Transcript
InstructionManual 1262-IN-003-0-02 January 1998
Model 7SP
FG
1/16 DIN, Four Digit Display Controller Programmer MODEL: 0 7 S P - 9 3 Field No.
1 2 3 4
5 6 7
11-300-0-0 0 8 9 10 11 12 13 14 15
Fields 1 through 4. BASE 07SP - Controller Programmer
Field 7. OUTPUT 1 1 - Relay 6 - SSR Driver
Field 5. INPUT 9 - TC Types J, K, L, N, R, S and T 3 wire RTD 0 to 20 mAdc and 4 to 20 mAdc 0 to 60 mVdc and 12 to 60 mVdc 0 to 5 Vdc and 1 to 5 Vdc 0 to 10 Vdc and 2 to 10 Vdc Note: All inputs are factory calibrated and selectable by keyboard. Factory set at Type J.
Field 8. OUTPUT 2. (Cooling/Alarm) 1 - Relay Field 9. OUTPUT 3 1 - Alarm 2 Field 10. POWER SUPPLY 3 - 100 to 240 Vac
Field 6. CONTROL ACTION 3 - PID and Smart AT
Fields 11 through 15. RESERVED
2
Congratulations . . . on your purchase of one of the easiest to configure controllers on the market. You will see that after a short 4 step configuration procedure, your process will be up and running.
Un p ac k t he In st ru m e nt
If for any reason you encounter difficulty with the controller set-up, please call your Barber-Colman Representative or Barber-Colman at 1-800-626-5561.
W iring
Guide to Simple Set-up Advantage-EZ To set-up the Advantage-EZ controllers only four steps are required: 1. Wire the Instrument 2. Configure the instrument 3. Check the operating mode parameters 4. Check the autotune (Smart AT) process
C o nfig u ra tio n
O p er ating Pa ra m et ers
Au to tu ning
SV
3
Contents CAUTION:
Mounting Requirements ........................ 6 Wiring Guidelines ................................... 7 Terminal Board .............................. 7 Configuration ....................................... 12 Preliminary Hardware Settings ... 12 Configuration Procedure ............. 13 Default Configuration Parameters17 Operating Mode ................................... 19 Operating Key Functions ............ 19 Operating Modes ........................ 20 Indicators .................................... 24 Autotuning (Smart AT) ................. 24 Operating Parameters ................. 24 Default Operating Parameters .... 26 Error Messages ........................... 28 Specifications ...................................... 29 Calibration ............................................ 33 Calibration Parameters ............... 34 Procedure ................................... 34 Maintenance ........................................ 39
USE WIRE SUITABLE FOR 75°C MINIMUM.
Notes • • •
4
For supply connections use No 16 AWG or larger wires rated for at least 75 °C. Use copper conductors only. Class 2 wiring must be separated a minimum of 1/4 inch from any Class 1 conductors.
Mounting Requirements Proceed as follows: 1) Insert gasket on the instrument case. 2) Insert instrument in control panel. 3) Pushing the instrument against the panel, insert the mounting bracket. 4) With a screwdriver, turn the screws with a torque between 0.3 and 0.4 Nm (2.6 to 3.5 lfb-in).
Select a location for instrument mounting where minimum vibrations are present and the ambient temperature is within 0 and 50°C (32 and 122°F). The instrument can be mounted on a panel up to 15 mm thick (.59") with a square cutout of 45 x 45 mm (1.77 x 1.77"). Surface texture of the panel must be better than 6.3 µmm (248 microinches). The instrument is shipped with rubber panel gasket (50 to 60 Sh). To assure IP65 and NEMA 4 protection, insert the panel gasket between the instrument and panel as shown.
Screw
Bracket
Panel Gasket
5
MOUNTING REQUIREMENTS Dimensions and Panel Cutout
48 mm (1 .89 0 in) B arbe r- C olm a n
48 mm (1 .89 0 in)
122 m m (4 .8 0 3 in )
75 mm (2 .95 3 in )
60 mm (2 .3 6 2 in )
4 5 m m , - 0, + 0 .6 m m (1 .7 7 2 in , -0 , +0 .02 4 in) 4 5 m m , -0, +0 .6 m m (1 .77 2 in, -0 , + 0.0 2 4 in )
6
A) Power Line and grounding
WIRING GUIDELINES Terminal Board +
6
C
7
NO
O UT1 SSR
11
NO O U T2
1
12
C O U T2 /3
2
Any external components (like zener diodes, etc.) connected between the sensor and input terminals can cause measurement errors (excessive or unbalanced line resistance or possible leakage currents).
_
+
13 R TD
8
10
15
CO N TA C T IN PU T
TC +
14
PWR LI NE 1 00 /24 0 V ac
C(µF) 0.047 0.1 0.33
R (Ω) 100 22 47
P (W) 1/2 2 2
9
4
Shield
5
+ 10
NOTE: The control output (OUT 1) is protected by a varistor against inductive loads up to 0.5 Amps. For other outputs or external contacts in series with the instrument outputs, connect an external snubber network (RC) across the terminals according to the following table: Load <40 mA <150 mA <0.5 A
10
3 -
L IN E AR
_
9
NO O U T3
Op. Voltage 260 Vac 260 Vac 260 Vac
7
-
9 Shield
Thermocouple Inputs NOTE: Do not run input wires with power cables. For TC wiring use proper compensating cable, preferably shielded (see Thermocouple Compensating Cable Color Codes). Shielded cable should be grounded at one end only.
RTD Inputs
Linear Inputs 10
_ 9
R TD
R TD
+ mA mV or V
G
10
+ _
9
8
mA, mV or V
9
10
8
9
10
NOTE: Do not run RTD wires with power cables. Shielded cables should be grounded at one end only. Use the correct size copper wire. The resistance of the 3 wires must be the same.
Shield Notes: 1) Don't run input wires together with power cables. 2) Pay attention to line resistance: a high line resistance may cause measurement errors. 3) When a shielded cable is used, it should be grounded at one side only to avoid ground loop currents. 4) The input impedance is equal to: <5 Ω for 20 mA input >1MΩ for 60 mV input >200 kΩ for 5 V input >400 kΩ for 10 V input
Logic Input Logic input 14
15 This logic input allows to start/stop the program execution by an external contct. Safety note: - Do not run logic input wiring with AC power cables. - Use an external dry contact capable of switching 0.5 mA, 5 Vdc. - The instrument needs 100 ms to recognize a contact status variation.
8
Thermocouple Compensating Cable Color Codes. Thermocouple Material Copper T Constantan Iron J/L Constantan Nickel Chromium K Nickel Aluminum Platinum/Platinum R 13% Rhodium Platinum/Platinum S 10% Rhodium Chromel E Constantan Platinum 30% Rh B Platinum 6 % Rh N Nicrosil / Nisil
British BS 1843 + White - Blue Blue + Yellow - Blue Black + Brown - Blue Red + White - Blue Green + White - Blue Green + Brown - Blue Brown -
American ANSI MC 96.1 + Blue - Red Blue + White - Red Black + Yellow - Red Yellow + Black - Red Green + Black - Red Green + Violet - Red Violet + Grey - Red Grey + Orange - Red Orange
9
German DIN 43710 + Red - Brown Brown + Red - Blue Blue + Red - Green Green + Red - White White + Red - White White + Red - Black Black + Red - Grey Grey -
French NFE 18-001 + Yellow - Blue Blue + Yellow - Black Black + Yellow - Purple Yellow + White - Green Green + White - Green Green + Yellow - Violet Violet -
Relay Outputs OUT 1 (heating)
Inductive Loads C 6
C NO
R
7 OUT 2 (cooling /AL1)
1
P O W ER LIN E
NO - OUT 2
LO AD C - OUT 2/3
2 OUT 3 (AL 2)
High voltage transients may occur when switching inductive loads. It is recommended to install an additional RC network across the external contacts as shown.
