Transcript
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-P0612P
For standby power supplies. Expected trickle life: Approx. 6 years at 25°C, Approx. 10 years at 20°C.
Dimensions (mm) Terminal type: Faston 187 or Faston 250
+ 0.039
1.969 - 0.020 50 +- 1.0 0.5
0.236 (6)
5.945 +- 0.059 0.020 151 +- 1.5 0.5
5.913 (150.2)
Photo/Label for reference only.
Specifications 6V 12Ah 5.945 inches (151.0 mm)
Width
1.969 inches (50.0 mm)
Height
3.702 inches (94.0 mm)
Total Height*
3.937 inches (100.0 mm)
Approx. mass
4.41 lbs. (2.0 kg) LC-P0612P1
UL94V-0 Faston 250 UL94V-0 Faston 187
LC-P0612P
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Dimensions
7.2 6.9 6.6 6.3 6.0 5.7 5.4 5.1 4.8 4.5 4.2 3.9
* The total height with #250 terminal is 101.5mm.
12A
1
2
4
2
4
6 8 10
20
40
(Hour)
Trickle use Control voltage
20 15 10
5.8A Approx. 15mΩ 102% 100% 85% 65% 91% 82% 64%
(Note)
30
12Ah 11.3Ah 10.4Ah 8.1Ah (Hour)
20 hour rate (600mA) 10 hour rate (1130mA) 5 hour rate (2080mA) 1 hour rate (8100mA) 1.5 hour rate discharge Cut-off voltage 5.25 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months Initial current
Duration of discharge
Self discharge 77˚F (25˚C)
40 60
Duration of discharge vs. Discharge current
104˚F (40˚C)
5 4 3
77˚F (25˚C)
2 1.5 32˚F (0˚C) 1 50 40
5˚F (-15˚C)
30
(Minute)
Temperature dependency of capacity (20 hour rate)
20
Duration of discharge
Characteristics
Internal Resistance
6 8 10
(Minute)
minimum order quantities.
Capacity (note) 77˚F (25˚C)
1.2A 0.6A
3A
6A
24A 0
♦ Please contact Panasonic for availability on optional items. Optional items may be subject to
Charge Method (Constant Voltage)
1.937 (49.2)
Battery case resin: Standard (UL94V-0) Color is grey.
Nominal Voltage Rated capacity (20 hour rate) Length
Standard Terminals and Resin Optional Terminals and Resin
0.012 (0.3)
+ 0.059
0.63 (16)
3.701- 0.020 (94 +- 1.5 0.5 )
5.13 (130.3)
20
10
1.8 A or smaller 6.8V to 6.9V (per 6V cell 25˚C)
5 3 300 500
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values. (Note) For cycle use of the battery, please contact us in advance.
VRLA BATTERIES
(mA)
1
3
5
10
30
50
100
(A) Discharge current
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-P067R2P
For standby power supplies. Expected trickle life: Approx. 6 years at 25°C, Approx. 10 years at 20°C.
Dimensions (mm) Terminal type: Faston 187 or Faston 250
+
0.059 1.339 - 0.020 34 -+ 1.5 0.5
+
0.236 (6)
5.945 - 0.059 0.020 + (151 - 1.5 0.5 )
5.913 (150.2)
Photo/Label for reference only.
Dimensions
6V 7.2Ah 5.945 inches (151.0 mm)
Width
1.339 inches (34.0 mm)
Height
3.702 inches (94.0 mm)
Total Height*
3.937 inches (100.0 mm)
Approx. mass
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated capacity (20 hour rate) Length
2.86 lbs. (1.30 kg) LC-P067R2P1
UL94V-0 Faston 250 UL94V-0 Faston 187
LC-P067R2P
7.5 7.0 6.5 6.0 5.5 5.0 4.5 4.0 3.5 3.0 2.5 0 1
2.88A 1.44A 11.52A 23.04A
2
4
6 8 10
Self discharge 77˚F (25˚C)
Trickle use Control voltage
7.2Ah 6.8Ah 6.3Ah 4.9Ah
2
4
6 8 10
20
40
(Hour)
20 15 10
(Hour)
3.5A Approx. 20mΩ 102% 100% 85% 65% 91% 82% 64% 1.08 A or smaller 6.8V to 6.9V (per 6V cell 25˚C)
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values. (Note) For cycle use of the battery, please contact us in advance.
(Note)
30
Duration of discharge
Temperature dependency of capacity (20 hour rate)
20 hour rate (360mA) 10 hour rate (680mA) 5 hour rate (1260mA) 1 hour rate (4900mA) 1.5 hour rate discharge Cut-off voltage 5.25 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months Initial current
104˚F (40˚C) 5 4 3
77˚F (25˚C)
32˚F (0˚C) 2 1.5 5˚F (-15˚C) 1 50 40 30
(Minute)
Internal Resistance
40 60
Duration of discharge vs. Discharge current
Characteristics Capacity 77˚F (25˚C)
20
Duration of discharge
minimum order quantities.
(note)
0.72A 0.36A
5.76A
(Minute)
♦ Please contact Panasonic for availability on optional items. Optional items may be subject to
Charge Method (Constant Voltage)
1.307 (33.2)
Battery case resin: Standard (UL94V-0) Color is grey.
Specifications
Standard Terminals and Resin Optional Terminals and Resin
0.012 (0.3)
+ 0.059
0.354 (9)
3.701- 0.020 (94 +- 1.5 0.5 )
5.13 (130.3)
20
10
5 3 100
300 500
1
3
5
(mA)
10
30
50
(A) Discharge current
VRLA BATTERIES
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-P127R2P
For standby power supplies. Expected trickle life: Approx. 6 years at 25°C, Approx. 10 years at 20°C.
Dimensions (mm) Terminal type: Faston 187 or Faston 250
(151
1.89 (48)
+ 0.059
1.5 0.5 )
3.701- 0.020 (94 +- 1.5 0.5 )
2.565 (65.15)
2.539 +- 0.059 0.020 (64.5 +- 1.5 0.5 )
0.236 (6)
5.945 +- 0.059 0.020
0.012 (0.3)
Photo/Label for reference only. 5.193 (150.2)
Specifications
Battery case resin: Standard (UL94V-0) Color is grey.
