0/32.0 31.8/42.4 — 13.9 16.5 27.8 33.0 41.7 — 7.8/10.4 12.0/16.0 24.0/32.0 31.8/42.4 37.6/50.0 — 16.5 27.8 33.0 41.7 50.0
50HJQ008 (71⁄2 Tons)
50HJQ012 (10 Tons)
FLA — 21.7/ 25.0 33.3/ 38.5 51.6/ 59.7 66.6/ 77.0 88.3/102.0 — 16.7 19.8 33.4 39.7 50.2 — 21.7/ 25.0 33.3/ 38.5 66.6/ 77.0 88.3/102.0 104.4/120.3 — 19.8 33.4 39.7 50.2 60.1
POWER SUPPLY MCA 43.0/ 43.0 70.1/ 74.3 84.6/ 91.1 107.5/117.6 126.3/139.3 153.4/170.5 21.4 42.3 46.1 63.1 71.0 84.1 61.6/ 61.6 88.8/ 92.9 103.3/109.6 144.9/157.9 172.0/189.1 192.1/181.9 30.9 55.6 72.6 80.5 93.6 91.0
MOCP 45/ 45** 80/ 80 90/100 110/125 150/150 175/175 25** 45** 50** 70 80 90 70/ 70 90/100 110/110 150/175 175/200 200/200 35** 60** 80 90 100 100
MINIMUM UNIT DISCONNECT SIZE FLA LRA 46/ 46 247/247 71/ 75 269/272 84/ 90 280/285†† 105/115 298/307†† 122/134 313/324†† 147/163 335/349†† 23 123 42 140 46 143 61 157 68 163 80 174 65/ 65 341/341 90/ 94 363/366†† 104/110 375/380†† 142/154 408/418†† 167/183 430/443†† 185/204 446/462†† 33 172 55 191 71 205 78 211 90 222†† 102 232††
LEGEND FOR TABLES 2A AND 2B EXAMPLE: Supply voltage is 460-3-60 AB = 452 v BC = 464 v AC = 455 v
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor Fan Motor RLA — Rated Load Amps
Average Voltage = = =
*Heaters are field installed only. †Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. **Fuse or HACR circuit breaker. ††Factory installed disconnect is not available for these units when electric heat package is installed. NOTES: 1. In compliance with NEC requirements for multimotor and combination load and equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance. % Voltage Imbalance = 100 x
452 + 464 + 455 3 1371 3 457
Determine maximum deviation from average voltage: (AB) 457 − 452 = 5 v (BC) 464 − 457 = 7 v (AC) 457 − 455 = 2 v Maximum deviation is 7 v. Determine percentage of voltage imbalance: 7 % Voltage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company immediately.
max voltage deviation from average voltage average voltage
8
4. On 012 units, install vertical discharge block-off plate over duct openings. See Fig. 13. 5. Slide economizer into unit and secure with screws. See Fig. 14. NOTE: Be sure to engage rear economizer flange under tabs in vertical return-air opening.
FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions. Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections on unit (shown in Fig. 8) as described in Steps 1 through 4 below. NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat. 1. If unit is mounted on roof curb and accessory thru-thecurb service plate connection is used, route wire through connection plate. 2. Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 6). 3. Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 9. The raceway provides the UL required clearance between the high- and low-voltage wiring. 4. Connect thermostat wires to screw terminals of lowvoltage connector (see Fig. 8). NOTE: If thru-the-bottom power connections are used refer to the accessory installation instructions for information on power wiring. Refer to Fig. 6 for drilling holes in basepan. DEFROST BOARD — The defrost board timer cycle is set to 30 minutes. To change the cycle time, remove the wire from defrost board connected to the 30 minute quickconnect. See Fig. 10. Connect the wire to the 50 or 90 minute quick-connects on the defrost board, depending on the desired defrost time. HEAT ANTICIPATOR SETTINGS — For units with electric heat, set heat anticipator settings as shown in Table 3.
LEGEND AHA — Adjustable Heat RH — 24V Heating Anticipator TC — Thermostat-Cooling CC — Cooling TH — Thermostat-Heating Compensator Field Wiring RC — 24V Cooling Factory Wiring *Used with 2-stage electric heater.
Fig. 8 — Low-Voltage Connections With or Without Economizer or Two-Position Damper
Step 6 — Adjust Factory-Installed Options DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch has the capability of being locked in place for safety purposes. OPTIONAL VARISLIDE™ ECONOMIZER — The optional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position. NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate. Assembly 1. Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 8. 2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 11. Remove optional outdoor-air damper hood package from filter section. 3. Assemble outdoor-air hood top and side plates as shown in Fig. 12. Install seal strips on hoop top and sides. Put aside screen retainer and retainer screw for later assembly. Do not attach hood to unit at this time.
Fig. 9 — Field Control Wiring Raceway
9
Table 3 — Heat Anticipator Settings
UNIT
50HJQ
Heater kW* 10.4, 16.0 32.0, 24.8 42.4, 50.0
UNIT VOLTAGE 208/230 Configuration Heater 2-Stage kW 1-Stage Stage 1 Stage 2 0.3 NA NA 13.9, 16.5 27.7, 33.0 0.6 0.3 0.3 0.9 0.6 0.3 41.7, 50.0
460 Configuration 2-Stage 1-Stage Stage 1 Stage 2 0.3
NA
NA
0.6
0.3
0.3
*kW is based on 240 v.
10. Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter access panel slides along the tracks and is securely engaged. 11. Fasten hood top and side plate assembly to outdoor-air opening panel with screws provided. 12. Place knob supplied with economizer on OAT. See Fig. 19. Set for 3° F below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 19. 13. Connect OAT per Fig. 20. 14. Slide outdoor-air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen retainer to hood using screws provided. NOTE: Refer to Fig. 21 for economizer barometric relief damper characteristics.
Fig. 10 — Defrost Board
6. To convert to horizontal discharge application: a. Rotate the economizer 90 degrees until the economizer motor faces the outdoor section (see Fig. 15). b. Rotate the barometric relief damper cover 90 degrees. c. Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assembly.) See Fig. 16. 7. Insert economizer plug into economizer harness. Remove tape from barometric relief damper. See Fig. 14. 8. If ventilation air is not required, proceed to Step 9. If ventilation air is required, determine the minimum position setting for required airflow. See Fig. 17. Adjust minimum position setting by adjusting the screws on the position setting bracket. See Fig. 18. Slide bracket until the top screw is in the position determined by Fig. 17. Tighten screws. 9. Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and speed clips provided. See Fig. 19. Make sure OAT terminals are positioned up.