NO - OUT 3 3
Relay output: Protected by varistor. OUT 1: Contact rating of 3 Amps/250 Vac resistive load. OUT 2 and 3: Contact rating of 2 Amps/250 Vac resistive load. Number of operations: 1 x 105 at the specified rating. Notes: 1) To avoid electric shock, connect power line at the end of wiring procedure. 2) For power connections, use no. 16 AWG or larger wires rated for at least 75°C 3) Use copper conductors only. 4) Don't run input wires together with power cables. 5) For output 1, the relay output or SSR drive output are mutually exclusive.
10
The value of capacitor (C) and resistor (R) are shown in the following table. LOAD CURRENT
R POWER C (µF) (Ω) (Watts)
Less than 40 mA 0.047 100 Less than 150 mA 0.1 22 Less than 0.5 Amp 0.33 47
1/2 2 2
RESISTOR AND CAPACITOR VOLTAGE 260 260 260
The cable used for relay output wiring must be as far away as possible from input or communication cables.
Voltage Outputs for SSR Drive 6 OUT 1
Power Line and Grounding
+ _
4
+ _
7
5
N POWER SUPPLY 100 to 240 Vac or 24 Vac/Vdc R (S,T)
SOLID STATE RELAY This is a time proportioning output. Logic voltage for SSR drive. Logic level 0: Less than 0.5 Vdc Logic level 1: 24 V +20% @ 1 mA. 14 V +20% @ 17 mA Maximum current = 17 mA. NOTE:
This output is not isolated. A double or reinforced isolation between the instrument output and the power supply must be made by an external solid state relay. For OUT 1, the relay output or SSR drive output are mutually exclusive.
11
N R (S,T) Note: 1) When the NEUTRAL line is present, connect it to terminal 4. 2) Before connecting the power line, check that the voltage is correct (see model number). 3) To avoid shock and possible instrument damage, connect power last. 4) For supply connections use no. 16 AWG or larger wires rated for at least 75°C. 5) Use copper conductors only. 6) Don't run input wires together with power cables. 7) For 24 Vdc the polarity is a do not care condition. 8) The power supply input is NOT fuse protected. Please provide it externally: Power Supply Type Current Voltage 24 Vac/Vdc T 500 mA 250 V 100/240 Vac T 125 mA 250 V When fuse is damaged it is advisable to verity the power supply circuit, so it is necessary to send back the instrument to your supplier. 9) The safety requirements for Permanently Connected Equipment say: • a switch or circuit breaker shall be included in the building installation • it shall be in close proximity to the equipment and within easy reach of the operator • it shall be marked as the disconnecting device for the equipment. Note: a single switch or circuit breaker can drive more than one instrument.
CONFIGURATION
Open Input Circuit
Preliminary Hardware Settings
This instrument is able to identify an open circuit for TC and RTD inputs. The open input circuit condition for an RTD input is shown by an "overrange" indication. For TC input, either an overrange indication (standard) or underrange indication can be selected from the following table: Overrange (default) CH101 = close SH101 = open Underrange CH101 = open SH101 = close
1) Remove the instrument from its case. 2) Set J106 according to the following table: 1-2 3-4 5-6 7-8 9-10 TC-RTD open close open open open 60 mV open close open open open 5V close open close open open 10 V open open close open open 20 mA open open open close close Note: The jumper not used can be placed on pins 7-9.
Both pads are located on the solder side of the CPU card.
CH101 3) Set the OUT 1 contacts by setting J102 as follows: NO (as shipped): 1-2; NC: 2-3.
2 4 6 8 10
V101
J102
J106 1 3 5 7
9
Figure 1. Caution: Solder carefully to avoid damage to PCB or other components.
12
SH101
Configuration Key Functions FUNC= The new setting of the selected parameter is stored and the next parameter is displayed (in increasing order). RUN = Scrolls back through the parameters without storing the new setting. s = Increases the setting of the selected parameter. t = Decreases the setting of the selected parameter. Configuration Procedure 1) Remove the instrument from its case. 2) Open switch V101, located 1 inch behind the upper right corner of the display (see Figure 1). 3) Re-insert the instrument in its case. 4) Switch on power to the instrument. The display will show COnF. NOTE: If "CAL" is displayed, press the s key and return to the configuration procedure. 5) Press the FUNC key. P1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
- Input type = TC type = TC type = TC type = TC type = TC type = TC type = TC type = TC type = TC type = TC type = RTD type = RTD type = mV = mV = mA = mA
and standard range L range 0 L range 0 J range 0 J range 0 K range 0 K range 0 T range 0 N range 0 R range 0 S range 0 Pt 100 range -199.9 Pt 100 range -200 Linear range 0 Linear range 12 Linear range 0 Linear range 4
to to to to to to to to to to to to to to to to
+400.0 °C +900 °C +400.0 °C +1000 °C +400.0 °C +1200 °C +400.0 °C +1400 °C +1760 °C +1760 °C +400.0 °C +800 °C 60 mV 60 mV 20 mA 20 mA 13
16 17 18 19 20 21 22 23 24 25 26 27 28
=V =V =V =V = TC type = TC type = TC type = TC type = TC type = TC type = TC type = RTD type = RTD type
NOTE:
Linear Linear Linear Linear L J K T N R S Pt 100 Pt 100
range 0 to range 1 to range 0 to range 2 to range 0 to range 0 to range 0 to range 0 to range 0 to range 0 to range 0 to range -199.9 to range -330 to
5V 5V 10 V 10 V +1650 °F +1830 °F +2190 °F +750 °F +2550 °F +3200 °F +3200 °F +400.0 °F +1470 °F
Selecting P1 = 0, 2, 4, 6, 10 or 27 sets the digital filter (P32) to FLtr. For all the remaining ranges it will be set to nOFL.
P2 = Decimal point position This parameter is available only when a linear input is selected (P1 = 12, 13, 14, 15, 16, 17, 18 or 19). ----. = No decimal. ---.- = One decimal place. --.-- = Two decimal places. -.--- = Three decimal places. P3 = Initial scale value (low) Can be set with keys from -1999 to 4000. Can be set with keys within the input range for TC and RTD. When this parameter is modified, rL will also change. P4 = Full scale value (high) Can be set with keys from -1999 to 4000. Can be set with keys within the input range for TC and RTD. When this parameter is modified, rH will also change. The initial and full scale values determine the input span used by the PID algorithm, autotuning (Smart AT), and the alarm functions.
P9 = Program Start/Stop 0 = Pushbutton starts/stops program. 1 = External contact starts/stops program.
NOTE: Minimum input span (S = P4 - P3) is as follows: For linear inputs, S > 100 units. For TC input with °C readout, S > 300 °C. For TC input with °F readout, S > 550 °F. For RTD input with °C readout, S > 100 °C. For RTD input with °F readout, S > 200 °F.