Dimensions
12V 7.2Ah 5.945 inches (151.0 mm)
Width
2.539 inches (64.5 mm)
Height
3.702 inches (94.0 mm)
Total Height*
3.937 inches (100.0 mm)
Approx. mass
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated capacity (20 hour rate) Length
Standard Terminals and Resin Optional Terminals and Resin
5.516 lbs. (2.50 kg) LC-P127R2P1
UL94V-0 Faston 250 UL94V-0 Faston 187
LC-P127R2P
15.0 14.0 13.0 12.0 11.0 10.0 9.0 8.0 7.0 6.0 5.0
∗ The total height with #250 terminal is 101.5mm. ♦ Please contact Panasonic for availability on optional items. Optional items may be subject to
2.88A 11.52A 23.04A
0 1
2
4
6 8 10
20
Self discharge 77˚F (25˚C)
Trickle use Control voltage
7.2Ah 6.8Ah 6.3Ah 4.9Ah
4
6 8 10
20
40
(Hour)
20 15 10
3.5A Approx. 40mΩ 102% 100% 85% 65% 91% 82% 64% 1.08 A or smaller 13.6V to 13.8V (per 12V cell 25˚C)
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values. (Note) For cycle use of the battery, please contact us in advance.
(Note)
30
(Hour)
20 hour rate (360mA) 10 hour rate (680mA) 5 hour rate (1260mA) 1 hour rate (4900mA) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months Initial current
Duration of discharge
Temperature dependency of capacity (20 hour rate)
2
Duration of discharge vs. Discharge current
104˚F (40˚C) 5 4 3 2 1.5 1 50 40
77˚F (25˚C) 32˚F (0˚C)
5˚F (-15˚C)
30
(Minute)
Internal Resistance
40 60
(Minute)
Discharge time
Characteristics Capacity (note) 77˚F (25˚C)
1.44A 0.72A 0.36A
5.76A
minimum order quantities.
Charge Method (Constant Voltage)
2.508 (63.7)
20
10
5 3 100
VRLA BATTERIES
300 500
1
3
5
(mA)
10
30
50
(A) Discharge current
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R0612P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm) Terminal type: Faston 187 or Faston 250
+ 0.039
1.969 - 0.020 50 +- 1.0 0.5
0.236 (6)
5.945 +- 0.059 0.020 151 +- 1.5 0.5
Photo/Label for reference only.
5.913 (150.2)
Specifications
1.937 (49.2)
Battery case resin: Standard (UL94HB) Color is black.
Dimensions
6V 12.0Ah 5.945 inches (151.0 mm)
Width
1.969 inches (50.0 mm)
Height
3.702 inches (94.0 mm)
Total Height*
3.937 inches (100.0 mm)
Approx. mass
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
Standard Terminals and Resin
0.012 (0.3)
+ 0.059
0.63 (16)
3.701- 0.020 (94 +- 1.5 0.5 )
5.13 (130.3)
4.30 lbs. (1.95 kg)
UL94HB Faston 187
LC-R0612P
UL94HB Faston 250
LC-R0612P1
∗ The total height with #250 terminal is 101.5mm.
7.2 6.9 6.6 6.3 6.0 5.7 5.4 5.1 4.8 4.5 4.2 3.9
12A
1.2A 0.6A
3A
6A
24A 0
1
2
4
6 8 10
20
40 60
2
4
(Minute)
Characteristics
Temperature dependency of capacity (20 hour rate) Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
40
20 15
Approx. 15mΩ
10
102% 100% 85% 65% 91% 82% 64% 4.8 A or smaller
Control voltage
7.25V to 7.45V (per 6V cell 25˚C)
Initial current
1.8 A or smaller
Control voltage
6.8V to 6.9V (per 6V cell 25˚C)
(Note)
30
5.8A
Initial current
Trickle use
Duration of discharge vs. Discharge current
(Hour)
Internal Resistance
12Ah 11.3Ah 10.4Ah 8.1Ah
Duration of discharge
Capacity 77˚F (25˚C)
20
Duration of discharge
20 hour rate (360mA) 10 hour rate (680mA) 5 hour rate (1260mA) 1 hour rate (4900mA) 1.5 hour rate discharge Cut-off voltage 5.25 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
104˚F (40˚C)
5 4 3
77˚F (25˚C)
2 1.5
32˚F (0˚C)
1 50 40
5˚F (-15˚C)
30
(Minute)
(note)
6 8 10
(Hour)
20
10
5 3 300 500
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
(mA)
1
3
5
10
30
50
100
(A) Discharge current
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R063R4P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm) Terminal type: Faston 187
+
0.236 (6)
5.276 +- 0.059 0.020 (134 +- 1.5 0.5 )
0.012 (0.3)
2.362 +- 0.039 (60 +- 1)
5.12 (129.8)
1.339 +- 0.039 (34 +- 1) 0.398 (10.1) 0.398 (10.1)
5.236 (133)
1.319 (33.5)
Photo/Label for reference only. Battery case resin: Standard (UL94HB) Color is black.
