IPSIP MICRO DC Modular Data Center Solution
IPSIP TECHNOLOGIES CO., LTD.
Content Product Series Product Introduction Key Sub-System Success Stories
Product Series
Group Data Center Concept: big center, small branch With the development and maturity of the IT automation age, rapid development of mobile Internet & cloud computing industry has posed a challenge to the traditional data center construction mode. For large and medium-sized group enterprises, the traditional IDC systems of their branches face challenges such as: without unified planning and standard architecture, hard to purchase, deploy and maintenance because of various vendors, can not be unified managed in the headquarter, etc. The "big center, small branch" group data center concept has been deeply accepted and spread. Therefore, Huawei release M Series-S series small modular data center.
M Series-S Small data center network location Remote DR center
Global MGMT SLA/KPI
Production center
IDC large center
Local DR center
(Core business & process)
Group Management
Regional service centers
Region MGMT Unified O&M Region Management
“Lights-out” MNGT Unified Spare parts
1
(Optional, reduce delay)
Region Management
IDC micro centers in branches Sales branch
Research branch
Sales branch
Research branch
Sales branch
Research branch
(Office, Light app)
Product Series
M Series-S Small Modular Data Center Products Series
Small modular data center products line
Product type
Basic version
AC version
Low noise version
Dimension W*H*D (mm)
600×2000×1200
600×2000×1200
600×1200×900
Cooling type
Free cooling Fan as an option
Air conditioning
Free cooling Fan as an option
M Series-S small modular data center features
Simple
•• Pre-installed in factory, transport with device, job site plug and play •• One cabinet integrates with power supply/battery/cooling/monitoring/ cabling, easy to install & saves CAPEX
Intelligent
•• Perfect monitoring system ensures whole solution running smoothly& stably •• Unified Centralized & accessInterface management
Standard
•• Standardized ICT Planning and construction for branches •• Product standardization, easy configuration, fast deployment, & reduces initial investment
2
Product Series
IDS2000-S Basic Version
M Series-S Basic Version – Product Introduction M Series-S Basic Version is meant for deployment in normal offi ffice buildings, which have cooling facility to ensure ambient ffi temp in the range of 5 ~ 30ºC.
Cabinet Standard 19 inch cabinet, compatible with thirdparty servers, 42U available user space, 1500kg static load-bearing, aesthetic appearance & structurally stable
Cooling DC variable speed fan is connected with the monitoring system, fan redundancy improves system reliability
Power distribution box
ECC500
C-class lightning protection module, supports manual maintenance bypass. Multiple protection ways to improve the distribution security.
Monitors internal environment of Cabinet, supports remote management & maintenance and SNMP north interface to global management
UPS
Battery
High efficiency & energy saving UPS, customized power supplies offered for different power applications
Variable backup time as option, continuously offers power supply after mains failure.
M Series-S Basic Version main features
Flexible configuration
•• Modular design to achieve on line flexible expansion •• Variable configuration solutions meets different application scenarios, improves customer value
3
Safety and Reliability
Low Cost & Energy saving
•• Improves facility safety by complete monitoring of all inside conditions of cabinet like temperature, humidity etc.
