70052-0217-01 08/2006
PRODUCT OPTION
IRIG-B GPS Time Synchronization The IRIG‐B option is available with all PowerLogic® ION8600 meters. These meters accept unmodulated IRIG‐B time code via twisted pair, compatible with the IRIG‐B00x format. The standard is outlined in the IRIG‐STANDARD 200‐98 “IRIG Serial Time Code Formats” prepared by the Timing Committee, Telecommunications and Timing Group, Range Commanders Council. IRIG‐B is the industry standard for GPS time synchronization. Power Industry‐ specific IRIG‐B applications include: 1.
Power Quality monitoring and sequence of events recording.
2.
Highly accurate time stamping for revenue billing (1ms).
3.
System stability monitoring.
NOTE This option requires a receiver capable of unmodulated IRIG-B time code output (not included).
All IRIG‐B equipped meters are configured in the factory to synchronize via GPS using unmodulated IRIG‐B time code data. You cannot configure IRIG‐B from the meter’s front panel. See “Configuring IRIG‐ B” on page 2 for configuration details. See the ION Reference for a detailed description of the Clock Module. Specifications
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Accuracy
+/- 1ms.
Format
IRIG-B00x format (unmodulated IRIG-B time code)
Nominal Voltage
5 Vdc +/- 10%
Maximum Voltage
8 Vdc
Connector Type (E8, F8, G8 form factors)
Captured wire
Connector Type (other form factors)
Twisted pair (22 AWG)
© 2006 Schneider Electric. All rights reserved. www.powerlogic.com
CONTROLLED DISTRIBUTION
Configuring IRIG-B
IRIG-B Time Synchronization
Configuring IRIG-B All IRIG‐B equipped meters are set by default to synchronize via IRIG‐B. Operation is controlled by the Clock module’s Timesync Source and Clock Source registers. Use ION Setup or ION Enterprise to confirm your IRIG‐B settings. See the ION Reference for more details on the Clock Module.
Using the front panel You cannot configure IRIG‐B via the meter’s front panel.
Using ION Setup
Page 2
1.
In the Setup Assistant, navigate to Clock and click the Timezone tab.
2.
Select the CL1 Time Sync Source parameter and click Edit.
3.
Select IRIG‐B and click OK.
4.
Select the Clock Source parameter and click Edit. Select COMM and click OK.
5.
Connect the meter to the time source (GPS receiver output).
© 2006 Schneider Electric. All rights reserved.
IRIG-B Time Synchronization
Configuring IRIG-B
Using ION Enterprise 1.
Use the Management Console to connect to the desired meter.
2.
Open your meter in Designer and navigate to the Clock module. Right‐click on the Clock module to edit.
3.
Select the Time Sync Source setup register and click Modify.
4.
Select IRIG‐B. Click OK.
5.
Select the Clock Source parameter and click Edit.
6.
Select COMM and click OK.
7.
Connect the meter to the time source (GPS receiver output).
Supported GPS Receivers Any GPS receiver may be used as a time synchronization source, providing the receiver outputs unmodulated IRIG‐B time code data.
Security Access to Clock Module configurations are not available via the front panel of ION8600 meters. ION Setup or ION Designer is required. ION meter security and ION software security are implemented.
Diagnostic Module Outputs The diagnostic module output registers update as described in the Time Synchronization and Timekeeping technical note, with the following exceptions:
© 2006 Schneider Electric. All rights reserved.
GPS Receiver Status ‐ Set to N/A.
Page 3
Getting More Information
IRIG-B Time Synchronization
Event Logging Events are logged as described in the Time Synchronization and Timekeeping technical note, with the following exceptions:
GPS locked ‐ Not generated.
GPS unlocked ‐ Not generated.
Getting More Information Installation & Basic Setup Instructions This document provides instructions on mounting and wiring the ION8600 meter to the power system, wiring the COM ports, configuring the meter’s basic settings from the front panel, and verifying operation. Time Synchronization and Timekeeping Technical Note This technical note provides precise sequence‐of events and power quality analyses configuration procedures, including clock synchronization and Global Positioning System (GPS) time signal broadcasts across networks. User’s Guide This manual provides the operation and usage details including: displaying data, making configuration changes, customizing operation with ION software, using the standard inputs/outputs, and more. ION Reference This online module reference describes how to make configuration changes to an ION compliant node with Designer software, and provides a detailed functional description of every ION module in the ION architecture.
NOTE Softcopies are available for download from the PowerLogic website at www.powerlogic.com.
Page 4
© 2006 Schneider Electric. All rights reserved.