Fig. 11 — Panel Locations
10
ECONOMIZER MOTOR ECONOMIZER CONTROL BOARD WIRING HARNESS
BAROMETRIC RELIEF DAMPER
ECONOMIZER MOUNTING SCREWS
Fig. 14 — Varislide™ Economizer Installed in Unit ECONOMIZER CONTROL BOARD WIRING HARNESS
ECONOMIZER MOTOR
Fig. 12 — Outdoor-Air Hood Details
Fig. 15 — Horizontal Varislide Economizer Installation (90 Degree Rotation)
Fig. 13 — Vertical Discharge Block-Off Plate (Size 012 Only)
Fig. 16 — Horizontal Discharge Block-Off Plate
11
EXAMPLE: Given — Negative Pressure . . . . . . . . . . . . . . . . . . 0.1 in. wg Outdoor Air . . . . . . . . . . . . . . . . . . . . . . . . 1100 cfm Determine — Setting = 6
Fig. 17 — Varislide™ Economizer Minimum Position Setting
9 8 7 6 5 4 3 2 1 0
C
SO
D
TR
REV. B 1 9 8 8 1 8 A
B
S 5
4
2
T1
P1
TR
C
24VAC
2
TR1
1
3 mA MIN. AT 11 VDC
B A
ENTHALPY CONTROL
3
D
CW–SETPOINTS–CCW
RUSH AT 24VAC
CONTACT RATINGS: 1.5A RUN, 3.5A IN
°F
CONTACTS SHOWN IN HIGH ENTHALPY OR UNPOWERED STATE
OUTDOOR TEMP.
% 90 H DAMPER U 70 CLOSED M I 60 DAMPER D OPEN I 30 T Y 10 50 55 60 65 70 75 80 85 REV.
1
P
T
MINIMUM 3 POSITION
OPEN
Fig. 18 — Varislide Economizer Minimum Position Damper Setting
97-3672
Fig. 19 — Varislide Economizer Outdoor-Air Thermostat/Enthalpy Control Installation
Fig. 20 — Wiring Connections for Outdoor-Air Thermostat 12
b. The 2 potentiometers with slots for adjustment are located on the face of the economizer logic module. Turn the lower potentiometer fully clockwise. The dampers should be fully closed. Turn the potentiometer gradually counterclockwise until the desired position is reached. c. Connect T and T1 to the 24 V power supply. d. After installation is complete, calculate the minimum airflow across the economizer. To calculate the minimum airflow, the following data is needed: total cfm (cfm3), temperature of the total cfm (T3), temperature of the return air (T2), and temperature of the entering outside air (T1). Cfm1 is the outside air cfm, which will be the minimum airflow. Insert the data into the following equations: T1 (cfm1) + T2 (cfm2) = T3 cfm3 cfm2 = (cfm3 – cfm1) Therefore: T1 (cfm1) + T2 (cfm3 – cfm1) cfm3 Fig. 21 — Varislide™ Economizer Barometric Relief Damper Characteristics OPTIONAL PARABLADE ECONOMIZER — The optional PARABLADE economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position. NOTE: Horizontal discharge block-off plate is shipped with the air hood package. The PARABLADE economizer can only be used for vertical discharge applications. Discard this plate. Assembly 1. Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 7. 2. Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. See Fig. 11. Save panels and screws. Remove optional economizer so the outdoor-air damper hood package can be removed from the filter section. 3. Assemble outdoor-air hood top and side plates as shown in Fig. 12. Install seal strips on the hoop top and sides. Put aside screen retainer and retainer screw for later assembly. Do not attach hood to unit at this time. 4. On 012 units, install vertical discharge block-off plate over duct openings. See Fig. 13. 5. Slide economizer into unit and secure with screws. See Fig. 22. NOTE: Be sure to engage rear economizer flange under tabs in vertical return-air opening. 6. Insert economizer plug into economizer harness. Remove tape from barometric relief damper. See Fig. 22. 7. If ventilation air is not required, proceed to Step 8. If ventilation air is required, perform the following: a. Make sure the factory-installed jumper is in place across terminals P and P1 on the economizer logic module. T and T1 should be disconnected during adjustment.
8.
9.
10. 11.
= T3
Use this equation to determine cfm1, which is the minimum airflow across the economizer. (T3 – T2) cfm3 cfm1 = (T1 – T2) If cfm1 does not match the desired minimum airflow from Step 1, re-adjust the minimum position setting screw. Determine the enthalpy changeover set point from Fig. 23. The enthalpy changeover set point should be set to return the outdoor air damper to the minimum position when enthalpy rises above the set point. The settings are A, B, C, and D. Set the enthalpy changeover per the setting in Fig. 23. Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter access panel slides along the tracks and is securely engaged. See Fig. 24. Fasten hood top and side plate assembly (Fig. 25) to outdoor-air opening panel with screws provided. Slide outdoor-air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen retainer to hood using screws provided. See Fig. 26.
Step 7 — Adjust Indoor-Fan Speed — Adjust indoorfan speed to meet jobsite conditions. For units with electric heat, required minimum cfm is 2250 for 50HJQ008 and 3000 for 50HJQ012 with the following exceptions: UNIT
UNIT VOLTAGE
HEATER kW
208/230 208/230
42.4 50.0
460
50.0
50HJQ012
UNIT CONFIGURATION Horizontal Horizontal
REQUIRED MINIMUM CFM 3200 3200
Horizontal or Vertical
3200
Table 4 shows indoor-fan motor data. Table 5 shows fan rpm at motor pulley settings for standard and alternate motors. Refer to Tables 6-9 to determine fan speed settings. Fan motor pulleys are factory set for speed shown in Table 1.
13
Fig. 24 — Panels Reinstalled on Unit
Fig. 22 — PARABLADE Economizer Installed in Unit
CONTROL CURVE A B C D
CONTROL POINT (APPOX. DEG.) AT 50% RH 73 (23) 70 (21) 67 (19) 63 (17)
Fig. 25 — Outdoor-Air Hood Installed on Unit
Fig. 23 — Enthalpy Settings for PARABLADE Economizer
Fig. 26 — Filter Installed on Outdoor-Air Hood
14
To change fan speeds: 1. Shut off unit power supply. 2. Loosen belt by loosening fan motor mounting nuts. See Fig. 27 and 28. 3. Loosen movable pulley flange setscrew (see Fig. 29). 4. Screw movable flange toward fixed flange to increase speed or away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1. 5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.) To align fan and motor pulleys: 1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft. 3. Make angular alignment by loosening motor from mounting plate.
Fig. 28 — Typical Belt-Drive Motor Mounting for Size 012
To adjust belt tension: 1. Loosen fan motor mounting nuts. 2. Size 008 — Slide motor mounting plate away from fan scroll for proper belt tension (1⁄2-in. deflection with one finger) and tighten mounting nuts (see Fig. 27). Size 012 — Slide motor mounting plate downward to tighten belt tension. Secure motor mounting plate nuts. See Fig. 28. 3. Adjust bolt and nut on mounting plate to secure motor evaporator in fixed position.