P10 = OUT 3 function and operation after last programmed cycle. 0 = Output not used. Automatically goes to standby. 1 = Used as Alarm 2 output and Alarm 2 is programmed as a process alarm. Automatically goes to standby. 2 = Used as Alarm 2 output and Alarm 2 is programmed as a band alarm. Automatically goes to standby. 3 = Used as Alarm 2 output and Alarm 2 is programmed as a deviation alarm. Automatically goes to standby. 4 = Used as "End of cycle" signal. Automatically goes to standby. 5 = Used as "End of cycle" signal. Automatically acts as controller using the setpoint of region 5 (setpoint can be modified from the keys).
P5 = OUT 1 type rEL= Relay (cycle time, CY1, will be forced to 15 s). SSr = SSR (cycle time, CY1, will be forced to 4 s). P6 = OUT 1 action rEV = Reverse (Heating) dir = Direct (Cooling) P7 = OUT 2 function 0 = Output not used. 1 = Used as Alarm 1 output and Alarm 1 is programmed as a process alarm. 2 = Used as Alarm 1 output and Alarm 1 is programmed as a band alarm. 3 = Used as Alarm 1 output and Alarm 1 is programmed as a deviation alarm. 4 = Used as event output. NOTE:
NOTE:
If P7 = 4, OUT 2 assumes the logic state programmed for each region with the EV1, EV2, EV3, EV4 and EV5 parameters.
P8 = Alarm 1 operating mode Available only when P7 is equal to 1, 2 or 3. H.A. = High alarm (or outside of the band) with automatic reset. L.A. = Low alarm (or inside the band) with automatic reset. H.L. = High alarm (or outside of the band) with manual reset. L.L. = Low alarm (or inside the band) with manual reset. 14
If P10 = 4 or 5, and more than one program cycle is performed, one of the following situations will occur: 1) When the instrument completes an intermediate cycle at the end of region 5, OUT 3 will be ON for an amount of time equal to the value of P11. 2) When the last cycle is complete (or a single cycle has been programmed) at the end of region 5, OUT 3 will be ON for an amount of time equal to the value of P12. If P12 = "InF" then OUT 3 remains ON until a new START command is detected. P11 = Display time for "end of the intermediate cycle" indicator From 0 to 60 seconds when P10 = 4 or 5. P12 = Display time for "end of the last cycle" indicator From 10 to 60 seconds when P10 = 4 or 5. The display will show "InF" after 60 seconds and at the end of the last programmed cycle. OUT 3 will be ON until a new START command is detected.
P13 = Alarm 2 operating mode Available only when P10 = 1, 2 or 3. H.A. =High alarm (or outside of the band) with automatic reset. L.A. = Low alarm (or inside the band) with automatic reset. H.L. = High alarm (or outside of the band) with manual reset. L.L. = Low alarm (or inside the band) with manual reset. P14 = Tracking below none = Function not used. From 1 to 400 units for linear input ranges. From 1 to 40°C for TC and RTD inputs with °C readout. From 1 to 72°F for TC and RTD inputs with °F readout. When enabled, the instrument calculates the control error (SP - measured) and will operate as follows: - If the error is positive and its absolute value is greater than P14, the instrument stops ramping and operates as a constant setpoint controller. - If the error is negative or less than P14 ramping will restart. P15 = Tracking above none = Function not used. From 1 to 400 units for linear input ranges. From 1 to 40°C for TC and RTD inputs with °C readout. From 1 to 72°F for TC and RTD inputs with °F readout. When enabled, the instrument calculates the control error (SP - measured) and will operate as follows: - If the error is negative and its absolute value is greater than P15, the instrument stops ramping and operates as a constant setpoint controller. - If the error is positive or less than P15, ramping will restart. P16 = Guaranteed soak none = Function not used. From 1 to 100 units for linear input ranges. From 1 to 10°C for TC and RTD inputs with °C readout. 15
From 1 to 18°F for TC and RTD inputs with °F readout. Defines a symmetrical band (±P16) for soaking. When out of this range, the soak time will stop. When returned to this range, the soak time will restart. P17 = Safety lock 0 = Unlocked. All parameters can be modified. 1 = Locked. No parameters (except for alarm manual reset) can be modified (for autotuning (Smart AT) status see P25). From 2 to 9999 = Password to be used in run time (see parameter "nnn" ) to lock/unlock the device. For manual reset, the lock/unlock condition has no effect (for autotuning status see P25).
The configuration procedure is now complete. The instrument should show " -.-.-. " on both displays. Press the FUNC key; the instrument will return to the beginning of the configuration procedure. To continue with controller set-up go to the operating mode found in the next section. To access the advanced configuration parameters proceed as follows: 1) Press s or t keys to enter 263 on the display. 2) Press the FUNC key. Advanced Configuration Procedure P18 = Alarm 1 action Not available when P7 = 0 or 4. dir = Direct (relay energized in alarm condition). rEV = Reverse (relay deenergized in alarm condition). P19 = Alarm 1 standby Not available when P7 = 0 or 4. OFF = Standby disabled. ON = Standby enabled. NOTE: If the alarm is a band or deviation alarm, the alarm is masked after a setpoint change or at
start-up until the process variable reaches the alarm setpoint plus or minus hysteresis. If the alarm is a process alarm, the condition is masked at start-up until the process variable reaches the alarm setpoint plus or minus hysteresis. P20 = Alarm 2 action Not available when P10 = 0 or 4. dir = Direct (relay energized in alarm condition). rEV = Reverse (relay deenergized in alarm condition).
If ON/OFF control is selected, P23 is ignored.
P24 = Protected display parameters Not used when P17 = 0. OFF = Protected parameters cannot be displayed. ON = Protected parameters can be displayed. P25 = Autotune (Smart AT) function 0 = Autotuning disabled. 1 = Autotuning is NOT protected by password. 2 = Autotuning is protected by password.
P21 = Alarm 2 standby function Not available when P10 = 0 or 4. OFF = Standby disabled ON = Standby enabled NOTE: For details on the standby function, see P19.
P26 = Maximum value of the proportional band calculated by autotuning Can be set with keys from P27 to 100.0%.
P22 = OFFSET applied to the measured value Used to apply a constant OFFSET throughout readout range (not used for linear inputs). - For readout ranges with a decimal place, P22 can be set with keys from -19.9 to 19.9. - For readout ranges without a decimal place, P22 can be set with keys from -199 to 199. Re a dou t R e al C u rve
P22
NOTE:
A dju sted C u rve
P27 = Minimum value of the proportional band calculated by autotuning Can be set with keys from 1.0% to P26. P28 = Minimum value of the integral time calculated by autotuning Can be set with keys from 20 sec. (0.20) to 2 minutes (2.00). P29 = Device status at instrument start-up 0 = The instrument starts in the standby mode. All outputs will be off, and the lower display shows "off." WARNING: When a "hot start" occurs (i.e. after a power failure), program execution will be aborted and the instrument will restart in standby mode. 1 = The instrument starts in the same mode it was in prior to shutdown.
In p ut
NOTES: A) If the instrument was ramping (region 2 or 4), it aligns the setpoint to the measured value and then restarts the ramp (up or down) by the programmed gradient.
