Transcript
Three phase input - single phase output UPS, 60 minutes backup time, 10KVA.
1 of 2
http://www.kert.it/PrintProduct.aspx?Sku=KBS10KTM60
Three phase input - single phase output UPS, 60 minutes backup time, 10KVA.
KBS10KTM60 Features Capacity (VA): 10000,00
Features
Power (W): 8000,00
Backup time (minutes): 60,00
Input
Wave form: Sine wave
Input voltage: 400,00 -20÷10% Vac
Thd (%): 3,00
Frequency (Hz): 50
Technology: On-Line
Input current (A): 12,00
Efficiency (%): 92,00
Output
Power dissipation (W): 695,00
Output voltage: 230,00 ± 1% Vac
Output protections:
Frequency (Hz): 50 same as input
Overload - Short-cirucit - Overtemperature
Connections Input: Terminal board Output: Terminal board
Suggested applications: Installation: On floor
Dimensions Dimensions (mm): W 450,00 x H 1200,00 x D 650,00 Weight (kg): 90,00
Standards:
Alerts: Back-up operation - By-pass activated - By-pass failure - Battery output sensed - Battery exhausted - Battery to be replaced Overtemperature - Overload - Short-circuit - Wrong input phases sequence - Battery test in progres - Output voltage out of range Abnormal inverter condition - Battery charger failure - Inverter voltage out of range - Abnormal operation - Fault Remote control functions: EPO - Abnormal operation - Fault - Dry contact for by-pass activated - Dry contact for emergency mode - Dry contact for abnormal inverter condition - Dry contact for by-pass failure - Dry contact for battery exhausted - Dry contact for output voltage out of range - Dry contact for abnormal rectifier condition Signaling: Acoustic signaling - LCD display
2006/95/EC Directive
Measuring instruments: Digital multimeter
2004/108/EC Directive
Battery tipe: Sealed lead acid, maintenance free batteries
CEI EN 62040-1-1
Audible noise (dB/m): 60at 1
CEI EN 62040-2
IP rating: IP20
CEI EN 62040-3
Cooling: Forced air convection
19/06/2014 08:57
Three phase input - single phase output UPS, 60 minutes backup time, 10KVA.
2 of 2
CEI EN 50272-2
http://www.kert.it/PrintProduct.aspx?Sku=KBS10KTM60
Working temperature (°C): 0 - 40 Relative humidity (%): 0 - 95
19/06/2014 08:57