Fig. 29 — Indoor-Fan Pulley Adjustment Table 4 — Indoor-Fan Motor Data
MOTOR MOUNTING PLATE NUTS
MAXIMUM MAXIMUM MAXIMUM UNIT UNIT AMP CONTINUOUS OPERATING VOLTAGE 50HJQ DRAW BHP* WATTS* 208/230 7.9 008 2.90 2615 460 3.6 208/230 11.1 012 4.20 3775 460 5.0
Fig. 27 — Typical Belt-Drive Motor Mounting for Size 008
LEGEND BHP — Brake Horsepower *Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be used with confidence. Using the fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
15
Table 5 — Fan Rpm at Motor Pulley Settings* UNIT 50HJQ 008 012
⁄ 1060 1060
0 1085 1080
12
1 1035 1035
11⁄2 1010 1015
MOTOR PULLEY TURNS OPEN 2 21⁄2 3 985 960 935 990 970 950
31⁄2 910 925
4 890 905
41⁄2 865 880
5 840 860
*Approximate fan rpm shown.
Table 6 — Fan Performance, 50HJQ008 — Vertical Discharge Units AIRFLOW (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
0.2 Rpm 511 518 534 549 557 565 581 597 613 629 646 662 679 696 712 729 746 755
AIRFLOW (Cfm) 2250 2300 2400 2500 2550 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
0.4 Bhp 0.52 0.55 0.61 0.67 0.71 0.74 0.81 0.89 0.97 1.06 1.15 1.25 1.35 1.46 1.57 1.69 1.85 1.89
Rpm 592 599 613 627 633 639 652 665 679 694 709 724 740 756 771 787 803 811
Bhp 1.97 2.00 2.08 2.18 2.24 2.29 2.40 2.52 2.65 2.78 2.91 3.04 3.18 3.32 3.48 — — —
BELT DRIVE MOTOR (cont) External Static Pressure (in. wg) 1.6 1.8 Rpm Bhp Rpm Bhp 937 2.33 947 2.66 939 2.36 979 2.69 944 2.40 987 2.76 949 2.48 1002 2.84 953 2.53 1003 2.87 957 2.58 1004 2.91 967 2.70 1010 3.01 978 2.62 1019 3.13 989 2.96 1030 3.27 1000 3.09 1040 3.41 1011 3.24 — — 1022 3.38 — — — — — — — — — — — — — — — — — — — — — — — — — —
1.4 Rpm 884 885 892 902 908 913 924 935 946 957 968 980 991 1003 1014 — — —
Bhp 0.74 0.77 0.84 0.90 0.94 0.97 1.04 1.12 1.20 1.29 1.39 1.50 1.61 1.73 1.85 1.98 2.12 2.20
BELT DRIVE MOTOR External Static Pressure (in. 0.6 0.8 Rpm Bhp Rpm 659 0.95 722 665 0.98 727 677 1.06 738 690 1.14 750 697 1.18 756 703 1.22 761 717 1.31 773 733 1.40 786 745 1.50 799 759 1.59 812 772 1.70 825 785 1.80 840 798 1.91 854 811 2.02 868 824 2.14 881 839 2.21 894 854 2.42 907 862 2.49 914
LEGEND Bhp — Brake Horsepower Input to Fan NOTES: 1. Boldface indicates a field-supplied drive is required. (See Note 6.)
wg) 1.0 Bhp 1.19 1.22 1.30 1.38 1.42 1.46 1.55 1.66 1.76 1.88 1.99 2.11 2.24 2.37 2.50 2.64 2.78 2.85
Rpm 778 783 794 805 811 816 827 839 850 862 875 887 900 914 928 942 956 963
1.2 Bhp 1.43 1.47 1.55 1.64 1.69 1.74 1.83 1.93 2.04 2.15 2.28 2.41 2.54 2.69 2.84 2.99 3.15 3.23
Rpm 829 834 844 855 861 866 878 889 900 911 923 934 946 959 971 984 997 —
Bhp 1.68 1.72 1.81 1.91 1.96 2.01 2.12 2.23 2.34 2.46 2.58 2.71 2.85 3.00 3.16 3.22 3.49 —
2.0 Rpm 1022 1025 1039 1041 1045 1050 1056 1061 — — — — — — — — — —
Bhp 3.10 3.12 3.20 3.25 3.28 3.31 3.37 3.47 — — — — — — — — — —
4. Values include losses for filters, unit casing, and wet coils. 5. Use of a field-supplied motor may affect wire sizing. Contact Carrier representative to verify. 6. Standard motor drive range: 840 to 1085 rpm. All other rpms require field-supplied drive. 7. Interpolation is permissible. Do not extrapolate.
2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.90. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
16
Table 7 — Fan Performance, 50HJQ012 — Vertical Discharge Units AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000
0.2 Rpm 459 478 500 519 537 561 592 654 668 683 697 711 726 741 755 770 784 799 814 829 843
AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000
0.4 Bhp 0.46 0.57 0.62 0.69 0.77 0.86 0.98 1.12 1.20 1.28 1.37 1.46 1.56 1.66 1.77 1.89 2.00 2.13 2.25 2.39 2.52
Rpm 625 637 647 658 669 680 692 714 727 741 754 767 780 794 808 821 835 849 863 877 892
Bhp 1.73 1.78 1.85 1.93 2.01 2.09 2.18 2.27 2.38 2.50 2.62 2.74 2.86 2.97 3.10 3.23 3.37 3.52 3.69 3.87 4.05
BELT DRIVE MOTOR (cont) External Static Pressure (in. wg) 1.6 1.8 Rpm Bhp Rpm Bhp 943 1.88 988 1.91 947 2.00 995 2.05 951 2.06 1000 2.17 959 2.10 1004 2.33 966 2.17 1009 2.46 974 2.24 1015 2.51 983 2.32 1023 2.58 991 2.47 1030 2.65 1001 2.58 1040 2.78 1010 2.70 1049 2.91 1020 2.83 1059 3.04 1029 2.96 1068 3.18 1039 3.10 1077 3.31 1049 3.23 1087 3.46 1059 3.37 1097 3.61 1070 3.51 1107 3.76 1081 3.64 1117 3.92 1092 3.78 1127 4.07 1103 3.93 1138 4.23 1114 4.09 1149 4.37 1126 4.25 1160 4.53
1.4 Rpm 886 892 899 907 915 924 933 950 959 969 979 989 1000 1011 1022 1033 1044 1056 1057 1079 1091
Bhp 0.85 0.90 0.97 1.03 1.10 1.17 1.24 1.31 1.40 1.49 1.59 1.69 1.80 1.91 2.03 2.15 2.27 2.40 2.53 2.67 2.81
BELT DRIVE MOTOR External Static Pressure (in. 0.6 0.8 Rpm Bhp Rpm 691 1.01 734 702 1.08 744 712 1.16 753 721 1.23 762 731 1.30 773 741 1.37 784 751 1.45 796 767 1.50 815 780 1.60 827 793 1.70 839 806 1.80 851 819 1.90 864 832 2.01 877 845 2.12 889 858 2.24 902 871 2.37 915 884 2.49 928 897 2.63 941 910 2.77 954 923 2.92 967 937 3.08 980
LEGEND Bhp — Brake Horsepower Input to Fan NOTES: 1. Boldface indicates a field-supplied drive is required. (See Note 6.)