P23 = Control output maximum rate of rise Can be set with keys from 1% to 10% of the output per second. Above 10%, the display will show "InF," meaning that no ramp is used. 16
B) If the instrument was performing a soak (region 1, 3 or 5), it divides the soak time into quarters and restarts from the beginning of the quarter that was being executed prior to shutdown. P30 = Integral pre-load Can be set with keys from 0% to 100% of the output range. P31 = Timeout selection This parameter sets the duration of the timeout used by the instrument during the operating mode. tn. 10 = 10 seconds tn. 30 = 30 seconds
Default Configuration Parameters The configuration parameters can be loaded with predetermined default values. These are the settings loaded into the instrument prior to shipment from the factory. To load the default values proceed as follows: a) Internal switch V101 must be open. b) The upper display will show:
c) Press the t key; the lower display will show the firmware version.
P32 = Digital filter on the measured value noFL. = No filter FLtr = Filter enabled: A first order digital filter with a time constant equal to: 4 seconds for TC and RTD inputs 2 seconds for linear inputs P33 = Conditions for output safety value 0 = No safety value (default). 1 = Safety value applied when an overrange or underrange condition is detected. 2 = Safety value applied when an overrange condition is detected. 3 = Safety value applied when an underrange condition is detected. P34 = Output safety value This parameter is skipped if P33 = 0. This value can be set from 0% to 100%. (This completes the configuration procedure. The display should show “COnF.”)
17
d) Hold down thet key and press thes key; the display will show:
e) Press the s key to select table 1 (European) or table 2 (American) default parameters; the display will show:
f) Press the FUNC key; the display will show:
This indicates that the loading procedure has been initiated. After about 1 second the procedure is complete and the instrument reverts to the “COnF” display. The following is a list of the default configuration parameters loaded during the procedure:
18
PARA. P1 P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12 P13 P14 P15 P16 P17 P18 P19 P20 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30 P31 P32 P33 P34
TABLE 1 European 3 ----. 0 400 rEL rEV 4 H.A. 1 4 10 10 H.A 8 8 4 0 rEV OFF rEV OFF 0 10 ON 2 10.0 1.0 00.50 0 30 tn 10 nOFL 0 0
TABLE 2 USA 21 ----. 0 1000 rEL rEV 4 H.A. 1 4 10 10 H.A. 16 16 8 0 rEV OFF rEV OFF 0 10 ON 2 10.0 1.0 00.50 0 30 tn 30 nOFL 0 0
OPERATING MODE
OUT1 OUT2
1) 2) 3) 4)
OUT3
Remove the instrument from its case. Set switch V101 to the closed condition. Re-insert the instrument in its case. Switch on power to the instrument.
Display Function The upper display shows the measured value while the lower display shows: - OFF when the instrument is in standby mode (all outputs off, programmer not running) - The time remaining during the initial delay (region 1) - The setpoint during a ramp - The time remaining during a soak (The above conditions are the “normal display mode.”) It is possible to change the information on the lower display as follows: - Press the FUNC key for 3 seconds. The lower display will show " H. " followed by the OUT 1 power value (from 0% to 100%). - Press the FUNC key again. The display will return to the "normal display mode." If no keys are pressed within the timeout period (see P31), the display will automatically return to the normal display mode. In order to keep the desired information on the lower display, press s or t key to stop the timeout. To return to the normal display mode, press the FUNC key again. Indicators °C Lit when the process variable is shown in degrees Celsius. °F Lit when the process variable is shown in degrees Fahrenheit. AT Flashes during autotuning (Smart AT). Lit when autotuning is active. 19
Lit when Output 1 is ON. Lit when Output 2 (used as event output) is ON or Alarm 1 is ON. Lit when Alarm 2 is ON or when Output 3 is used as an "End of cycle" logic output.
Other functions are shown by decimal points: A) When the decimal point to the right of the least significant digit of the lower display is lit, the instrument is using SP2. B) When the decimal point to the right of the most significant digit of the lower display is flashing, the instrument is in the manual mode. C) When the decimal point to the right of the least significant digit of the upper display is lit: - The program is running or, - The instrument is performing the 2 initial regions ("wait" and "ramp to SP1") before operating as a controller. When the decimal point to the right of the least significant digit of the upper display is flashing: - The tracking or guaranteed soak functions are delaying program execution. - An out of range condition has been detected. Operating Key Functions FUNC = - During parameter modification the new setting of the selected parameter is stored and the next parameter is displayed (in increasing order). - During program execution or when operating as a controller (without program), pressing the FUNC key for more than 3 seconds will show " H. " on the lower display, followed by the OUT 1 power (from 0 to 100%). Press the FUNC key again, and the display will return to the "normal display mode."
RUN = - With P9 = 0 and the instrument in standby mode, press RUN for 1 second to start program execution. - With P9 = 0, press for 5 seconds to abort the program. - During parameter modification, RUN is used to scroll back the parameters without memorizing the new setting. s = - Increases the value of the selected parameter during parameter modification. - Allows direct access to the setpoint when the instrument is operating as a controller. - Increases the output when the instrument is in manual mode. t = - Decreases the value of the selected parameter during parameter modification. - Allows direct access to the setpoint when the instrument is operating as a controller. - Decreases the output when the instrument is in the manual mode. s + FUNC = Toggles between standby and manual mode. s + FUNC or t + FUNC = Increases or decreases the value of the selected parameter at a faster rate. s and t = When autotuning (Smart AT) is disabled, the up and down arrow keys are used to start the default parameter loading procedure. NOTE: A 10 or 30 second timeout (P 31) can be selected for parameter modification. If no keys are pressed during this time period, the instrument automatically goes to the “normal display mode” and the last parameter is NOT changed.
20
Operating Modes The 7SP is a controller/programmer. This instrument can be operated in 3 modes: - MODE A Standby The device operates as an indicator; the power out is OFF and the alarms are in the no alarm condition. The upper display shows the process variable while the lower display shows “OFF.” The Manual mode (MODE C) can be enabled by pressing the s + FUNC keys. -
MODE B Run This mode can be enabled by pressing the “RUN” key or by closing the external contact for more than 1 second (see P9). The RUN LED will be lit. The device operates as follows: B.1) As a Controller: With the SP1 soak time set to "infinite," the instrument performs the first 2 regions ("Wait" and "Ramp to SP1") and then operates as a standard controller. Note: When the instrument operates as a controller it is possible to modify the operating setpoint (SP1) using the direct access to the setpoint function or by selecting the SP1 parameter and entering a new setting. When the instrument reaches the SP1 setting, it turns OFF the RUN LED. B.2) As a Controller/Programmer. The program has 5 regions. Refer to "Programmer Worksheet": 1. WAIT REGION The power output is OFF and the alarms are in the no alarm condition. The time duration of this region is programmed using the “dELY” parameter. The upper display shows the process variable while the lower display flashes the time to reach the end of this region.
-
-
2. RAMP to SP1 The instrument aligns the setpoint to the actual measured value and starts ramping towards SP1. The slope of this ramp is programmed by the “Grd1” parameter. The tracking function may be active during the ramp (see P14 and P15). The upper display shows the process variable while the lower display shows the final setpoint (SP1). 3. SOAK at SP1 The guaranteed soak feature may be active (see P16). The upper display shows the process variable while the lower display shows the time to reach the end of this region. Use the "tin1" parameter. 4. RAMP to SP2 The instrument starts ramping from SP1 to SP2. The slope of this ramp is programmed by the “Grd2” parameter. During the ramp the tracking function may be active (see P14 and P15). The upper display shows the process variable while the lower display shows the final setpoint (SP2). The "SP2" LED will be lit. 5. SOAK at SP2 The guaranteed soak feature may be active (see P16). The upper display shows the process variable while the lower display shows the time to reach the end of this region. See parameter "tin2." The "SP2" LED will be lit. When this region is completed, two different situations may occur: If no "repeats" have been programmed and P10 does not = 5, the device returns to standby mode. The "rPt" parameter is used to program the number of repeats. If one or more repeat has been programmed, the next cycle starts from region 2 (Ramp to SP1) or from region 1 (Wait) according to the "dELY" (either ON/ OFF) parameter setting.
