Preview only show first 10 pages with watermark. For full document please download

Iwatec Ups M/70 Tech. Data

   EMBED


Share

Transcript

IWATEC UPS M/70 Tech. Data M/70 Technical Specifications Electrical Data Output Output power Voltage 5 kVA 10 kVA 230V / 240V Voltage stability -static -dynamic ±1% ±1% Frequency 50 Hz / 60 Hz ±0.5% Wave form Sinus <2% THD (linear load) Overload (without by-pass) 125% 10 min / ˜ 300% 1 min 1000% 50 ms (mains on) Max. overload (with by-pass) 1000% 50 ms Efficiency (total) Losses Nominal current at pf 0.8 0.95 0.21 kW 0.42 kW 220V / 22.7A 220V / 45.4A 240V / 20.8A 240V / 41.6A Input Nominal voltage 220V / 240V ±15% Nominal frequency 50 Hz / 60 Hz ±4% Input current (nominal) 220V / 22A 240V / 20A 220V / 43A 240V / 39A Input current (maximal) 220V / 24A 240V / 22A 220V / 47A 240V / 43A Input wattage 4.2 kW 8.4 kW Battery Rated voltage Rated capacity 384V 6.5 Ah 12 Ah IWATEC UPS M/70 Tech. Data Standard autonomy 15 min 18 min Interfaces RS 232 optional AS 400 / Voltagefree contacts included Mechanical and environment data Dimensions (W x H x D) Weight with std. batt. Noise level 350 x 620 x 700 mm 164 kg 219 kg 40... 50 dB(A) Ambient temperature 0... 40 °C Relative Humidity 95% max. Degree of protection IP 30 Observed standards VDE, IEC, EN,SEV Options ● ● ● ● ● Remote panels Comm. Software for MS-DOS / MS-Windows Interface connection SNMP Automatic shut-down Software for CPU Batterie cabinet Technical data are subject to changes without notice Copyright © 1997 iwatec UPS