wg) 1.0 Bhp 1.10 1.16 1.23 1.30 1.38 1.47 1.57 1.67 1.77 1.88 1.99 2.10 2.22 2.35 2.48 2.61 2.75 2.88 3.02 3.17 3.32
Rpm 787 796 805 814 823 832 841 861 873 884 895 907 919 931 943 955 968 981 993 1006 1019
1.2 Bhp 1.30 1.36 1.43 1.50 1.57 1.65 1.72 1.85 1.95 2.05 2.16 2.28 2.41 2.54 2.68 2.82 2.96 3.11 3.27 3.43 3.60
Rpm 829 837 845 853 862 871 880 906 916 927 938 949 960 971 983 995 1006 1018 1030 1043 1055
Bhp 1.50 1.56 1.63 1.71 1.78 1.86 1.95 2.08 2.18 2.28 2.38 2.49 2.60 2.72 2.86 3.01 3.17 3.32 3.48 3.65 3.82
2.0 Rpm 995 1008 1021 1036 1043 1054 1058 1064 1075 1085 1095 1105 1114 1124 1133 1143 1152 1162 1172 1182 1193
Bhp 1.95 2.07 2.20 2.36 2.47 2.59 2.70 2.82 2.96 3.11 3.25 3.39 3.54 3.69 3.84 4.00 4.17 4.33 4.50 4.68 4.85
4. Values include losses for filters, unit casing, and wet coils. 5. Use of a field-supplied motor may affect wire sizing. Contact Carrier representative to verify. 6. Standard motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive. 7. Interpolation is permissible. Do not extrapolate.
2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 4.20 with standard motor. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
17
Table 8 — Fan Performance, 50HJQ008 — Horizontal Discharge Units AIRFLOW (Cfm) 2250 2300 2400 2500 2550 2660 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
0.2 Rpm 465 471 482 494 501 507 520 533 546 559 572 585 598 610 623 636 649 655
AIRFLOW (Cfm) 2250 2300 2400 2500 2550 2660 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600 3700 3750
0.4 Bhp 0.43 0.45 0.50 0.54 0.57 0.59 0.65 0.71 0.77 0.83 0.90 0.96 1.03 1.10 1.17 1.25 1.33 1.37
Rpm 554 559 569 581 587 592 604 615 626 637 648 660 671 682 694 707 720 727
1.2 Rpm 810 816 824 832 836 839 846 855 863 872 882 892 902 912 921 930 940 945
1.4 Bhp 1.62 1.65 1.72 1.79 1.83 1.87 1.95 2.04 2.13 2.22 2.33 2.45 2.57 2.69 2.82 2.95 3.07 3.14
Rpm 850 859 872 882 887 891 898 906 913 921 930 939 948 958 968 978 — —
BELT DRIVE MOTOR External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Bhp Rpm 0.64 630 0.86 695 0.66 635 0.89 699 0.71 645 0.95 708 0.76 654 1.01 717 0.79 659 1.05 722 0.82 663 1.08 727 0.89 672 1.14 737 0.95 683 1.20 747 1.02 693 1.27 756 1.09 704 1.35 765 1.17 715 1.43 775 1.24 727 1.52 785 1.32 739 1.62 795 1.41 750 1.72 806 1.50 761 1.82 817 1.60 772 1.93 828 1.71 783 2.03 840 1.77 789 2.09 846 BELT DRIVE MOTOR (cont) External Static Pressure (in. wg) 1.6 1.8 Bhp Rpm Bhp Rpm 1.91 873 2.20 883 1.94 888 2.24 903 2.01 909 2.32 931 2.09 925 2.40 955 2.13 931 2.45 964 2.17 936 2.49 973 2.26 946 2.58 987 2.35 954 2.67 997 2.44 961 2.77 1006 2.54 969 2.88 1014 2.65 976 2.99 1021 2.76 984 3.10 — 2.88 993 3.21 — 3.01 1002 3.34 — 3.15 — — — 3.29 — — — — — — — — — — —
LEGEND Bhp — Brake Horsepower Input to Fan NOTES: 1. Boldface indicates a field-supplied drive is required. (See Note 6.)
1.0 Bhp 1.09 1.12 1.18 1.25 1.29 1.32 1.40 1.49 1.57 1.66 1.74 1.83 1.91 2.01 2.11 2.23 2.35 2.42
Rpm 757 760 768 776 780 784 793 802 813 823 832 841 851 860 870 880 890 896
Bhp 1.34 1.37 1.44 1.51 1.55 1.58 1.66 1.75 1.84 1.94 2.05 2.15 2.26 2.36 2.47 2.57 2.69 2.75
2.0 Bhp 2.50 2.55 2.64 2.72 2.77 2.82 2.91 3.01 3.12 3.22 3.34 — — — — — — —
Rpm 895 911 935 972 986 999 1019 1034 — — — — — — — — — —
Bhp 2.78 2.85 2.96 3.06 3.11 3.16 3.26 3.36 — — — — — — — — — —
4. Values include losses for filters, unit casing, and wet coils. 5. Use of a field-supplied motor may affect wire sizing. Contact Carrier representative to verify. 6. Standard motor drive range: 840 to 1085 rpm. All other rpms require field-supplied drive. 7. Interpolation is permissible. Do not extrapolate.
