KX12-50 VRLA/AGM Standard Terminal (mm) Threaded Insert 6mm STUD
16
T6
132 114
2 2
6
200 2 190 2
M6
2-M6
216 257
2 2
10 9 8
PHYSICAL PHYSICAL SPECIFICATION SPECIFICATION Nominal Voltage
12V
Nominal Capacity (10HR)
51AH
6 5 4 3 2
(min)
Discharge time
(h)
7
60 50 40 30 20 10
40 C(104 F ) 25 C( 77 F ) 0 C( 32 F )
8 6 4
Dimension
Length
257 2mm (10.12 inches)
Width
132 2mm (5.20 inches)
Container Height
200 2mm (7.87 inches)
Total Height (with Cover)
200 2mm (7.87 inches)
0
1 2 3 4
6 7
5
10 16 30 50 105 160 320
Discharge Current (A)
Weight
Approx 17kg (37.5 lbs)
Standard Terminal
Threaded Insert 6mm STUD
Discharge Characteristics (25 C,77
)
13
Rated Capacity
20 hour rate (2.75A)
55.0 AH
10 hour rate (5.10A)
51.0 AH
5 hour rate (8.8A)
44.0 AH
Initial Charging Current less than 15A.Voltage Cycle
3 hour rate (13.3A) 39.9 AH Constant1 hour rate (30.6A) 30.6 AH
0 14.4V~ 15.0V at 25C
0 (77F )
0 Temp. Coefficient -30mV/C
Voltage
Capacity affected by Temperature
o 40C o
25C o
0C
o (104F ) o
(77F)
103%
Standby
11 10.8 10.5 10
5.1A 2.75A 13.3A
9.6
50A 30.6A
150A
100A
i n g C u r r e n t Vo l t a g e 0
0
0
13.5V~13.8V at 25C (77F )
3
5 10
16
30
60 2
3
o
( 32F)
0 Temp. Coefficient - 20mV/C
86%
8.8A
9 7.8
No limit on Initial Charg-
Charge
100%
Loading Voltage(V)
12
ELECTRICAL SPECIFICATION
5
10
20
h
min
Discharge Time
Constant Current (Amp) and Constant Power (Watt) Discharge Table (25 C,77 F) Time(minute) Final voltage
10 1.3
15 1.3
20 1.3
30 1.6
45 1.6
60 1.67
120 1.7
180 1.75
A
127.5
96.9
76.5
58.7
40.8
30.6
17.9
13.3
W
239.7
183.6
149.9
110.7
81.1
60.6
35.5
26.4
Amp/Watt/Cell
300 1.75
360 1.75
480 1.8
600 1.8
1200 1.8
10.2
8.8
7.8
6.1
5.1
2.75
20.3
17.5
15.5
12.1
10.2
5.5
240 1.75
10 P.O. Box 700, Innaloo WA 6918, Australia - Tel. +61 8 63635420, Fax +61 8 62101548 -