•• Operations cost is saved as the fan speed is automatically adjusted according to the ambient temp
•• Power distribution system supports lighting protection & manual maintenance bypass to improve system reliability
•• Heat Dissipation by Fan; Dynamic Cooling load shared by 04 Fans, mutual backup completely support smooth business operations
Product Series
IDS2000-S Basic Version
M Series-S Basic Confi figuration
Products
IT cabinet with UPS
IT cabinet without UPS
IT cabinet with UPS +Network cabling cabinet
IT cabinet without UPS +Network cabling cabinet
IT cabinet with UPS +battery cabinet
IT cabinet with UPS + Network cabling cabinet + battery cabinet
Main cabinet user space
25U
37U
25U
37U
31U
31U
Network cabling cabinet user space
×
×
42U
42U
×
42U
Battery cabinet
×
×
×
×
√
√
UPS
√
×
√
×
√
√
30min
×
30min
×
30min~4h optional
30min~4h optional
Configuration
Back up time
Notes: •• “×” stands for no configuration, “√”stands for standard configuration •• All above six configurations are designed based on condition of the maximum heat dissipation (3kW) •• Main cabinet standard configuration: One set of PDU, monitoring unit, smoke sensor, temp and humidity water leakage detector & door magnetic switch •• Network cabling cabinet standard configuration: One set of PDU, smoke sensor & door magnetic switch •• Battery standard configuration: One set of smoke sensor & magnetic switch
4
Product Series
M Series-S Basic Version
M Series-S Basic Confi figuration M Series-S Basic Confi figuration Items
Description
Overall Specification
Cabinet system
UPS Power distribution system
rPDU
Battery
Monitoring system
Cooling
Fan
Dimension/weight
IDS2000-S basic type
IT rated capacity
4.5kW/rack
Power supply
220V, 230, 240/50(60)Hz; 208V(Double firing line)/50(60)Hz
Ambient
5 ~ 30ºC
Humidity
10~90%
Altitude
0~3000m
Certificate
CE / RoHS
Dimensions
W*H*D(mm): 600×2000×1100
IT user space
25U
Capacity
1KVA, 3KVA, 6KVA, 10KVA, 15KVA, 20KVA
Configuration
Without UPS / Single UPS/ Double UPS(1+1 redundancy)
Certificate
CE
Installation type
Horizontal installation, vertical installation
Mode
32A single phase(20*C13+4*C19); 32A single phase(9*C13+4*C19); 16A single phase(9*C13);
Capacity
7Ah, 9Ah, 40Ah, 65Ah, 100Ah
Backup time
10 mins, 15 mins, 30 mins, 60 mins, 120 mins, 240 mins
Monitoring unit
ECC500
Monitoring components
Smoke sensor(Available for cabinet inside & outside)/Temp & humidity sensor/ water leakage sensor /video/ door switch
Function
Web remote management / supports connection with NetEco / Access customer network management, SMS notification, cabinet equipment & micro-environmental monitoring
Installation location
4 No fans located on the top of cabinet
Type
DC variable speed fan, automatically adjusted fan speed
Control type
PMW control
Packaging dimensions
W*D*H(mm)734×1268×2200
Gross weight
250kg
Net weight
220kg
Notes: •• IT rated capacity is taken as either max. power supply capacity of UPS (6KVA) or max. heating dissipation, whichever is less. •• 32A single phase rPDU horizontal installation/ 16A single phase rPDU vertical installation •• The net & gross weight of single cabinet is not more than 220kg and 250kg respectively (excluding IT equipment and batteries) •• 25U IT user space of standard configuration 5
Product Series
M Series-S AC Version
M Series-S AC Version – Product Introduction M Series-S AC Version deployment is meant for hot areas of normal offi ffice building where ambient temp should be in the ffi range of 5 ~ 45ºC, offering proximal exclusive cooling for critical equipment.
ECC500
Battery
Monitors internal environment of Cabinet, supports remote management & maintenance and SNMP north interface to global management
Various battery modes offer different backup time to continuously supply power after mains failure
UPS Air conditioning
High efficiency & energy saving UPS, PFC value is up to 90%, Visualization friendly operation interface, customized power supplies offered for different power applications
Placed Close to IT equipment for achieving proximal exclusive cooling
IDS2000-S AC Version Features
Effective Heat Dissipation •• Integrated with rack-mounted air conditioning, Proximal cooling to make high density IT equipment operate smoothly •• Supports cooling redundancy( N+1), if one ac fails others can totally support cooling source
High efficiency & energy saving •• Integrated with high efficiency UPS (UL ENERGY STAR certified for 10kVA) •• Saves Energy by Automatically switching to fan heating dissipation under low ambient temp
Intelligent & safety
•• Smoke sensor / water sensor / temp & humidity sensor etc. devices monitor cabinet’s micro environment to ensure safe operations of data center business •• Support remote monitoring and maintenance, Unified Centralized & access Interface management
6
Product Series
M Series-S AC Version
Items
Overall specifications
Cabinet
UPS Power distribution system
rPDU
Battery
Monitoring system
Cooling
Air conditioning
Dimension/weight