Specifications
Dimensions
Width
1.339 inches (34.0 mm)
Height
2.362 inches (60.0 mm)
Total Height
2.598 inches (66.0 mm) 1.37 lbs. (0.62 kg)
Approx. mass Standard Terminals and Resin
Discharge characteristics 77°F (25°C) (Note) 6V 3.4Ah 5.276 inches (134.0 mm)
UL94HB Faston 187
LC-R063R4P
Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
7.2 6.9 6.6 6.3 6.0 5.7 5.4 5.1 4.8 4.5 4.2 3.9
3.4A
0
1
2
4
6 8 10
20
40 60
0.34A 0.17A
1.7A 0.85A
2
(Minute)
4
6 8 10
20
40
(Hour)
Duration of discharge
Characteristics
Temperature dependency of capacity (20 hour rate) Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
15 10
Approx. 30mΩ
91% 82% 64%
initial current
1.36 A or smaller
Control voltage
7.25V to 7.45V (per 6V cell 25˚C)
initial current
0.51 A or smaller
Control voltage
6.8V to 6.9V (per 6V cell 25˚C)
Trickle use
20
1.5A
102% 100% 85% 65%
(Note)
30
(Hour)
Internal Resistance
3.4Ah 3Ah 2.7Ah 2.1Ah
Duration of discharge
Capacity 77˚F (25˚C)
20 hour rate (170mA) 10 hour rate (300mA) 5 hour rate (540mA) 1 hour rate (2100mA) 1.5 hour rate discharge Cut-off voltage 5.25 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
104˚F (40˚C) 5 4 77˚F (25˚C)
3 2 1.5 5˚F (-15˚C)
1 50 40 30
(Minute)
(note)
Duration of discharge vs. Discharge current
32˚F (0˚C)
20
10
5 3 30
50
100
300 500
1
(mA) Discharge current
3
5
10
(A)
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R067R2P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm) Terminal type: Faston 187 or Faston 250
+
1.339 - 0.059 0.020 34 -+ 1.5 0.5
+
0.236 (6)
5.945 - 0.059 0.020 + (151 - 1.5 0.5 )
+ 0.059
0.354 (9)
3.701- 0.020 (94 +- 1.5 0.5 )
5.13 (130.3)
0.012 (0.3)
Photo/Label for reference only. 5.913 (150.2)
Specifications
Dimensions
6V 7.2Ah 5.945 inches (151.0 mm)
Width
1.339 inches (34.0 mm)
Height
3.702 inches (94.0 mm)
Total Height*
3.937 inches (100.0 mm)
Approx. mass Standard Terminals and Resin Optional Terminals and Resin
2.78 lbs. (1.26 kg)
UL94HB Faston 187
LC-R067R2P
UL94HB Faston 250
LC-R067R2P1
UL94HB Faston 187/250
LC-R067R2P2
Battery case resin: Standard (UL94HB) Color is black.
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
1.307 (33.2)
7.5 7.0 6.5 6.0 5.5 5.0 4.5 4.0 3.5 3.0 2.5
♦ Please contact Panasonic for availability on optional items. Optional items may be subject to
2.88A 1.44A 11.52A 23.04A
0 1
minimum order quantities.
0.72A 0.36A
5.76A
2
4
6 8 10
20
40 60
2
4
(Minute)
6 8 10
20
40
(Hour)
Discharge time
Characteristics
Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
3.5A
10
Approx. 20mΩ 102% 100% 85% 65% 91% 82% 64%
Initial current
2.88 A or smaller
Control voltage
7.25V to 7.45V (per 6V cell 25˚C)
Initial current
1.08 A or smaller
Control voltage
6.8V to 6.9V (per 6V cell 25˚C)
Trickle use
20 15
(Hour)
Temperature dependency of capacity (20 hour rate)
(Note)
30
Duration of discharge
Internal Resistance
7.2Ah 6.8Ah 6.3Ah 4.9Ah
104˚F (40˚C) 5 4 3 2 1.5
77˚F (25˚C) 32˚F (0˚C)
5˚F (-15˚C) 1 50 40 30
(Minute)
Capacity (note) 77˚F (25˚C)
Duration of discharge vs. Discharge current 20 hour rate (360mA) 10 hour rate (680mA) 5 hour rate (1260mA) 1 hour rate (4900mA) 1.5 hour rate discharge Cut-off voltage 5.25 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
20
10
5 3 100
300 500
1
3
5
(mA)
10
30
50
(A) Discharge current
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R121R3P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm)
1.969 +- 0.039
3.819 +- 0.039 (97 +- 1)
1.213 (30.8)
1.85 (47)
0.012 (0.3)
3.799 (96.5)
1.870 +- 0.039 (47.5 +- 1)
(50 +- 1)
0.187 (4.75)
Terminal type: Faston 187
Battery case resin: Standard (UL94HB) Color is black.
Photo/Label for reference only.
Specifications Nominal Voltage Rated Capacity (20 hour rate) Length Dimensions
Width
1.870 inches (47.5 mm)
Height
1.969 inches (50.0 mm)
Total Height
2.165 inches (55.0 mm) 1.30 lbs. (0.59 kg)
Approx. mass Standard Terminals and Resin
12V 1.3Ah 3.819 inches (97.0 mm)
UL94HB Faston 187
Terminal voltage (V)
Discharge characteristics 77°F (25°C) (Note)
LC-R121R3P
14.4 13.8 13.2 12.6 12.0 11.4 10.8 10.2 9.6 9.0 8.4 7.8
0.26A 0.13A 0.065A 1.3A
0
1
2
4 6 8 10 20 (Minute)
Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
1.3Ah 1.2Ah 1.05Ah 0.85Ah
4 6 8 10 20 (Hour)
40
Duration of discharge vs. Discharge current 20
0.6A
15 10
102% 100% 85% 65% 91% 82% 64%
(Hour)
Approx. 90mΩ
5 4 3 2 1.5 104˚F (40˚C)
1 50 40 30
32˚F (0˚C)
0.52 A or smaller
Control voltage
14.5V to 14.9V (per 12V cell 25˚C)
Initial current
0.195 A or smaller
5
Control voltage
13.6V to 13.8V (per 12V cell 25˚C)
3 30
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
77˚F (25˚C)
20
Initial current
Trickle use
(Note)
30
Duration of discharge
Temperature dependency of capacity (20 hour rate)
20 hour rate (65mA) 10 hour rate (120mA) 5 hour rate (210mA) 1 hour rate (850mA) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
(Minute)
Internal Resistance
2
Duration of discharge
Characteristics Capacity (note) 77˚F (25˚C)
40 60
10
5˚F (-15˚C)
50
100
300 500
1
(mA) Discharge current
3
5
10
(A)
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R122R2P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm)
0.236 (6)
Terminal type: Faston 187
1.339 +- 0.039 (34 +- 1) 0.398 (10.1)
0.11 (2.8)
0.039
6.969 +- 0.020 177 +- 1.5 0.5
0.012 (0.3)
2.362 +- 0.039 (60 +- 1)
6.811 (173)
6.937 (176.2)
Photo/Label for reference only.
1.319 (33.5)
Battery case resin: Standard (UL94HB) Color is black.