2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 2.90. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
18
Table 9 — Fan Performance, 50HJQ012 — Horizontal Discharge Units AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000
0.2 Rpm 459 478 500 519 537 561 592 607 621 636 650 665 680 696 711 727 742 758 773 789 805
AIRFLOW (Cfm) 3000 3100 3200 3300 3400 3500 3600 3700 3800 3900 4000 4100 4200 4300 4400 4500 4600 4700 4800 4900 5000
0.4 Bhp 0.35 0.46 0.57 0.62 0.69 0.77 0.86 0.97 1.05 1.13 1.21 1.30 1.39 1.49 1.60 1.70 1.82 1.94 2.06 2.19 2.32
Rpm 595 605 615 625 637 647 658 670 681 693 705 717 728 739 750 762 774 786 799 812 826
1.2 Rpm 822 829 837 845 853 862 871 879 889 898 908 917 925 935 945 955 967 980 992 1003 1014
1.4 Bhp 1.44 1.50 1.56 1.63 1.71 1.78 1.86 1.95 2.03 2.12 2.21 2.32 2.44 2.56 2.68 2.82 2.96 3.11 3.26 3.41 3.56
Rpm 872 882 886 892 899 907 915 927 934 942 950 960 969 979 988 996 1005 1015 1025 1036 1049
BELT DRIVE MOTOR External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Bhp Rpm 0.74 657 0.88 716 0.79 667 0.94 725 0.85 679 1.01 734 0.90 691 1.08 744 0.97 702 1.16 753 1.03 712 1.23 762 1.10 721 1.30 773 1.18 732 1.37 782 1.25 742 1.45 795 1.32 751 1.53 808 1.40 761 1.61 819 1.48 772 1.71 830 1.57 783 1.81 839 1.66 794 1.91 848 1.75 805 2.02 857 1.85 817 2.12 867 1.96 828 2.23 877 2.07 840 2.34 888 2.18 852 2.46 899 2.30 863 2.57 910 2.43 875 2.70 921 BELT DRIVE MOTOR (cont) External Static Pressure (in. wg) 1.6 1.8 Bhp Rpm Bhp Rpm 1.69 919 1.88 950 1.73 932 2.00 965 1.78 943 2.06 978 1.85 947 2.10 988 1.93 951 2.17 995 2.01 959 2.24 1000 2.09 965 2.32 1005 2.17 973 2.38 1013 2.26 980 2.48 1022 2.36 987 2.59 1030 2.46 994 2.70 1037 2.55 1001 2.81 1045 2.65 1009 2.92 1051 2.77 1018 3.03 1058 2.89 1028 3.14 1066 3.02 1037 3.25 1074 3.16 1046 3.38 1084 3.30 1056 3.52 1093 3.45 1064 3.67 1103 3.61 1073 3.83 1112 3.79 1083 4.00 1121
LEGEND Bhp — Brake Horsepower Input to Fan NOTES: 1. Boldface indicates a field-supplied drive is required. (See Note 6.)
1.0 Bhp 1.05 1.10 1.16 1.23 1.30 1.38 1.47 1.56 1.66 1.76 1.86 1.96 2.05 2.14 2.24 2.35 2.46 2.59 2.72 2.86 2.99
Rpm 770 779 787 796 805 814 823 833 842 851 861 871 883 896 908 919 929 938 947 957 966
Bhp 1.24 1.30 1.36 1.43 1.50 1.57 1.65 1.73 1.82 1.92 2.02 2.13 2.25 2.38 2.51 2.63 2.75 2.87 2.98 3.11 3.24
2.0 Bhp 1.70 1.80 1.91 2.05 2.17 2.33 2.46 2.57 2.69 2.81 2.92 3.04 3.17 3.29 3.41 3.54 3.66 3.79 3.92 4.07 4.23
Rpm 962 971 984 995 1008 1021 1036 1046 1058 1068 1077 1085 1092 1100 1106 1113 1121 1129 1137 1147 1157
Bhp 1.82 1.95 2.07 2.20 2.32 2.47 2.59 2.73 2.87 3.01 3.14 3.21 3.40 3.53 3.67 3.81 3.95 4.09 4.22 4.36 4.50
4. Values include losses for filters, unit casing, and wet coils. 5. Use of a field-supplied motor may affect wire sizing. Contact Carrier representative to verify. 6. Standard motor drive range: 860 to 1080 rpm. All other rpms require field-supplied drive. 7. Interpolation is permissible. Do not extrapolate.
2. indicates field-supplied motor and drive are required. 3. Maximum continuous bhp is 4.20. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
19
PRE-START-UP
START-UP Unit Preparation — Make sure that unit has been installed in accordance with these installation instructions and applicable codes.
Failure to observe the following warnings could result in serious personal injury: 1. Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured. 3. Do not remove compressor terminal cover until all electrical sources are disconnected. 4. Relieve all pressure from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals. Use accepted methods to recover refrigerant. 5. Never attempt to repair soldered connection while refrigerant system is under pressure. 6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To remove a component, wear protective goggles and proceed as follows: a. Shut off electrical power to unit. b. Relieve all pressure from system using both highand low-pressure ports. Use accepted methods to recover refrigerant. c. Cut component connection tubing with tubing cutter and remove component from unit. d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame.
Return-Air Filters — Make sure correct filters are installed in unit (see Table 1). Do not operate unit without returnair filters. Outdoor-Air Inlet Screen — Outdoor-air inlet screen must be in place before operating unit. Compressor Mounting — Compressors are internally spring mounted. Do not loosen or remove compressor holddown bolts.
Internal Wiring — Check all electrical connections in unit control boxes; tighten as required. Refrigerant Service Ports — Each refrigerant system has 5 Schrader-type service gage ports: 2 on the suction line, one on the cooling mode liquid line, and 2 on the compressor discharge line. Be sure that caps on the ports are tight. Compressor Rotation — It is important to be certain the scroll compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gages to suction and discharge pressure fittings. 2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up. If the suction pressure does not drop and the discharge pressure does not rise to normal levels: 1. Note that the indoor fan is probably also rotating in the wrong direction (006 and 007 3-phase units only). 2. Turn off power to the unit. 3. Reverse any two of the unit power leads. 4. Turn on power to the compressor. The suction and discharge pressure levels should now move to their normal start-up levels. NOTE: When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not provide heating/cooling.
Proceed as follows to inspect and prepare the unit for initial start-up: 1. Remove all access panels. 2. Read and follow instructions on all WARNING, CAUTION, and INFORMATION labels attached to or shipped with unit. 3. Make the following inspections: a. Inspect for shipping and handling damages such as broken lines, loose parts, or disconnected wires. b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a refrigerant leak. Leak-test all refrigerant tubing connections using electronic leak detector, halide torch, or liquid-soap solution. c. Inspect all field- and factory-wiring connections. Be sure that connections are completed and tight. d. Inspect coil fins. If damaged during shipping and handling, carefully straighten fins with a fin comb.
Cooling — To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at AUTO position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor. Check unit charge. Refer to Refrigerant Charge section on page 23. Reset thermostat at a position above room temperature. Compressor will shut off. TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting. Units are equipped with CycleLOC™ protection device. Unit shuts down on any safety trip and remains off; an indicator light on the thermostat comes on. Check reason for safety trip. Compressor restart is accomplished by manual reset at the thermostat by turning the selector switch to OFF position and then ON position.
4. Verify the following conditions: a. Make sure that outdoor-fan blades are correctly positioned in fan orifice. Refer to Outdoor Fan Adjustment section on page 23 for more details. b. Make sure that air filter(s) is in place. c. Make sure that condensate drain trap is filled with water to ensure proper drainage. d. Make sure that all tools and miscellaneous loose parts have been removed.
