KOL Timer, electronic ■ ■ ■ ■ ■ ■ ■
Multi function or mono function 4 (KOL251) or 6 time ranges (KOL 1, KOL 3) 17.5 mm width for DIN rail 110…240 VAC 24 …48 VDC and 24…240 VAC 1 make contact (KOL 1) or 2 make contacts (KOL251) 1 changeover contact (KOL 3)
From left to right: KOL360, KOL311
KOL 1/ 2 • •
Delayed release
•
Fleeting-on delay timer
•
Flasher relay
KOL 3 • • • •
•
•
• •
1 make contact
• •
• •
• •
• •
• •
• •
• •
• •
•
•
•
•
•
• •
2 make contacts with a joint connection
• KOL251H7MKVPN00
KOL160H7MRR1N00
KOL142H7MRR1N00
KOL121H7MRR1N00
KOL112H7MRR1N00
KOL111H7MRR1N00
1 changeover contact Order no.
• •
KOL360H7MRVPN00
•
KOL342H7MRVPN00
•
24…48 VDC and 24…240 VAC 110…240 VAC
Number of contacts
•
KOL321H7MRVPN00
0.15 s…10 min 0.05 s…10 h
Operating voltage
Settings
Rough time setting e.g., 1 m = 1 minute
Fine setting time Divides the value set in the rough setting by a factor of 10 Example: rough setting 1 m = 1 minute 1 unit = 6 s. If 24 s are necessary, factor 4 must be set here
•
• • • •
•
• •
Star-delta timer Time ranges
•
KOL312H7MRVPN00
Delayed operation
KOL311H7MRVPN00
Functions
Function settings (only with KOL160/360) Here you can set the relay function, e.g.,11 - delayed operation
Technical data Multi time ranges
Setting accuracy Repeat accuracy Reset time Operating voltage
Power consumption Duty cycle Pulse control Outputs Switching capacity
Insulation characteristics EMC/immunity to interference EMC/emissions Approvals Ambient temperature Connections
Mounting
KOL251 0.15…3 s, 0.5…10 s, 3 s…60 s, 0.5…10 min
KOL 1 und KOL 3 0.05…1 s, 0.5…10 s, 0.05…1 min, 0.5…10 min, 0.05…1 h, 0.5…10 h Time range can be freely selected on the front using a screwdriver ±5 % of the time range final value (tmax) 1% of the time range final value (tmax) 100 ms KOL 1 KOL251, KOL 3 110…240 VAC, 50/60 Hz (A1/A2) 24…48 VDC and 24…240 VAC, 50/60 Hz AC: –15 %/10 % DC: ±20% AC: –15 %/10 % 0.5 W at 24 VDC or 5 VA at 250 VAC 100 % Operating voltage range, current 1 mA, duration of the control pulse >50 ms 1 make contact (KOL 1), 2 make contacts (KOL251) or 1 changer (KOL 3) U = 250 VAC, Ith = 5 A, P = 1250 VA 1.5 A/ 250 VAC (AC15) or 1 A/24 VDC (DC13) in accordance with IEC60947-5-1 2 kV/ 50 Hz test voltage in accordance with VDE 0435 and 4 kV 1.2 /50 µs surge voltage in accordance with IEC60947-5-1 between all inputs and outputs Surge capacity in accordance with IEC61000-4-5, 4 kV (2 kV to A3-A2) Burst in accordance with IEC61000-4-4, 4 kV ESD in accordance with IEC61000-4-2, 8 kV Electromagnetic fields in accordance with EN 55 022, class B UL, C-UL (KOL 1) or UL, C-UL, Germanischer Lloyd (KOL251, KOL 3) KOL 1 KOL 2 and KOL 3 –20 °C to +50 °C –20 °C to +60 °C Screw terminals for 1 × 0.5 mm² or 2 × 2.5 mm², for Pozidrive no. 1 (max. 1Nm) or screwdriver. Finger protection in accordance with VDE0106 Snap-on mounting on 35 mm rail according to EN60715TH35 or screw mounting by adapter (accessories)
Accessories ■ Adapter
Order no.
CJ260 for screw mounting
4 104 5077 3
Dimension diagrams Timer Screw adaptor (accessories CJ260, order no. 4 104 5077 3)
80
45
43
17.5
2|
www.saia-pcd.com
66 70 Datenblatt 31/005: Timer, electronic KOL
Time diagram and connection diagram KOL 1/ 2
Delayed operation (11) L/+
= LED orange: Output in operating mode = LED green: operating voltage available
A1/A2 or A3/A2
U
15
A2
18
15/18
t
Output
A1
N/–
Delayed release (12)
= LED green: operating voltage available
A1/A2 or A3/A2
U
= LED orange: Output in operating mode
S
L/+
A1 B1 S
15
A2
18
A1
15
A2
18
A1
15
A2
18
B1/B2 or A3/A1
Output
t
15/18 N/–
Fleeting-on delay timer (21) L/+
= LED orange: Output in operating mode = LED green: operating voltage available
A1/A2 or A3/A2
U
15/18
t
Output
N/–
Flasher relay (42) = LED orange: Output in operating mode = LED green: operating voltage available
A1/A2 or A3/A2
U Output
t
t
t
t
t
L/+
15/18
N/-
Star-delta (51) A1/A2 U
= LED green: operating voltage available
Datenblatt 31/005: Timer, electronic KOL
Y
t
L/+ A1
17
A2
18
17/18 17/28
tu = 50...65 ms
N/-
28
www.saia-pcd.com
|3
Time diagram and connection diagram KOL 3
Delayed operation (11) L/+
= LED orange: Output in operating mode = LED green: operating voltage available
A1/A2 or A3/A2
U
15
t
Output
A1
15
A2
18 16
18 16 N/–
Delayed release (12)
= LED green: operating voltage available
A1/A2 or A3/A2
U
= LED orange: Output in operating mode
S
L/+
A1 B1 S
15
A2
18 16
A1
15
A2
18 16
B1/B2 or A3/A1
Output
15 18 16
t
N/–
Fleeting-on delay timer (21) L/+
= LED orange: Output in operating mode = LED green: operating voltage available
A1/A2 or A3/A2
U
15
t
Output
18 16 N/–
Flasher relay (42) = LED orange: Output in operating mode = LED green: operating voltage available
A1/A2 or A3/A2
U Output
t
t
t
t
t
L/+
Bahnhofstrasse 18 | 3280 Murten, Schwitzerland T +41 26 672 72 72 | F +41 26 672 74 99 www.saia-pcd.com
[email protected] | www.sbc-support.com P+P31/005 EN04 01. 2014 Subjects to change without notice.
15
A2
18 16
15 18 16 N/-
Saia-Burgess Controls AG
A1