Specifications
Dimensions
Width
1.339 inches (34.0 mm)
Height
2.362 inches (60.0 mm)
Total Height
2.598 inches (66.0 mm) 1.76 lbs. (0.80 kg)
Approx. mass Standard Terminals and Resin
12V 2.2Ah 6.968 inches (177.0 mm)
UL94HB Faston 187
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
LC-R122R2P
14.4 13.8 13.2 12.6 12.0 11.4 10.8 10.2 9.6 9.0 8.4 7.8
2.2A
0
1
2
4 6 8 10 20 (Minute)
0.22A 0.11A 1.1A 0.55A
40 60
2
4 6 8 10 20 (Hour)
40
Duration of discharge
Characteristics
Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
20 15
0.95A
10
Approx. 70mΩ 102% 100% 85% 65% 91% 82% 64%
Initial current
0.88 A or smaller
Control voltage
14.5V to 14.9V (per 12V cell 25˚C)
Initial current
0.33 A or smaller
Control voltage
13.6V to 13.8V (per 12V cell 25˚C)
Trickle use
(Note)
30
(Hour)
Temperature dependency of capacity (20 hour rate)
Duration of discharge vs. Discharge current
Duration of discharge
Internal Resistance
2.2Ah 2Ah 1.8Ah 1.3Ah
5 4 3
104˚F (40˚C)
2 1.5
77˚F (25˚C)
1 50 40
32˚F (0˚C)
30 5˚F (-15˚C)
(Minute)
Capacity (note) 77˚F (25˚C)
20 hour rate (110mA) 10 hour rate (200mA) 5 hour rate (360mA) 1 hour rate (1300mA) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
20
10
5 3 30
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
50
100
300 500
1
(mA)
3
5
10
(A)
Discharge current
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R1233P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm)
0.295(7.5)
Terminal type: M6 bolt and nut
Photo/Label for reference only.
12V 33Ah 7.701 inches (195.6 mm) 5.118 inches (130.0 mm) 6.102 inches (155.0 mm) 7.087 inches (180.0 mm) 26.5 (12.0 kg)
UL94HB M6 Bolt and Nut
LC-R1233P
UL94V-0 M6 Bolt and Nut
LC-V1233P
minimum order quantities.
Characteristics
Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
0.177 (4.5)
3.3A 1.65A 13.2A 6.6A
52.8A 105.6A 1
2
4 6 8 10 20 (Minute)
40 60
2
4 6 8 10 20 (Hour)
40
Duration of discharge vs. Discharge current
13.4A
(Note)
30
Approx. 7mΩ
20 15
102% 100% 85% 65% 91% 82% 64%
Initial current
13.2 A or smaller
Control voltage
14.5V to 14.9V (per 12V cell 25˚C)
Initial current
4.95 A or smaller
Control voltage
13.6V to 13.8V (per 12V cell 25˚C)
Trickle use
26.4A
Duration of discharge
(Hour)
10
Duration of discharge
Temperature dependency of capacity (20 hour rate)
14.4 13.8 13.2 12.6 12.0 11.4 10.8 10.2 9.6 9.0 8.4 7.8 0
7 5 4 3 2 1.5 1 50 40 30
(Minute)
Internal Resistance
33Ah 30Ah 27Ah 20Ah
4.921 (125)
Discharge characteristics 77°F (25°C) (Note)
♦ Please contact Panasonic for availability on optional items. Optional items may be subject to
20 hour rate (1.65A) 10 hour rate (3A) 5 hour rate (5.4A) 1 hour rate (20A) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
1.043 (26.5)
Battery case resin: Standard (UL94HB) Color is black. Optional (UL94V-0) Color is grey.
Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length Width Dimensions Height Total Height Approx. mass (lbs.)
Capacity (note) 77˚F (25˚C)
0.236 (6)
7.661 (194.6)
Specifications
Standard Terminals and Resin
1.969 (50)
6.102±0.079 (155±2)
0.63 (16)
5.118±0.079 (130±2)
0.354 (9)
6.26 (159)
7.087 (180)
7.701±0.079 (195.6±2)
77˚F (25˚C)
20 15 10
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values. (Note) For cycle use of the battery, please consult us in advance.
VRLA BATTERIES
5˚F (-15˚C)
7 5
32˚F (0˚C) 3 1
2
3 4 5
7 10
20
30 40 50 70 100
200 300
(A) Discharge current
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R123R4P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm) Terminal type: Faston 187
0.236 (6)
0.059 5.276 + -1.50.020 (134 + - 0.5 )
2.638 + - 0.039 (67 +- 1)
0.012 (0.3)
2.362 +- 0.039 (60 +- 1)
2.094 (53.2)
5.236 (133)
Photo/Label for reference only.
Specifications
Battery case resin: Standard (UL94HB) Color is black. Optional (UL94V-0) Color is grey.
Dimensions
12V 3.4Ah 5.276 inches (134.0 mm)
Width
2.638 inches (67.0 mm)
Height
2.362 inches (60.0 mm)
Total Height
2.598 inches (66.0 mm) 2.65 lbs. (1.20 kg)
Approx. mass UL94HB Faston 187
LC-R123R4P
Terminal voltage (V)
Discharge characteristics 77°F (25°C) (Note)
Nominal Voltage Rated Capacity (20 hour rate) Length
Standard Terminals and Resin
2.618 (66.5)
14.4 13.8 13.2 12.6 12.0 11.4 10.8 10.2 9.6 9.0 8.4 7.8
3.4A
0
1
2
4
6 8 10
20
40 60
2
(Minute)
Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
3.4Ah 3Ah 2.7Ah 2.1Ah
6 8 10
20
40
(Hour)
20 15
Approx. 60mΩ
91% 82% 64% 1.36 A or smaller
Control voltage
14.5V to 14.9V (per 12V cell 25˚C)
Initial current
0.51 A or smaller
Control voltage
13.6V to 13.8V (per 12V cell 25˚C)
10
(Hour)
102% 100% 85% 65%
(Note)
30
1.5A
Initial current
Trickle use
Duration of discharge vs. Discharge current
Duration of discharge
Temperature dependency of capacity (20 hour rate)
20 hour rate (170mA) 10 hour rate (300mA) 5 hour rate (540mA) 1 hour rate (2100mA) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
104˚F (40˚C) 5 4 3
77˚F (25˚C)
2 1.5 5˚F (-15˚C) 1 50 40 30
(Minute)
Internal Resistance
4
Duration of discharge
Characteristics Capacity (note) 77˚F (25˚C)
0.34A 0.17A
1.7A 0.85A
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
32˚F (0˚C)
20
10
5 3 30
50
100
300 500
1
(mA) Discharge current
3
5
10
(A)
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-RA1212P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm) Terminal type: Faston 187 or Faston 250
0.394 + 0.039 (10 +1.0 )
+ 0.059
0.236 (6)
3.858 +- 0.059 0.020 (98 +- 1.5 0.5 )
3.701- 0.020 (94 +- 1.5 0.5 )
0.534±0.3 (13.5±0.75)
5.945 +- 0.059 0.020 151 +- 1.5 0.5
Photo/Label for reference only.