20
When the supply-air temperature is between 55 F and 57 F, the supply-air thermostat has open switches between the T2 and 24 vac terminals. This causes the economizer damper to remain in an intermediate open position. If the outdoor air alone cannot satisfy the cooling requirements of the conditioned space, economizer cooling is integrated with mechanical cooling, providing second stage cooling. Compressor no. 1 and outdoor fans will be energized, and the position of the economizer damper will be determined by the supply-air temperature. Compressor no. 2 is locked out. When the second stage of cooling is satisfied, the compressor and outdoor fan motors will be deenergized. The damper position will be determined by the supply-air temperature. When the first stage of cooling is satisfied, the damper will move to fully closed position. COOLING, UNITS WITH PARABLADE ECONOMIZER — When the outdoor air is above the enthalpy control setting, and the room thermostat calls for cooling, the compressor contactor no. 1 is energized to start compressor no. 1 and the outdoor fan motors. The indoor fan motor is energized and the economizer damper moves to the minimum position. Upon further call for cooling, compressor contactor no. 2 is energized, starting compressor no. 2. After the room thermostat is satisfied the damper will spring return to the fully closed position. When the outdoor air is below the enthalpy control setting and the thermostat calls for cooling, the economizer outdoor air damper is opened proportionally to maintain between 50 and 56 F at the mixed air sensor. If outside air alone cannot satisfy the cooling requirements, economizer cooling is integrated with mechanical cooling and the second compressor is locked out. When the room thermostat is satisfied, the damper will spring return to the fully closed position. HEATING, UNITS WITH ECONOMIZER (If Accessory Heater is Installed) — When the room thermostat calls for heat through terminal W1, the indoor-fan contactor outdoor fan contactor, C1, and C2 are energized. On units equipped for 2 stages of heat, when additional heat is needed, heater contactor is energized through W2. The indoor-fan motor is energized, and the economizer damper moves to the minimum position. If the two-position damper is used, the outdoorair damper opens to the minimum position whenever the indoor fan opens. When the thermostat is satisfied, the damper moves to the fully closed position. DEFROST — When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT2) and the defrost timer is at the end of a timed period (adjustable at 30, 50, or 90 minutes), reversing valve solenoids (RVS1 and RVS2) are energized and the OFC is deenergized. This switches the position of the reversing valves and shuts off the outdoor fans. The electric heaters (if installed) will be energized. The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65 F, or the duration of defrost cycle completes a 10-minute period. During the defrost mode, if circuit 1 defrosts first, RVS1 will oscillate between heating and cooling modes until the defrost mode is complete. At the end of the defrost cycle, the electric heaters (if installed) will be deenergized; the reversing valves switch and the outdoor-fan motors will be energized. The unit will now operate in the heating mode. If the space thermostat is satisfied during a defrost cycle, the unit will continue in the defrost mode until the time or temperature constraints are satisfied.
Heating — To start unit, turn on main power supply. Set thermostat at HEAT position and a setting above room temperature, fan at AUTO position. First stage of thermostat energizes the indoor fan motor, compressor, and outdoor fan; second stage energizes electric heater elements if installed. Check heating effects at air supply grille(s). If accessory electric heaters do not energize, reset limit switch (located on indoor-fan scroll) by depressing button located between terminals on the switch. TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting heating selector lever below room temperature temporarily shuts unit off until space temperature falls below thermostat setting.
Safety Relief — A soft solder joint in the suction line at the loss-of-charge/low-pressure switch fitting provides pressure relief under abnormal temperature and pressure conditions. Ventilation (Continuous Fan) — Set fan and system selector switches at ON and OFF positions, respectively. Indoor fan operates continuously to provide constant air circulation.
Operating Sequence COOLING, UNITS WITHOUT ECONOMIZER — When the thermostat calls for cooling, terminals G and Y1 are energized. The indoor fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and the indoor-fan motor, compressor no. 1, and outdoor fans start. The outdoor-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts. HEATING, UNITS WITHOUT ECONOMIZER — Upon a call for heating through terminal W1, IFC, OFC, C1, and C2 are energized. On units equipped for 2 stages of heat, when additional heat is needed, HC is energized through W2. COOLING, UNITS WITH VARISLIDE™ ECONOMIZER — When the outdoor-air temperature is above the OAT setting and the room thermostat calls for cooling, the compressor contactor no. 1 is energized to start compressor no. 1 and outdoor fan motors. The indoor fan motor (IFM) is energized and the economizer damper moves to the minimum position. Upon a further call for cooling, compressor contactor no. 2 will be energized, starting compressor no. 2. After the thermostat is satisfied and the IFM is deenergized, the damper moves to the fully closed position. When the outdoor air temperature is below the OAT setting and the thermostat calls for Y1 and G, the economizer damper moves to the minimum position when the indoor fan starts. The first stage of cooling is provided by the economizer. If the supply-air temperature is above 57 F, a switch on the supply-air thermostat is closed between the T2 terminal and the 24 vac terminal. This causes the damper to continue to modulate open until the supply-air temperature falls below 55 F or the damper reaches the fully open position. When the supply-air temperature is between 55 F and 52 F, the supply-air thermostat has open switches between the T2 and 24 vac terminals and between the T1 and 24 vac terminals. This causes the economizer damper to remain in an intermediate open position. If the supply-air temperature falls below 52 F, a switch on the supply-air thermostat is closed between the T1 terminal and the 24 vac terminal. This causes the damper to modulate closed until the supply-air temperature rises above 55 F or the damper reaches the minimum position. 21
SERVICE When servicing unit, shut off all electrical power to unit to avoid shock hazard or injury from rotating parts.
Cleaning — Inspect unit interior at the beginning of each heating and cooling season or as operating conditions require. INDOOR COIL 1. Turn unit power off. Remove filter access panel and indoor coil access panel. 2. If economizer or accessory two-position damper is installed, remove economizer/two-position damper by disconnecting economizer plug and removing mounting screws (see Fig. 14 or 15). Refer to Accessory Economizer or Two-Position Damper Installation Instructions for more details. 3. Slide filters out of unit.
Fig. 31 — Propping Up Top Panel
4. Clean coil using a commercial coil cleaner or dishwasher detergent in a pressurized spray canister. Wash both sides of coil and flush with clean water. For best results, backflush toward return-air section to remove foreign material. 5. Flush condensate pan after completion. 6. Reinstall economizer/two-position damper and filters. 7. Reconnect wiring. 8. Replace access panels. OUTDOOR COILS — Inspect coils monthly. Clean condenser coils annually, and as required by location and outdoorair conditions. Clean 2-row coils as follows: 1. Turn off unit power. 2. Remove top panel screws on outdoor end of unit. 3. Remove outdoor coil corner post. See Fig. 30. To hold top panel open, place coil corner post between top panel and center post. See Fig. 31. 4. Remove device holding coil sections together at return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 32.
Fig. 32 — Separating Coil Sections 5. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner. 6. Secure the sections together. Reposition the coil sections, and remove the coil corner post from between the top panel and center post. Install the coil corner post and coil center post, and replace all screws. CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drain dry or protect against freeze-up. FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters. OUTDOOR-AIR INLET SCREEN — Clean screen with steam or hot water and a mild detergent. Do not use disposable filters in place of screens.
Lubrication COMPRESSORS — Each compressor is charged with correct amount of oil at the factory. FAN MOTOR BEARINGS — Fan motor bearings are permanently lubricated. No further lubrication of outdoor- or indoor-fan motors is required.