21
-
MODE C "Manual" Manual mode can be enabled only from the standby mode by pressing the s + FUNC keys. When the instrument is in manual mode the lower display shows "n." followed by the OUT 1 power (from 0 to 100%). The decimal point after the most significant digit of the lower display will be flashing. The power output can be modified using the s and t keys. By pressings + FUNC keys again, the device returns to Standby. Note: If a shutdown occurs while in the manual mode, the instrument will restart in the Manual mode with the same power settings.
22
Tem p eratu re
SP# S T EP
S tep N um be r
1
W ait T im e (h h:m m ) E nd S etpo int 1 R ate o f Ra m p to S P 1 S o ak T im e (hh :m m ) E nd S etpo in t 2 R ate of R am p to S P 2 S oa k T im e (h h :m m ) N u m be r o f P rog ra m R ep etitio n s W ait T im e o n Re petition
23
2
3
4
5
6
7
NOTE: 1) Autotuning enabling/disabling can be protected by password (see P25). 2) During the first region (WAIT) the autotuning LED will be OFF.
Indicators The following table identifies the LEDs and displays during each operating mode and region. Mode
AT LED
RUN LED
SP2 MAN LED† LED
Lower display
Standby
OFF
OFF
OFF
OFF
"OFF"
Manual
OFF
OFF
OFF
flash output %
RUN Region 1 Region 2 Region 3 Region 4 Region 5
OFF ON * ON * ON * ON *
ON ON** ON ON ON
OFF OFF OFF ON ON
OFF time (flash) OFF oper. SP OFF time 1 OFF oper. SP OFF time 2
(†)
(*) (**)
SETPOINT ACCESS (controller only) When the device is operating as a controller it is possible to directly access the setpoint (SP1): 1) Press the s or t key (and hold for 2 seconds); the setpoint will start to change. 2) Once the desired setting is reached, wait 2 seconds before pressing a key and the new setpoint will be used.
Flashes when the value is out of range or the tracking or guaranteed soak functions suspend program execution. Lit when autotuning (Smart AT) is enabled. When the instrument operates as a controller the RUN LED will be OFF.
Autotuning (Smart AT) Autotuning is used to automatically optimize the control action. To enable autotuning, press the FUNC key until the “Snrt” parameter is shown. Press the s or t key to set the display to “On” and then press the FUNC key. The AT LED will turn on. When autotuning is enabled, it is not possible to display or to modify the control parameters (Pb, TI and Td). To disable autotuning, press the FUNC key until the “Snrt” parameter appears. Press the s or t key to set the display to “OFF” and press the FUNC key again. The AT LED will turn off. Once autotuning is turned off, the instrument retains the calculated control parameters, but allows the parameters to be modified. 24
Operating Parameters Press and hold the FUNC key (for about 3 seconds). The lower display will show the parameter code and the upper display will show the setting or status (ON or OFF) of the selected parameter. Pressing the s or t key to select a setting. NOTES: 1) Manual reset of the alarms is active. 2) When P24 = ON and the instrument is in manual or standby mode, parameter modification is limited by the status of the Software key (see parameter "nnn") and autotuning (Smart AT). 3) When P24 = ON and the instrument is operating as a controller, it is possible to display but not to modify the following parameters: dELY (hh.mm), EV1, SP1, Grd1, EV2, tIn1, EV3 (parameters SP2, Grd2, EV4, tIn2, EV5, rPt and dELY (ON/OFF) will be skipped). Display and modification of the remaining parameters is limited by the status of the Software key (see parameter "nnn" ) and autotuning. 4) When P24 = ON and the instrument is in the RUN mode, it is possible to display but not to modify the following parameters: dELY (hh.mm), EV1, SP1, Grd1, EV2, tIn1, EV3, SP2, Grd2, EV4, tIn2, EV5, rPt and dELY (ON/OFF). Modification of the remaining
parameters is limited by the status of the Software key (see parameter "nnn") and autotuning. Pressing the FUNC key enters the new setting and advances to the next parameter.
EV3
Some of the following parameters may be skipped according to the instrument configuration.
Grd2
Param. Snrt
n.RSt nnn
dELY EV1
SP1 Grd1
EV2
tin 1
DESCRIPTION Autotune (Smart AT) status. ON or OFF indicates the status of autotuning (enabled or disabled). Set to ON to enable autotuning. Set to OFF to disable autotuning. Manual reset of the alarms. Set to ON to reset the alarms. Software key for parameter protection: ON = The instrument is LOCKED OFF = The instrument is UNLOCKED To switch from LOCK to UNLOCK, enter the P17 parameter setting. To switch from UNLOCK to LOCK, enter any number other than the P17 parameter setting. Wait time (region 1) in hours and minutes. From 00.00 to 99.59 (hh.mm). Region 1 contact status. ON = Contact closed. OFF = Contact open. First setpoint. From rL to rH (in engineering units). Gradient for ramp to SP1 (region 2). From 1 to 500 units per minute; above this value the display will show "InF" and the transfer will be a step change. Region 2 contact status. ON = Contact closed. OFF = Contact open. Soak time at SP1 (region 3). From 00.00 to 99.59 (hh.mm) or infinite (inF). 25
SP2
EV4
tin 2 EV5
rPt
dELY
AL1
HSA1 AL2 HSA2
Region 3 contact status. ON = Contact closed. OFF = Contact open. Second setpoint. From rL to rH (in engineering units). Gradient for ramp to SP2 (region 4). From 1 to 500 units per minute; above this value the display will show "InF" and the transfer will be a step change. Region 4 contact status. ON = Contact closed. OFF = Contact open. Soak time at SP2 (region 5). From 00.00 to 99.59 (hh.mm). Region 5 contact status. ON = Contact closed. OFF = Contact open. Number of program repetitions. From 0 (one execution only) to 100; or "InF" = Infinite executions. Note: When in the RUN mode, the instrument shows the remaining repetitions. Delay between cycles. When rPt is not 0, dELY can be set to start the next cycle from region 1 or 2. OFF = The next cycle will restart from region 2 (Ramp to SP1). ON = The next cycle will restart from region 1 (Wait). Alarm 1 setpoint (in engineering units). For process alarm (within P4 - P3 span). For band alarm (from 0 to 500). For deviation alarm (from -500 to +500). Alarm 1 hysteresis from 0.1 to 10% (in % of P4 - P3 span). Alarm 2 setpoint (in engineering units). (For range limits see AL1 parameter.) Alarm 2 hysteresis from 0.1 to 10% (in % of P4 - P3 span).