Dimensions
12V 12Ah 5.945 inches (151.0 mm)
Width
3.860 inches (98.0 mm)
Height
3.702 inches (94.0 mm)
Total Height*
3.937 inches (100.0 mm)
Approx. mass Standard Terminals and Resin
Battery case resin: Standard (UL94HB) Color is black.
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
0.012 (0.3)
Specifications
8.36 lbs. (3.8 kg)
UL94HB Faston 187
LC-RA1212P
UL94HB Faston 250
LC-RA1212P1
* The total height with #250 teminal is 101.5mm.
14.4 13.8 13.2 12.6 12.0 11.4 10.8 10.2 9.6 9.0 8.4 7.8
Characteristics
Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
30
Approx. 30mΩ
20 15
91% 82% 64%
Initial current
4.8 A or smaller
Control voltage
14.5V to 14.9V (per 12V cell 25˚C)
Initial current
1.8 A or smaller
Control voltage
13.6V to 13.8V (per 12V cell 25˚C)
Trickle use
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
4
6 8 10
20
40 60
2
4
6 8 10
20
40
(Hour)
Duration of discharge vs. Discharge current
5.8A
102% 100% 85% 65%
2
Duration of discharge (Note)
10
(Hour)
Temperature dependency of capacity (20 hour rate)
1
(Minute)
Duration of discharge
Internal Resistance
12Ah 11.3Ah 10.4Ah 8.1Ah
104˚F (40˚C)
5 4 3
77˚F (25˚C)
2 1.5
32˚F (0˚C)
1 50 40
5˚F (-15˚C)
30
(Minute)
Capacity (note) 77˚F (25˚C)
24A 0
20 hour rate (600mA) 10 hour rate (1130mA) 5 hour rate (2080mA) 1 hour rate (8100mA) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
1.2A 0.6A
3A
6A
12A
20
10
5 3 300 500
(mA)
1
3
5
10
30
50
100
(A) Discharge current
VRLA BATTERIES
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-RD1217P
For main and standby power supplies. Expected trickle life: Approx 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm)
Photo/Label for reference only.
0.886 (22)
0.040 (1)
0.492 (12.5) 6.043 (153.5)
0.197 (5) 4.429 (112.5) 0.197 (5)
2.992±0.079 (76±2)
0.443 (11)
6.575±0.079 (167±2)
7.126±0.079 (181±2)
0.217 (5.5)
Terminal type: LC-RD1217P: M5 bolt and nut
7.067 (179.5)
2.933 (74.5)
Specifications
Dimensions
12V 17Ah 7.126 inches (181.0 mm)
Width
2.992 inches (76.0 mm)
Height
6.575 inches (167.0 mm)
Total Height
6.575 inches (167.0 mm)
Approx. mass Standard Terminals and Resin
14.34 lbs. (6.5 kg)
UL94HB M5 Bolt and Nut
LC-RD1217P
Battery case resin: Standard (UL94HB) Color is black.
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
14.4 13.8 13.2 12.6 12.0 11.4 10.8 10.2 9.6 9.0 8.4 7.8
Characteristics
Temperature dependency of capacity (20 hour rate) Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
34A
2
4 6 8 10 20 (Minute)
40 60
2
4 6 8 10 20 (Hour)
40
Duration of discharge vs. Discharge current
7A
(Note)
30 20
Approx. 12mΩ
15
102% 100% 85% 65% 91% 82% 64%
Initial current
6.8 A or smaller
Control voltage
14.5V to 14.9V (per 12V cell 25˚C)
Initial current
2.55 A or smaller
Control voltage
13.6V to 13.8V (per 12V cell 25˚C)
Trickle use
1
Duration of discharge
10
(Hour)
Internal resistance
17Ah 15Ah 13Ah 10Ah
Duration of discharge
Capacity 77˚F (25˚C)
20 hour rate (850mA) 10 hour rate (1500mA) 5 hour rate (2600mA) 1 hour rate (10000mA) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
1.7A 0.85A
51A 0
5 4 3 2 1.5
104˚F (40˚C) 77˚F (25˚C)
1 50 40 30
(Minute)
(note)
4.25A 17A
20
32˚F (0˚C) 5˚F (-15˚C)
10
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values. (Note) For cycle use of the battery, please contact us in advance.
VRLA BATTERIES
5 3
300 500
(mA)
1
3
5
10
30
50
100
(A) Discharge current
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
For pitch backup systems in wind turbines
LC-WTP1212
Expected life: 10 years at 20℃, 5 years at 25℃ (based on a weekly discharge cycle of max 15 seconds)
■Dimensions(mm) Terminal type (option) 4.5
6.35
Contents indicated (including the recycle marking, etc) are subject to change without notice.
Battery case resin: Flame-retardant (UL94V-0)
■Duration of discharge vs. discharge current
■Specification 12V 12Ah
Length
151 mm
Width
98 mm
Height
94 mm
Total height
100 mm
Dimensions
Approx. Mass
3.85 kg
Terminal
250M
30 20
Internal Resistance Temperature Dependency of Capacity (20 hour rate) Self Discharge (25 ℃)
20 hour rate
12Ah
10 hour rate
10Ah
3 hour rate
9.3Ah
1 hour rate
8.1Ah
Fully charged battery
(25 ℃)
15 mΩ
40 ℃
102%
25 ℃
100%
0℃
85%
-15 ℃ After 3 months
91%
After 6 months
82%
After 12 months
64%
5 25℃
3
60 0℃
30
(minute)
■Characteristics Capacity (25 ℃)
40℃
10 (hour)
Rated Capacity(20HR)
Duration of discharge
Nominal Voltage
10 -15℃
5 3
65% 1
0.1
1
0.3
3
10
30
100
Discharge current(A)
■Large current discharge characteristics(25℃) Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
267 240 3
250 225 6
233 210 10
217 195 15
200 180 20
187 168 25
175 158 30
157 142 40
143 130 50
133 120 60
125 113 70
Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
117 105 80
110 100 90
103 93 100
98 88 110
92 83 120
87 78 130
82 73 140
77 70 150
73 67 160
70 63 170
67 60 180
The cut off voltage should be more than 8.0V. Battery should be charged after each discharge.
