PRODUCT SPECIFICATIONS
SYSTEM FEATURES AND BENEFITS • Fail- Safe Design with individually fused MOV’s that eliminate single point failure protecting against both over-current and over-voltage events. • 200 KAIC Short Circuit Rating permits direct buss connection to most electrical services. • Proven Performance and Tested at its full rated surge capacity by a nationally recognized third-party laboratory using NEMA-LS1 test procedure with a fully configured standard unit. • Low Let Through Voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events. • Extended Durability and proven to exceed 4,000 surges of 10,000 amps/mode using the ANSI/IEEE C62.41.1 2000 and IEC 61643 test procedures. • Compact Design provides superior surge protection in a 10”H x 8”H x 6”D housing. • All Weather sealed, powder-coated NEMA 4/IP65 housing is designed for indoor/outdoor applications. • 10-Year Standard Warranty with optional 15-year extended warranty.
MODEL NUMBER SCHEME
PRODUCT SPECIFICATIONS
Available Configurations
General Specifications
Model Number
Voltage
Configuration
JSP160-1P120
120V
Single Phase 2-wire + grd
JSP160-1P240*
240V
Single Phase 2-wire + grd
JSP160-1S240
120/240V
Split-Phase 3-wire + grd
Maximum Surge Current Rating: Repetitive Surge Current Rating:
Product Design:
160kA per phase; 80kA per mode 4,000 impulses 10,000 amps/mode using the ANSI/IEEE C62.41.1 2000 and IEC 61643 test procedures Parallel design with individual fused MOVs and optional UL 1283 EMI/RFI filter UL 1449 2nd Edition 2005 Revision
JSP160-3Y208
120/208V
Three-Phase WYE, 4-wire + grd
JSP160-3Y380*
220/380V
Three-Phase WYE, 4-wire + grd
JSP160-3Y415*
240/415V
Three-Phase WYE, 4-wire + grd
JSP160-3Y480
277/480V
Three-Phase WYE, 4-wire + grd
JSP160-3Y600
347/600V
Three-Phase WYE, 4-wire + grd
JSP160-3H240
120/240V
Three-Phase High-Leg 4-wire + grd
Operating Frequency:
47-63 Hz
JSP160-3D240
240V
Three-Phase DELTA, 3-wire + grd
Connection Method:
Parallel to electrical distribution system
JSP160-3D380
380V
Three-Phase DELTA, 3-wire + grd
Modes of Protection:
L-N, L-G, N-G, & L-L
JSP160-3D480
480V
Three-Phase DELTA, 3-wire + grd
Fault Rating (SCCR):
JSP160-3D600
600V
Three-Phase DELTA, 3-wire + grd
200kAIC – no upstream over-current protection device (breaker or fuse) required
*Denotes units that are CE listed Units suitable for TT and IT grounded power systems available upon request. Consult factory for model number.
Regulatory Listing:
(effective 2/9/07), UL 1283, CE on 220, 230, and 240V units Warranty:
Electrical Specifications
Response Time:
Less than 0.5 nanoseconds
Standard Monitoring:
Status indicator lights (one per phase) Dual remote relay contacts – normal open and normal close. Relay contacts are rated 150VDC/125 VAC with maximum switching power of 30WDC/60VA AC. Audible Alarm with Silence Button 8-digit surge counter provides maximum surge count capability
Available Options Transient Filter that meets UL 1283*:
add suffix “-F”
Surge Counter:
add suffix “-B”
Stainless Steel Enclosure:
add suffix “-S”
Optional Monitoring:
*Not recommended when using telecommunication rectifiers
EMI/RFI Filter Attenuation – Mil Standard 220B Max. Attenuation Freq. 41 dB @ 106kHz Made in U.S.A.