Pb
HYS
ti
td
CY1 rL rH OLH
Proportional band (in % of P4 - P3 span). From 0.0 (ON/OFF control) to 100.0% of P4 - P3 span. (Appears only when Pb = 0) Hysteresis of the ON/OFF control. From 0.1% to 10.0% of P4 - P3 span. Integral time - from 00.20 to 20.00, in minutes and seconds (mm.ss). Above this value the display blanks, and integral action is excluded. Note: when the device is working with SMART algorithm, minimum value of integral time will be limited by P28 parameter. Derivative time - from 00.00 to 10.00, in minutes and seconds (mm.ss). Note: when working with SMART algorithm, td value will be equal to a quarter of Ti value. Output 1 cycle time (in seconds). When P5 = rEL, CY1 can be set with keys from 1 to 200 seconds. When P5 = SSr, CY1 can be set with keys from 0.1 to 20.0 seconds. Setpoint low limit (in engineering units). Setpoint high limit (in engineering units). Output high limit (from 0 to 100 % of the output).
Default Operating Parameters The control parameters can be loaded with predetermined default values. These are the settings loaded into the instrument prior to shipment from the factory. To load the default values proceed as follows: a) b) c) d)
Internal switch V101 must be closed. Autotuning (Smart AT) must be disabled. The instrument must be in the Standby mode. Hold down the s key and press the t key; the display will show:
e) Press either the s or t key; the display will show:
g) Press the FUNC key; the display will show:
This indicates that the loading procedure has been initiated. After about 3 seconds the loading procedure is complete and the instrument reverts to the normal display mode. The following is a list of the default operating parameters loaded during the procedure:
26
Parameter Snrt n.RSt nnn dELY EV1 SP1 Grd1 EV2 tin 1 EV3 SP2 Grd2 EV4 tin 2 EV5 rPt dELY AL1
= = = = = = = = = = = = = = = = = =
HSA1 AL2
= =
HSA2 Pb ti td CY1
= = = = =
rL rH OLH
= = =
Default Value ON OFF OFF (UNLOCK) 00.00 OFF Low scale value "InF" OFF 00.00 OFF Low scale value "InF" OFF 00.00 OFF 0 OFF Low range value for process alarm. Zero for band or deviation alarms. 0.1% Low range value for process alarm. Zero for band or deviation alarms. 0.1% 4.0% 04.00 (mm.ss) 01.00 (mm.ss) 15 seconds when P5 = rEL 4 seconds when P5 = SSr Low scale value High scale value 100%
27
Error Messages Overrange, Underrange, and Sensor Break This device is capable of detecting process variable faults (OVERRANGE, UNDERRANGE or SENSOR BREAK). When the process variable exceeds the span limits established by configuration parameter P1, an OVERRANGE condition will appear as:
An UNDERRANGE condition will appear as:
Output action on Over/Underrange When P33 = 0, the following conditions will occur: - If an OVERRANGE condition is detected, OUT 1 turns OFF (if reverse acting) or ON (if direct acting). - If an UNDERRANGE condition is detected, OUT 1 turns ON (if reverse acting) or OFF (if direct acting). When P33 is not zero and an out of range condition is detected, the instrument operates in accordance with parameters P33 and P34. The sensor break can be signalled as: - for TC/mV input: OVERRANGE or UNDERRANGE selected by a solder jumper. - for RTD input: OVERRANGE - for mA/V input: UNDERRANGE Note: On the mA/V input, sensor break can be detected only when the range selected has a zero elevation (4-20 mA, 1-5 V, or 2-10 V). On the RTD input a special test is provided to signal an OVERRANGE when input resistance is less than 15 ohms (short circuit sensor detection). 28
Start-Up On powerup, the instrument performs a self-diagnostic test. When an error is detected, the lower display shows an “Err” indication while the upper display shows the code of the detected error. 100 EEPROM Write error. 150 CPU error. 200 Attempt to write to protected memory. 201 - 2xx Configuration parameter error. The two least significant digits show the number of the wrong parameter (ex. 209 Err indicates an Error in Parameter P9). 301 RTD input calibration error. 305 TC/mV input calibration error. 307 RJ input calibration error. 311 20 mA input calibration error. 313 5 V input calibration error. 315 10 V input calibration error. 400 Operating parameter error. 500 Auto-zero error. 502 RJ error. 510 Calibration procedure error. Dealing with Error Messages: 1) When a configuration parameter error is detected, repeat the configuration procedure of that specific parameter. 2) If an error 400 is detected, simultaneously press the s or t keys to load the default parameters and then repeat the control parameter setup. 3) For all other errors, contact your supplier.
SPECIFICATIONS General Case: Polycarbonate grey. Self-extinguishing degree: V-0 according to UL, VDE and CSA. Front Protection: Designed and tested for IP65 and NEMA 4X for indoor locations when panel gasket is installed. Tests were performed in accordance with IEC529, CEI70-1 and NEMA 250-1991STD. Installation: Panel mounting by means of bracket (included). Instrument removable from case by safety screw. Rear Terminal Board: With screw terminals, connection diagram and safety rear cover. Dimensions: 1.89" x 1.89" (48 x 48 mm) according to DIN 43700; depth 4.8" (122 mm) Weight: 1 lb. max. (450 g). Power Supply: (switching mode) from 100 to 240 Vac, 50/60 Hz, +10% to -15% of nominal value; or 24 Vac/Vdc, ±10% of the nominal value. Power Consumption: 8 VA. Insulation Resistance: >100 MΩ according to IEC 348. Isolation Voltage: 1500 V rms according to IEC 348. Common Mode Rejection Ratio: 120 dB @ 50/ 60 Hz. Normal Mode Rejection Ratio: 60 dB @ 50/60 Hz. Noise Rejection: 1) High frequency electromagnetic noises: according to IEC 801-4 level 3. 2) Electric discharge: 8 kV. 29
D/A Conversion: Dual slope integration. Sampling Time: For linear inputs, 250 ms. For TC or RTD inputs, 500 ms. Accuracy: ±0.2% f.s.v. @ 25°C and nominal power supply voltage. Operating Temperature: 32 to 122°F (0 to 50°C). Storage Temperature: -4 to 158°F(-20 to 70°C). Humidity: 20% to 85% rh non-condensing. Protections: 1) WATCH DOG for automatic reset. 2) DIP SWITCHES for configuration and calibration parameter protection. Measuring Inputs All inputs are factory calibrated and selectable by front keyboard. Thermocouples Type: J, K, L, N, R, S, and T keyboard programmable. Engineering Units: °F or °C Keyboard programmable Line Resistance Compensation Error: Max. ±0.1% of the input span with input impedance less than or equal to 100 ohms. Burnout: Detection of the open input circuit (wires or sensor) with underrange or overrange selectable indication. Cold Junction: Automatic compensation for ambient temperature between 0 and 122°F (0 and 50°C). Cold Junction Compensation Error: 0.1°C/°C. Input Impedance: > 100 kΩ. Calibration: According to IEC 584-1.