■Charging Method **Control voltage: 13.6V~13.8V at 20℃~25℃ with temperature compensation, Initial current: 1.80A or smaller **Please consult us for the right control voltage if the ambient temperature is different.
■Operating Temperature Range *Storage -40℃~ 50℃
Charge -20℃~ 50℃
Discharge -20℃~ 50℃
* For storage, please ensure that battery is fully charged.
Data in this sheet are for reference only and are not guaranteed values. 1/1
2009.06
For pitch backup systems in wind turbines
LC-WTP127R2
Expected life: 10 years at 20℃, 5 years at 25℃ (based on a weekly discharge cycle of max 15 seconds)
■Dimensions(mm) Terminal type 4.5
6.35
Contents indicated (including the recycle marking, etc) are subject to change without notice.
Battery case resin: Flame-retardant (UL94V-0)
■Duration of discharge vs. discharge current
■Specification Nominal Voltage
12V 7.2Ah 151 mm
Width
64.5 mm
Height
94 mm
Total height
100 mm
Dimensions
Approx. Mass
2.50 kg
Terminal
250M
30 20 40℃ 10
Capacity (25 ℃)
Internal Resistance Temperature Dependency of Capacity (20 hour rate) Self Discharge (25 ℃)
20 hour rate
7.2Ah
10 hour rate
6.5Ah
3 hour rate
5.8Ah
1 hour rate
4.9Ah
Fully charged battery
(25 ℃)
21 mΩ
40 ℃
102%
25 ℃
100%
0℃
85%
-15 ℃ After 3 months
91%
After 6 months
82%
After 12 months
64%
5 25℃
3
60 0℃
30
(minute)
■Characteristics
(hour)
Length
Duration of discharge
Rated Capacity(20HR)
10 -15℃ 5 3
65% 1
0.1
3
1
0.3
10
30
100
Discharge current(A)
■Large current discharge characteristics(25℃) Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
160 144 3
150 135 6
140 126 10
130 117 15
120 108 20
112 101 25
105 95 30
94 85 40
86 78 50
80 72 60
75 68 70
Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
70 63 80
66 60 90
62 56 100
59 53 110
55 50 120
52 47 130
49 44 140
46 42 150
44 40 160
42 38 170
40 36 180
The cut off voltage should be more than 8.0V. Battery should be charged after each discharge.
■Charging Method **Control voltage: 13.6V~13.8V at 20℃~25℃ with temperature compensation, Initial current: 1.08A or smaller **Please consult us for the right control voltage if the ambient temperature is different.
■Operating Temperature Range *Storage -40℃~ 50℃
Charge -20℃~ 50℃
Discharge -20℃~ 50℃
* For storage, please ensure that battery is fully charged.
Data in this sheet are for reference only and are not guaranteed values. 1/1
2009.06
For pitch backup systems in wind turbines
LC-WTV1212
Expected life: 5 years at 20℃, 3 years at 25℃ (based on a weekly discharge cycle of max 15 seconds)
■Dimensions(mm) Terminal type (option) 4.5
6.35
Contents indicated (including the recycle marking, etc) are subject to change without notice.
Battery case resin: Flame-retardant (UL94V-0)
■Duration of discharge vs. discharge current
■Specification 12V
Length
12Ah
Width
98 mm
Height
94 mm
Total height
100 mm
Dimensions
30 20
151 mm
Approx. Mass
3.85 kg
Terminal
250M
Internal Resistance Temperature Dependency of Capacity (20 hour rate) Self Discharge (25 ℃)
20 hour rate
12Ah
10 hour rate
10Ah
3 hour rate
9.3Ah
1 hour rate
8.5Ah
Fully charged battery
(25 ℃)
15 mΩ
40 ℃
102%
25 ℃
100%
0℃
85%
-15 ℃ After 3 months
91%
After 6 months
82%
After 12 months
64%
5 25℃
3
60 0℃
30
(minute)
■Characteristics Capacity (25 ℃)
40℃
10 (hour)
Rated Capacity(20HR)
Duration of discharge
Nominal Voltage
10 -15℃
5 3
65% 1
0.1
1
0.3
3
10
30
100
Discharge current(A)
■Large current discharge characteristics(25℃) Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
267 240 3
250 225 6
233 210 10
217 195 15
200 180 20
187 168 25
175 158 30
157 142 40
143 130 50
133 120 60
125 113 70
Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
117 105 80
110 100 90
103 93 100
98 88 110
92 83 120
87 78 130
82 73 140
77 70 150
73 67 160
70 63 170
67 60 180
The cut off voltage should be more than 8.0V. Battery should be charged after each discharge.
■Charging Method **Control voltage: 13.6V~13.8V at 20℃~25℃ with temperature compensation, Initial current: 1.80A or smaller **Please consult us for the right control voltage if the ambient temperature is different.
■Operating Temperature Range *Storage -40℃~ 50℃
Charge -20℃~ 50℃
Discharge -20℃~ 50℃
* For storage, please ensure that battery is fully charged.
Data in this sheet are for reference only and are not guaranteed values. 1/1
2009.06
For pitch backup systems in wind turbines
LC-WTV127R2
Expected life: 5 years at 20℃, 3 years at 25℃ (based on a weekly discharge cycle of max 15 seconds)
■Dimensions(mm) Terminal type 4.5
6.35
Contents indicated (including the recycle marking, etc) are subject to change without notice.
Battery case resin: Flame-retardant (UL94V-0)
■Duration of discharge vs. discharge current
■Specification Nominal Voltage
12V 7.2Ah 151 mm
Width
64.5 mm
Height
94 mm
Total height
100 mm
Dimensions
Approx. Mass
2.50 kg
Terminal
250M
30 20 40℃ 10
Capacity (25 ℃)
Internal Resistance Temperature Dependency of Capacity (20 hour rate) Self Discharge (25 ℃)
20 hour rate
7.2Ah
10 hour rate
6.5Ah
3 hour rate
5.8Ah
1 hour rate
4.9Ah
Fully charged battery
(25 ℃)
21 mΩ
40 ℃
102%
25 ℃
100%
0℃
85%
-15 ℃ After 3 months
91%
After 6 months
82%
After 12 months
64%
5 25℃
3
60 0℃
30
(minute)
■Characteristics
(hour)
Length
Duration of discharge
Rated Capacity(20HR)
10 -15℃ 5 3
65% 1
0.1
3
1
0.3
10
30
100
Discharge current(A)
■Large current discharge characteristics(25℃) Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
160 144 3
150 135 6
140 126 10
130 117 15
120 108 20
112 101 25
105 95 30
94 85 40
86 78 50
80 72 60
75 68 70
Peak current(A for milliseconds) Discharge current(A) Discharge time(sec)
70 63 80
66 60 90
62 56 100
59 53 110
55 50 120
52 47 130
49 44 140
46 42 150
44 40 160
42 38 170
40 36 180
The cut off voltage should be more than 8.0V. Battery should be charged after each discharge.