Description
IDS2000-S AC version
IT rated power capacity
5kW/rack
Power supply
220V, 230, 240/50Hz; 208V (Double firing line)/50Hz
Ambient
5 ~ 40ºC
Humidity
20~80%
Altitude
< 1000m, reduce the rated value if more than 1000m
Certificate
CE, RoHS
Dimensions
W*H*D(mm): 600×2000×1200
IT user space
25U
Mode
6KVA, 10KVA, 15KVA, 20KVA
Configuration
Single UPS
Certificate
CE
Installation
Vertical installation / horizontal installation
Mode
32A single phase(20*C13+4*C19); 32A single phase(9*C13+4*C19); 16A single phase (9*C13);
Capacity
7Ah, 9Ah
Backup time
10 min, 15 min, 30 min
Monitoring unit
ECC500
Monitoring equipment
Smoke sensor (Available for cabinet inside & outside) / temp & humidity sensor/ water sensor / video / door switch sensor
Function
Web remote management / supports connection with NetEco / Access customer network management, SMS notification, cabinet equipment & micro-environmental monitoring
Type
Air cooled rack mounted air conditioning
Rated cooling capacity
4kW
Rated power consumption
2kW
Standard air flow
Evaporator side high fan speed ≥ 1000 (m3/h)
Packaging dimensions
W*D*H (mm)734×1268×2200
Net weight
300kg
Gross weight
264kg
Notes: •• IT rated capacity is taken as either max. power supply capacity of UPS (6KVA) or max. heating dissipation, whichever is less. •• 32A single phase rPDU horizontal installation/ 16A single phase rPDU vertical installation •• The net & gross weight of single cabinet is not more than 220kg and 250kg respectively (excluding IT equipment and batteries) •• 25U IT user space of standard configuration
7
Product Series
MSeries-SLowNoiseVersion
M Series-S Low Noise Version – Product Introduction M Series Low Noise Version deployment is meant for normal offi ffice building where ambient temp should be in the range of ffi 5 ~ 30ºC, can be deployed close to person due to small size / low noise.
11U IT user space Cooling DC variable speed fan is connected with the monitoring system, fan redundancy improves system reliability
ECC500 Monitors internal environment of Cabinet, supports remote management & maintenance and SNMP north interface to global management
Power distribution box C-class lightning protection module, supports manual maintenance bypass. Multiple protection ways to improve the distribution security.
Battery
UPS
Variable backup time as option, continuously offers power supply after mains failure.
High efficiency & energy saving UPS, customized power supplies offered for different power applications
M Series S Low Noise Version Features Plug & Play, All In One Rack Solution •• All in one rack solution; Integrated IT equipment/power distribution/ battery/heating dissipation/ monitoring/cabling etc. •• Plug & Play; All devices are factory pre-installed, support transportation with devices, free-tool installation.
Reliable & Saves Energy
•• Pre-test in factory to ensure system runs smoothly to enhance reliability •• Heat dissipation by Fan, Dynamic Cooling load shared by 02 Fans, mutual backup completely support business smooth operation.
Environmentfriendly & Saves Space
•• Operational noise as low as 50d (B) A, can be deployed close to a person •• Small size, easy to install, saves room space
8
Product Series
MSeries-SLowNoiseVersion
Items
Description
Overall parameter
Cabinet
UPS Power distribution system
rPDU
Battery
Monitoring system
Heating dissipation
Fan
Dimension/Weight
IDS2000-S Low Noise Version
IT rated capacity
2kW/rack
Power supply
220V, 230, 240/50Hz; 208V(Double firing line)/50Hz
Noise level
50dB(A)
Ambient
5 ~ 30ºC
Humidity
10~90%
Altitude
0~3000m
Certificate
CE, RoHS
Dimensions
W*H*D(mm): 600×900×1200
IT User space
11U
Modes
3KVA
Configuration
Single UPS
Certificate
CE
Installation type
Vertical installation / Horizontal installation
Specifications
16A single phase(9*C13)
Capacity
7Ah
Backup time
5min, 10min, 15min, 25min, 35min
Monitoring unit
ECC500
Monitoring equipment
Smoke sensor ( Available for cabinet outside & inside)/ temp & humidity sensor / water leakage sensor / video / door switch sensor
Function
Web remote management / supports connection with NetEco / Access customer network management, SMS notification, cabinet equipment and micro-environmental monitoring
Installation location
2 No fans are located on the top of cabinet
Type
DC variable speed fan, auto adjust cooling
Control type
PWM control
Package dimension
W*D*H(mm)734×1118×1400
Gross weight
170kg
Net weight
140kg
Notes: •• IT rated capacity is taken as either max. power supply capacity of UPS (3KVA) or max. heating dissipation, whichever is less. •• 16A single phase rPDU vertical installation •• The net & gross weight of single cabinet is not more than 170kg and 140kg respectively (excluding IT equipment and batteries) •• 11U IT user space of standard configuration
9
Key Sub-system
Cabinet
Key Sub-system – Cabinet NetHos cabinet with high reliability/high security/high compatibility can be easily installed, also meets different customized requirements.