10-Year Standard, 15-Year Extended
Page 1 of 2
SURGE SUPPRESSION SYSTEM
JSP 160
Dimensional Specifications Typical 3-Phase Installation Dim H1 H2 H3 W1 W2 D
(W1) (W2)
(D)
ø0.31 (7.87)
JSP 160 10.00 10.75 11.50 8.00 6.00 6.20
4-Wire WYE (254.0) (273.1) (292.1) (203.2) (152.4) (157.5)
JSP RED ORN
All measurements in inches (mm) 2
(H1)
JSP
Mechancial Specifications (H2)
Enclosure Type:
Altitude:
Powder coated, impact-resistance steel, weather-proof NEMA 4 Indoor or outdoor 10"H x 8"W x 6.2”D (254 x 205.2 x 157.5) Pre-wired with 36 inches(910mm) of #10AWG(5.27mm2) conductor Dual mounting flanges -40° C to +70° C (-40° F to +158° F) 5% - 95% non-condensing humidity Up to 13,000 ft. (4000m)
Weight:
20 lbs. (9 kg)
(H3)
Installation Location: Dimensions: Connection Method: Mounting Method: Operating Environment:
JSP 160 Performance Data
Model Number
Voltage Configuration
JSP160-1P120
1P120
JSP160-1P240
1P240
JSP160-1S240
1S240
JSP160-3Y208
3Y208
JSP160-3Y380
3Y380
JSP160-3Y415
3Y415
JSP160-3Y480
3Y480
JSP160-3Y600
3Y600
JSP160-3H240
3H240
JSP160-3D240
3D240
JSP160-3D380
3D380
JSP160-3D480
3D480
JSP160-3D600
3D600
Protection Mode
MCOV
L-N L-G N-G L-N L-G N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N H-N L-G H-G L-L H-L L-G L-L L-G L-L L-G L-L L-G L-L
150 150 150 320 320 320 150V 150V 300V 150V 150V 150V 300V 150V 320V 320V 640V 320V 320V 320V 640V 320V 320V 320V 640V 320V 420V 420V 840V 420V 150V 320V 150V 320V 300V 470V 320V 320V 550V 550V 550V 550V 750V 750V
ANSI/IEEE C62.41.1-2002, C62.41.2-2002, & C62.45-2002 Measured Limiting Voltage UL 1449 2nd B3 Ring Wave B3/C1 Combo C3 Combo 2005 Revision 6kV, 500A Wave 6kV, 3kA Wave 20kV, 10kA 6kV, 500A SVR 440V 496V 464V 347V 1145V 1090V 440V 496V 544V 464V 440V 496V 544V 464V 347V 1145V 491V 1090V 347V 1145V 491V 1090V 347V 1145V 491V 1090V 715V 829V 1130V 670V 440V 347V 496V 1145V 544V 980V 759V 640V 1050V 860V 1050V 860V 1260V 1070V
629V 640V 624V 525V 565V 507V 629V 640V 971V 624V 629V 640V 971V 624V 525V 565V 860V 507V 525V 565V 860V 507V 525V 565V 860V 507V 1250V 1340V 2300V 1230V 629V 525V 640V 565V 971V 1250V 982V 1070V 1500V 1720V 1500V 1720V 1960V 2260V
1413V 1360V 1360V 1069V 1117V 930V 1413V 1360V 1707V 1360V 1413V 1360V 1707V 1360V 1069V 1117V 1443V 930V 1069V 1117V 1443V 930V 1069V 1117V 1443V 930V 1910V 1960V 2910V 1880V 1413V 1069V 1360V 1117V 1707V 1640V 1630V 1550V 2260V 2340V 2260V 2340V 2760V 2950V
400V 400V 400V 800V 800V 800V 400V 400V 800V 400V 400V 400V 800V 400V 800V 800V 1500V 800V 800V 800V 1500V 800V 800V 800V 1500V 800V 1000V 1200V 2000V 1000V 400V 800V 400V 800V 800V 1500V 800V 800V 1500V 1500V 1500V 1500V 1800V 1800V
All JSP systems measured limited voltages are peak values (±10%) measured from the zero reference point and are in compliance with test and evaluation procedures outlined in NEMA LS1-1992 (R2000), paragraphs 2.210 and 3.10. Specifications subject to change without notice, refer to www.joslynsurge.com for latest revision. ™
©2007 Joslyn® and JSP.™ Made in U.S.A. 1M/9.6.07/JSP160
Page 2 of 2
5900 Eastport Boulevard Richmond, VA 23231-4453 USA
[email protected] TEL: 804.236.3300 800.238.5000 FAX: 804.236.4047