Fig. 30 — Cleaning Outdoor Coil
22
Outdoor Fan Adjustment (Fig. 33) 1. Shut off unit power supply. 2. Remove outdoor-fan assembly (grille, motor, motor cover, and fan) and loosen fan hub setscrews. 3. Adjust fan height as shown in Fig. 33. 4. Tighten setscrews and replace outdoor-fan assembly.
UNIT VOLTAGE 208/230 V 460 V
‘‘A’’ in. 2.75 3.50
Fig. 33 — Outdoor Fan Adjustment
Economizer Adjustment — Refer to Optional Economizer sections on pages 9 and 13.
Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Refer to Carrier Refrigerant Service Techniques Manual, Refrigerants section. Unit panels must be in place when unit is operating during charging procedure. NO CHARGE — Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 1). LOW CHARGE COOLING — Use Cooling Charging Charts, Fig. 34 and 35. Vary refrigerant until the conditions of the appropriate chart are met. Note that charging charts are different from the type normally used. Charts are based on charging the units to the correct superheat for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading. Indoorair cfm must be within the normal operating range of the unit. TO USE COOLING CHARGING CHARTS — Take the outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine what the suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted. EXAMPLE: (Fig. 34) Outdoor Temperature . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . 70 psig Suction Temperature should be . . . . . . . . . . . . . 51 F (Suction Temperature may vary 65° F.) If Chargemastert charging device is used, temperature and pressure readings must be accomplished using the charging chart.
Fig. 34 — Cooling Charging Chart, 50HJQ008
Fig. 35 — Cooling Charging Chart, 50HJQ012
23
TROUBLESHOOTING Table 10 — Heating and Cooling Troubleshooting PROBLEM Compressor and outdoor fan will not start.
CAUSE Power failure. Fuse blown or circuit breaker tripped. Defective thermostat, contactor, transformer, or control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high. High-pressure switch tripped. Low-pressure switch tripped. Freeze-up protection thermostat tripped. Compressor will not start Faulty wiring or loose connections in compressor circuit. but outdoor fan runs. Compressor motor burned out, seized, or internal overload open. Defective overload. One leg of 3-phase power dead.
REMEDY Call power company. Replace fuse or reset circuit breaker. Replace component. Determine cause and correct. Check wiring diagram and rewire correctly. Lower thermostat setting below room temperature. See problem ‘‘Excessive head pressure.’’ Check for leaks, repair, and recharge. See problem ‘‘Suction pressure too low.’’ Check wiring and repair or replace. Determine cause. Replace compressor.
Determine cause and replace. Replace fuse or reset circuit breaker. Determine cause. Compressor cycles Refrigerant overcharge or undercharge. Recover refrigerant, evacuate system, and (other than normally recharge to nameplate. satisfying thermostat). Defective compressor. Replace and determine cause. Insufficient line voltage. Determine cause and correct. Blocked outdoor coil or dirty air filter. Determine cause and correct. Defective overload. Determine cause and replace. Defective thermostat. Replace thermostat. Faulty outdoor-fan (cooling) or indoor-fan (heating) motor or Replace. capacitor. Restriction in refrigerant system. Locate restriction and remove. Compressor operates Dirty air filter. Replace filter. continuously. Unit undersized for load. Decrease load or increase unit size. Thermostat set too low. Reset thermostat. Low refrigerant charge. Locate leak, repair, and recharge. Leaking valves in compressor. Replace compressor. Air in system. Recover refrigerant, evacuate system, and recharge. Outdoor coil dirty or restricted. Clean coil or remove restriction. Scroll compressor Compressor rotating in the wrong direction. Reverse the 3-phase power leads as described in makes excessive noise Start-Up, page 20. Excessive head pressure. Dirty air filter. Replace filter. Dirty outdoor coil. Clean coil. Refrigerant overcharged. Remove excess refrigerant. Air in system. Recover refrigerant, evacuate system, and recharge. Condensing air restricted or air short-cycling. Determine cause and correct. Head pressure too low. Low refrigerant charge. Check for leaks, repair, and recharge. Compressor valves leaking. Replace compressor. Restriction in liquid tube. Remove restriction. Excessive suction High heat load. Check for source and eliminate. pressure. Compressor valves leaking. Replace compressor. Refrigerant overcharged. Recover excess refrigerant. Suction pressure too low. Dirty air filter (cooling) or dirty outdoor coil (heating). Replace filter. Low refrigerant charge. Check for leaks, repair, and recharge. Metering device or low side restricted. Remove source of restriction. Insufficient indoor airflow (cooling mode). Increase air quantity. Check filter and replace if necessary. Temperature too low in conditioned area. Reset thermostat. Field-installed filter drier restricted. Replace. Outdoor ambient temperature below 25 F. Install low-ambient kit. Compressor no. 2 Unit in economizer mode. Proper operation; no remedy necessary. will not run.
24
Table 11 — Varislide™ Economizer Troubleshooting PROBLEM Damper does not open.
CAUSE Indoor fan is off.
No power to economizer motor.
Economizer motor failure. Economizer operation limited to minimum position.
OAT or EC set too high.
Economizer control board incorrectly wired or not functioning.
Incorrect SAT wiring or inoperative SAT.
Damper does not close.
Incorrect economizer wiring.
Incorrect damper actuator wiring or inoperative economizer circuit board.
Incorrect SAT wiring or inoperative SAT.
Economizer motor failure. Economizer damper does not close on power loss.
Insufficient battery power, inoperative economizer control board.