■Charging Method **Control voltage: 13.6V~13.8V at 20℃~25℃ with temperature compensation, Initial current: 1.08A or smaller **Please consult us for the right control voltage if the ambient temperature is different.
■Operating Temperature Range *Storage -40℃~ 50℃
Charge -20℃~ 50℃
Discharge -20℃~ 50℃
* For storage, please ensure that battery is fully charged.
Data in this sheet are for reference only and are not guaranteed values. 1/1
2009.06
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-X1220P/LC-X1220AP
For main and standby power supplies. Expected trickle life: Approx. 6 years at 25°C, Approx. 10 years at 20°C.
Dimensions (mm) Terminal type: LC-X1220P: M5 bolt and nut LC-X1220AP: M5 threaded post
6.043 (153.5)
Photo/Label for reference only. (a) The photo and dimensions represent LC-X1220P.
0.040 (1)
4.429 (112.5)
0.886 (22) 0.443 (11)
6.575±0.079 (167±2)
0.217 (5.5)
0.197 (5)
0.197 (5)
0.492 (12.5)
2.992±0.079 (76±2) 7.126±0.079 (181±2)
2.933 (74.5)
7.067 (179.5)
Specifications
Dimensions
12V 20Ah 7.126 inches (181.0 mm)
Width
2.992 inches (76.0 mm)
Height
6.575 inches (167.0 mm)
Total Height
6.575 inches (167.0 mm)
Approx. mass Standard Terminals and Resin Optional Terminals and Resin
UL94HB M5 Bolt and Nut UL94HB M5 Threaded Post
14.56 lbs. (6.6 kg) LC-X1220P LC-X1220AP
Battery case resin: Standard (UL94HB) Color is black.
Discharge characteristics 77°F (25°C) (Note) Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
♦ Please contact Panasonic for availability on optional items. Optional items may be subject to minimum order quantities.
14.4 13.8 13.2 12.6 12.0 11.4 10.8 10.2 9.6 9.0 8.4 7.8 7.2
20A
2A
2
4 6 810
40A 60A 0
1 2
4 6 810
20
40 60
20
40
(Minute) (Hour) Duration of Discharge
Characteristics 20Ah 18Ah 16Ah 12Ah
Duration of discharge vs. Discharge current
(Note)
30 20
9.8A
15
Approx. 11mΩ
91% 82% 64% 8 A or smaller 14.5 V to 14.9 V (per 12V cell 25˚C) 3 A or smaller 13.6V to 13.8V (per 12V cell 25˚C)
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values. (Note) For cycle use of the battery, please contact us in advance.
(Hour) Duration of discharge
102% 100% 85% 65%
10
5 4 104˚F (40˚C)
3
77˚F (25˚C)
2 1.5 1 50 40 30 32˚F (0˚C)
(Minute)
20 hour rate (1.2A) 10 hour rate (2.2A) Capacity (note) 5 hour rate (3.8A) 1 hour rate (14A) 77˚F (25˚C) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery Internal Resistance 77˚F (25˚C) Temperature 104˚F (40˚C) dependency 77˚F (25˚C) of capacity 32˚F (0˚C) (20 hour rate) 5˚F (-15˚C) Residual capacity after standing 3 months Self discharge Residual capacity 77˚F (25˚C) after standing 6 months Residual capacity after standing 12 months Initial current Cycle use Charge (Repeating Control voltage use) Method (Constant Initial current Voltage) Trickle use Control voltage
1A
5A
20 5˚F (-15˚C) 10
5 3
300 500
(mA)
VRLA BATTERIES PAGE 49
1
3
5
10
30
50
100
(A) Discharge current
AUGUST 2005
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-X1228P/LC-X1228AP
For standby power supplies. Expected trickle life: Approx. 6 years at 25°C, Approx. 10 years at 20°C.
Dimensions (mm)
0.33 (8.3) 0.09 (2.2) 0.47 (12)
1.79 (45.5)
Terminal type: LC-X1228AP: M5 threaded post LC-X1228P: M5 bolt and nut
0.39 (9.8)
5.28 (134) 3.54 (90)
Specifications
Optional Terminals and Resin
4.921 inches (125 mm)
Height
7.07 inches (179.5 mm)
Total Height
LC-X1228AP 6.890 inches (175 mm) LC-X1228P 7.067 inches (179.5 mm)
Approx. mass Standard Terminals and Resin
Discharge characteristics 77°F (25°C) (Note) 12V 28Ah 6.496 inches (165 mm)
Terminal voltage (V)
Width
24.34 lbs. (11 kg) LC-X1228P
UL94HB M5 Bolt and Nut
LC-X1228AP
UL94HB M5 Threaded Post UL94V-0 M5 Bolt and Nut UL94V-0 M5 Threaded Post
Charge Method (Constant Voltage)
2
4
2.8A 1.4A
2
4
6 8 10
20
40 60
6 8 10
20
40
(Hour)
Duration of discharge
Duration of discharge vs. Discharge current
(Note)
30
Trickle use Control voltage
28.0Ah 26.5Ah 25.0Ah 21.0Ah
20 15 10
(Hour)
20 hour rate (1.40A) 10 hour rate (2.65A) 5 hour rate (5.00A) 1 hour rate (21.0A) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months Initial current
9.80A Approx. 6.0mΩ 102% 100% 85% 65% 91% 82% 64%
Duration of discharge
Self discharge 77˚F (25˚C)
1
(Minute)
5 4 3
104˚F (40˚C)
2 1.5 1 50 40
77˚F (25˚C)
32˚F (0˚C)
30
(Minute)
Temperature dependency of capacity (20 hour rate)
7A
56A 0
Characteristics
Internal Resistance
14A 28A
LC-P1228AP
order quantities.
