Transcript
SURGE SUPPRESSION SYSTEM
PRODUCT SPECIFICATIONS
SYSTEM FEATURES AND BENEFITS • Fail- Safe Design with individually fused MOV’s that eliminate single point failure protecting against both over-current and over-voltage events. • 200 KAIC Short Circuit Rating permits direct buss connection to most electrical services. • Proven Performance and Tested at its full rated surge capacity by a nationally recognized third-party laboratory using NEMA-LS1 test procedure with a fully configured standard unit. • Low Let Through Voltage ensured by the lowest possible impedance path to ground and equal current sharing during surge events. • Extended Durability and proven to exceed 6,500 surges of 10,000 amps/mode using the ANSI/IEEE C62.41.1 2000 and IEC 61643 test procedures. • Compact Design provides superior surge protection in a 14”H x 12”H x 6”D housing. • All Weather sealed, powder-coated NEMA 4/IP65 housing is designed for indoor/outdoor applications. • 10-Year Standard Warranty with optional 15-year extended warranty.
MODEL NUMBER SCHEME
PRODUCT SPECIFICATIONS
Available Configurations
General Specifications
Model Number
Voltage
Configuration
JSP240-1P120
120V
Single Phase 2-wire + grd
JSP240-1P240
240V
Single Phase 2-wire + grd
JSP240-1S240
120/240V
Split-Phase 3-wire + grd
JSP240-3Y208
120/208V
Three-Phase WYE, 4-wire + grd
JSP240-3Y380
220/380V
Three-Phase WYE, 4-wire + grd
JSP240-3Y415
240/415V
Three-Phase WYE, 4-wire + grd
JSP240-3Y480
277/480V
Three-Phase WYE, 4-wire + grd
JSP240-3Y600
347/600V
Three-Phase WYE, 4-wire + grd
JSP240-3H240
120/240V
Three-Phase High-Leg 4-wire + grd
JSP240-3D240
240V
Three-Phase DELTA, 3-wire + grd
JSP240-3D380
380V
Three-Phase DELTA, 3-wire + grd
JSP240-3D480
480V
Three-Phase DELTA, 3-wire + grd
JSP240-3D600
600V
Three-Phase DELTA, 3-wire + grd
Units suitable for TT and IT grounded power systems available upon request. Consult factory for model number.
Maximum Surge Current Rating: Repetitive Surge Current Rating:
Product Design: Regulatory Listing:
(effective 2/9/2007), UL 1283, CE on 220, 230, and 240V units Warranty:
add suffix “-F”
Surge Counter:
add suffix “-B”
Stainless Steel Enclosure:
add suffix “-S”
Operating Frequency:
47-63 Hz
Connection Method:
Parallel to electrical distribution system
Modes of Protection:
L-N, L-G, N-G, & L-L
Fault Rating (SCCR):
200kAIC – no upstream over-current protection device (breaker or fuse) required
Response Time:
Less than 0.5 nanoseconds
Standard Monitoring:
Status indicator lights (one per phase) Dual remote relay contacts – normal open and normal close. Relay contacts are rated 150VDC/125 VAC with maximum switching power of 30WDC/60VA AC. Audible Alarm with Silence Button 8-digit surge counter provides maximum surge count capability
Optional Monitoring:
*Not recommended when using telecommunication rectifiers
EMI/RFI Filter Attenuation – Mil Standard 220B Max. Attenuation Freq. 41 dB @ 106kHz
Made in U.S.A.
