SUBMITTAL AJ009JNLDCH/AA Samsung FJM Series, Slim Duct Unit
Job Name Purchaser Submitted to Unit Designation
Location Engineer Reference Schedule #
Approval
Construction
Specifications Performance
Nominal Capacity
Cooling (Btu/h)
9,000
Heating (Btu/h)
10,000
Condensate
Pints/Hour
1.7
Voltage (ø/V/Hz)
1 / 208-230 / 60
Power Nominal Running Current (A)
0.35
Type Fan
Sirocco (2) BLDC (1)
Type Motor
FLA / Output
0.35A / 76 W 295 / 320 / 345
Airflow
CFM (UL)
L/M/H
External Static Pressure
Standard
"WC
0.08
Min. / Max.
"WC
0.04 / 0.16
Type
R410A
Refrigerant
Electronic Expansion Valve (at outdoor unit)
Control Method
Piping Connections
Unit Dimensions
Sound Level
Liquid (flare)
Inches
1/4
Suction (flare)
Inches
3/8
Drain
Inches
OD 1 1/4, ID 1
WXHXD
Inches
35 7/16 X 7 13/16 X 23 5/8
Weight
lbs.
Duct Connections (refer to drawing)
Supply (inches)
33 7/8 X 6
Return (inches)
30 9/16 X 6 11/16
L/H
51.36
dB
25 / 30
External Contact Control
MIM-B14
Condensate Pump W/Float Switch
MDP-E075SEE3D
Premium Wired Controller W/Scheduling
MWR-WE10
Standard Wired Controller (included)
Accessories Wireless Signal Wireless Signal Receiver Control Wireless Controller Line sets - insulated and flared, interconnect cables included Safety Certifications
• High-voltage terminal block temperature sensor to disable unit in the event overheating of power connection. • Gravity drain as standard • The indoor unit shall be powerd by the outdoor unit Construction The unit shall be constructed of insulated, galvanized steel Heat Exchanger The heat exchanger shall be mechanically bonded fin to copper tube Indoor Fan Indoor fan is a twin, backward curved centrifugal type with a single fan motor Three fan speed settings and auto setting Controls Control signal shall be a DDC type signal Interconnect control wire between outdoor and indoor shall be 16AWG X 2 shielded Controls shall integrate with a BMS system The system shall integrate with the Samsung Controls Solution.
✔
MWR-WH02
MR-EH00U
Air Filtration The unit includes a simple filter as standard. Field provided filtration is recommended.
25' - ILS2506
Pressure drop across the filter must be factored into the total ESP.
50' - ILS5006
Compatibility Will only operate with Samsung outdoor unit model numbers: AJ020JCJ2CH/AA, AJ024JCJ3CH/AA, AJ036JCJ5CH/AA.
MRK-A00 + MRW-10A
ETL & ETLc
Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95 ⁰F DB, 75⁰F WB. Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47 ⁰F DB, 43⁰F WB. Samsung and Quietside maintains a policy of ongoing development, specifications are subject to change without notice.
QS-DVMS-022015B
www.Quietside.com 888-699-6067
Page 2 of 2
SUBMITTAL AJ009JNLDCH/AA Samsung FJM Series, Slim Duct Unit Bottom of unit
30 1/4"
2 3/4" 4"
6 11/16"
3/8"
1/2"
30 9/16" (return opening)
6
Suction 7
Recommended Service Access (min.) (Verify Local Codes)
23 5/8"
23 5/8"
18 3/4"
36 7/8" 35 7/16"
TOP
Suspension Bolt Hanger
33 7/8" 8 1
2
4
2 7/8" 2 1/8"
7 13/16" 6"
1 1/4" 1 1/4"
4 5/8" 5 3/4"
6"
3/4"
Discharge
Supply Side
7 1/8" 9 5/8" 13 1/8" No.
BOTTOM
Suction
5
3
Name
Ø 1/4" Flare Ø 3/8" Flare
Liquid Pipe Connection
1 2
Gas Pipe Connection
Description
OD 1 1/4", ID 1"
3
Drain Pipe Connection, Without Condensate Pump
4
Drain Pipe Connection, With Condensate Pump
-
5 6
Controls Box Conduit for Power & Communication Wiring
7 8
Return Air Side Supply Air Outlet Duct Flange
-
Unit Clearance From Structure
Inspection Opening Requirements Unit Depth + 2"
Structure
13/16" or more Unit Unit Width (W) A=W+4"
B=23 5/8"
13/16" or more
Ceiling
In applications where there is not a tile ceiling, an inspection hole is required. If height between ceiling and structure is 3.25' or more, inspection opening "B" is recommended. If height between ceiling and structure is less than 3.25', inspection opening "A" and "B" is recommended. (verify state and local codes).
www.Quietside.com
Service Access