Standard Ranges TC Type Range °C Range °F L 0 to 400.0 L 0 to 900 0 to 1650 J 0 to 400.0 J 0 to 1000 0 to 1830 K 0 to 400.0 K 0 to 1200 0 to 2190 N 0 to 1400 0 to 2550 R 0 to 1760 0 to 3200 S 0 to 1760 0 to 3200 T 0 to 400.0 0 to 750 Note: For TC inputs it is possible to select a measuring range within the standard input range with a minimum span of 600°F or 300°C. In this way it is possible to increase the sensibility of the control parameters. RTD Input Type: Pt 100, three wire connection. Calibration: According to DIN 43760. Line Resistance: Max. 20Ω/wire with no measurable error. Engineering Units: °F and °C, keyboard programmable. Burnout: Detection of the sensor open circuit and of one or more wires open circuit. Detection of sensor short circuit. Standard Ranges: -199.9 to 400.0 °C -199.9 to 400.0°F -200 to 800°C -330 to 1470°F Note: For RTD input it s possible to select a measuring range within the standard input range with a minimum span of 200°F or 100°C. In this way it is possible to increase the sensibility of the control parameters. 30
mA and V Input mA Input (standard): 0 to 20 mA and 4 to 20 mA keyboard programmable. Input impedance: 3 Ω. 0 to 5 V and 1 to 5 V: Programmable. Input impedance; > 90 kΩ. 0 to 10 V and 2 to 10 V: Programmable. Input impedance; > 180 kΩ. 0 to 60 mV and 12 to 60 mV: Programmable. Input impedance; > 1 MΩ. Readout: Keyboard programmable from -1999 to 4000. Decimal Point: Programmable in any position. Standard Ranges: Input Impedance 0 to 20 mA 3W 4 to 20 mA 3Ω 0 to 60 mV >1 MΩ 12 to 60 mV >1 MΩ 0 to 5 V >90 kΩ 1 to 5 V >90 kΩ 0 to 10 V >180 kΩ 2 to 5 V >180 kΩ Logic Input Model 7SP is equipped with a logic input used to start the program execution. Setpoint Pattern -- Regions Description: 1) Standby Region: The instrument operates as an indicator. Power output is off and alarms are in no alarm status. Range: 0 to 99 h 59'. 2) Wait Region: In this region the power out is off and alarms are in no alarm status. The time duration is programmed by "wait time"
parameter. Upper display shows the process variable while the lower display shows, flashing, the time to reach the end of this region. Range: 0 to 99 h 59'. 3) Ramp to SPx Regions: At the beginning of this region the instrument aligns the operating setpoint to the actual measured value and then it will start ramping toward SPx (SP1 or SP2). Upper display shows the process variable while the lower display shows the actual setpoint. The gradient of this ramp is programmable. During ramp execution the tracking function may be activated. Range: 1 to 100 dgt/min. or step transfer. 4) Soak to SPx Regions: In this region the guaranteed soak feature may be activated. The upper display shows the process variable while the lower display shows the time to reach the end of this region. Ramp: 0 to 99 h 59'. Manual Mode: When the instrument is in the manual mode the lower displays shows "n." followed by OUT 1 power output value (from 0 to 100%). The power output can be modified by using the s and t pushbuttons. Note: if shutdown occurs when the instrument is in the manual mode, at instrument powerup it will restart in manual mode with the same power output assigned to the instrument before shutdown.
31
Control Action Algorithm: PID and SMART AT. Type: One control output. Proportional Band: Programmable from 1.0% to 100.0% of the input span. Integral Time: Programmable from 20 seconds to 20 minutes or excluded. Derivative Time: Programmable from 1 second to 10 minutes or excluded. Integral Pre-load: Programmable from 0 to 100% of the output range. Out 1 Cycle Time: From 1 to 200 seconds. Stand-by/Manual Mode: Selectable by front pushbutton. Setpoint Limiters: Setpoint low limit and setpoint high limit are programmable. Control Outputs Type: Time proportioning. Updating Time: 250 ms. Direct/Reverse Action: Keyboard programmable. Cycle Time: Programmable from 1 to 99 seconds. Output Level Indication: In percent on the lower display. Output Status Indication: One indicator (OUT1) lit when the output is in the ON condition. Output Level Limiter: 0 to 100%. Relay Output: SPDT contact with rated current 4A at 250 Vac on resistive load. Logic Voltage Output for SSR Driver : Logic Level 0: Vout < 0.5 Vdc Logic Level 1: 14V < Vout < 24 Vdc. Maximum current = 20 mA.
Alarms This instrument is equipped with three independent outputs. The first is used as control output; the other two can be programmed as: - Alarm 1 + Alarm 2 - Break Event + Alarm 2 - Alarm 1 + End of Cycle - Break Event + End of Cycle. Output Action: Direct or reverse function programmable. Alarm Functions: Each alarm can be configured as process alarm, band alarm, or deviation alarm. Alarm Reset: Automatic or manual reset programmable on each alarm. Alarm Masking: Each alarm can be configured as masked alarm or standard alarm. Alarm Indications: Two indicators lit when the respective alarm is on. Alarm Outputs: Two relay, SPST. Contact rated at 2 A, 250 Vac on resistive load. Process Alarm Operating Mode: Minimum or maximum programmable. Setpoint: Programmable in engineering units within the whole range. Hysteresis: Programmable from 0.1% to 10.0% of the input span.
32
Band Alarm Operating Mode: Inside or outside programmable. Setpoint: Programmable from 0 to 500 units. Hysteresis: Programmable from 0.1% to 10.0% of input span. Deviation Alarm Operating Mode: High or low programmable. Setpoint: Programmable from -500 to 500 units. Hysteresis: Programmable from 0.1% to 10.0% of the input span. Break Event When the OUT 2 is used as break event output, it will assume, during program execution the status (on or off) programmed for the region actually in execution. End of Cycle Indication When the OUT 3 is used as end of cycle indicator, at the end of every program repetition cycle it will be forced in "on" status for ten seconds.
CALIBRATION Calibration parameters are logically divided into groups of two parameters each – initial scale value and final scale value. A calibration check is provided after entering the values of each group. A calibration check can be initiated without making an entry: press the FUNC key to advance to the desired calibration check. The lower display will show the parameter code (t., rJ., etc.) and the upper display will show “on” or “off.” Press the s or t key to select on or off. To go to the next parameter without modifying the calibration, press the FUNC key when the displays shows “off.” To return the previous parameter without modifying the calibration, press the MAN key. To set the parameter calibration, pres the FUNC key when the display shows “on.” The display will blank, and only the decimal point of the LSD of the lower display will be lit during the calibration step. Before beginning calibration, be sure internal switch V101 is open (see Configuration section of this manual, Figure 1). General Guidelines a) The instrument should be mounted in its case in order to keep the internal temperature constant. b) Ambient temperature should be stable. Avoid drift due to air conditioning or other 33
mechanical devices. c) Relative humidity should not exceed 70%. d) Minimum warm up time should be at least 20 minutes. e) Operate as much as possible in a noise free environment. f) During calibration, connect one input at a time to the rear terminal block. g) Before input calibration, the specific preliminary hardware settings described in the Configuration section must be made. h) Use calibrators with the following: Accuracy Current Input: ±0.025% output ±0.0025% range ±0.01 microamp Voltage Input: ±0.005% output ±0.001% range ±5 microvolt TC Input: ±0.005% output ±0.001% range ±5 microvolt RTD Input: ±0.02% ±0.0025 Ω/decade Reference Junction Compensation: better than 0.1°C mA output: better than ±0.1% of the readout ±2 microamp
Procedure
Resolution Current Input: 0.5 microamp Voltage Input: 100 microvolt TC Input: 1 microvolt RTD Input: 10 milliohm Ref. Jct. Compensation: better than 0.1°C mA output 1 microamp
Switch on the instrument; the upper display will show “COnF”. Press the s key and the display will show “CAL”. Press the “FUNC” key to start the calibration process. Repeatedly press the FUNC key until the desired calibration (parameter) code appears.
Calibration Parameters
Use the s and t keys to select between ON and OFF. To go to the next parameter without modifying the calibration, press the FUNC key when the display shows “OFF” .