C1 — Common Power EC — Enthalpy Control IFC — Indoor Fan Contactor
REMEDY 1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that 24 vac is present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Check proper thermostat connection to G on the connection board. 1. Check that SW3 is properly making contact with the damper blade. Check that SW1 is in the NC (normally closed) position. 2. Check diode D18. If diode is not functioning properly, replace economizer control board. 3. Confirm that the economizer control board is grounded properly at PL6-4 (brown wire) and at brown terminal of the economizer control board (brown wire). The economizer motor must also be grounded properly at the negative motor terminal (brown wire). 4. Verify SW1 and SW3 are working and wired properly (see unit label diagram). 5. Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black wire). If 24 vac not present, check unit wiring (see unit label diagram). If 24 vac is found in both places, check for 24 vac at the yellow terminal of the economizer control board (yellow wire). If 24 vac power is not present, replace the economizer control board. If the indoor fan and economizer motor are energized, verify that there is a minimum of 18 vdc at the positive motor terminal. If the motor is not operating, replace the motor. 1. Set at correct temperature (3 F below indoor space temperature). 2. Check OAT or EC by setting above outdoor temperature or humidity level. If the OAT or EC switches do not close, replace OAT or EC. 1. Perform the following tests when OAT or EC is closed, Y1 is called for, and damper is at minimum position. Confirm 24 vac on gray terminal of the economizer control board (gray wire). If 24 vac is not present, check wiring (see unit label diagram). 2. Verify that SW1 and SW3 are wired correctly and working properly (see unit label diagram). 3. Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is not present, check wiring (see unit wiring label diagram). 4. Check 24 vac output at PL6-10 (white wire). If 24 vac is not present, replace economizer control board. 1. After verifying that the OAT and EC settings and the economizer control board wiring are correct, check to ensure that the 24 vac terminal of the SAT has 24 vac (white wire). If OAT, EC, and control board are functioning and wired properly and no 24 vac exists, check wiring (see unit label diagram). 2. If supply-air temperature is greater than 57 F, 24 vac should be found at terminal T2 on the SAT (pink wire). If 24 vac is not present, replace SAT. 1. Verify that SW2 and SW4 are wired and working properly (see unit label diagram). 2. Check diode D19. If diode is not functioning properly, replace economizer control board. 1. After verifying that the wiring is correct, modulate the damper to the minimum position. Remove the calls for G. 2. If the damper does not move, check for 24 vac at PL6-1 (red wire). If 24 vac is not present, check wiring (see unit label diagram). 3. If damper still does not move, check for 24 vac at blue terminal of economizer control board (blue wire). If 24 vac is not present, replace the economizer control board. 1. After verifying that the wiring is correct and the economizer control board is functioning properly, place the OAT or EC switch in the closed position. Place a call for Y1 and open the damper to the fully open position. Confirm that the 24 vac terminal of the SAT has 24 vac (white wire). If 24 vac is not present, check wiring (see unit label diagram). 2. If supply-air temperature is less than 52 F, 24 vac should be found at terminal T1 on the SAT (violet wire). If 24 vac not found, replace SAT. If economizer control board and SAT are functioning properly, verify that there is a minimum of 18 vdc at the positive motor terminal. If a minimum of 18 vdc is present and the motor is still not operating, replace the motor. 1. Check voltage potential across batteries. If lower than 14 vdc, replace close-onpower-loss power supply (9-v alkaline batteries). Check this emergency power supply on a regular basis or whenever the filters are changed. 2. If the close-on-power-loss and economizer control board are functioning properly, check for 14 vdc or higher at the blue terminal of the economizer control board (blue wire) when power is disconnected from unit. If 14 vdc is not present, replace the control board.
LEGEND IFO — Indoor Fan On OAT — Outdoor-Air Thermostat PL — Plug
25
SAT — Supply-Air Thermostat SW — Economizer Position Switch
Table 12 — PARABLADE Economizer Troubleshooting PROBLEM Damper does not open.
CAUSE Indoor fan not on.
REMEDY Check wiring between G on connection board and indoor fan contactor. No power to economizer 1. Disconnect power at TR and TR1. Disconnect jumper across P and P1. motor. 2. Connect jumper across TR and 1. 3. Connect jumper across T1 and T. 4. If connected, remove enthalpy sensor from terminals SO and 1. 5. Apply power (24 vac) to terminals TR and TR1. The LED should be off and the damper should be in the closed position. 6. Disconnect the factory-installed 620 ohm resistor from terminals SR and 1. The LED should light up and the motor should drive towards open. If this does not happen, replace the economizer control module. Economizer motor If the indoor fan and economizer motor are energized, verify that there is a failure. minimum of 24 vac at terminals TR and TR1. If the motor is not operating, replace the motor. Economizer operation limited Economizer control mod1. To simulate high or low enthalpy, reconnect the factory-installed 620 ohm to minimum position. ule failure. resistor across terminals SR and 1. 2. Connect 1.2 Kohm checkout resistor across terminals SO and 1. Turn the enthalpy set point to ‘‘A.’’ The LED should turn on, indicating low enthalpy. The motor should drive towards open. If LED does not light, replace module. If motor does not drive open, check motor operation. 3. Turn the enthalpy set point to ‘‘D.’’ The LED should turn off, indicating high enthalpy. The motor should drive towards closed. If these actions do not occur, replace module. 4. Disconnect 1.2 Kohm checkout resistor before resuming operation. Damper does not close. No power to economizer. 1. Disconnect power at TR and TR1. Disconnect jumper across P and P1. 2. Connect jumper across TR and 1. 3. Connect jumper across T1 and T. 4. If connected, remove enthalpy sensor from terminals SO and 1. Factoryinstalled 620 ohm resistor should be connected to terminals SR and 1. 5. Apply power (24 Vac) to terminals TR and TR1. The LED should be off and the damper should be in the closed position. 6. Disconnect the factory-installed 620 ohm resistor from terminals SR and 1. The LED should light up and the motor should drive towards open. If this does not happen, replace the economizer control module. Spring return failure. If power to unit is off and damper does not close, check for a bound linkage. If linkage is not bound, then internal spring may be broken. Replace actuator. Economizer motor If the economizer control module is functioning properly, verify that there is a failure. minimum of 24 vac at terminals TR and TR1. If the motor is not operating, replace the motor. Damper does not open Sensor incorrectly wired or To verify sensor operation, reconnect the 1 lead of the outdoor enthalpy sensor or close according bad. to the 1 terminal of the economizer control module. Connect a DC milliammeter to enthalpy readings. between terminals SO of the economizer control module and terminal S of the enthalpy sensor. The milliammeter should indicate between 3 and 25 mA if the sensor is operating properly. If the milliammeter indicates 0, the sensor may be wired backwards. If any other readings are shown, replace the sensor.
LED — Light-Emitting Diode
PACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions. For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included.
Copyright 1995 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No. 565-066 Printed in U.S.A. Form 50HJQ-2SI Pg 26 6-95 Replaces: New Tab 5a 5a
I. PRELIMINARY INFORMATION MODEL NO.:
SERIAL NO.:
DATE:
TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed) M VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS M CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS M CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE M VERIFY THAT UNIT INSTALLATION IS LEVEL M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS M CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
III. START-UP ELECTRICAL SUPPLY VOLTAGE
L1-L2
L2-L3
L3-L1
CIRCUIT 1 COMPRESSOR AMPS
L1
L2
L3
CIRCUIT 2 COMPRESSOR AMPS
L1
L2
L3
INDOOR FAN AMPS TEMPERATURES OUTDOOR-AIR TEMPERATURE
DB
RETURN-AIR TEMPERATURE
DB
WB
COOLING SUPPLY AIR PRESSURES REFRIGERANT SUCTION, CIRCUIT 1
PSIG
REFRIGERANT SUCTION, CIRCUIT 2
PSIG
REFRIGERANT DISCHARGE, CIRCUIT 1
PSIG
REFRIGERANT DISCHARGE, CIRCUIT 2
PSIG
M VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION M VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGE 23.
Copyright 1995 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No. 565-066 Printed in U.S.A. Form 50HJQ-2SI Pg CL-1 6-95 Replaces: New Tab 5a 5a
CUT ALONG DOTTED LINE
(Remove and Store in Job File)
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
START-UP CHECKLIST