High reliability
High security
•• High strength & corrosion resistance to ensure the enclosure mechanical strength and corrosion resistance •• High heat dissipation capacity: overhead variable fan speed, dynamically adjusting the cooling rate through cabinet holes to maintain adequate ventilation air ratio
•• Special antistatic wrist design •• Comprehensive ground protection
High compatibility
•• Supports Huawei IT equipment installation
Environment friendly
•• Complies with RoHS requirements
•• complies with 3rd 19 inchIT equipment installation standards
•• Complies with IEC60297-2 requirements
10
Key Sub-system
Power Distribution System
Key Sub-system – Power Distribution System Huawei power distribution system of small modular data center with flexible configuration / high performance design / high reliable etc. can be easily deployed in different customized scenarios.
Various UPS capacity available UPS type
Standard 19-inch rack
UPS capacity
1KVA
3KVA
6KVA
UPS efficiency
>88%
>91%
>93.5%
PFC
0.7
0.7
0.9
0.9
0.9
0.9
Output power co-efficiency
0.95
0.99
0.99
0.99
0.99
0.99
Flexible configuration
•• Various backup time are available to meet customized requirements •• Flexible UPS configuration to meet different application scenarios
11
High performance design
•• Complies with EN 62040- & EN 62040-2 standards, CB and CE certified •• High input co-efficiency: PFC control technology to improve electricity utilization
10KVA
15KVA
20KVA
>94.5%
High reliability
•• Manual bypass to support on line maintenance •• C class level lighting protection to improve system reliability
Key Sub-system
Monitoring system
Key Sub-system – Monitoring system Small DC monitor’s the cabinet’s microenvironment such as power distribution, battery, cooling, etc. It supports remote access via the Web interface, SMS notification via the GPRS module and near-end & far-end maintenance via the alarm function.
Web access (local or remote)
LAN Camera
-48 V DC power adapter
Collector
SPD (option)
Video alarm
Door status sensor
Smoke sensor (In cabinet)
Smokesensor (In room) (option)
Water sensor (option)
Air inlet temperature and humidity sensor
UPS
Aircondition (option)
Notes: •• Fan is available if application condition with ventilation and cooling device
12
Key Sub-system
Monitoring system
Monitoring system – Features
SMS notification for Maintenance
••Fault alarm SMS notification to achieve unattached for reducing maintenance cost
Micro environment management
••Complete cabinet environment management supported by water sensor/smoke sensor/door switch/temp & humidity sensor, improves reliability. ••Supports Free Cooling and local & remote management of UPS
User Friendly Operator Interface Supports
••Local & remote web interface operations
••Global Unified access management
••15 users rights and hierarchical management
••North SNMP/BIN access to connect with NetEco
••Multi-user concurrent access
13
Standard Interfaces of Monitoring System supports
Key Sub-system
Cooling system
Key Subsystem – Cooling system Small modular data center cooling system with rack mounted air conditioning/ free cooling option provides high reliability and energy saving to the customer.
Cooling 1–Rack Mounted AC Energy saving •• AC is integrated into the IT cabinet (10U user space ) •• Intelligent control automatically switches to free cooling when ambient temp is less than 28ºC, thereby saving energy
High efficiency cooling •• AC placed close to IT equipment so that the equipment achieves proximal exclusive refrigeration, leading to high efficiency •• Special design of IT cabinet structure to prevent air leakage
High reliable and safety •• Expert-level fault diagnosis of alarm to provide reliable protection for equipment operation •• AC Cabinet Fan offers cooling backup when AC fails/malfunctions
Cooling 2- Free Cooling
Green and energy saving •• Fan speed adjusts automatically to ambient cabinet temp
Safety and reliable •• 4 fans mutual redundancy, 1 failed the others can totally support business smooth operation
14