Following is a complete list of calibration symbols: Code Parameter tL TC/mV Input Minimum Range Value tH TC/mV Input Maximum Range Value t. TC/mV Input Check rJ Reference Junction Compensation rJ. Reference Junction Compensation Check PL RTD Input Minimum Range Value PH RTD Input Maximum Range Value P. RTD Input Check nAL Current Input Minimum Range Value (0 mA) nAH Current Input Maximum Range Value (20 mA) nA. Current Input Check 5UL 5 Volt Input Min. Range Value (0 V) 5UH 5 Volt Input Max Range Value (5 V) 5U. 5 Volt Input Check 10UL 10 Volt Input Minimum Value (0 V) 10UH 10 Volt Input Maximum Value (10 V) 10U. 10 Volt Input Check
tL TC/mV input minimum range value a) Perform the preliminary hardware settings described in the Configuration section; connect the calibrator and instrument as shown below.
10 9 b) The displays show “OFF” and “tL”. c) Set calibrator to 0.000 mV. d) Press the s key; the display changes to “ON”. e) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When calibration is complete, 34
the instrument will proceed to the next parameter. tH TC/mV input maximum range value a) Set the calibrator to 60.000 mV. b) Press the s key; the displays will show “ON” and “tH”. c) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter. t. TC/mV input check The display will show “t.” followed by a number showing the measured value in counts.
Check the linear calibration by setting: a) 0.000 mV; the readout must be equal to “t.0 0000” ±10 counts. b) 60.000 mV; the readout must be equal to “t.3 0000” ±10 counts. c) 30.000 mV; the readout must be equal to “t.1.5000” ±10 counts. d) Press the FUNC key; go to the next parameter.
rJ Reference junction compensation Note: Make sure tL and tH are correctly calibrated before attempting rJ calibration. a) Measure the temperature close to terminals 10 and 9 using an appropriate instrument, as shown below. 10
+ M ea su ring D ev ice
9
-
b) Wait a few minutes to allow temperature stabilization of the entire system (compensation cable, sensor, calibrator and instrument). c) The displays will show “rJ” and “OFF.” Use the s and t keys to make the readout value equal to the temperature measured by the measuring device in tenths of °C. d) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter. rJ. Reference junction compensation check The display will show “rJ.” and the temperature in tenths of °C. Check that the display readout is equal to the value read by the measuring device.
35
Press the FUNC key; the instrument will proceed to the next parameter. PL RTD input minimum range value a) Perform the preliminary hardware settings described in the Configuration section. Connect the calibrator and instrument as shown below.
P. RTD input check The display shows “P.” followed by a number showing the measured value in counts.
8
Check the calibration (not linear) by setting the resistance box to: a) 0.00 Ω; the readout should be “P. 0 0000” ±10 counts. b) 125.00 Ω; the readout should be “P.1 0190” ±10 counts. c) 250.00 Ω; readout should be “P. 2 0189” ±10 counts. d) 375.00 Ω; readout should be “P. 3 0000” ±10 counts. e) Press the FUNC key and proceed to next parameter.
9 10
b) Set 0.00 Ω on the resistor box. c) Press the s key; the displays show “ON” and “PL”. d) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter.
nAL Current input (mA) minimum range value a) Perform the preliminary hardware settings described in the Configuration section; connect the calibrator and instrument as shown:
PH RTD input maximum range value a) Set resistor box to 375.00 Ω. b) Press the s key; the displays will show “ON” and “PH”. c) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter. 36
nA. Current input (mA) check The display will show “nA.” followed by a number showing the measured value in counts.
10 9
b) Set 0.000 mA on the calibrator (even if the minimum range value is 4 mA). The upper display shows “OFF.” c) Press the s key, the display will switch to “ON”. d) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter. nAH Current input (mA) maximum range value a) Set 20 mA on the calibrator. b) Press the s key, the displays will show “nAH” and “ON”. c) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter.
37
Check the linear calibration by setting the calibrator to: a) 0.000 mA; the readout should be “nA. 0 0000” ±10 counts. b) 20.000 mA; readout should be “nA. 3 0000” ±10 counts. c) 10.000 mA; readout should be “nA. 1 5000” ± 10 counts. d) Press the FUNC key. 5UL 5 volt input-minimum range value a) Perform the preliminary hardware settings described in the Configuration section. Connect the calibrator and instrument as shown:
10 9
b) Set 0.000 V on the calibrator (even if the minimum range value is 1 V). The upper display will show “OFF.” c) Press the s key, the display will show “5UL” and “ON.” d) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter.
Check the calibration by setting the calibrator to: a) 0.000 V; the readout should be “5U. 0 0000” ±10 counts. b) 5.000 V; readout should be “5U. 3 0000” ±10 counts. c) 2.500 V; readout should be “5U. 1 5000” ± 10 counts. d) Press the FUNC key to proceed to next parameter. 10UL 10 volt input - minimum range value a) Perform preliminary hardware settings as described in the Configuration section. Connect the instrument to the calibrator as shown:
5UH 5 volt input-maximum range value a) Set 5.000 V on the calibrator. b) Press the s key, the display will show “5UH” and “ON”. c) After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter
10 9
5U. 5 volt input check The display will show “5U.” followed by a number showing the measured value in counts.
b) Set 0.000 V on the calibrator (even if the minimum range value is 2 V). The upper display will show “OFF”. c) Press the s key to enable calibration. The upper display will switch to “ON”. d) Wait a few seconds until the measurement has stabilized, then push the FUNC key. When calibration is complete, the instrument will go to the next parameter. 10UH 10 volt input-maximum range value a) Set 10.000 V on the calibrator. b) Press the s key, the display will show “10UH” and “ON”.
38
c)
After a few seconds, start calibration by pressing the FUNC key. The decimal point of the least significant digit will light to indicate the instrument is performing the calibration. When this calibration is complete, the instrument will proceed to the next parameter
10U. 10 volt input check The display will show “10U.” followed by a number showing the measured value in counts.
Check the calibration (linear) by setting the calibrator to: a) 0.000 V; the readout should be “10U.0 0000” ±10 counts. b) 10.000 V; readout should be “10U.3 0000” ±10 counts. c) 5.000 V; readout should be “10U.1 5000” ±10 counts. d) Press the FUNC key.
This completes the calibration procedure. To enter the configuration procedure press the s key, the display will show “CnF”. If configuration and calibration are complete, switch the instrument off and set the DIP switches according to the Configuration section. 39
MAINTENANCE 1) Remove power from power supply terminals and from relay output terminals. 2) Remove instrument from its case. 3) With a vacuum cleaner or compressed air (max. 3 kg/cm 2, or 40 psig), remove all deposit of dust and dirt on louvers and internal circuits. Be careful not to damage internal components. 4) Clean external plastic or rubber parts with cloth moistened with Ethyl Alcohol (pure or denatured) C 2H5OH, or isopropyl alcohol (pure or denatured) [(CH 3)2 CHOH], or water (H2 O). 5) Verify that there are no loose terminals. 6) Before re-inserting the instrument in its case, be sure it is perfectly dry. 7) Re-insert the instrument and turn it on.
Barber-Colman Company Industrial Instruments Division 1354 Clifford Avenue P.O. Box 2940 Loves Park, IL U.S.A. 61132-2940 Telephone +1 800 232 4343 Facsimile +1 815 637 5341 http://www.barber-colman.com A Siebe Group Company
Copyright © 1997 Barber-Colman Company. 40