Capacity 77˚F (25˚C)
13.5 13.0 12.5 12.0 11.5 11.0 10.5 10.0 9.5 9.0 8.5 8.0
LC-P1228P
♦ Please contact Panasonic for availability on optional items. Optional items may be subject to minimum
(note)
4.88 (124)
Battery case resin: Standard (UL94HB) Color is black. Optional (UL94V-0) Color is grey.
(a) The photo and dimensions represent LC-X1228AP.
Dimensions
0.47 (12)
6.43 (163.4)
Photo/Label for reference only.
Nominal Voltage Rated Capacity (20 hour rate) Length
4.921±0.079 (125±2)
6.890±0.079 (175±2)
6.496±0.079 (165±2)
5˚F (-15˚C)
20
10
4.20 A or smaller 13.6V to 13.8V (per 12V cell 25˚C)
5 3
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
1
5
10
50
100
500
Discharge current (A)
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-XC1228AP
For main power supplies. Cycle long life type.
Dimensions (mm)
1.79 (45.5)
Terminal type: LC-XC1228AP: M5 threaded post
0.39 (9.8)
5.28 (134) 3.54 (90)
4.921±0.079 (125±2) 0.47 (12)
6.890±0.079 (175±2)
6.496±0.079 (165±2)
0.33 (8.3) 0.09 (2.2) 0.47 (12)
+
4.88 (124)
6.43 (163.4)
Battery case resin: Standard (UL94HB) Color is black.
Photo/Label for reference only.
Discharge characteristics 77°F (25°C) (Note)
Nominal Voltage Rated Capacity (20 hour rate) Length Dimensions
12V 28Ah 6.496 inches (165 mm)
Width
4.921 inches (125 mm)
Height
6.890 inches (175 mm)
Total Height
7.07 inches (179.5 mm)
Approx. mass Standard Terminals and Resin
24.34 lbs. (11 kg)
UL94HB M5 Threaded Post
14.4 13.8
Terminal Voltage (V)
Specifications
LC-XC1228AP
13.2 12.6 12.0 11.4 10.8 28A
0
1
Internal Resistance Temperature dependency of capacity (20 hour rate) Self discharge 77˚F (25˚C)
Charge Method (Constant Voltage)
Cycle use (Repeating use)
20 hour rate (1.4A) 10 hour rate (2.65A) 5 hour rate (4.8A) 1 hour rate (18A) 1.5 hour rate discharge Cut-off voltage 10.5 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months Initial current Control voltage
28Ah 26.5Ah 24Ah 18Ah
100
1000 2000
Duration of discharge vs. Discharge current
(Note)
2000
14A
1000
Approx. 10mΩ 102% 100% 85% 65% 91% 82% 64% 11.2 A or smaller
Duration of Discharge (minutes)
Capacity 77˚F (25˚C)
10
Duration of Discharge (minutes)
Characteristics (note)
1.4A
7A
10.2 9.6 9.0 8.4 7.8 7.2
0˚C
100
40˚C
25˚C
10
14.5V to 14.9V (per 12V cell 25˚C)
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values. 1 1
3
5
10
30
50
100
Discharge Current (A)
VRLA BATTERIES
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.
VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-R061R3P
For main and standby power supplies. Expected trickle life: 3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm)
0.187 (4.75)
Terminal type: Faston 187
3.799 (96.5)
Photo/Label for reference only.
0.925 (23.5)
Battery case resin: Standard (UL94HB) Color is black.
Dimensions
6V 1.3Ah 3.819 inches (97.0 mm)
Width
0.945 inches (24.0 mm)
Height
1.969 inches (50.0 mm)
Total Height
2.165 inches (55.0 mm) .661 lbs. (0.30 kg)
Approx. mass UL94HB Faston 187
LC-R061R3P
Terminal voltage (V)
Nominal Voltage Rated Capacity (20 hour rate) Length
7.2 6.9 6.6 6.3 6.0 5.7 5.4 5.1 4.8 4.5 4.2 3.9
0.065A 0.26A 0.13A 1.3A
0
1
2
4
6 8 10
20
40 60
2
(Minute)
Temperature dependency of capacity (20 hour rate) Self discharge 77˚F (25˚C)
Cycle use (Repeating use)
6 8 10
20
40
(Hour)
20 15 10
Approx. 50mΩ 102% 100% 85% 65% 91% 82% 64% 0.52 A or smaller
Control voltage
7.25V to 7.45V (per 6V cell 25˚C)
initial current
0.195 A or smaller
Control voltage
6.8V to 6.9V (per 6V cell 25˚C)
(Note)
30
0.6A
initial current
Trickle use
Duration of discharge vs. Discharge current
(Hour)
Internal Resistance
1.3Ah 1.2Ah 1.05Ah 0.85Ah
Duration of discharge
Capacity 77˚F (25˚C)
20 hour rate (65mA) 10 hour rate (120mA) 5 hour rate (210mA) 1 hour rate (850mA) 1.5 hour rate discharge Cut-off voltage 5.25 V Fully charged battery 77˚F (25˚C) 104˚F (40˚C) 77˚F (25˚C) 32˚F (0˚C) 5˚F (-15˚C) Residual capacity after standing 3 months Residual capacity after standing 6 months Residual capacity after standing 12 months
5 4 3 2 1.5 104˚F (40˚C)
1 50 40 30
(Minute)
(note)
4
Duration of discharge
Characteristics
Charge Method (Constant Voltage)
0.165 (4.2)
Discharge characteristics 77°F (25°C) (Note)
Specifications
Standard Terminals and Resin
0.165 (4.2)
0.012 (0.3)
1.969 +- 0.039
3.656 (92.9)
0.945 +- 0.039 (24 +- 1)
(50 +- 1)
3.819 +- 0.039 (97 +- 1)
(Note) The above characteristics data are average values obtained within three charge/discharge. Cycles not the minimum values.
VRLA BATTERIES
77˚F (25˚C)
20 32˚F (0˚C) 10
5˚F (-15˚C)
5 3 30
50
100
300 500
1
(mA) Discharge current
3
5
10
(A)
AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to modification without notice. Contact Panasonic for the latest information.