10-Year Standard, 15-Year Extended
Electrical Specifications
Available Options Transient Filter that meets UL 1283*:
240kA per phase; 120kA per mode 6,500 impulses 10,000 amps/mode using the ANSI/IEEE C62.41.1 2000 and IEC 61643 test procedures Parallel design with individual fused MOVs and optional UL 1283 EMI/RFI filter UL 1449 2nd Edition 2005 Revision
Page 1 of 2
SURGE SUPPRESSION SYSTEM
JSP 240
Dimensional Specifications Dim H1 H2 H3 W1 W2 D
(W1) (W2)
(D)
ø0.31 (7.87)
JSP 240 14.00 14.75 15.50 12.00 10.00 6.20
Typical 3-Phase Installation 4-Wire WYE
(355.6) (374.7) (393.7) (304.8) (254.0) (157.5)
JSP RED ORN
All measurements in inches (mm) 2
JSP
(H1)
Mechancial Specifications (H2)
Enclosure Type:
Altitude:
Powder coated, impact-resistance steel, weather-proof NEMA 4 Indoor or outdoor 14"H x 12"W x 6”D (355.6 x 304.8 x 157.5) Hard-wired via internal lugs #10AWG - #3 AWG (5.27mm2 -26.7mm2 ) Dual mounting flanges -40° C to +70° C (-40° F to +158° F) 5% - 95% non-condensing humidity Up to 13,000 ft. (4000m)
Weight:
40 lbs. (18.2 kg)
(H3)
Installation Location: Dimensions: Connection Method: Mounting Method: Operating Environment:
JSP 240 Performance Data
Model Number
Voltage Configuration
JSP240-1P120
1P120
JSP240-1P240
1P240
JSP240-1S240
1S240
JSP240-3Y208
3Y208
JSP240-3Y380
3Y380
JSP240-3Y415
3Y415
JSP240-3Y480
3Y480
JSP240-3Y600
3Y600
JSP240-3H240
3H240
JSP240-3D240
3D240
JSP240-3D380
3D380
JSP240-3D480
3D480
JSP240-3D600
3D600
Protection Mode
MCOV
L-N L-G N-G L-N L-G N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N H-N L-G H-G L-L H-L N-G L-G L-L L-G L-L L-G L-L L-G N-G
150V 150V 150V 320V 320V 320V 150V 150V 300V 150V 150V 150V 300V 150V 320V 320V 640V 320V 320V 320V 640V 320V 320V 320V 640V 320V 420V 420V 840V 420V 150V 320V 150V 320V 320V 470V 150V 320V 320V 550V 550V 550V 550V 750V 750V
ANSI/IEEE C62.41.1-2002, C62.41.2-2002, & C62.45-2002 Measured Limiting Voltage UL 1449 2nd B3 Ring Wave B3/C1 Combo C3 Combo 2005 Revision 6kV, 500A Wave 6kV, 3kA Wave 20kV, 10kA 6kV, 500A SVR 464V 672V 512V 427V 944V 848V 464V 672V 576V 512V 464V 672V 576V 512V 427V 944V 555V 848V 427V 944V 555V 848V 427V 944V 555V 848V 715V 829V 1130V 670V 464V 427V 672V 944V 576V 980V 512V 750V 630V 1050V 860V 1050V 860V 1245V 1060V
502V 627V 568V 828V 996V 899V 502V 627V 864V 568V 502V 627V 864V 568V 828V 996V 1497V 899V 828V 996V 1497V 899V 828V 996V 1497V 899V 1250V 1340V 2300V 1230V 502V 828V 627V 996V 864V 1250V 568V 940V 1020V 1450V 1670V 1450V 1670V 1960V 2260V
907V 1173V 1090V 1170V 1540V 1500V 907V 1173V 1267V 1090V 907V 1173V 1267V 1090V 1170V 1540V 1950V 1500V 1170V 1540V 1950V 1500V 1170V 1540V 1950V 1500V 1910V 1960V 2910V 1880V 907V 1170V 1173V 1540V 1267V 1640V 1090V 1650V 1680V 2160V 2470V 2160V 2470V 2760V 2960V
400V 400V 400V 700V 800V 800V 400V 400V 700V 400V 400V 400V 700V 400V 700V 800V 1500V 800V 700V 800V 1500V 800V 700V 800V 1500V 800V 1000V 1200V 2000V 1000V 400V 800V 400V 800V 800V 1500V 400V 700V 800V 1500V 1500V 1500V 1500V 1800V 1800V
All JSP systems measured limited voltages are peak values (±10%) measured from the zero reference point and are in compliance with test and evaluation procedures outlined in NEMA LS1-1992 (R2000), paragraphs 2.210 and 3.10. Specifications subject to change without notice, refer to www.joslynsurge.com for latest revision. ™
©2007 Joslyn® and JSP.™ Made in U.S.A. 1M/12.7.07/JSP240
Page 2 of 2
5900 Eastport Boulevard
[email protected] Richmond, VA 23231-4453 USA TEL: 804.236.3300 800.238.5000 FAX: 804.236.4047